Design catalogue NXAIR


≤ 17,5 kV, ≤ 40 kA, busbar ≤ 4000 A, feeder ≤ 4000 A

Author / Originator Department Telephone Version Date


Herbert Soens IC LMV MS GI TSS +49 9131 7 33776 1.0 – 33.0 17.06.2010 –
24.10.2012
Ralf Weichert EM MS S PLM AIS +49 9131 7 21227 34.0 – 55.0 25.04.2013 –
15.11.2021
Ralf Weichert SI DS S PLM-AIS +49 9131 17 31681 55.1 01.12.2021
Ralf Weichert SI EA PLM MV-AIS PRI +49 9131 17 31681 56.0 03.08.2021
Ralf Weichert SI EA PLM MV-AIS PRI +49 9131 17 31681 57.0 02.05.2022
Ralf Weichert SI EA PLM V-AIS PRI +49 9131 17 31681 58.0 02.06.2022
Ralf Weichert SI EA PLM V-AIS PRI +49 9131 17 31681 59.0 15.08.2022
Ralf Weichert SI EA PLM MV-AIS PRI +49 9131 17 31681 60.0 30.03.2023
Ralf Weichert SI EA PLM MV-AIS PRI +49 9131 17 31681 61.0 10.10.2023

Draft

Release X

Paper Released by:

Name Function Department Date Signature

Kaan Bilge R&D Project Engineer SI EA R&D AIS 04.09.2023

Bidar Aykoc R&D Project Engineer SI EA R&D AIS 04.09.2023

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 1 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

Distribution list:
Name Function Department Date Signature

current version generally included in intranet

Continuous Recording of Changes


In this overview, enter changes as against the released / distributed documents only

Revised chapters New issue Object and reason for change /


or pages Reference to change requests
00 -33 Revisions see version 24.10.2012
34  Addition of CB-typicals for 1600A and 2000A feeder current (up to 31,5kA and busbar
currents up to 2500A) and some different changes (marked yellow)
35  Integration of 2500A and 3150A panels (800mm with forced ventilation) for 40kA
36  Integration of SION M (3AE55) in 600mm-panels (12kV, 25kA, 630A feeder current)
37  Changes in typical “Bus sectionalizer type II” regarding ventilation and dimensions,
 2000A for 40kA deleted
 changed design for metering module an VT
38  Additional version with busbar current of 2000A
 labels in Spanish available
 additional pressure relief duct devices
 adding of additional switching duties for CB
 changed ratings of the HV-fuses for VT
39  Vacuum contactor panel with 600mm panel width and 3TL8 for 7,2kV
40  New typical for ≤17,5kV ≤31,5kA and busbar ratings 3150A and 4000A in 600mm
 integration of SION M31 (17,5kV, 25kA and 12kV 31,5kA)
 additional extended CT 4MA72 Size 4 and size 6 for ratings ≤ 2500A
33, 35, 39 41  Addition of different variants of openings times for 3TL8
 Adding of control transformers for CFC for 3,0 kV; 3,3 kV and 3,6kV
 Adding supplement drawings into standard accessories set and creating separate
MLFB for German, Spanish and English language
 Adding additional explanation for optical arc limitation system and pressure switch
system regarding engineering topics
42  New Typical 1000A for 40kA in 800mm panel width
 HRC fuses from INTRATEK for VT’s with integrated fuse
43  Integration of circuit breaker 3AE5 for
o ≤ 12kV, 25 kA and 31,5 kA, 2500 A
o 17,5 kV, 25 kA, 2500 A
o 17,5 kV; 31,5 kA, 800 A, 1250 A and 2500 A
 Delete CB panels up to 17,5kV, up to 31,5kA (1600A version and 2400A)
 Integration of 3AE5 25kA 1600A in replacement of 3AE5 31,5kA 1600A for CB panel
1250A 25kA
 Revised permissible current ratings for busbar and feeder up to 2500 A
44  Integration of 3TM into vacuum contactor panels with 435mm panel width,
 blocking selection of “VT with PTB approval”
 new surge arrester type 3EJ integrated
45  Integration of switch-disconnector panel with HRC fuses (SDF-panel) for ≤ 17,5 kV, ≤
31,5 kA, ≤ 4000 A
46  Integration of new typical 2000 A for 31,5 kA and 3150 A / 4000 A busbar currents
 withdrawable VT for panels with 600 mm width
 selection of Inter-teknik fuses for vacuum contactor panels as option to SIBA possible
 increased permissible current ratings for natural ventilated versions of 2500 A and
3150 A feeder

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 2 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

Revised chapters New issue Object and reason for change /


or pages Reference to change requests
47  Marine application, special design for up to 12 kV, up to 40 kA and up to 2500 A
busbar current
 changed technical data (electrical endurance) for 3TM3
 release of 3rd shunt release for 3AE5

48  Integration of SIQuench and special ratings for VT (for Columbia)


8, 9, 15 48.1  Changed interlocking conditions for withdrawable VT in panel with 600 mm width
10, 11, 21 49  Busbar Earthing switch in top box for Bus sectionalizer for 1250 A available
 addition of electromagnetic interlocking coils for 120 V AC and 220 V AC for cassette
and earthing switch
 Phase out of 2500 A and 3150 A typicals in 800 mm width (forced ventilated) and
vacuum contactor panel 7,2 kV in 600 mm width
 Deleting of disconnector panel 1000 A for 40 kA in 800 mm width
 New hand lever for switch disconnector panel with fuses
50  Integration SION M40 tested acc. IEC 62271-100
 Deleting circuit breaker/disconnector panel 1000 A for 40 kA
 upgraded version of circuit breaker/disconnector panel 2000 A for 40 kA
 new absorber logic
 technical changes for 3TM
o new auxiliary switch 6NC + 6NO
o changes in additional closing and opening delay times
o new controller for aux. voltages 110-125 VDC / 100-120 VAC and 220-250 VDC /
230-240 VAC
 HV-fuse for VT as spare parts added
 Transverse partition for 3150 A / 4000 A for 25 kA and 31,5 kA as option (no more in
standard)
51  Integration SION M40 tested acc. to IEC/IEEE 62271-37-013
 addition of following measures (DTO into standard):
o Entry of LV cables from the top in LV box
o Motor operated cassette for disconnector link
o Pressure resistant floor cover in double layer made in insulation material for
connection compartment
 New metering panel for ≤ 17,5kV, ≤ 31,5 kA, ≤ 4000 A in 600 mm width
52  addition of following measures (DTO into standard):
o Handrails on panel’s front side
o Handrails on panel’s rear side
o Surge arrester type 3EK in top box at the busbar
 new controller for aux. voltages 24-60 VDC incl. changed closing and opening delay
times
 new MLFB-structure for 3TM (16. position incl. language of manuals)
 revised permissible current ratings for 630 A feeders for 25 kA and 31.5 kA
5-7, 30, 36, 58, 59, 94- 53.0  addition of following measures (DTO into standard):
96 o Pressure relief outlet to the top
o Zero-CT in deep bottom pan
o Degree of protection IP31/IP32/IP41/IP42
 Addition of coupling element for testing equipment for pressure switch in accessories
54.0  addition of following measures (DTO into standard):
o Thermal inspection window
o Zero sequence CT type 4MC4_40 installed in cable connection compartment
 changed HV-fuses for SDF-panels for 500 kVA and 630 kVA transfomer
 new table with operating times at rated voltage of the secondary circuit depending on
release combinations
 changed ordering code for 3TM (routine test protocoll)
55.0  addition of following measures (DTO into standard):
o Door retrainer for HV-door
o Door retrainer for LV-door
o Special edge protection for wiring of auxiliary circuits
 Changed type of fan for forced ventilated panels (4000 A)
 Updated installation manual for IPX1 / IPX2 roof for NXAIR and NXAIR for marine
application (german and english)
8, 15, 59 55.1  Restriction for thermal inspection window in combination with surge arrester and fixed
mounted VT
 new LSC-categorization based on IEC 62271-200 Edition 3

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 3 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

Revised chapters New issue Object and reason for change /


or pages Reference to change requests
74 56.0  addition of duplex version (front-to-front and back-to-back arrangement)
57.0  addition of bushing type CT 4MD17 in CB-panels of bus sectionalizer (1250 A, 2000 A
and 2500 A)
10, 15, 72, 73 58.0  height and width adjustable service truck for 600 mm 800/1000 mm panels
 installation manual, operation manual and supplement drawings for IP-roof in Turkish
available
 addition of terminal lugs for connection of earthing bar to station earth in accessories
 additional interlocking (facility for padlocking w/o padlock)
46, 47, 72, 74, 116, 128 59.0  change of rated short-time withstand current rating for earthing circuits depending on
neutral point grounding
 change switching capability of earthing switch in vacuum contactor panel
 new supplier for fan (for forced ventilated panels)
 implementation of “voltage detecting and indicating system VDIS” acc. IEC62271-213
53, 85, 87, 133 60.0  addition of capacitive voltage indication systems type OVI+ S and OVI+ SR
 new wall outlet box with 0,224 m length for pressure relief duct
 release of improved hand lever for operation of SDF-panel (8BX2042-1CC39)
7, 54, 86, 87, 114, 115, 61.0  selection of earthing of MV- and LV-door with braided copper strap as option
116, 118, 119  selection of optical arc fault detection system type Arcteq
 selection of optical arc fault detection system type SIPROTEC
 additition of bushing type insulator 4ME as LPIT
 addition of Zero-sequence CT type Zelisko as LPIT
 addition of fuse trip indication for metering unit in metering panel
 extension to up to 4 cables per phase 630 mm² in cable connection compartment for
≤ 17.5 kV, ≤ 40 kA, 1250 A, 2000 A and 2500 A feeder
 extension to up to 6 cables per phase 630 mm² in cable connection compartment for
≤ 17.5 kV, ≤ 40 kA, 3150 A and 4000 A feeder
 KP Glow lamp voltage tester with operation rod suitable for 50 Hz and 60 Hz
 addition of an outlet flap (weatherproof) for pressure relief channel
 Supplementary Instructions - Installation of the low-voltage compartment for NXAIR
 table with released type cable lugs depending on cross section of HV-cable
 Cancellation of zero sequence transformer 4MC9602 (split core ct with 80 mm inner
diameter

Note for Use:


The individual requirements must be included in the function specification in a table of requirements. During
the reviews to the main milestone it must be checked and documented whether the requirements were
implemented. To do this, use the requirement tracing matrix.

Attention:
All red marked text blocks are not valid at the moment and blocked in NXTools+
All yellow marked textblocks are updated against previous version of design catalogue

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 4 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

Content Page
1 Switchgear specification for NXAIR in standard design 9

1.1 Technical data 9


1.2 Busbars 10
1.3 IAC resistance and pressure relief 10
1.4 Design features 11
1.5 Processing 13
1.6 Table of selectable versions of type of operating mechanism, interlocking systems and auxiliary 14
voltages
1.7 Electromagnetic and Ronis interlocking and padlock options for manual or motor driven busbar 15
earthing switch
1.8 Combinations of rated auxiliary voltages, if selected (without circuit breaker) 16
1.9 selectable versions of mechanism in combination with interlocking systems for SDF panel 16
1.10 selectable versions of mechanism in combination with interlocking systems for SIQuench 16
1.11 Padlocking facilities (hand and motor operated) 16
1.12 Rated supply voltages 17
2 Switchgear specification in design for NXAIR for marine and offshore application 18
2.1 Technical data 18
2.2 Busbars 20
2.3 Special design options for marine application 20
2.4 Design features 21
2.5 Processing 21
2.6 Table of selectable versions of type of operating mechanism, interlocking systems and auxiliary 21
voltages
2.7 Electromagnetic and Ronis interlocking and padlock options for manual or motor driven busbar 21
earthing switch
2.8 Combinations of rated auxiliary voltages, if selected (without circuit breaker) 21
2.9 selectable versions of mechanism in combination with interlocking systems for SDF panel 21
2.10 selectable versions of mechanism in combination with interlocking systems for SIQuench 21
2.11 Padlocking facilities (hand and motor operated) 21
2.12 Rated supply voltages 21
3 Panel specification – single busbar 22
3.1 Components in basic versions 22
3.1.1 Circuit breaker panel 22
3.1.2 Contactor panel 26
3.1.3 Metering panel 26
3.1.4 Switch-disconnector panel with HRC fuses (SDF panel) 27
3.1.5 Busbar current metering panel 27
3.1.6 Bus sectionalizer 28
3.1.6.1 Bus sectionalizer type 1 31
3.1.6.2 Bus sectionalizer type 2 33
3.1.7 Busbar connecting panel 34

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 5 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

Content Page

4 Panel specification – duplex in back-to-back arrangement 35


4.1 Components in duplex versions in back-to-back arrangement 36
4.1.1 Circuit breaker panel 36
4.1.2 Bus coupler 40
5 Panel specification – duplex in front-to-front arrangement 44
5.1 Components in duplex versions in front-to-front arrangement 44
5.1.1 Circuit breaker panel 44
6. Configuration of panels 48
6.1 Panel types 48
7 Components 53
7.1 Capacitive voltage detection system (CVD) 54
7.2 Panel connection – cable compartment 54
7.3 Panel connection - busbar compartment 54
7.4 Bushing type insulators 54
7.5 Earthing switch 55
7.6 Block type current transformer 4MA72 – PL 57
7.7 Block type current transformer 4MA72 – size 2 (extended version) 57
7.8 Block type current transformer 4MA72 – size 4 58
7.9 Block type current transformer 4MA72 – size 6 59
7.10 Block type current transformer 4MB61 – size 2 60
7.11 Block type current transformer 4MA72 – PL for SDF panel 60
7.12 Bushing type current transformer 4MD17 for bus sectionalizer 61
7.13 Bushing type insulator 4ME17 with LPIT 61
7.14 Zero sequence current transformer – with conventional technology 63
7.15 Zero sequence current transformer – with LPCT technology 64
7.16 Voltage transformer 4MR12 65
7.17 Surge arrester 3EJ / 3EK 66
7.18 Withdrawable part 66
7.19 Portable earthing devices 66
8 Vacuum circuit breaker 67
8.1 VCB 3AE5 – 12 kV- 25 kA (tested acc. IEC 62271-100) 67
8.2 VCB 3AE5 – 12 kV- 31.5 kA (tested acc. IEC 62271-100) 68
8.3 VCB 3AE5 – 12 kV- 40 kA (tested acc. IEC 62271-100) 69
8.4 VCB 3AE5 – 17.5 kV- 25 kA (tested acc. IEC 62271-100) 70
8.5 VCB 3AE5 – 17.5 kV- 31.5 kA (tested acc. IEC 62271-100) 71
8.6 VCB 3AE5 – 17.5 kV- 40 kA (tested acc. IEC 62271-100) 72
8.7 VCB 3AE2 - 7,2 kV, 12 kV and 15 kV – 25 kA (tested acc. IEC/IEEE 62271-37.013) 73
8.8 VCB 3AE2 - 7,2 kV and 12 kV – 31.5 kA (tested acc. IEC/IEEE 62271-37.013) 74
8.9 VCB 3AE2 - 15 kV / 17.5 kV – 31.5 kA acc. (tested acc. IEC/IEEE 62271-37.013) 75

