Professional Documents
Culture Documents
July 3, 2020
Learning objectives
©ABB
7/5/20 | Slide 2
Why bus protection?
©ABB
7/5/20 | Slide 3
Bus fault protection
Easy to detect because of robust nature
Easy to protect for internal faults (87B)
Summation of currents not equal to zero for internal fault
External faults can cause current transformer saturation
which results in unwanted differential currents
Infrequent, but must be cleared with high speed for internal
fault and stable for external faults
Substation is well shielded
Protected environment
©ABB
7/5/20 | Slide 4
Bus configurations
Single bus
Main and transfer bus
Double bus, single breaker
Double bus, double breaker
Breaker and a half
Ring bus
©ABB
7/5/20 | Slide 5
Single bus
©ABB
7/5/20 | Slide 6
Main and transfer bus
©ABB
7/5/20 | Slide 7
Double bus single breaker
Advantages
1. Permits some flexibility with two operating
buses.
2. Either main bus may be isolated for
maintenance.
3. Circuit can be transferred readily from one
bus to the other by use of bus-tie breaker
and bus selector disconnect switches.
Disadvantages
1. One extra breaker is required for the bus
tie.
2. Four switches are required per circuit.
3. Bus protection scheme may cause loss of
substation when it operates if all circuits are
connected to that bus.
4. High exposure to bus faults.
5. Line breaker failure takes all circuits
connected to that bus out of service.
6. Bus-tie breaker failure takes entire
substation out of service.
©ABB
7/5/20 | Slide 8
Double bus, double breaker
Advantages
1. Each circuit has two
dedicated breakers.
2. Has flexibility in permitting
feeder circuits to be connected
to either bus.
3. Any breaker can be taken out
of service for maintenance.
4. High reliability.
Disadvantages
1. Most expensive.
2. Would lose half of the circuits
for breaker failure if circuits are
not connected to both buses.
©ABB
7/5/20 | Slide 9
Breaker and one half
Advantages
1. Most flexible operation.
2. High reliability.
3. Breaker failure of bus side breakers
removes only one circuit from service.
4. All switching is done with breakers.
5. Simple operation; no disconnect switching
required for normal operation.
6. Either main bus can be taken out of service
at any time for maintenance.
7. Bus failure does not remove any feeder
circuits from service.
Disadvantages
1. 1 1/2 breakers per circuit.
2. Relaying and automatic reclosing are
somewhat involved since the middle breaker
must be responsive to either of its associated
©ABB
circuits
7/5/20 | Slide 10
Ring bus
Advantages
1. Low initial and ultimate cost.
2. Flexible operation for breaker maintenance.
3. Any breaker can be removed for maintenance without
interrupting load.
4. Require only one breaker per circuit.
5. Does not use main bus.
6. Each circuit is fed by two breakers.
7. All switching is done with breakers.
Disadvantages
1. If a fault occurs during a breaker maintenance period, the
ring can be separated into two sections.
2. Automatic reclosing and protective relaying circuitry rather
complex.
3. If a single set of relays is used, the circuit must be taken out
of service to maintain the relays. (Common on all schemes.)
4. Requires potential devices on all circuits since there is no
definite potential reference point. These devices may be
required in all cases for synchronizing, live line, or voltage
indication.
5. Breaker failure during a fault on one of the circuits causes
loss of one additional circuit owing to operation of breaker-
failure relaying.
©ABB
7/5/20 | Slide 11
Main-Tie-Main
©ABB
7/5/20 | Slide 12
Some issues
©ABB
7/5/20 | Slide 13
Zones of protection
Station A Station B
G
G
G
Station C
Bus
Station D
protection
M
©ABB
7/5/20 | Slide 14
Zones of protection
CT for CT for
Green Zone Blue Zone
Green Zone
Blue Zone
Dead tank breaker,
two CTs
©ABB
7/5/20 | Slide 15
Zones of protection
CT for
Green Zone CT for
Blue Zone
Green Zone
Blue Zone
Live tank breaker,
single CT
©ABB
7/5/20 | Slide 16
Current Transformers: Equivalent circuit of a CT
7/5/20 l Slide 17
Current transformer
Ratings of concern for bus protection
Ratio: 200/5, 1200/5, …500/1
Burden capability: VA burden
Accuracy Class: C800, K200, T400
Knee point, saturation voltage (can be derived from
chart in C class CTs)
CT availability
IEEE Standard C57.13-1993 (R2003), IEEE Standard
Requirements for Instrument Transformers
IEEE Standard C37.110-1996, IEEE Guide for the
Application of Current Transformers Used for Protective
Relaying Purposes
©ABB
7/5/20 | Slide 18
Steady State Performance of CT
1000
500 V
VSM
VX C400
230 V 10% error for 20 times rated
VK
secondary current (5 A)
Secondary Excitation Voltage, VS
1
0.001 0.01 0.1 1.0 10 100
Secondary Excitation Current, IE
ANSI current transformer accuracy class
©ABB
7/5/20 | Slide 20
ANSI accuracy class