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 6 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

Content Page

9 Vacuum contactor incl. HRC-fuses and control transformers 76


9.1 Vacuum contactor 3TM 76
9.2 Control transformer 77
9.3 Fuse motor application for vacuum contactor 77
9.3.1 Type SIBA 77
9.3.2 Type Inter-teknik 77
9.4 Fuses for withdrawable voltage transformers resp. control transformer of contactor panel 78

10 Switch-disconnector- fuse combination incl. HRC-fuses 78


10.1 Switch disconnector – fuse combination L-TRI 5 F 78
10.2 HV-fuses for switch-disconnector – type SIBA 79
11 SIQuench 80

12 Optical arc fault detection system 82

13 Accessories 85

14 Spare parts 87

15 Additional tables 88
15.1 Technical standards 88
15.2 Dimensions 89
15.3 Loss of service continuity class 90
15.4 Partition class 90
15.5 Access to compartments 91
15.6 Degree of protection 91
15.7 Creepage distances, clearance in air 91
15.8 Internal arc fault classification 92
15.9 Type tests in accordance to IEC 62271-1 resp. IEC 62271-200 93
15.10 Routine tests in accordance to IEC 62271-1 resp. IEC 62271-200 93
16 Permissible current values 94
16.1 ≤ 12 kV, 50 Hz, 25/31.5 kA, ≤ 2500 A 94
16.2 ≤ 12 kV, 60 Hz, 25/31.5 kA, ≤ 2500 A 96
16.3 17.5 kV, 50 Hz, 25 / 31.5 kA, ≤ 2500 A 98

16.4 17.5 kV, 60 Hz, 25 / 31.5 kA, ≤ 2500 A 100

16.5 ≤ 12 kV, 50 Hz, 40 kA, ≤ 4000 A or 25/31,5 kA with 3150/4000 A busbar 102

16.6 ≤ 12 kV, 60 Hz, 40 kA, ≤ 4000 A or 25/31,5 kA with 3150/4000 A busbar 104

16.7 17.5 kV, 50 Hz, 40 kA, ≤ 4000 A or 25/31,5 kA with 3150/4000 A busbar 106
16.8 17.5 kV, 60 Hz, 40 kA, ≤ 4000 A or 25/31,5 kA with 3150/4000 A busbar 108
16.9 ≤ 12 kV, 50 Hz, 25/31.5 kA, ≤ 2500 A – bus sectionalizer with bushing type CT 4MD17 110
16.10 ≤ 12 kV, 60 Hz, 25/31.5 kA, ≤ 2500 A – bus sectionalizer with bushing type CT 4MD17 111
16.11 17.5 kV, 50 Hz, 25 / 31.5 kA, ≤ 2500 A – bus sectionalizer with bushing type CT 4MD17 112

16.12 17.5 kV, 60 Hz, 25 / 31.5 kA, ≤ 2500 A – bus sectionalizer with bushing type CT 4MD17 113

16.13 Combination of components in connection compartment 114


16.14 Combination of components in busbar compartment 117
16.15 Released type of cable lugs 118

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 7 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

Content Page

17 Technical data of components 122


17.1 Technical data of vacuum circuit breaker 3AE5 (tested acc. to IEC 62271-100) 122
17.2 Technical data of vacuum circuit breaker 3AE2 (up to 31,5 kA tested acc. to IEC/IEEE 62271-37- 123
013)
17.3 Technical data of vacuum contactor 3TM3 125
17.4 Technical data of contactor fuse combination for motor or transformer application 126
17.5 Technical data of switch-disconnector- fuse combination L-TRI 5F 133
17.6 Technical data of SIQuench (Arc Quenching Device) 134
17.7 Technical data of earthing switches with short circuit making capacity 134
17.8 Technical data of withdrawable part for circuit breaker, disconnector link, metering module 135
17.9 Switching classifications of breaker, withdrawable part, earthing switch 135
17.10 Position indication of electrical devices 135
17.11 Power consumptions of electrical devices 135
17.12 Configuration information pressure release system (standard) 136
17.13 Climate and ambient influences 142
17.14 Protection of voltage transformers with fuses, technical argumentation 143
17.15 Application of surge arrestors 143
17.16 Packing dimensions and transport weights (tare) of packing 143
17.17 Weights of panels (appr., net weight) 144
17.18 Transport and storage information 144
17.19 Painting, surface treatment 144
17.20 Cross section of earthing bar 144
17.21 Thickness of used steel sheets 144
17.22 Material of bottom plate in cable connection compartment 145
17.23 Interlocks 145
17.24 Used materials (average values) 145
17.25 Fire loads 145
17.26 Dynamic loads 145
17.27 Fixing hardware 145
17.28 Heat losses at rated current 146
17.29 Maintenance 146
17.30 Spare parts 146
17.31 Fan (used for forced ventilation) 146

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 8 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

1 Switchgear specification for NXAIR in standard design


1.1 Technical data
Standard  IEC 62271-200  GOST 1)  IEC 62271-200  GOST 1)  IEC 62271-200
Rated voltage Ur  7.2 kV  12 kV  17.5
Rated lightning impulse withstand  60 kV  60 kV  75 kV  75 kV  95 kV
voltage Up
(phase/phase, phase/earth, open
contact gap)
Rated lightning impulse  70 kV  70 kV  85 kV  85 kV  110 kV
withstand voltage Up 2)
(isolating distance)
Rated short time power  20 kV  32 kV  28 kV  42 kV  38 kV
frequency withstand voltage Ud
(phase/phase, phase/earth, open
contact gap)
Rated short time power  23 kV  36 kV  32 kV  48 kV  45 kV
frequency withstand voltage Ud 2)
(isolating distance)
Operating voltage UN  3.0 kV  6.0 kV  6.0 kV  10.0 kV  10 kV
 3.3 kV  6.3 kV  6.3 kV  10.5 kV  10.5 kV
 4.16 kV  6.6 kV  6.6 kV  11.0 kV  11 kV
3)
 4.8 kV  10.0 kV  11.4 kV
 5.0 kV  10.5 kV  12.8 kV
 6.0 kV  11.0 kV  13.2 kV
3)
 6.3 kV  11.4 kV  13.8 kV
 6.6 kV  15 kV
 15.4 kV
Rated frequency fr  50 Hz  50 Hz  50 Hz
 60 Hz  60 Hz  60 Hz
Rated short-time withstand  25kA  31.5 kA  40 kA  25 kA  31.5kA  40 kA  25 kA  31.5kA  40 kA
current Ik
Rated peak withstand current Ip  63kA  80 kA  100 kA  63 kA  80kA  100 kA  63 kA  80kA  100 kA
for 50 Hz
Rated peak withstand current Ip  65kA  82 kA  104 kA  65kA  82 kA  104 kA  65kA  82 kA  104 kA
for 60 Hz
Rated short-circuit duration tk  1s
 3s
Ambient temperature 4)  30 °C
 35 °C
 40 °C
 45 °C
 50 °C
 55 °C
6)
Degree of protection  IP 3XD
 IP 31
 IP 32
 IP 4X
 IP 41
 IP 42
 IP 5X 5)
 IP 51 5)
Sea level (m)  ≤ 1000

1) GOST = Russian standard, but only general insulation levels of GOST standard can be fulfilled, for contactor panel GOST values only for 7.2 kV, only
selectable for SPC Turkey (Gebze)
2) only applicable for SDF panels due to LSC2 design
3) only for SPC Mexico
4) switchgear is designed for ambient temperatures between -25°C and +55°C
5) general only for non-ventilated panels possible, additionally only in combination with channel system to lead the gases outside switchgear room, see also
accessories chapter 12 and 16.12
6) in combination with IPX1 or IPX2 no cable connection or bar connection in top box at the busbar possible, IPX1 or IPX2 not possible for duplex in back-
to-back arrangement

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 9 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

1.2 Busbars
Rated continous current and  1250 A; (1 x 80 mm x 10 mm, copper)  3150 A, (3 x 120mm x 10 mm, copper)
dimensions
 2000 A; (2 x 80 mm x 10 mm, copper) – not for 40 kA  4000 A, (3 x 120 mm x 10 mm, copper)
 2500 A, (2 x 100 mm x 10 mm, copper)
Busbar insulation  Optionally with (insulated horizontal busbars for SDF in standard)
1)
Busbar transverse partition  Optionally with

1) always in standard for 40 kA panels, contactor panels and for SDF (partition on both sides necessary)

1)
1.3 IAC resistance and pressure relief
Resistance to internal arc faults  IAC A FLR, 1 s (standard version)
 IAC A FLR, 1 s (standard version), additionally pressure switches for all three compartments without
testing device
 IAC A FLR, 1 s (standard version), additionally pressure switches for all three compartments with testing
device
 IAC A FLR, 1 s (standard version), additionally with arc flash protection via Arcteq make light point
sensors (requires use of Arcteq make arc flash protection relays), without selective tripping, limiting arcing
time to max. 100 ms 6)
 IAC A FLR, 1 s (standard version), additionally with arc flash protection via Arcteq make light point
sensors (requires use of Arcteq make arc flash protection relays), with possibility for selective tripping of
the outgoing feeder CBs, limiting arcing time to max. 100 ms 6)
 IAC A FLR, 1 s (standard version), additionally with arc flash protection via SIPROTEC light point sensors
(requires use of SIPROTEC 5 relays and arc protection modules), with possibility for selective tripping of
the outgoing feeder CBs, limiting arcing time to max. 100 ms 6)
 IAC A FLR, 1 s (standard version), additionally with optical sensors for all three compartments per typical
SIQuench and controller at the busbar system 3)
Confinement of internal arc Standard, only up to and including 31,5 kA for 1 sec, but not for contactor panel 435 mm and SDF panel
within compartments (pressure
tied partitions) 2)
Pressure relief with absorber to  Optionally with
release gases inside switchgear
room
Pressure relief duct to release Optionally with adaption of the duct at the left side
gases outside switchgear room
Optionally with adaption of the duct at the right side
5)
Optionally with adaption of the duct at the rear side
4)
Optionally with adaption of the duct at the top

1) must be ordered depending on room heights, internal arc value etc, see also table in chapter 1.3; special channel devices see under accessories and
configuration information in chapter 12 (additional tables) and 16.12
2) definition, see chapter 14.7
3) Arcteq make arc flash relays type AQ-110P as master unit and AQ-101 as add-on units must be selected with the browser for low-voltage equipment
4) Not possible in combination with IPX1 or IPX2
5) Not possible for duplex in back-to-back arrangement
6) Installation of light point sensors in all primary compartments. Number of sensors per panel depending on number of compartments and will be pre-
selected automatically per typical. Sensors, related connection cables (fiber or copper) and wiring from the sensor up to the relay in LV box are
included.
A. For Arcteq make solution:
a) the connection between the sensors and up to the relay is made with insulated copper wires
b) For the selection “without selective tripping”, all three point light sensors in a functional unit will be daisy chained to each other. Therefore, a
single relay can accommodate four feeders. In this case, fault localization will be on feeder level but not on compartment level.
c) For the selection “with possibility for selective tripping of the feeder CBs”, only the point light sensors located in the busbar and the switching
device compartments will be daisy chained to each other. The point light sensor located in the connection compartment will be separately
plugged to the arc flash protection relay. In this way, each feeder will use two of the four light input channels on the relay. Therefore, a single
relay can accommodate two feeders.
d) connection of line sensors in busbar compartment is possible but must be asked for a DTO
e) Arcteq arc flash relay must be selected with the browser for low-voltage equipment

B. For SIPROTEC make solution


a) the connection between the sensors up to the relay is made with optical-fiber cable
b) for the selection of “SIPROTEC optical sensors with possibility for selective tripping of the outgoing feeder CBs”, each point light sensor will
be connected to the relay individually
c) connection of line sensors in busbar compartment is possible but must be asked for a DTO
d) SIPROTEC 5 arc flash relay and additional arc flash protection modules must be selected with the browser for low-voltage equipment

Attention: Metal-enclosed compartments of AIS are not light tight hence nuisance tripping may occur depending on the density of light in the case of arcing
fault. So selective tripping of an outgoing feeder can not be guaranteed

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 10 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

1.4 Design features


Busbar system  Single busbar
6)
 Double busbar (in Duplex design (back to back)
 Double busbar (in Duplex design (front to front)
1)
Design version  Withdrawable part design
2)
 Truck type design
Installation  Freestanding with cable access from front or rear, for SDF panel only from front possible
 Freestanding with cable access only from front for Duplex in back-to-back-arrangement
 Freestanding with cable access from above and rear for 600/800/1000 mm panels up to 17.5 kV/31.5 kA/
2500 A or 800/1000 mm panels up to 17.5 kV/40 kA / ≤4000 A resp. up to 17.5 kV 25/31.5 kA 3150/4000
A (increasing of depth: 600 mm, not possible for Duplex in back-to-back arrangement)
 Wall standing with cable access from front
Partitions LSC2B (metal clad) (standard for all CB and disconnector panels)
LSC2 for SDF panel; Partition class PI (upper shutter made of insulating material)
Pressure resistant to neighboring compartments and panels up to 31.5 kA, 1 s
Shutters 4) Independently lockable (Standard)
 With labels “busbar” and “feeder” (Standard), only label “busbar” for SDF panel in standard
Mechanical locking device Without (standard)
 padlocking facility with padlock
 padlocking facility without padlock
Padlocks facilities 3) padlock for mechanical cover  padlock for mechanical cover for  padlock for high voltage
for ON push button of breaker OFF push button of breaker door
 padlock for mechanical cover  padlock for mechanical cover for  padlocks for both shutters
for ON push button of SDF OFF push button of SDF (standard) 4)
 padlock for mechanism of  padlock for mechanism of feeder  padlock for mechanism of
withdrawable part earthing switch busbar earthing switch
 padlock for slider for charging
mechanism of SIQuench
3)
electromagnetic interlocking coil  electromagnetic interlock for  electromagnetic interlock for  electromagnetic interlock
mechanism of withdrawable mechanism of feeder earthing for mechanism of busbar
part switch earthing switch
Key interlocking system based on
“Ronis” principle
Key interlocking system 3) for  Key free in test position
withdrawable part, with circuit
breaker, disconnecting link,
contactor or SDF
Key interlocking system 3) for  1. Key free in closed position  2. Key free in open position  1. Key free in closed position and
feeder earthing switch in panels 2. Key free in open position
with circuit breaker, disconnecting
link or contactor
Key interlocking system 3) for  1. Key free in closed position  2. Key free in open position  1. Key free in closed position and
busbar earthing switch 2. Key free in open position
Height of low voltage compartment 630 mm (Standard)
5)
 980 mm
Cable entry of LV-cables in low voltage compartment From bottom
 From top (cable gland plate type FL21 located at the right side of the
panel incl. one separate package of PG glands 8BX1028) as option
Cable entry for HV cables in combination with roof for IPX1/IPX2 From bottom in standard
 Form top via rear duct as option
Special edge protection for wiring of auxiliary circuits without
 Optionally with

1) not possible for 435 mm (only in truck type design), SDF panel always with fixed mounted load break switch
2) When truck type design is selected than a truck won’t be scope of supply for the following typicals:
 for feeder current 3150A (1000mm - natural ventilated)
 for bus riser panel of bus sectionalizer type II for 2500A, 3150A and 4000A
 for busbar connection panels (natural ventilated)
 contactor panel 435mm (always in truck type design)
 withdrawable voltage transformers in connection compartment are not possible
3) possible combinations of type of mechanism / interlocking systems / auxiliary voltages see chapter 1.6; If withdrawable part with “Ronis” will be used in a
reserve panel, DTO must be applied”
4) for SDF panel only one shutter between fixed contact and switch blade of load-break switch made of insulation material (PI), not lockable
5) standard for panels with SIQuench mounted in top box at the busbar due to integration the charging mechanism or for panels with busbar earthing switch
6) only freestanding installation in combination with cable connection from the front possible, selectable typicals see chapter 5; not possible for “NXAIR
Marine application”

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 11 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

1.4 Design features


1)
Thermal inspection window for cable connection compartment without
 Optionally with
Language for labels 2)  Optionally english
 Optionally german
 Optionally spanish
 Optionally portuguese
Mimic diagram and symbols for components  Acc. IEC (standard)
 Acc. ANSI (optionally)
3)
Anti-condensation heater in switching device compartment, 100 W  Optionally with
3)
Anti-condensation heater in cable compartment, 100 W  Optionally with
Anti-condensation heater in switching device/cable connection  Optionally with
compartment of SDF, 100 W 3)
3)
Anticondensation heater in low voltage compartment, 20 W  Optionally with
Surface treatment enclosure, partitions Standard:
Steel parts zinc-plated, high voltage and low voltage door at front and
end walls powder coated RAL 7035
Or all sheet metal parts powder coated in RAL 7035 (depending on
manufacturing location)
9)
 Optionally powder coating of rear wall in standard color RAL 7035
 Optionally with special color instead of standard color for high voltage
and low voltage door at front and end walls
9)
 Optionally powder coating of rear wall in special color
4)
Seismic withstand capability  Optionally with
vibration withstand capability (must be selected always in  Optionally with 4)
combination with seismic withstand capability)
Handrails 5) Without in standard
 on front side as option
 on rear side at rear cover of connection compartment or rear duct
only for free standing installation as option 9)
6)
Door retainer for high voltage and low voltage door Without in standard
 Door retainer for LV door and HV door continuously adjustable
Door hinges for high voltage and low voltage door 7)  left
 right
Pressure resistant floor cover in cable compartment metallic cover incl. drillings as standard
 Non-metallic cover as double layer without drillings as option, but not
for cable entry from top with rear box 8)

1) Assembly of IR-inspection window is only possible in combination with free standing design:
o at the rear side of the switchgear at the rear cover of the cable connection compartment and
o at the rear side for panels with rear duct for cable entry from the top
 Possible for following typicals (2 windows per rear cover per rear cover, only 1 window for VCP):
o Circuit breaker panel (for all released ratings)
o Disconnector panel (for all released ratings)
o SDF panel (for all released ratings)
o Busbar connecting panel (for all released ratings)
o Vacuum contactor panel for 7,2 kV, up to 40 kA, up to 4000 A
o Vacuum contactor panel for 12 kV, 40 kA, up to 4000 A
o Vacuum contactor panel for 12 kV, up to 31,5 kA, 3150 A and 4000 A
 Not possible for following typicals:
o Metering panels
o Bus sectionalizer,
o Busbar current metering panel,
o Vacuum contactor panel for 12 kV, up to 31,5 kA, up to 2500 A
o Duplex in back-to-back arrangement
 Not possible for fixed mounted VT in combination with surge arresters in cable connection compartment of CB panels or disconnector panels
2) manuals in German, English or Spanish, only for labels in Portuguese manuals only in English
3) When anti condensation heater is selected in primary part, the thermostat or hygrostat are not included and must be configured in secondary part
4) special marking-spreading tool for drive-in anchors to fix panel to bottom and drilling jig needed, see chapter accessories
5) standard when marine application is selected
6) for contactor panel 435mm only possible on the left side, not possible for HV-door for withdrawable VT at cable side
7) for contactor panel 435mm only possible on the left side
8) only for incoming or outgoing panels with cable or bar connection from bottom (not in combination with metering panels, busbar metering panels and
bus sectionalizer panels
9) not possible for Duplex in back-to-back arrangement

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 12 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

1.4 Design features


Transverse partition in low voltage compartment Standard
Lightning in low voltage compartment without
 Optionally with
Earthing bar in switching device compartment Without (standard)
 Optionally with (needed for flexible earthing device)
Separate earthing bar between withdrawable part and earthing bar in  With
cable compartment (only in combination with “earthing bar in
switching device compartment” possible)
Additional earthing wire between high voltage door and enclosure Standard (yellow-green colored copper wire)
 Optionally with braided copper strap
Additional earthing wire between low voltage door and enclosure Standard (yellow-green colored copper wire)
 Optionally with braided copper strap
Surface treatment of primary contacts Silver plated (Standard)
Surface treatment of busbar and earthing bar Bare
 Optionally silver plated
Surface treatment of components in primary part Standard
 Optionally silicon free
Secondary wiring and channels Standard
 Optionally halogen free
 Optionally silicon free
Panel arrangement  Intermediate panel
 Left end panel
 Right end panel

1.5 Processing
Scope of order  Panels complete

 Panels complete with low voltage compartment as advance delivery (not possible for
panels with busbar earthing switch or SIQuench)

Transport units  Single panels

Packing  Packing for truck on road or rail

 Packing for airfreight

 Packing for sea freight, transport and storage period up to 6 months

 Packing for sea freight, transport and storage period up to 12 months

Acceptance test  Visual inspection

 Complete routine test per panel in acc. to IEC 62271-200

 Complete routine test per typical in acc. to IEC 62271-200

 Visual inspection and mechanical function test per typical

 Without

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 13 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

1.6 Table of selectable versions of type of operating mechanism, interlocking system and auxiliary
voltages
Selectable versions of operating mechanism in combination with interlocking system of withdrawable parts and
feeder earthing switch

withdrawable part / disconnector feeder earthing switch

mechanism interlocking mechanism interlocking


1) 6) 6)
manual motor electro- Ronis padlock manual motor electro- Ronis padlock
1) 2)
magnetic magnetic 5)

1.6.1 Withdrawable part / disconnector, manual operated – feeder earthing switch, manual operated

base  - - - -  - - - -

 -  - -  - - - -
 -  -   - - - -
 -  -   -  - -
 -  -   -  - 
 -  -   - - - 

electromagnetic  -  - -  -  - -
and/or padlock  -  - -  -  - 
 -  - -  - - - 
 - - -   -  - -
 - - -   -  - 
 - - - -  -  - -
 - - - -  -  - 

 - -  -  - - - -
 - -    - - - -
 - -    - -  -
 - -    - -  
 - -    - - - 

Ronis and/or  - -  -  - -  -
padlock  - -  -  - -  
 - -  -  - - - 
 - - -   - -  -
 - - -   - -  
 - - - -  - -  -
 - - - -  - -  

 - - -   - - - -
padlock  - - -   - - - 
 - - - -  - - - 
1.6.2 Withdrawable part / disconnector, motor operated – feeder earthing switch, motor operated

base -  - - - -  - - -

electromagnetic and/or padlock: not possible

Ronis and/or padlock: not possible

padlock -  - -  -  - - 

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 14 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

1.6 Table of selectable versions of type of operating mechanism, interlocking system and auxiliary
voltages
Selectable versions of operating mechanism in combination with interlocking system of withdrawable parts
and feeder earthing switch

withdrawable part / disconnector feeder earthing switch

mechanism interlocking mechanism interlocking


1) 6) 6) 1) 2) 6)
manual motor electro- Ronis padlock manual motor electro- Ronis padlock
magnetic magnetic 5)

1.6.3 Withdrawable part / disconnector, motor operated – feeder earthing switch, manual operated

base -  - - -  - - - -

electromagnetic -  - -   -  - 
and/or padlock -  - - -  -  - -

Ronis and/or padlock: not possible

padlock -  - -   - - - 
1.6.4 Withdrawable part / disconnector, manual operated – feeder earthing switch, motor operated

base  - - - - -  - - -

electromagnetic  -  - - -  - - -
and/or padlock  -  -  -  - - 

Ronis and/or padlock: not possible

padlock  - - -  -  - - 

1.7 Electromagnetic and Ronis interlocking and padlock options for manual or motor driven busbar
earthing switch
3)
busbar earthing switch

mechanism interlocking
manual motor electromagnetic Ronis padlock

 - - - -
 -  - -
 -  - 
 - -  -
 - -  
 - - - 
-  - - -
-   - -
-   - 
-  - - 

1) not possible for contactor panel 435 mm and metering panel


2) for contactor panel and 600 mm panel not possible
3) only possible in 600 mm and 800 mm panels in closed design
4) only same voltage values for above mentioned functions possible, different values are not allowed within these functions
5) not possible for contactor panel 435 mm
6) key interlocking or motor operated withdrawable part not possible in combination with withdrawable VT in 600 mm width; if withdrawable part with “Ronis”
will be used in a reserve panel, DTO must be applied”

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 15 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

1.8 Combinations of rated auxiliary voltages, if selected (without circuit breaker)


Rated value Withdrawable part 4) Earthing switch 4) feeder and / or busbar 3)

1) 2)
Motor Electromagnetic Motor Electromagnetic
interlocking interlocking 5)
24 V DC ---  --- 
48 V DC    
60 V DC    
110 V DC    
125 V DC    
220 V DC    
5)
110 V AC ---  --- 
5)
120 V AC ---  --- 
5)
230 V AC ---  --- 
5)
240 V AC ---  --- 

1.9 selectable versions of mechanism in combination with interlocking system for SDF panel
Load break switch Feeder earthing
mechanism interlocking mechanism interlocking
manual motor electro key padlock manual motor electro key padlock
magnetical interlocking magnetical interlocking
 ╺ ╺ ╺ ╺  ╺ ╺ ╺ ╺

 ╺ ╺  ╺  ╺ ╺  ╺

 ╺ ╺ ╺   ╺ ╺ ╺ 
 ╺  ╺ ╺  ╺  ╺ ╺

1.10 selectable versions of mechanism in combination with interlocking system for SIQuench
Fixed mounted at busbar
mechanism interlocking
manual motor electro magnetical key interlocking padlock
 ╺ ╺ ╺ 
 ╺ ╺ ╺ 
 ╺ ╺ ╺ 
 ╺ ╺ ╺ 

1) not possible for contactor panel 435 mm and metering panel


2) for contactor panel and 600 mm panel not possible
3) only possible in 600 mm and 800 mm panels in closed design
4) only same voltage values for above mentioned functions possible, combination of different values is not allowed within these functions
5) not possible for contactor panel 435 mm

1)
1.11 Padlocking facilities (hand and motor operated )
Typical HV-door Withdrawable Earthing switch Busbar earthing
part at cable side switch 2)
circuit breaker panel ○/●/x ○/●/x ○/●/x -- / ● / x
disconnector panel ○/●/x -- / ● / -- ○/●/x -- / ● / x
vacuum contactor panel ○/●/x ○/●/x ○/●/x -- / -- / --
metering panel / metering module in bus riser or busbar
connecting panel
○/●/x ○/●/x -- / -- / -- -- / ● / x
switch disconnector panel with HV-fuses ○/●/x ○/●/x 3)
○/●/x 3)
-- / -- / --
busbar current metering panel -- / -- / -- -- / -- / -- -- / -- / -- -- / -- / --
busbar connecting panel -- / -- / -- -- / -- / -- -- / -- / -- -- / ● / x
spare panel prepared for CB ○/●/x ○/●/x ○/●/x -- / ● / x
spare panel prepared for disconnector ○/●/x -- / ● / -- ○/●/x -- / ● / x
○ without ● padlocking facility with padlock x padlocking facility without padlock

1) for motor operated cassette or earthing switch the control door in front of HV-door always provided with padlocking facility padlock in standard
2) for busbar earthing switch “padlocking facility with padlock” always pre-selected
3) for switch disconnector panel with HV-fuses common padlocking facilities applicable for actuating opening for operating the switch-fuse combination
and the earthing switch

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 16 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

1.12 Rated supply voltages (other supply voltages must be clarified with engineering department)
Auxiliary voltage  DC 24 V  DC 120 V  AC 100 V 1)
1)
 DC 30 V  DC 125 V  AC 110 V
1)
 DC 32 V  DC 127 V  AC 120 V
1)
 DC 48 V  DC 220 V  AC 125 V
1)
 DC 60 V  DC 240 V  AC 230 V
1)
 DC 110 V   AC 240 V
4)
Circuit breaker motor voltage  DC 24 V  DC 120 V  AC 100 V
1)
 DC 30 V  DC 125 V  AC 110 V
1)
 DC 32 V  DC 127 V  AC 120 V
1)
 DC 48 V  DC 220 V  AC 125 V
1)
 DC 60 V  DC 240 V  AC 230 V
1)
 DC 110 V  AC 240 V
1)
Operating voltage for closing solenoid  DC 24 V  DC 110 V  AC 100 V
and closing latch of contactor 3TM  DC 32 V  DC 125 V  AC 110 V 1)
1)
 DC 48 V  DC 220 V  AC 115 V
1)
 DC 60 V  DC 250 V  AC 120 V
1)
 AC 230 V
1)
 AC 240 V
Operating voltage for releasing  DC 24 V  DC 110 V  AC 100 V 1)
mechanical closing latching 3TM  DC 32 V  DC 125 V  AC 110 V 1)
1)
 DC 48 V  DC 220 V  AC 115 V
1)
 DC 60 V  DC 250 V  AC 120 V
1)
 AC 230 V
1)
 AC 240 V
1)
Shunt trip ( -AA) voltage of Load break  DC 24 V  DC 110 V  AC 110 V
switch type 1)
 DC 48 V  DC 220 V  AC 220 V
L-TRI 5 F-24-200/250-UH-KS-A-EUI
 DC 60 V
1)
First shunt trip voltage of SION  DC 24 V  DC 120 V  AC 100 V
1)
 DC 30 V  DC 125 V  AC 110 V
1)
 DC 32 V  DC 127 V  AC 120 V
1)
 DC 48 V  DC 220 V  AC 125 V
1
 DC 60 V  DC 240 V  AC 230 V
1)
 DC 110 V  AC 240 V
1)
Second shunt trip voltage of SION  DC 24 V  DC 120 V  AC 100 V
1)
 DC 30 V  DC 125 V  AC 110 V
1)
 DC 32 V  DC 127 V  AC 120 V
1)
 DC 48 V  DC 220 V  AC 125 V
1)
 DC 60 V  DC 240 V  AC 230 V
1)
 DC 110 V  AC 240 V
Motor mechanism withdrawable part,  DC 48 V  DC 60 V  DC 110 V
feeder and busbar earthing 2)  DC 125 V  DC 220 V
Interlocking supply (electromagnetic  DC 24 V  DC 48 V  DC 60 V
interlock of withdrawable part / truck  DC 110 V  DC 125 V  DC 220 V
and earthing switch 2) 3)
 AC 110 V  AC 120 V
 AC 230 V  AC 240 V
Controller for SIQuench  AC/DC 110V up to 250V 1)