Standard chart for class C current transformers
©ABB
7/5/20 | Slide 21
CT saturation
©ABB
7/5/20 | Slide 23
CT saturation
CT secondary model
a perfect current source in parallel with an exciting
impedance branch that drives proportional current
Exciting impedance is normally very high
At saturation, exciting impedance drops to a very low value
the CT appears short-circuited
neither delivers nor resists current flow
Time to saturation is important in low impedance bus
protection
©ABB
7/5/20 | Slide 24
Issues effecting bus protection selection
Bus arrangement
Fixed
Switchable
Availability and characteristics of current transformers
Performance requirements
Speed
Dependability
Security
Sensitivity (for high impedance grounded system)
©ABB
7/5/20 | Slide 25
Types of bus protection
Differential
Differentially connected overcurrent
Percentage-restrained differential (low Z)
High impedance differential
Partial differential
Zone interlocked scheme
Back up schemes (eg. remote over-reaching zones)
©ABB
7/5/20 | Slide 26
Differentially connected over-current relay
51
©ABB
7/5/20 | Slide 27
External fault case
Protected Bus
= FAULT
LOCATION
IE
IT TOTAL OUT OF
TOTAL INTO BUS BUS MINUS IE
TOTAL OUT
OF BUS
Relay I d = IE
©ABB
7/5/20 | Slide 28
Internal fault case
Protected Bus
I1 I2 I3 I4
Id
Id = I + I + I +
1 2 3 I4
Overcurrent relay bus differential
Application OK if:
Protected bus
Symmetrical CT secondary current
less than 100
Burden less than rated
Typical pickup setting IPU > 10A
Trip delay greater than 3 x primary
time constant (L/R) Id
©ABB
7/5/20 | Slide 30
Multiple restraint Percentage Differential (Legacy)
PROTECTED BUS
A B C D
©ABB
7/5/20 | Slide 32
Multiple restraint Percentage Differential (Legacy)
PROTECTED BUS
A B C D
©ABB
7/5/20 | Slide 33
Torque for typical multi-restraint relay
Operating
Torque
Two Restraint
One Restraint
0 20 40 60 80 100
Amperes
©ABB
7/5/20 | Slide 34
Torque for typical multi-restraint relay
55 A. of restraint overcomes 7 A
Operating of operating current with one
Two Restraint restraint winding
Torque
One Restraint
0 7 20 40 55 60 80 100
Amperes
©ABB
7/5/20 | Slide 35
Multi-restraint percentage differential
Good sensitivity
Good security
Allows other relays on the same CT core
Different CT ratios with Aux CTs.
Slow compared to high impedance
Number of feeders limited by restraint windings
Each CT is wired to relay
Not easily extendable
©ABB
7/5/20 | Slide 36
High impedance bus protection
High resistor (R > 1500 ohm) in
series with relay coil and a MOV to
prevent over-voltages
High voltage develops for internal
faults. lower Voltage will develop on
external faults under ct saturation
Voltage unit must be set higher than
the maximum junction point voltage
for any external fault
The lowest achievable sensitivity
must verified for the application
R
Proven reliability and very sensitive
Operating times of less than one
cycle for internal faults
©ABB
7/5/20 | Slide 37
High impedance bus protection
EXTERNAL FAULT - SECURITY
Setting VR > (IF / N ) ( RL +R S)
K = margin factor
IF = Max external fault current
RS = Ct secondary resistance
RL = Lead resistance to junction box
N = ct turns ratio
X = number of circuits
IE = Ct exciting current at VR
IR = resistor current at VR
IV = Varistor current at VR
©ABB
7/5/20 R > 1500 W
| Slide 38
High impedance bus protection
Criteria to be met
Objective: Keep VR and Imin low
Ct secondary loop resistance kept low
Impedance from junction point to relay is of no consequence so
good practice to parallel the CTs as close to the CTs as possible.
Theoretically no limitations in the number of parallel CTs but
sensitivity reduced with each parallel connection
Setting VR higher that the CT rated voltage (400V for C400 CTs)
will produce errors when estimating CT exciting branch current,
hence inaccurate sensitivity calculation.
All cts must have the same ratio and magnetizing characteristics
©ABB
7/5/20 | Slide 39
Differential comparator (Legacy, Static type)
RADSS/REB103
Developed to lessen restrictions
imposed by high impedance
All CT secondary circuits connected via
interposing cts
Connection made using a special diode
circuit producing rectified incoming,
outgoing and differential currents
AUX CTs
IOUT SR
IDIFF
DR
IIN
©ABB
7/5/20 | Slide 40
Differential comparator
Single phase connection
IIN is sum of all feeder instantaneous
positive values
IOUT is sum of all feeder instantaneous
negative values
IDIFF = IIN - IOUT
AUX CTs
Start
IDIFF VOp
IOUT Trip
VRes
IIN
©ABB
7/5/20 | Slide 41
Differential comparator
L1 L1
L2 L2
Internal
L3 L3
L4 L4
L1 L2 L3 L4
X
IIN IIN
External
IOUT IOUT
IDIFF IDIFF
External Internal
©ABB
7/5/20 | Slide 42
Differential comparator
Single phase connection
IDIFF is typically small (normally 0) for
external fault and restraint voltage, VRes, is
greater than operating voltage, VOp.