Heater supply voltage  AC 110 V  AC 220 – 240 V


Fan of forced ventilation  AC 230 V, 50/60 Hz

1) AC for 50 and 60 Hz
2) possible combinations of type of mechanism / interlocking systems / auxiliary voltages see chapter 1.8
3) AC not possible for contactor panels

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 17 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

2 Switchgear specification (design for Marine and Offshore application)


2.1 Technical data
Standard  IEC 62271-200  GOST 1)  IEC 62271-200  GOST 1)
Rated voltage Ur  7.2 kV  12 kV
Rated lightning impulse withstand voltage Up  60 kV  60 kV  75 kV  75 kV
(phase/phase, phase/earth, open contact gap)
Rated lightning impulse withstand voltage Up 2)  70 kV  70 kV  85 kV  85 kV
(disconnecting distance)
Rated short time power frequency withstand  20 kV  32 kV  28 kV  42 kV
voltage Ud
(phase/phase, phase/earth, open contact gap)
Rated short time power  23 kV  36 kV  32 kV  48 kV
frequency withstand voltage Ud 2)
(disconnecting distance)
Operating voltage UN  3.0 kV  6.0 kV  6.0 kV  10.0 kV
 3.3 kV  6.3 kV  6.3 kV  10.5 kV
 4.16 kV  6.6 kV  6.6 kV  11.0 kV
 4.8 kV  10.0 kV
 5.0 kV  10.5 kV
 6.0 kV  11.0 kV
3)
 6.3 kV  11.4 kV
 6.6 kV

Rated frequency fr  50 Hz  50 Hz
 60 Hz  60 Hz
Rated short-time withstand current Ik  25kA  31.5 kA  40 kA  25 kA  31.5kA  40 kA
Rated peak withstand current Ip for 50 Hz  63kA  80 kA  100 kA  63 kA  80kA  100 kA
Rated peak withstand current Ip for 60 Hz  65kA  82 kA  104 kA  65kA  82 kA  104 kA
Rated short-circuit duration tk  1s
 3s
Ambient temperature 4)  30 °C
 35 °C
 40 °C
 45 °C
 50 °C
 55 °C
5)
Resistance to internal arc faults  IAC A FLR, 1 s (standard version)
 IAC A FLR, 1 s (standard version),
additional pressure switches for all three compartments without testing device
 IAC A FLR, 1 s (standard version),
additional pressure switches for all three compartments with testing device
 IAC A FLR, 1 s (standard version), additionally with arc flash protection via Arcteq make light
point sensors (requires use of Arcteq make arc flash protection relays), without selective
tripping, limiting arcing time to max. 100 ms 6)
 IAC A FLR, 1 s (standard version), additionally with arc flash protection via Arcteq make light
point sensors (requires use of Arcteq make arc flash protection relays), with possibility for
selective tripping of the outgoing feeder CBs, limiting arcing time to max. 100 ms 6)
 IAC A FLR, 1 s (standard version), additionally with arc flash protection via SIPROTEC light
point sensors (requires use of SIPROTEC 5 relays and arc protection modules), with possibility
for selective tripping of the outgoing feeder CBs, limiting arcing time to max. 100 ms 6)
 IAC A FLR, 1 s (standard version), additionally with optical sensors for all three compartments
per typical SIQuench and controller at the busbar system 7)
Confinement of internal arc within Standard, only up to and including 31,5 kA for 1 sec, but not for contactor panel 435 mm and
compartments (pressure tied partitions) 6) SDF panel
Degree of protection  IP 31
 IP 32
 IP 41
 IP 42
Sea level (m)  ≤ 1000

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 18 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

1) GOST = Russian standard; general insulation levels of GOST standard can be fulfilled, for contactor panel GOST values only for 7.2 kV
2) only applicable for SDF panels due to LSC2 design
3) only for SPC Mexico
4) switchgear is designed for ambient temperatures between -25°C and +55°C
5) versions of pressure relief system see table in chapter 16.12
6) definition, see chapter 14.7
7) ARCTEQ make arc flash relays type AQ-110P as master unit and AQ-101 as add-on units must be selected with the browser for low-voltage equipment
8) Installation of light point sensors in all primary compartments. Number of sensors per panel depending on number of compartments and will be pre-
selected automatically per typical. Sensors, related connection cables (fiber or copper) and wiring from the sensor up to the relay in LV box are included.
A. For Arcteq make solution:
f) the connection between the sensors and up to the relay is made with insulated copper wires
g) For the selection “without selective tripping”, all three point light sensors in a functional unit will be daisy chained to each other. Therefore, a
single relay can accommodate four feeders. In this case, fault localization will be on feeder level but not on compartment level.
h) For the selection “with possibility for selective tripping of the feeder CBs”, only the point light sensors located in the busbar and the switching
device compartments will be daisy chained to each other. The point light sensor located in the connection compartment will be separately
plugged to the arc flash protection relay. In this way, each feeder will use two of the four light input channels on the relay. Therefore, a single
relay can accommodate two feeders.
i) connection of line sensors in busbar compartment is possible but must be asked for a DTO
j) Arcteq arc flash relay must be selected with the browser for low-voltage equipment

B. For SIPROTEC make solution


e) the connection between the sensors up to the relay is made with optical-fiber cable
f) for the selection of “SIPROTEC optical sensors with possibility for selective tripping of the outgoing feeder CBs”, each point light sensor will
be connected to the relay individually
g) connection of line sensors in busbar compartment is possible but must be asked for a DTO
h) SIPROTEC 5 arc flash relay and additional arc flash protection modules must be selected with the browser for low-voltage equipment

Attention: Metal-enclosed compartments of AIS are not light tight hence nuisance tripping may occur depending on the density of light in the case of arcing
fault. So selective tripping of an outgoing feeder can not be guaranteed

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 19 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

2.2 Busbars
Busbar system  Single busbar
Rated continuous current and dimensions  1250 A; (1 x 80 mm x 10 mm, copper)
 2000 A; (2 x 80 mm x 10 mm, copper) – not for 40 kA
 2500 A, (2 x 100 mm x 10 mm, copper)
Busbar insulation  Optionally with (insulated horizontal busbars for SDF in standard)
Busbar transverse partition 1)  Optionally with

2.3 Special design options for marine applications


Pressure resistant floor cover in cable metallic cover incl. drillings
compartment
 Non-metallic cover as double layer without drillings as option, but not for cable entry
from top with rear box
Height of low voltage compartment 980 mm
4)
Anti condensation heater In switching device compartment, 100 W
In cable compartment, 100 W
In low voltage compartment, 20 W
Cable entry for LV-cables From bottom
 From top (cable gland plate type FL21 located at the right side of the panel incl. one
separate package of PG glands 8BX1028) as option
Cable entry for HV cables in combination with From bottom in standard
roof for IPX1/IPX2 5)
 Form top via rear duct as option
Handrails on front side in standard
 on rear side at rear cover of connection compartment or rear duct only for free standing
installation as option
Door retainer for high voltage and low voltage Without in standard
door 6)
 Door retainer for LV door and HV door continuously adjustable
Thermal inspection window for cable without
connection compartment 2)
 Optionally with
vibration withstand capability (must be With 3)
selected always in combination with seismic
withstand capability)
Special design measures against damage Special wire protection at the panel (improved protection against sharp edges of LV-
caused by vibrations wiring in the primary part with plastic tube and adhesive tape in cable channels)
Cable harness with double insulation for shipbuilding industry (ordering code Z-B58)
Special fixing of wiring harness in LV compartment
Bus wiring screw type socket for ring loop (vibration resistant)
Halogen free of secondary wiring and cable channels
 Secondary wiring of VT type RADOX 4 GKW-AX in 4,0 mm²
 Zero sequence CT type 4MC4_40 installed in cable connection compartment without
deep bottom pan as option 7)

1) always in standard for 40 kA panels, contactor panels and for SDF (partitions on both sides necessary)
2) Assembly of IR-inspection window is only possible in combination with free standing design:
o at the rear side of the switchgear at the rear cover of the cable connection compartment and
o at the rear side for panels with rear duct for cable entry from the top
 Possible for following typicals (2 windows per rear cover per rear cover, only 1 window for VCP):
o Circuit breaker panel (for all released ratings)
o Disconnector panel (for all released ratings)
o SDF panel (for all released ratings)
o Busbar connecting panel (for all released ratings)
o Vacuum contactor panel for 7,2 kV, up to 40 kA, up to 4000 A
o Vacuum contactor panel for 12 kV, 40 kA, up to 4000 A
o Vacuum contactor panel for 12 kV, up to 31,5 kA, 3150 A and 4000 A
 Not possible for following typicals:
o Metering panels
o Bus sectionalizer,
o Busbar current metering panel,
o Vacuum contactor panel for 12 kV, up to 31,5 kA, up to 2500 A
 Not possible for fixed mounted VT in combination with surge arresters in cable connection compartment of CB panels or disconnector panels
3) special drilling jig needed, see chapter accessories
4) When anti condensation heater is selected in primary part, the thermostat or hygrostat are not included and must be configured in secondary part
5) No cable connection or bar connection in top box at the busbar for Marine application possible
6) for contactor panel 435mm only possible on the left side, not possible for HV-door for withdrawable VT at cable side
7) only possible in combination with singe-core cables (not in combination with three-core cables possible)
Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 20 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

2.4 Design features


Selection identically with 1.4

2.5 Processing
Selection identically with 1.5

2.6 Table of selectable versions of type of operating mechanism, interlocking systems and
auxiliary voltages
Selection identically with 1.6

2.7 Electromagnetic and Ronis interlocking and padlock options for manual or motor driven
busbar earthing switch
Selection identically with 1.7

2.8 Combinations of rated auxiliary voltages, if selected (without circuit breaker)


Selection identically with 1.8

2.9 selectable versions of mechanism in combination with interlocking systems for SDF panel
Selection identically with 1.9

2.10 selectable versions of mechanism in combination with interlocking system for SIQuench
Selection identically with 1.10

2.11 Padlocking facilities (hand and motor operated)


Selection identically with 1.11

2.12 Rated supply voltages


Selection identically with 1.12

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 21 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

3 Panel specification – Single busbar


3.1 Components in basic versions
3.1.1 Circuit breaker panel
panel width (mm) compartment 1) design resp. devices

600 2) busbar bare copper 

optionally insulated copper 

optionally with top box for voltage transformers 

optionally with busbar earthing switch hand operated 3) 

optionally with top box for earthing switch motor operated 3) 


6)
optionally with top box for bar or cable connection 

optionally with top box for SIQuench, controller, charging mechanism and CAPDIS S2 3) 

optionally with top box for surge arrester type 3EK 

bushing type insulators between breaker and busbar 

optionally bushing type insulator 4ME as LPCT for current measuring 

optionally bushing type insulator 4ME as LPVT for voltage measuring 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 

optionally capacitive voltage indication 

switching device withdrawable circuit breaker, hand operated 

optionally withdrawable circuit breaker, motor operated 

closed panel, without slots 

connection cables 

bushing type insulators and optionally block type current transformers 

bushing type insulators and optionally extended block type current transformers up to 17.5 
kV / 31.5 kA / 2500 A possible 4)

optionally bushing type insulator 4ME as LPCT for current measuring 

optionally bushing type insulator 4ME as LPVT for voltage measuring 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 

optionally fixed mounted voltage transformers 

optionally withdrawable voltage transformers in separate compartment with fuses 5) 

optionally earthing switch hand operated 

optionally surge arrestors 

optionally capacitive voltage indication 

optionally devices for zero sequence transformers 

optionally devices for zero sequence transformers as LPCT 

detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) only up to 31.5 kA, top boxes on busbar compartment only for busbar currents ≤ 2500A possible
3) low voltage compartment as advanced delivery is not possible for this version, only in combination with a panel
4) higher specific core data of ct possible, panel depth increases (see chapter 6.1), not possible as single panel in combination with duplex in back-to-back
arrangement
5) not possible when truck type design is selected, fuses without any tripping mechanism, in 600 mm panel withdrawable VT also not possible in combination
with key interlocking or motor operated cassette
6) when bar connection is selected bars, insulating bushings and bottom plate is part of delivery but loose delivery and must be assembled on site. Cross
section of bars see chapter 7.3
Attention: Insulated bars (DURESCA, Moser Glaser, …) must be assembled outside the connection compartment

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 22 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

3.1.1 Circuit breaker panel


panel width (mm) compartment 1) design resp. devices

800 busbar bare copper 

(closed panel) optionally insulated copper 

optionally with top box for earthing switch hand operated 2) 

optionally with top box for earthing switch motor operated 2) 

optionally with top box for voltage transformers 

bushing type insulator between breaker and busbar 

optionally bushing type insulator 4ME as LPCT for current measuring 

optionally bushing type insulator 4ME as LPVT for voltage measuring 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 
6)
optionally with top box for bar or cable connection 

optionally with top box for SIQuench, controller, charging mechanism and CAPDIS S2 2) 

optionally with top box for surge arrester type 3EK 

optionally capacitive voltage indication 

switching device withdrawable circuit breaker, hand operated 

optionally withdrawable circuit breaker, motor operated 

optionally withdrawable disconnector link, hand operated 

optionally withdrawable disconnector link, motor operated 

closed panel, without slots 5) 


6)
connection cables or optionally bar connection 

bushing type insulators and optionally block type current transformers 

bushing type insulators and optionally extended block type current transformers up to 17.5 
kV / 31.5 kA / 2500 A possible 3) or up to 17.5 kV/40 kA / ≤ 4000 A resp. up to 17.5 kV
25/31.5 kA / 3150/4000 A 3)

optionally bushing type insulator 4ME as LPCT for current measuring 

optionally bushing type insulator 4ME as LPVT for voltage measuring 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 

optionally fixed mounted voltage transformers 

optionally withdrawable voltage transformers in separate compartment with fuses 4) 

optionally earthing switch hand operated 

optionally earthing switch motor operated 

optionally surge arrestors 

optionally capacitive voltage indication 

optionally devices for zero sequence transformers 

optionally devices for zero sequence transformers as LPCT 

detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) low voltage compartment as advanced delivery is not possible for this version, only in combination with a panel
3) higher specific core data of ct possible, panel depth increases (see chapter 6.1), not possible as single panel in combination with duplex in back-to-
back arrangement
4) not possible when truck type design is selected, fuses without any tripping mechanism, in 600 mm panel withdrawable VT also not possible in
combination with key interlocking or motor operated cassette
5) only up to 17,5 kV, ≤ 40 kA, 1250 A
6) when bar connection is selected bars, insulating bushings and bottom plate is part of delivery but loose delivery and must be assembled on site. Cross
section of bars see chapter 7.3
Attention: Insulated bars (DURESCA, Moser Glaser, …) must be assembled outside the connection compartment

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 23 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

3.1.1 Circuit breaker panel


panel width (mm) compartment 1) design resp. devices

800 mm busbar bare copper 

(ventilated panel) optionally insulated copper 

bushing type insulator between breaker and busbar 

optionally bushing type insulator 4ME as LPCT for current measuring 

optionally bushing type insulator 4ME as LPVT for voltage measuring 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 

optionally capacitive voltage indication 

switching device withdrawable circuit breaker, hand operated 

optionally withdrawable circuit breaker, motor operated 

optionally withdrawable disconnector link, hand operated 

optionally withdrawable disconnector link, motor operated 

natural ventilated 4) 
5)
connection cables or optionally bar connection 

bushing type insulators and optionally block type current transformers 

bushing type insulators and optionally extended block type current transformers up to 17.5 
kV / 31.5 kA / 2500 A possible 2) or up to 17.5 kV/40 kA / ≤ 4000 A resp. up to 17.5 kV
25/31.5 kA / 3150/4000 A 2)

optionally bushing type insulator 4ME as LPCT for current measuring 

optionally bushing type insulator 4ME as LPVT for voltage measuring 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 

optionally fixed mounted voltage transformers 

optionally withdrawable voltage transformers in separate compartment with fuses 3) 

optionally earthing switch hand operated 

optionally earthing switch motor operated 

optionally surge arrestors 

optionally capacitive voltage indication 

optionally devices for zero sequence transformers 

optionally devices for zero sequence transformers as LPCT 

detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) higher specific core data of ct possible, panel depth increases (see chapter 6.1), not possible as single panel in combination with duplex in back-to-back
arrangement
3) not possible when truck type design is selected, fuses without any tripping mechanism, in 600 mm panel withdrawable VT also not possible in
combination with key interlocking or motor operated cassette and in 3150 A feeder (1000 mm)
4) only for up to 17,5kV, ≤ 40 kA, 2000A (only ventilation box at the top)
5) when bar connection is selected bars, insulating bushings and bottom plate is part of delivery but loose delivery and must be assembled on site. Cross
section of bars see chapter 7.3
Attention: Insulated bars (DURESCA, Moser Glaser, …) must be assembled outside the connection compartment

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 24 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

3.1.1 Circuit breaker panel


panel width (mm) compartment 1) design resp. devices

1000 mm busbar bare copper 

(ventilated panel) optionally insulated copper 

bushing type insulator between breaker and busbar 

optionally bushing type insulator 4ME as LPCT for current measuring 

optionally bushing type insulator 4ME as LPVT for voltage measuring 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 

optionally capacitive voltage indication optionally 

switching device withdrawable circuit breaker, hand operated 

optionally withdrawable circuit breaker, motor operated 

optionally withdrawable disconnector link, hand operated 

optionally withdrawable disconnector link, motor operated 

natural ventilated 4) 

forced ventilated 4), current relays controlled 

forced ventilated 4), current relays controlled and redundant version 


5)
connection cables or optionally bar connection 

bushing type insulators and optionally block type current transformers 

bushing type insulators and optionally extended block type current transformers up to 17.5 
kV/31.5 kA / 2500 A possible 2) or up to 17.5 kV/40 kA / ≤4000 A resp. up to 17.5 kV
25/31.5 kA / 3150/4000 A 2)

optionally bushing type insulator 4ME as LPCT for current measuring 

optionally bushing type insulator 4ME as LPVT for voltage measuring 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 

optionally fixed mounted voltage transformers 

optionally withdrawable voltage transformers in separate compartment with fuses 3) 

optionally earthing switch hand operated 

optionally earthing switch motor operated 

optionally surge arrestors 

optionally capacitive voltage indication 

optionally devices for zero sequence transformers 

optionally devices for zero sequence transformers as LPCT 

detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) higher specific core data of ct possible, panel depth increases (see chapter 6.1), not possible as single panel in combination with duplex in back-to-
back arrangement
3) not possible when truck type design is selected, fuses without any tripping mechanism, in 600 mm panel withdrawable VT also not possible in
combination with key interlocking or motor operated cassette and in 3150 A feeder (1000 mm)
4) 2500 A / 3150 A natural ventilated, 4000 A forced ventilated
5) when bar connection is selected bars, insulating bushings and bottom plate is part of delivery but loose delivery and must be assembled on site. Cross
section of bars see chapter 7.3
Attention: Insulated bars (DURESCA, Moser Glaser, …) must be assembled outside the connection compartment

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 25 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

2)
3.1.2 Contactor panel
panel width compartment 1) design resp. devices
435 mm busbar bare copper
optionally insulated 
bushing type insulators between contactor and busbar
switching device withdrawable contactor with 1 fuse per phase, without fused control transformer, hand 
operated
optionally withdrawable contactor with 2 fuses per phase, without fused control 
transformer, hand operated
optionally withdrawable contactor with 1 fuse per phase, with fused control transformer, 
hand operated
optionally withdrawable contactor with 2 fuses per phase, with fused control transformer, 
hand operated
connection Cables 
bushing type insulators and block type current transformers 
optionally earthing switch (16,4 kA peak value) hand operated 
optionally surge arrestors (only with high energy charge capabilities type 3EJ) 
optionally capacitive voltage indication optionally 
optionally devices for zero sequence transformers 
detailed configuration in NX-Tools+

3.1.3 Metering panel (voltage of busbar)


panel width compartment 1) design resp. devices
800 mm busbar bare copper
optionally with top box for SIQuench, controller, charging mechanism and CAPDIS S2 3) 
optionally insulated copper 
optionally with top box for earthing switch hand operated 3) 
optionally with top box for earthing switch motor operated 3) 
bushing type insulator
optionally with top box for bar or cable connection 
optionally with top box for surge arrester type 3EK 
optionally capacitive voltage indication 
switching device withdrawable part with voltage transformers and primary fuses without any tripping
mechanism, hand operated
withdrawable part with voltage transformers and primary fuses with tripping mechanism, 
hand operated
detailed configuration in NX-Tools+

3.1.3 Metering panel (voltage of busbar)


panel width compartment 1) design resp. devices
4)
600 mm busbar bare copper
optionally with top box for SIQuench, controller, charging mechanism and CAPDIS S2 3) 
optionally insulated copper 
optionally with top box for earthing switch hand operated 3) 
optionally with top box for earthing switch motor operated 3) 
bushing type insulator
optionally with top box for bar or cable connection 
optionally with top box for surge arrester type 3EK 
optionally capacitive voltage indication 
switching device withdrawable part with voltage transformers and primary fuses without any tripping
mechanism, hand operated
withdrawable part with voltage transformers and primary fuses with tripping mechanism, 
hand operated
detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) up to 40 kA, at least two panels needed if direct connection with busbar current metering panel is planned, can be used for motor feeder, for
transformer incomer earthing switch must be interlocked electromechanically with secondary breaker of transformer; insulation level of GOST standard
for 7.2 kV rated voltage as an option possible,
3) low voltage compartment as advanced delivery is not possible for this version, only in combination with a panel
4) only up to 31.5 kA, top boxes on busbar compartment only for busbar currents ≤ 2500A possible

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 26 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

3.1.4 Switch-disconnector panel with HRC fuses (LSC2 and PI)


panel width compartment 1) design resp. devices

800 mm busbar bare copper 

with insulated copper as standard 

shutter between fixed contact and switch blade of switch-disconnector made of insulation 
material (PI)

busbar transverse partition on both sides as standard 

switching device fixed-mounted load break switch with 1 fuse per phase, hand operated 
and
earthing switch 16 kA /1 sec, hand operated with auxiliary switch 
connection
position indication for earthing switch as standard 

optionally position indicator for load break switch 

optionally capacitive voltage indication 

cables connection 

post insulators 

optionally block type current transformers 

optionally devices for zero sequence transformers 

detailed configuration in NX-Tools+

3.1.5 Busbar current metering panel 3) for ≤ 17.5 kV / 40kA / ≤ 4000 A resp. ≤ 17.5 kV / 25/31.5 kA / 3150/4000 A
panel width (mm) compartment 1) design resp. devices

800 busbar bare copper with 3 block type cts 

optionally insulated copper with 3 block type cts 

Remark: detailed configuration in NX-Tools+

Top box on busbar compartment only possible for non–ventilated panels in general

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) low voltage compartment as advanced delivery is not possible for this version, only in combination with a panel
3) up to 2500 A busbar current non-ventilated, 3150 A / 4000 A busbar current naturally ventilated, when this typical is directly added to contactor panel,
at least two contactor panels are needed

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 27 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

3.1.6 Bus sectionalizer


3.1.6.1 Bus sectionalizer can be designed as:
Type I
For ≤ 31,5kA consisting of: For 40kA consisting of
circuit breaker panel bus riser panel with circuit breaker panel bus riser panel with
disconnector disconnector
rated width of ventilation width of ventilation width of ventilation width of Ventilation
continuous panel panel panel panel
current 1)
(mm) (mm) (mm) (mm)
(A)
1250 800 closed 800 closed 800 closed 800 closed
2000 6) 1000 natural 2) 1000 natural 2) --- --- --- ---
2500 1000 natural 2) 1000 natural 2) 1000 natural 2) 1000 natural 2)
3) 3) 3)
3150 1000 natural 1000 natural 1000 natural 1000 natural 3)
4000 1000 forced 2) 1000 forced 2) 1000 forced 2) 1000 forced 2)
Type I
For ≤ 31,5kA consisting of: For 40kA consisting of
circuit breaker panel bus riser panel with circuit breaker panel bus riser panel with
with bushing type CT disconnector with bushing type 4MD disconnector
4MD between circuit between circuit
breaker and busbar breaker and busbar
rated width of ventilation width of ventilation
continuous panel panel
current 1)
(mm) (mm)
(A)
Not available
1250 800 natural 7) 800 closed
2000 6) 1000 natural 3) 1000 natural 2)
2500 1000 natural 3) 1000 natural 2)

1) rated continuous current, see also tables in chapter 13


2) ventilation slots on the left and the right side
3) ventilation slots on the left side, the right side and in front door (no truck type version possible)
4) ventilation slots in front door (no truck type version possible)
5) bus riser panel with metering module for current ≥ 2000 A not in truck-type version possible
6) technical identical with 2500A version
7) no ventilation slots at the front, only ventilation boxes at the top of the busbar compartment

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 28 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

3.1.6.2 Bus sectionalizer can be designed as:


Type II
For ≤ 31,5kA consisting of: For 40kA consisting of
circuit breaker panel bus riser panel circuit breaker panel bus riser panel
rated width of ventilation width of ventilation width of ventilation width of Ventilation
continuous panel panel panel panel
current 1)
(mm) (mm) (mm) (mm)
(A)
1250 800 closed 800 closed 800 closed 800 closed
2) 4)
2000 6)
1000 natural 800 natural --- --- --- ---
2500 1000 natural 2) 800 natural 4) 1000 natural 2) 800 natural 4)
3150 1000 natural 3) 1000 natural 4) 1000 natural 3) 1000 natural 4)
4000 1000 forced 2) 1000 natural 4) 1000 forced 2) 1000 natural 4)
Type II
For ≤ 31,5kA consisting of: For 40kA consisting of
circuit breaker panel bus riser panel circuit breaker panel bus riser panel
with bushing type CT with bushing type CT
4MD between circuit 4MD between circuit
breaker and busbar breaker and busbar
rated width of ventilation width of ventilation
continuous panel panel
current 1)
(mm) (mm)
(A)
Not available
1250 800 natural 7) 800 closed
2000 6) 1000 natural 3) 800 natural 2)
2500 1000 natural 3) 800 natural 2)

1) rated continuous current, see also tables in chapter 13


2) ventilation slots on the left and the right side
3) ventilation slots on the left side, the right side and in front door (no truck type version possible)
4) ventilation slots in front door (no truck type version possible)
5) bus riser panel with metering module for current ≥ 2000 A not in truck-type version possible
6) technical identical with 2500A version
7) no ventilation slots at the front, only ventilation boxes at the top of the busbar compartment

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 29 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

3.1.6.2 Bus sectionalizer can be designed as:


Type II
For ≤ 31,5kA consisting of: For 40kA consisting of
circuit breaker panel bus riser panel with circuit breaker panel bus riser panel with
metering module 5) metering module 5)
rated width of ventilation width of ventilation width of ventilation width of Ventilation
continuous panel panel panel panel
current 1)
(mm) (mm) (mm) (mm)
(A)
1250 800 closed 800 closed 800 closed 800 closed
2) 4)
2000 6
1000 natural 800 natural --- --- --- ---
2) 4) 2)
2500 1000 natural 800 natural 1000 natural 800 natural 4)
3150 1000 natural 3) 1000 natural 4) 1000 natural 3) 1000 natural 4)
4000 1000 forced 2) 1000 natural 4) 1000 forced 2) 1000 natural 4)

For ≤ 31,5kA consisting of: For 40kA consisting of


circuit breaker panel bus riser panel with circuit breaker panel bus riser panel with
with bushing type CT metering module 5) with bushing type CT metering module 5)
4MD between circuit 4MD between circuit
breaker and busbar breaker and busbar
rated width of ventilation width of ventilation
continuous panel panel
current 1)
(mm) (mm)
(A)
Not available
1250 800 natural 7) 800 closed
2000 6) 1000 natural 3) 1000 natural 2)
3)
2500 1000 natural 1000 natural 2)

1) rated continuous current, see also tables in chapter 13


2) ventilation slots on the left and the right side
3) ventilation slots on the left side, the right side and in front door (no truck type version possible)
4) ventilation slots in front door (no truck type version possible)
5) bus riser panel with metering module for current ≥ 2000 A not in truck-type version possible
6) technical identical with 2500A version
7) no ventilation slots at the front, only ventilation boxes at the top of the busbar compartment

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 30 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

3.1.6.1 Bus sectionalizer type I, 1250 A (mirror-image installation possible)


Circuit breaker panel, 1250 A
panel width (mm) compartment 1) design resp. devices
4)
800 Busbar bare copper 
optionally insulated copper 
2)
optionally with top box for earthing switch hand operated 
2)
optionally with top box for earthing switch motor operated 
optionally with top box for voltage transformers 
optionally with top box for surge arrester type 3EK 
bushing type insulators between breaker and busbar 
5)
optionally bushing type CT 4MD between breaker and busbar 
optionally bushing type insulator 4ME as LPCT for current measuring 
optionally bushing type insulator 4ME as LPVT for voltage measuring 
optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 
6)
optionally with top box for bar or cable connection 
optionally capacitive voltage indication 
switching device withdrawable circuit breaker, hand operated 
optionally withdrawable circuit breaker, motor operated 
Connection bar connection to bus riser panel 
3)
bushing type insulators and optionally block type current transformers 
optionally bushing type insulator 4ME as LPCT for current measuring 
optionally bushing type insulator 4ME as LPVT for voltage measuring 
optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 
optionally fixed mounted voltage transformers 
optionally capacitive voltage indication 
Bus riser panel with disconnecting module, 1250 A
panel width (mm) compartment 1) design resp. devices
4)
800 Busbar bare copper 
optionally insulated copper 
2)
optionally with top box for earthing switch hand operated 
2)
optionally with top box for earthing switch motor operated 
optionally with top box for voltage transformers 
optionally with top box for surge arrester type 3EK 
bushing type insulators between breaker and busbar 
optionally bushing type insulator 4ME as LPCT for current measuring 
optionally bushing type insulator 4ME as LPVT for voltage measuring 
optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 
6)
optionally with top box for bar or cable connection 
optionally capacitive voltage indication 
switching device withdrawable disconnector link, hand operated 
optionally withdrawable disconnector link, motor operated 
connection bar connection to bus circuit breaker panel 
3)
bushing type insulators and optionally block type current transformers 
optionally bushing type insulator 4ME as LPCT for current measuring 
optionally bushing type insulator 4ME as LPVT for voltage measuring 
optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 
optionally fixed mounted voltage transformers 
optionally capacitive voltage indication 
Remark: detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) low voltage compartment as advanced delivery is not possible for this version, only in combination with a panel
3) higher specific core data of ct possible, panel depth increases (see chapter 6.1), not possible as panel in combination with duplex in back-to-back
arrangement
4) top box to busbar only possible in circuit breaker panel or bus riser panel but not coexisting in both
5) no top box possible due to ventilation boxes at the busbar
6) when bar connection is selected bars, insulating bushings and bottom plate is part of delivery but loose delivery and must be assembled on site. Cross
section of bars see chapter 7.3
Attention: Insulated bars (DURESCA, Moser Glaser, …) must be assembled outside the connection compartment