IDIFF is typically large for an internal fault
and operating voltage, VOp, is greater than
restraining voltage, VRes. This produces
AUX CTs voltage across trip relay.
Trip / LO
Start Start
IDIFF VOp
Trip
IOUT Trip
VRes
IIN
©ABB
7/5/20 | Slide 43
Numerical differential comparator
Analog input currents are instantaneously sampled and
quantized to numerical number
Similar technique to legacy differential comparator, but
with measured sampled data
Secondary circuit loop resistance no longer a critical
factor
Critical factor is time available to make the
measurement, i.e. time to saturation. (only 3ms required
to properly restrain for heavy external faults)
Algorithms for Ct saturation Detection and CT state
supervision
©ABB
7/5/20 | Slide 44
Differential comparator
©ABB
7/5/20 | Slide 46
Differential comparator
Advantages over high impedance differential
Lower ct requirements
Allows much higher ct loop resistances
Accommodate different CT ratios / auxiliary CTs
Fast operating times for internal faults
Detects internal 1 - 3 ms
Before ct saturation
©ABB
7/5/20 | Slide 47
Quick operation for internal fault
Internal Fault
16
14
12 REB 670 detects that
10
I_IN goes up while i_in
Curre n t
41
51
81
16
21
26
31
36
46
56
61
66
71
76
1
6
Samples
©ABB
7/5/20 | Slide 48
Proper & secure restrain during external fault
External Fault REB 670 detects this short
interval when i_in=i_out
(after every fault current
16
zero crossing) and restrain
properly during external
14
fault
12
REB 670 detects that
I_IN=I_OUT at the
10
beginning of the i_in
Cu rre n t
0
13
17
21
29
33
37
45
49
57
61
65
69
73
77
81
25
41
53
1
Samples
©ABB
7/5/20 | Slide 49
Fast open CT algorithm
REB 670 detects that I_IN
Open CT
doesn't change while
I_OUT goes down when
1,6 some of the CTs is
open/short circuited
1,4
1,2
1
i_in
Cu rren t
0,2
0
17
53
13
21
25
29
33
37
41
45
49
57
61
65
69
73
77
81
1
Samples
©ABB
7/5/20 | Slide 50
Other Features in Modern Numerical Bus IEDs
Each device capable of connecting multiple bays (eg. CTs) in 3-ph
or 1-ph design
Multiple differential zones, dynamic bay switching, zone
interconnection, and check zone logic
External fault/CT saturation detection, open CT detection
algorithms
Blind zone protection (see next 2 slides)
End zone protection (see next 2 slides)
Backup protection (eg. 50/51, 50BF) for each connected bay
Modern substation automation communication (DNP 3.0,
IEC61850)
©ABB
7/5/20 | Slide 51
Blind zone detection for bus coupler bays
Blind zone between live tank CT and breaker
Fault strikes in the blind zone
Tie bkr normally closed: ZA operates but
Zone B restrains -> the fault is persisting
Tie bkr normally open: ZA operates
unnecessarily and ZB restrains
Solution: connect BKR NC (open) status to
the bay to remove the tie CT from ZA, ZB
(software)
ZA will then restrain and ZB operates
properly for the blind zone fault
©ABB
7/5/20 | Slide 52
Blind zone detection for feeder bays
Regions not overlapped by both red and
blue boundaries are blind zones
CTs are used for both feeder and bus
protection measurement (live tank CTs)
Common in HV 1-1/2 stations
For 3. measuring CT can be removed
(BBP) to avoid over-tripping on open pos.
Fast OC set up to DTT (open pos)
For 4. measuring CT can be removed
(BBP) to force tripping on open pos
(feeder protection operates first)
©ABB
7/5/20 | Slide 53
Other distribution (MV) bus protection methods
Partial differential
Blocking on feeder fault
©ABB
7/5/20 | Slide 54
Partial differential
©ABB
7/5/20 | Slide 55
Blocking scheme
©ABB
7/5/20 | Slide 56
Conventional Blocking Scheme
Zone of protection
T+100 ms
Traditional busbar
I> 100 ms protection based on
I>>
upstream blocking
blocking
Dedicated hard-wire
I> signal paths needed
I>>
Signal path delay needs
to be considered, input
Delay setting with inst. O/C protection
(conventional approach)
and output delay +
Safety marginal, e.g. delay in operation 20…40 ms auxiliary relays
due to CT saturation.
O/C protection start delay + output relay’s <40 ms Changes in the protection
delay
scheme may require re-
Start delay with receiving relay + retarding
time for the blocking signal *)
<40 ms
wiring
ALL TOGETHER 100…120 ms Typical needed delay in
incoming relay is over 100 ms
Blocking Scheme with IEC-61850 GOOSE
©ABB
7/5/20
| Slide 59
Questions?
Recommended reading
©ABB
7/5/20 | Slide 60
Thank you for your participation
For more
information on ABB’s protection and control solutions, visit:
www.abb.com/relion
Please subscribe to our YouTube channel to view recorded webinars and technical training
www.youtube.com/ABBSAProductsNAM
© ABB Group
7/5/20 | Slide 61