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 31 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

3.1.6.1 Bus sectionalizer type I, 2000A, 2500 A, 3150 A, 4000 A, (mirror-image installation possible)
Circuit breaker panel, 2000 A, 2500 A, 3150 A, 4000 A
panel width (mm) compartment 1) design resp. devices
1000 busbar bare copper 
optionally insulated copper 
bushing type insulators between breaker and busbar 
4)
optionally bushing type CT 4MD between breaker and busbar 
optionally bushing type insulator 4ME as LPCT for current measuring 
optionally bushing type insulator 4ME as LPVT for voltage measuring 
optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 
optionally capacitive voltage indication 
switching device withdrawable circuit breaker, hand operated 
optionally withdrawable circuit breaker, motor operated 
natural ventilated 2) 
forced ventilated 2), current relays controlled 
forced ventilated 2), current relays controlled and redundant version 
connection bar connection to bus riser panel 
3)
bushing type insulators and optionally block type current transformers 
optionally bushing type insulator 4ME as LPCT for current measuring 
optionally bushing type insulator 4ME as LPVT for voltage measuring 
optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 
optionally fixed mounted voltage transformers 
optionally capacitive voltage indication 
Bus riser panel with disconnecting module, 2000A, 2500 A, 3150 A, 4000 A
panel width (mm) compartment 1) design resp. devices
1000 busbar bare copper 
optionally insulated copper 
bushing type insulators between breaker and busbar 
optionally bushing type insulator 4ME as LPCT for current measuring 
optionally bushing type insulator 4ME as LPVT for voltage measuring 
optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 
optionally capacitive voltage indication 
switching device withdrawable disconnector link, hand operated 
optionally withdrawable disconnector link, motor operated 
natural ventilated 2) 
2)
forced ventilated , current relays controlled 
forced ventilated 2), current relays controlled and redundant version 
connection bar connection to bus circuit breaker panel 
bushing type insulators and optionally block type current transformers 3) 
optionally bushing type insulator 4ME as LPCT for current measuring 
optionally bushing type insulator 4ME as LPVT for voltage measuring 
optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 
optionally fixed mounted voltage transformers 
optionally capacitive voltage indication 
detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) 2000 A / 2500 A / 3150 A natural ventilated panel, 4000 A forced ventilated panel
3) higher specific core data of CT possible, panel depth increases (see chapter 6.1), not possible as panel in combination with duplex in back-to-back
arrangement
4) only for 2000 A and 2500 A busbar currents but no top box possible due to ventilation boxes at the busbar

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 32 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

3.1.6.2 Bus sectionalizer type II, 1250 A (mirror-image installation possible)


Circuit breaker panel, 1250 A
1)
panel width (mm) compartment design resp. devices
5)
800 busbar bare copper 

optionally insulated copper 


3)
optionally with top box for earthing switch hand operated 

optionally with top box for earthing switch motor operated 3) 

optionally with top box for voltage transformers 

optionally with top box for surge arrester type 3EK 

bushing type insulators between breaker and busbar 


6)
optionally bushing type CT 4MD between breaker and busbar 

optionally bushing type insulator 4ME as LPCT for current measuring 

optionally bushing type insulator 4ME as LPVT for voltage measuring 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 
7)
optionally with top box for bar or cable connection 

optionally capacitive voltage indication 

switching device withdrawable circuit breaker, hand operated 

optionally withdrawable circuit breaker, motor operated 

connection bar connection to bus riser panel 


2)
bushing type insulators and optionally block type current transformers 

optionally bushing type insulator 4ME as LPCT for current measuring 

optionally bushing type insulator 4ME as LPVT for voltage measuring 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 

optionally fixed mounted voltage transformers 

optionally capacitive voltage indication 

Bus riser panel 1250 A, optionally with metering module


panel width (mm) compartment 1) design resp. devices
5)
800 busbar bare copper 

optionally insulated copper 


3)
optionally with top box for earthing switch hand operated 
3)
optionally with top box for earthing switch motor operated 
7)
optionally with top box for bar or cable connection 

optionally with top box for surge arrester type 3EK 


4.)
optionally capacitive voltage indication 

switching device optionally withdrawable part with voltage transformers and primary fuses without any tripping 
mechanism, hand operated

optionally withdrawable part with voltage transformers and primary fuses with tripping 
mechanism, hand operated

connection bar connection to circuit breaker panel 

optionally fixed mounted voltage transformers 

Remark: detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) higher specific core data of ct possible, panel depth increases (see chapter 6.1), not possible as panel in combination with duplex in back-to-back
arrangement
3) low voltage compartment as advanced delivery is not possible for this version, only in combination with a panel
4) only in combination with metering module possible
5) top box to busbar only possible in circuit breaker panel or bus riser panel but not coexisting in both
6) no top box possible due to ventilation boxes at the busbar
7) when bar connection is selected bars, insulating bushings and bottom plate is part of delivery but loose delivery and must be assembled on site. Cross
section of bars see chapter 7.3
Attention: Insulated bars (DURESCA, Moser Glaser, …) must be assembled outside the connection compartment

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 33 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

3.1.6.2 Bus sectionalizer type II, 2000A, 2500 A, 3150 A, 4000 A, (mirror-image installation possible)
Circuit breaker panel, 2000A, 2500 A, 3150 A, 4000 A
panel width (mm) compartment 1) design resp. devices
1000 busbar bare copper 
optionally insulated copper 
bushing type insulators between breaker and busbar 
8)
optionally bushing type CT 4MD between breaker and busbar 
optionally bushing type insulator 4ME as LPCT for current measuring 
optionally bushing type insulator 4ME as LPVT for voltage measuring 
optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 
optionally capacitive voltage indication 
switching device withdrawable circuit breaker, hand operated 
optionally withdrawable circuit breaker, motor operated 
natural ventilated 5) 
forced ventilated 5), current relays controlled 
forced ventilated 5), current relays controlled and redundant version 
connection bar connection to bus riser panel 
bushing type insulators and optionally block type current transformers 
optionally bushing type insulator 4ME as LPCT for current measuring 
optionally bushing type insulator 4ME as LPVT for voltage measuring 
optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 
optionally fixed mounted voltage transformers 
optionally capacitive voltage indication 
Bus riser panel 2000A, 2500 A, 3150 A, 4000 A, optionally with metering module
panel width (mm) compartment 1) design resp. devices
800/1000 busbar bare copper 
optionally insulated copper 
optionally capacitive voltage indication 7) 
switching device optionally withdrawable part with voltage transformers with primary fuses without any tripping 
mechanism, hand operated 3)
optionally withdrawable part with voltage transformers and primary fuses with tripping 
mechanism, hand operated ..3)
natural ventilated 
connection bar connection to circuit breaker panel 
optionally fixed mounted voltage transformers 
detailed configuration in NX-Tools+

3.1.7 Busbar connecting panel


panel width (mm) compartment 1) design resp. devices
800 / 1000 busbar bare copper 
optionally insulated copper 
optionally with top box 2) for earthing switch hand operated 4) 
optionally with top box 2) for earthing switch motor operated 4) 
optionally with top box 2) for voltage transformers 
optionally with top box 2) for surge arrester type 3EK 
optionally with top box 2) for bar or cable connection 9) 
3)
switching device optionally withdrawable part with voltage transformers and fuses, hand operated 
closed (1250A) 
natural ventilated 
connection cable connection 
9)
bar connection 
optionally block type current transformers 
optionally fixed mounted voltage transformers 6) 
7)
optionally capacitive voltage indication 
detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) possible only in 1250 A panel
3) not possible in combination with truck type
4) low voltage compartment as advanced delivery is not possible for this version, only in combination with a panel
5) 2000A, 2500 A and 3150 A panels are natural ventilated, 4000 A panel is forced ventilated
6) possible only in 1250A and 2500A panel
7) only in combination with metering module possible
8) only for 2000 A and 2500 A busbar currents but no top box possible due to ventilation boxes at the busbar
9) when bar connection is selected bars, insulating bushings and bottom plate is part of delivery but loose delivery and must be assembled on site. Cross
section of bars see chapter 7.3
Attention: Insulated bars (DURESCA, Moser Glaser, …) must be assembled outside the connection compartment

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 34 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

4 Panel specification – Duplex in back-to-back arrangement

Example: CB panel in back-to-back arrangement

Example: Bus coupler panel in back-to-back arrangement

A. Following typicals are selectable as duplex with bar connection between row A and row B
 Circuit breaker panels in back-to-back design (4.1.1)
 Disconnector panels in back-to-back design (4.1.1)
 Bus coupler panel in back-to-back design (4.1.2)

B. Following typicals can be adapted to Duplex in back-to-back arrangement (w/o connection between row A and row) as single panels
 Circuit breaker panels (3.1.1)
 Disconnector panels (3.1.1)
 Vacuum contactor panels (3.1.2)
 Metering panels (3.1.3)
 Switch disconnector panels with HRC-fuses (3.1.4)
 Bus sectionalizer type I (CB panel and bus riser panel with disconnecting module) (3.1.6.1)
 Bus sectionalizer type II (CB panel and bus riser panel or CB panel and bus riser panel with metering unit) (3.1.6.2)
 Busbar current metering panel (3.1.5)
 Busbar connecting panel (3.1.7)

C. Following restrictions are given:


 No handrails at rear side possible
 No thermal inspection window at rear cover of cable connection compartment possible
 Not possible in combination with rear box
 Not possible in combination with IPX1 or IPX2
 Pressure relief duct to rear side not possible
 Extended CT not possible for:
o All types of bus coupler panels
o All types of Bus sectionalizer
o All types of circuit breaker and disconnector panels as single panels
 No mechanical interlocking of switching devices between row A and row B possible, for realization of an interlocking an
electrical interlocking must be engineered

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 35 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

4.1 Components in duplex versions in back-to-back arrangement


4.1.1 Circuit breaker panel
panel width (mm) compartment 1) design resp. devices – duplex in back-to-back arrangement

600 2) busbar bare copper 

optionally insulated copper 

optionally with top box for voltage transformers 

optionally with busbar earthing switch hand operated 3) 

optionally with top box for earthing switch motor operated 3) 


6)
optionally with top box for bar or cable connection 

optionally with top box for SIQuench, controller, charging mechanism and CAPDIS S2 3) 

optionally with top box for surge arrester type 3EK 

bushing type insulators between breaker and busbar 

optionally bushing type insulator 4ME as LPCT for current measuring at row A and row B 

optionally bushing type insulator 4ME as LPVT for voltage measuring at row A and row B 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage 
measuring (both at row A and row B)

optionally capacitive voltage indication at row A and row B 

switching device withdrawable circuit breaker, hand operated, for row A 

withdrawable circuit breaker, hand operated, for row A and row B 

optionally withdrawable circuit breaker, motor operated, for row A 

optionally withdrawable circuit breaker, motor operated, for row A and row B 

closed panel, without slots

connection cables from front at row A 

bushing type insulators for each panel and optionally 1 set block type current 
transformers installed in row A

bushing type insulators for each panel and optionally 1 set extended block type current 
transformers up to 17.5 kV / 31.5 kA / 2500 A possible 4) installed in row A

optionally bushing type insulator 4ME as LPCT for current measuring at row A and row B 

optionally bushing type insulator 4ME as LPVT for voltage measuring at row B 

optionally bushing type insulator 4ME as LPCT for current measuring at row A and row B 
and LPVT for voltage measuring at row B

optionally fixed mounted voltage transformers installed in row B 

optionally withdrawable voltage transformers in separate compartment with fuses 5) 


installed in row A

optionally earthing switch hand operated installed in row A 

optionally surge arrestors installed in row B 

optionally capacitive voltage indication at row A and row B 

optionally devices for zero sequence transformers at row A 

optionally devices for zero sequence transformers as LPCT at row A 

detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) only up to 31.5 kA, top boxes on busbar compartment only for busbar currents ≤ 2500A possible
3) low voltage compartment as advanced delivery is not possible for this version, only in combination with a panel
4) higher specific core data of ct possible, panel depth does not increases (see chapter 6.1)
5) not possible when truck type design is selected, fuses without any tripping mechanism, in 600 mm panel withdrawable VT also not possible in combination
with key interlocking or motor operated cassette
6) when bar connection is selected bars, insulating bushings and bottom plate is part of delivery but loose delivery and must be assembled on site. Cross
section of bars see chapter 7.3
Attention: Insulated bars (DURESCA, Moser Glaser, …) must be assembled outside the connection compartment

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 36 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

4.1.1 Circuit breaker panel


panel width (mm) compartment 1) design resp. devices – duplex in back-to-back arrangement

800 busbar bare copper 

(closed panel) optionally insulated copper 

optionally with top box for earthing switch hand operated 3) 

optionally with top box for earthing switch motor operated 3) 

optionally with top box for voltage transformers 

bushing type insulator between breaker and busbar 

optionally bushing type insulator 4ME as LPCT for current measuring at row A and row B 

optionally bushing type insulator 4ME as LPVT for voltage measuring at row A and row B 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage 
measuring (both at row A and row B)
7)
optionally with top box for bar or cable connection 

optionally with top box for SIQuench, controller, charging mechanism and CAPDIS S2 3) 

optionally with top box for surge arrester type 3EK 

optionally capacitive voltage indication at row A and row B 

switching device withdrawable circuit breaker, hand operated, for row A 

withdrawable circuit breaker, hand operated, for row A and row B 

optionally withdrawable circuit breaker, motor operated, for row A 

optionally withdrawable circuit breaker, motor operated, for row A and row B 

optionally withdrawable disconnector link, hand operated, for row A 

optionally withdrawable disconnector link, hand operated, for row A and row B 

optionally withdrawable disconnector link, motor operated, for row A 

optionally withdrawable disconnector link, motor operated, for row A and row B 

closed panel, without ventilation slots 6)

7)
connection cables or optionally bar connection from front at row A 

bushing type insulators for each panel and optionally 1 set block type current 
transformers installed in row A

bushing type insulators for each panel and optionally 1 set extended block type current 
transformers up to 17.5 kV / 31.5 kA / 2500 A possible 4) or up to 17.5 kV/40 kA / ≤ 4000
A resp. up to 17.5 kV 25/31.5 kA / 3150/4000 A 4) installed in row A

optionally bushing type insulator 4ME as LPCT for current measuring at row A and row B 

optionally bushing type insulator 4ME as LPVT for voltage measuring at row B 

optionally bushing type insulator 4ME as LPCT for current measuring at row A and row B 
and LPVT for voltage measuring at row B

optionally fixed mounted voltage transformers installed in row B 

optionally withdrawable voltage transformers in separate compartment with fuses 5) 


installed in row A

optionally earthing switch hand operated at row A 

optionally earthing switch motor operated at row A 

optionally surge arrestors installed in row B 

optionally capacitive voltage indication at row A and row B 

optionally devices for zero sequence transformers installed in row A 

optionally devices for zero sequence transformers as LPCT at row A 

detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) only up to 31.5 kA, top boxes on busbar compartment only for busbar currents ≤ 2500A possible
3) low voltage compartment as advanced delivery is not possible for this version, only in combination with a panel
4) higher specific core data of ct possible, panel depth does not increases (see chapter 6.1)
5) not possible when truck type design is selected, fuses without any tripping mechanism, in 600 mm panel withdrawable VT also not possible in
combination with key interlocking or motor operated cassette
6) only up to 17,5 kV, ≤ 40 kA, 1250 A
7) when bar connection is selected bars, insulating bushings and bottom plate is part of delivery but loose delivery and must be assembled on site. Cross
section of bars see chapter 7.3
Attention: Insulated bars (DURESCA, Moser Glaser, …) must be assembled outside the connection compartment

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 37 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

4.1.1 Circuit breaker panel


panel width (mm) compartment 1) design resp. devices – duplex in back-to-back arrangement

800 mm busbar bare copper 

(ventilated panel) optionally insulated copper 

bushing type insulator between breaker and busbar 

optionally bushing type insulator 4ME as LPCT for current measuring at row A and row B 

optionally bushing type insulator 4ME as LPVT for voltage measuring at row A and row B 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage 
measuring (both at row A and row B)

optionally capacitive voltage indication at row A and row B 

switching device withdrawable circuit breaker, hand operated, for row A 

withdrawable circuit breaker, hand operated, for row A and row B 

optionally withdrawable circuit breaker, motor operated, for row A 

optionally withdrawable circuit breaker, motor operated, for row A and row B 

optionally withdrawable disconnector link, hand operated, for row A 

optionally withdrawable disconnector link, hand operated, for row A and row B 

optionally withdrawable disconnector link, motor operated, for row A 

optionally withdrawable disconnector link, motor operated, for row A and row B 

natural ventilated 4) 
5)
connection cables or optionally bar connection from front at row A 

bushing type insulators for each panel and optionally 1 set block type current 
transformers installed in row A

bushing type insulators for each panel and optionally 1 set extended block type current 
transformers up to 17.5 kV / 31.5 kA / 2500 A possible 2) or up to 17.5 kV/40 kA / ≤ 4000
A resp. up to 17.5 kV 25/31.5 kA / 3150/4000 A 2) installed in row A

optionally bushing type insulator 4ME as LPCT for current measuring at row A and row B 

optionally bushing type insulator 4ME as LPVT for voltage measuring at row B 

optionally bushing type insulator 4ME as LPCT for current measuring at row A and row B 
and LPVT for voltage measuring at row B

optionally fixed mounted voltage transformers in row B 

optionally withdrawable voltage transformers in separate compartment with fuses 3) 


installed in row A

optionally earthing switch hand operated at row A 

optionally earthing switch motor operated at row A 

optionally surge arrestors installed in row B 

optionally capacitive voltage indication at row A and row B 

optionally devices for zero sequence transformers installed in row A 

optionally devices for zero sequence transformers as LPCT at row A 

detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) higher specific core data of ct possible, panel depth does not increases (see chapter 6.1)
3) not possible when truck type design is selected, fuses without any tripping mechanism, in 600 mm panel withdrawable VT also not possible in
combination with key interlocking or motor operated cassette
4) only for up to 17,5kV, ≤ 40 kA, 2000A (only ventilation box at the top, no ventilation slots at the front)
5) when bar connection is selected bars, insulating bushings and bottom plate is part of delivery but loose delivery and must be assembled on site. Cross
section of bars see chapter 7.3
Attention: Insulated bars (DURESCA, Moser Glaser, …) must be assembled outside the connection compartment

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 38 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

4.1.1 Circuit breaker panel


panel width (mm) compartment 1) design resp. devices – duplex in back-to-back arrangement

1000 mm busbar bare copper 

(ventilated panel) optionally insulated copper 

bushing type insulator between breaker and busbar 

optionally bushing type insulator 4ME as LPCT for current measuring at row A and row B 

optionally bushing type insulator 4ME as LPVT for voltage measuring at row A and row B 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage 
measuring (both at row A and row B)

optionally capacitive voltage indication at row A and row B 

switching device withdrawable circuit breaker, hand operated, for row A 

withdrawable circuit breaker, hand operated, for row A and row B 

optionally withdrawable circuit breaker, motor operated, for row A 

optionally withdrawable circuit breaker, motor operated, for row A and row B 

optionally withdrawable disconnector link, hand operated, for row A 

optionally withdrawable disconnector link, hand operated, for row A and row B 

optionally withdrawable disconnector link, motor operated, for row A 

optionally withdrawable disconnector link, motor operated, for row A and row B 

natural ventilated 4) 

forced ventilated 5), current relays controlled 

forced ventilated 5), current relays controlled and redundant version 


6)
connection cables or optionally bar connection from front at row A 

bushing type insulators for each panel and optionally 1 set block type current 
transformers installed in row A

bushing type insulators for each panel and optionally 1 set extended block type current 
transformers up to 17.5 kV/31.5 kA / 2500 A possible 2) or up to 17.5 kV/40 kA / ≤4000 A
resp. up to 17.5 kV 25/31.5 kA / 3150/4000 A 2) installed in row A

optionally bushing type insulator 4ME as LPCT for current measuring at row A and row B 

optionally bushing type insulator 4ME as LPVT for voltage measuring at row B 

optionally bushing type insulator 4ME as LPCT for current measuring at row A and row B 
and LPVT for voltage measuring at row B

optionally fixed mounted voltage transformers in row B 

optionally withdrawable voltage transformers in separate compartment with fuses 3) 


installed in row A

optionally earthing switch hand operated at row A 

optionally earthing switch motor operated at row A 

optionally surge arrestors installed in row B 

optionally capacitive voltage indication at row A and row B 

optionally devices for zero sequence transformers installed in row A 

optionally devices for zero sequence transformers as LPCT at row A 

detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) higher specific core data of ct possible, panel depth does not increase (see chapter 6.1)
3) not possible when truck type design is selected, fuses without any tripping mechanism, in 600 mm panel withdrawable VT also not possible in
combination with key interlocking or motor operated cassette and in 3150 A feeder
4) 2500 A / 3150 A natural ventilated,
5) 4000 A forced ventilated
6) when bar connection is selected bars, insulating bushings and bottom plate is part of delivery but loose delivery and must be assembled on site. Cross
section of bars see chapter 7.3
Attention: Insulated bars (DURESCA, Moser Glaser, …) must be assembled outside the connection compartment

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 39 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

4.1.2 Bus coupler (coupling row A with row B)


4.1.2.1 Bus coupler panel 1250 A
Panel width (mm) Compartment 1) Design resp. devices per panel in back-to-back design

800 mm busbar busbar current must be maximum from both neighboring busbars

(closed panel) bare copper 

optionally insulated copper 

optionally with top box for earthing switch hand operated 3) 

optionally with top box for earthing switch motor operated 3) 

optionally with top box for voltage transformers 

bushing type insulator between breaker and busbar 

optionally bushing type insulator 4ME as LPCT for current measuring at row A 

optionally bushing type insulator 4ME as LPVT for voltage measuring at row A and row B 

optionally bushing type insulator 4ME as LPCT for current measuring at row A and LPVT 
for voltage measuring at row A and row B
4)
optionally with top box for bar or cable connection 

optionally with top box for SIQuench, controller, charging mechanism and CAPDIS S2 3) 

optionally with top box for surge arrester type 3EK 

optionally capacitive voltage indication at row A and row B 

switching device withdrawable circuit breaker, hand operated, for row A 

withdrawable circuit breaker, hand operated, for row A and B 

optionally withdrawable circuit breaker, motor operated for row A 

optionally withdrawable circuit breaker, motor operated for row A and B 

optionally withdrawable disconnector link, hand operated, for row A 

optionally withdrawable disconnector link, hand operated, for row A and B 

optionally withdrawable disconnector link, motor operated, for row A 

optionally withdrawable disconnector link, motor operated, for row A and B 

closed panel, without ventilation slots 


2)
connection bushing type insulators and optionally block type current transformers installed in row A 

optionally bushing type insulator 4ME as LPCT for current measuring at row A 

optionally bushing type insulator 4ME as LPVT for voltage measuring at row A 

optionally bushing type insulator 4ME as LPCT for current measuring and LPVT for 
voltage measuring at row A

optionally capacitive voltage indication at row A and row B 


detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) no extended CT in bus coupler panel possible
3) low voltage compartment as advanced delivery is not possible for this version, only in combination with a panel
4) when bar connection is selected bars, insulating bushings and bottom plate is part of delivery but loose delivery and must be assembled on site. Cross
section of bars see chapter 7.3
Attention: Insulated bars (DURESCA, Moser Glaser, …) must be assembled outside the connection compartment

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 40 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

4)
4.1.2.2 Bus coupler panel 2000 A
Panel width (mm) Compartment 1) Design resp. devices per panel in back-to-back design

800 mm busbar busbar current must be maximum from both neighboring busbars

(ventilated panel) bare copper 

optionally insulated copper 

bushing type insulator between breaker and busbar 

optionally bushing type insulator 4ME as LPCT for current measuring at row A 

optionally bushing type insulator 4ME as LPVT for voltage measuring at row A and row B 

optionally bushing type insulator 4ME as LPCT for current measuring at row A and LPVT 
for voltage measuring at row A and row B

optionally capacitive voltage indication at row A and row B 

switching device withdrawable circuit breaker, hand operated, for row A 

withdrawable circuit breaker, hand operated, for row A and B 

optionally withdrawable circuit breaker, motor operated for row A 

optionally withdrawable circuit breaker, motor operated for row A and B 

optionally withdrawable disconnector link, hand operated, for row A 

optionally withdrawable disconnector link, hand operated, for row A and B 

optionally withdrawable disconnector link, motor operated, for row A 

optionally withdrawable disconnector link, motor operated, for row A and B 

natural ventilated 3) 
2)
connection bushing type insulators and optionally block type current transformers installed in row A 

optionally bushing type insulator 4ME as LPCT for current measuring at row A 

optionally bushing type insulator 4ME as LPVT for voltage measuring at row A 

optionally bushing type insulator 4ME as LPCT for current measuring and LPVT for 
voltage measuring at row A

optionally capacitive voltage indication at row A and row B 


detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) no extended CT in bus coupler panel possible
3) only for up to 17,5kV, ≤ 40 kA, 2000A (only ventilation box at the top, no ventilation slots at the front)
4) not for 40 kA

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 41 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

1.1.1.1.1
4.1.2 Bus coupler (coupling row A with row B)
4.1.2.3 Bus coupler panel 2500 A
Panel width (mm) Compartment 1) Design resp. devices per panel in back-to-back design

1000 mm busbar busbar current must be maximum from both neighboring busbars

(ventilated panel) bare copper 

optionally insulated copper 

bushing type insulator between breaker and busbar 

optionally bushing type insulator 4ME as LPCT for current measuring at row A 

optionally bushing type insulator 4ME as LPVT for voltage measuring at row A and row B 

optionally bushing type insulator 4ME as LPCT for current measuring at row A and LPVT 
for voltage measuring at row A and row B

optionally capacitive voltage indication at row A and row B 

switching device withdrawable circuit breaker, hand operated, for row A 

withdrawable circuit breaker, hand operated, for row A and B 

optionally withdrawable circuit breaker, motor operated for row A 

optionally withdrawable circuit breaker, motor operated for row A and B 

optionally withdrawable disconnector link, hand operated, for row A 

optionally withdrawable disconnector link, hand operated, for row A and B 

optionally withdrawable disconnector link, motor operated, for row A 

optionally withdrawable disconnector link, motor operated, for row A and B 

natural ventilated 3) 
2)
connection bushing type insulators and optionally block type current transformers installed in row A 

optionally bushing type insulator 4ME as LPCT for current measuring at row A 

optionally bushing type insulator 4ME as LPVT for voltage measuring at row A 

optionally bushing type insulator 4ME as LPCT for current measuring and LPVT for 
voltage measuring at row A

optionally capacitive voltage indication at row A and row B 


detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) no extended CT in bus coupler panel possible
3) 2500 A / 3150 A natural ventilated

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 42 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

4.1.2.4 Bus coupler panel 3150 A and 4000 A


Panel width (mm) Compartment 1) Design resp. devices per panel in back-to-back design

1000 mm busbar busbar current must be maximum from both neighboring busbars

(ventilated panel) bare copper 

optionally insulated copper 

bushing type insulator between breaker and busbar 

optionally bushing type insulator 4ME as LPCT for current measuring at row A 

optionally bushing type insulator 4ME as LPVT for voltage measuring at row A and row B 

optionally bushing type insulator 4ME as LPCT for current measuring at row A and LPVT 
for voltage measuring at row A and row B

optionally capacitive voltage indication at row A and row B 

switching device withdrawable circuit breaker, hand operated, for row A 

withdrawable circuit breaker, hand operated, for row A and B 

optionally withdrawable circuit breaker, motor operated for row A 

optionally withdrawable circuit breaker, motor operated for row A and B 

optionally withdrawable disconnector link, hand operated, for row A 

optionally withdrawable disconnector link, hand operated, for row A and B 

optionally withdrawable disconnector link, motor operated, for row A 

optionally withdrawable disconnector link, motor operated, for row A and B 

natural ventilated 3) 

forced ventilated 4), current relais controlled 

forced ventilated 4), current relais controlled and redundant version 


2)
connection bushing type insulators and optionally block type current transformers installed in row A 

optionally bushing type insulator 4ME as LPCT for current measuring at row A 

optionally bushing type insulator 4ME as LPVT for voltage measuring at row A 

optionally bushing type insulator 4ME as LPCT for current measuring and LPVT for 
voltage measuring at row A

optionally capacitive voltage indication at row A and row B 


detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) no extended CT in bus coupler panel possible
3) 2500 A / 3150 A natural ventilated,
4) 4000 A forced ventilated

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 43 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

5 Panel specification – Duplex in front-to-front arrangement


5.1 Components in duplex versions in font-to-front arrangement

A. Following typicals are selectable as duplex in front-to-front arrangement (without bar or cable connection between row A
and row B):
 Circuit breaker panels (5.1.1 – 5.1.4)
 Disconnector panels (5.1.1 – 5.1.4)
 Vacuum contactor panels (3.1.2)
 Metering panels (3.1.3)
 Switch disconnector panels with HRC-fuses (3.1.4)
 Busbar current metering panel (3.1.5)
 Bus sectionalizer type I (CB panel and bus riser panel with disconnecting module) (3.1.6.1)
 Bus sectionalizer type II (CB panel and bus riser panel or CB panel and bus riser panel with metering unit) (3.1.6.2)
 Busbar connecting panel (3.1.7)

B. Configuration of NXAIR Duplex in front-to-front arrangement in NXTools+


 as single panels, definition of row A and row B chosen in NXTools+ separately
 No mechanical interlocking of switching devices between row A and row B possible for realization of an
interlocking an electrical interlocking must be engineered
 Current transformers in circuit breaker panels and disconnector panels must be configured in corresponding
panels of row A and row B identically

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 44 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

5.1.1 Circuit breaker panel


panel width (mm) compartment 1) design resp. devices – duplex in front-to-front arrangement
600 2) busbar bare copper 
optionally insulated copper 
optionally with top box for voltage transformers 
optionally with busbar earthing switch hand operated 3) 
optionally with top box for earthing switch motor operated 3) 
7)
optionally with top box for bar or cable connection 
optionally with top box for SIQuench, controller, charging mechanism and CAPDIS S2 3) 
optionally with top box for surge arrester type 3EK 
bushing type insulators between breaker and busbar 
optionally bushing type insulator 4ME as LPCT for current measuring 
optionally bushing type insulator 4ME as LPVT for voltage measuring 
optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 
optionally capacitive voltage indication at row A and row B 
switching device withdrawable circuit breaker, hand operated, for row A 
withdrawable circuit breaker, hand operated, for row A and row B 
optionally withdrawable circuit breaker, motor operated, for row A 
optionally withdrawable circuit breaker, motor operated, for row A and row B 
closed panel, without slots
6)
connection cable connection at row A and row B 
bushing type insulators for each panel and optionally 1 set block type current transformers 
for each panel installed at row A and row B
bushing type insulators for each panel and optionally 1 set extended block type current 
transformers up to 17.5 kV / 31.5 kA / 2500 A possible 4) for each panel installed at row A
and row B
optionally bushing type insulator 4ME as LPCT for current measuring 
optionally bushing type insulator 4ME as LPVT for voltage measuring 
optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 
optionally fixed mounted voltage transformers installed in row A 
optionally withdrawable voltage transformers in separate compartment with fuses 5) 
installed in row A
optionally earthing switch hand operated installed in row A 
optionally surge arrestors installed in row A 
optionally capacitive voltage indication at row A and row B 
optionally devices for zero sequence transformers at row A 
optionally devices for zero sequence transformers as LPCT at row A 
detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) only up to 31.5 kA, top boxes on busbar compartment only for busbar currents ≤ 2500A possible
3) low voltage compartment as advanced delivery is not possible for this version, only in combination with a panel
4) higher specific core data of ct possible, panel depth increases (see chapter 6.1)
5) not possible when truck type design is selected, fuses without any tripping mechanism, in 600 mm panel withdrawable VT also not possible in combination
with key interlocking or motor operated cassette
6) in panels of row A cables to load and connection to opposite panel in row B are connected, quantity of cables at opposite panel is half of cables quantity at
main panel, max. quantity of cable sealing ends in cable connection compartment of row A must be considered
7) when bar connection is selected bars, insulating bushings and bottom plate is part of delivery but loose delivery and must be assembled on site. Cross
section of bars see chapter 7.3
Attention: Insulated bars (DURESCA, Moser Glaser, …) must be assembled outside the connection compartment

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 45 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

5.1.2 Circuit breaker panel


panel width (mm) compartment 1) design resp. devices – duplex in front-to-front arrangement

800 busbar bare copper 

(closed panel) optionally insulated copper 

optionally with top box for earthing switch hand operated 3) 

optionally with top box for earthing switch motor operated 3) 

optionally with top box for voltage transformers 

bushing type insulator between breaker and busbar 


8)
optionally with top box for bar or cable connection 

optionally bushing type insulator 4ME as LPCT for current measuring 

optionally bushing type insulator 4ME as LPVT for voltage measuring 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 

optionally with top box for SIQuench, controller, charging mechanism and CAPDIS S2 3) 

optionally with top box for surge arrester type 3EK 

optionally capacitive voltage indication at row A and row B 

switching device withdrawable circuit breaker, hand operated, for row A 

withdrawable circuit breaker, hand operated, for row A and row B 

optionally withdrawable circuit breaker, motor operated, for row A 

optionally withdrawable circuit breaker, motor operated, for row A and row B 

optionally withdrawable disconnector link, hand operated, for row A 

optionally withdrawable disconnector link, hand operated, for row A and row B 

optionally withdrawable disconnector link, motor operated, for row A 

optionally withdrawable disconnector link, motor operated, for row A and row B 

closed panel, without slots 6) 


7) 8)
connection cable or optionally bar connection at row A and row B 

bushing type insulators for each panel and optionally block type current transformers for each 
panel installed at row A and row B

bushing type insulators for each panel and optionally 1 set extended block type current 
transformers up to 17.5 kV / 31.5 kA / 2500 A possible 4) or up to 17.5 kV/40 kA / ≤ 4000 A
resp. up to 17.5 kV 25/31.5 kA / 3150/4000 A 4) for each panel installed at row A and row B

optionally fixed mounted voltage transformers installed in row A 

optionally withdrawable voltage transformers in separate compartment with fuses 5) installed 


in row A

optionally bushing type insulator 4ME as LPCT for current measuring 

optionally bushing type insulator 4ME as LPVT for voltage measuring 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 

optionally earthing switch hand operated at row A 

optionally earthing switch motor operated at row A 

optionally surge arrestors installed in row A 

optionally capacitive voltage indication at row A and row B 

optionally devices for zero sequence transformers installed in row A 

optionally devices for zero sequence transformers as LPCT at row A 

detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) only up to 31.5 kA, top boxes on busbar compartment only for busbar currents ≤ 2500A possible
3) low voltage compartment as advanced delivery is not possible for this version, only in combination with a panel
4) higher specific core data of ct possible, panel depth increases (see chapter 6.1)
5) not possible when truck type design is selected, fuses without any tripping mechanism, in 600 mm panel withdrawable VT also not possible in
combination with key interlocking or motor operated cassette
6) only up to 17,5 kV, ≤ 40 kA, 1250 A
7) in panels of row A cables to load and connection to opposite panel in row B are connected, quantity of cables at opposite panel is half of cables
quantity at main panel, max. quantity of cable sealing ends in cable connection compartment of row A must be considered
8) when bar connection is selected bars, insulating bushings and bottom plate is part of delivery but loose delivery and must be assembled on site. Cross
section of bars see chapter 7.3
Attention: Insulated bars (DURESCA, Moser Glaser, …) must be assembled outside the connection compartment

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 46 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

5.1.3 Circuit breaker panel


panel width (mm) compartment 1) design resp. devices – duplex in front-to-front arrangement

800 mm busbar bare copper 

(ventilated panel) optionally insulated copper 

bushing type insulator between breaker and busbar 

optionally bushing type insulator 4ME as LPCT for current measuring 

optionally bushing type insulator 4ME as LPVT for voltage measuring 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 

optionally capacitive voltage indication at row A and row B 

switching device withdrawable circuit breaker, hand operated, for row A 

withdrawable circuit breaker, hand operated, for row A and row B 

optionally withdrawable circuit breaker, motor operated, for row A 

optionally withdrawable circuit breaker, motor operated, for row A and row B 

optionally withdrawable disconnector link, hand operated, for row A 

optionally withdrawable disconnector link, hand operated, for row A and row B 

optionally withdrawable disconnector link, motor operated, for row A 

optionally withdrawable disconnector link, motor operated, for row A and row B 

natural ventilated 4) 
5) 6)
connection cable or optionally bar connection at row A and row B 

bushing type insulators for each panel and optionally block type current transformers for each 
panel installed at row A and row B

bushing type insulators for each panel and optionally 1 set extended block type current 
transformers up to 17.5 kV / 31.5 kA / 2500 A possible 2) or up to 17.5 kV/40 kA / ≤ 4000 A
resp. up to 17.5 kV 25/31.5 kA / 3150/4000 A 2) for each panel installed at row A and row B

optionally bushing type insulator 4ME as LPCT for current measuring 

optionally bushing type insulator 4ME as LPVT for voltage measuring 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 

optionally fixed mounted voltage transformers in row A 

optionally withdrawable voltage transformers in separate compartment with fuses 3) installed 


in row A

optionally earthing switch hand operated at row A 

optionally earthing switch motor operated at row A 

optionally surge arrestors installed in row A 

optionally capacitive voltage indication at row A and row B 

optionally devices for zero sequence transformers installed in row A 

optionally devices for zero sequence transformers as LPCT at row A 

detailed configuration in NX-Tools+

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) higher specific core data of ct possible, panel depth increases (see chapter 6.1)
3) not possible when truck type design is selected, fuses without any tripping mechanism, in 600 mm panel withdrawable VT also not possible in
combination with key interlocking or motor operated cassette
4) only for up to 17,5 kV, ≤ 40 kA, 2000 A (only ventilation box at the top no ventilation slots at the front)
5) in panels of row A cables to load and connection to opposite panel in row B are connected, quantity of cables at opposite panel is half of cables
quantity at main panel, max. quantity of cable sealing ends in cable connection compartment of row A must be considered
6) when bar connection is selected bars, insulating bushings and bottom plate is part of delivery but loose delivery and must be assembled on site. Cross
section of bars see chapter 7.3
Attention: Insulated bars (DURESCA, Moser Glaser, …) must be assembled outside the connection compartment

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 47 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

5.1.4 Circuit breaker panel


panel width (mm) compartment 1) design resp. devices – duplex in front-to-front arrangement

1000 mm busbar bare copper 

(ventilated panel) optionally insulated copper 

bushing type insulator between breaker and busbar 

optionally bushing type insulator 4ME as LPCT for current measuring 

optionally bushing type insulator 4ME as LPVT for voltage measuring 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 

optionally capacitive voltage indication at row A and row B 

switching device withdrawable circuit breaker, hand operated, for row A 

withdrawable circuit breaker, hand operated, for row A and row B 

optionally withdrawable circuit breaker, motor operated, for row A 

optionally withdrawable circuit breaker, motor operated, for row A and row B 

optionally withdrawable disconnector link, hand operated, for row A 

optionally withdrawable disconnector link, hand operated, for row A and row B 

optionally withdrawable disconnector link, motor operated, for row A 

optionally withdrawable disconnector link, motor operated, for row A and row B 

natural ventilated 4) 

forced ventilated 4), current relais controlled 

forced ventilated 4), current relais controlled and redundant version 


5) 6)
connection cable or optionally bar connection at row A and row B 

bushing type insulators for each panel and optionally block type current transformers for 
each panel installed at row A and row B

bushing type insulators for each panel and optionally 1 set extended block type current 
transformers up to 17.5 kV/31.5 kA / 2500 A possible 2) or up to 17.5 kV/40 kA / ≤4000 A
resp. up to 17.5 kV 25/31.5 kA / 3150/4000 A 2) for each panel installed at row A and row B

optionally bushing type insulator 4ME as LPCT for current measuring 

optionally bushing type insulator 4ME as LPVT for voltage measuring 

optionally bushing type insulator 4ME as LPCT for current and LPVT for voltage measuring 

optionally fixed mounted voltage transformers in row A 

optionally withdrawable voltage transformers in separate compartment with fuses 3) 


installed in row A

optionally earthing switch hand operated at row A 

optionally earthing switch motor operated at row A 

optionally surge arrestors installed in row A 

optionally capacitive voltage indication at row A and row B 

optionally devices for zero sequence transformers installed in row A 

optionally devices for zero sequence transformers as LPCT at row A 

5.1.5 Other typicals for duplex in front-to-front arrangement

Following typicals can be selected and mixed in front-to-front installation with above described circuit breaker or disconnector panels:
 Vacuum contactor panels
 Switch disconnector panels with HRC-fuses
 Metering panels
 Busbar current metering panel
 Bus sectionalizer type I (CB panel and bus riser panel with disconnecting module)
 Bus sectionalizer type II (CB panel and bus riser panel or CB panel and bus riser panel with metering unit)
 Busbar connecting panel

1) permissible combinations of equipment in busbar and connection compartment, see also chapter 15.9, 15.10
2) higher specific core data of ct possible, panel depth increases (see chapter 6.1)
3) not possible when truck type design is selected, fuses without any tripping mechanism, in 600 mm panel withdrawable VT also not possible in
combination with key interlocking or motor operated cassette and in 3150 A feeder (1000 mm)
4) 2500 A / 3150 A natural ventilated, 4000 A forced ventilated
5) in panels of row A cables to load and connection to opposite panel in row B are connected, quantity of cables at opposite panel is half of cables
quantity at main panel, max. quantity of cable sealing ends in cable connection compartment of row A must be considered
6) when bar connection is selected bars, insulating bushings and bottom plate is part of delivery but loose delivery and must be assembled on site. Cross
section of bars see chapter 7.3
Attention: Insulated bars (DURESCA, Moser Glaser, …) must be assembled outside the connection compartment

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 48 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

6 Configuration of panels
6.1. Panel types
basic rated panel type short busbar current 1) feeder current 1) panel design width depth depth
2)
ver- voltage circuit (A) (A) (with
sion breaking extended
current rated busbar rated rated rated CT) 6)
current current breaker panel
current current
(kV) (kA) (A) (A) (A) (A) (mm) (mm) (mm)
 ≤ 17.5 Switching 25 1250 630 800 630 closed 600 1350 1500
device
 1000 1250 1000
panel
 with circuit 1250 1600 1250 800
breaker
 or 2000 630 800 630 closed 600
disconnecting
 1000 1250 1000
link
 1250 1600 1250 800
 2000 2500 2000 natural ventilated 800
 2500 630 800 630 closed 600
 1000 1250 1000
 1250 1600 1250 800
 2000 2500 2000 natural ventilated 800
 2500 2500 2500 natural ventilated 1000
 3150 630 800 630 closed 600 1500 1500
 1000 1250 1000
 1250 1600 1250 800
 2000 2500 2000 natural ventilated 800
 2500 2500 2500 natural ventilated 1000
 3150 3150 3150 natural ventilated 1000 1540 1650
 4000 630 800 630 closed 600 1500 1500
 1000 1250 1000
 1250 1600 1250 800
 2000 2500 2000 natural ventilated 800
 2500 2500 2500 natural ventilated 1000
 3150 3150 3150 natural ventilated 1000 1540 1650
 4000 4000 4000 forced ventilated 3) 1000
 31.5 1250 630 800 630 closed 600 1350 1500
 1000 1250 1000
4)
 1250 1250 1250 800
 2000 630 800 630 closed 600
 1000 1250 1000
4)
 1250 1250 1250 800
 2000 2500 2000 natural ventilated 800
 2500 630 800 630 closed 600
 1000 1250 1000
4)
 1250 1250 1250 800
 2000 2500 2000 natural ventilated 800
 2500 2500 2500 natural ventilated 1000
 3150 630 800 630 closed 600 1500 1500
 1000 1250 1000
4)
 1250 1250 1250 800
 2000 2500 2000 natural ventilated 800
 2500 2500 2500 natural ventilated 1000
 3150 3150 3150 natural ventilated 1000 1540 1650
 4000 630 800 630 closed 600 1500 1500
 1000 1250 1000
4)
 1250 1250 1250 800
 2000 2500 2000 natural ventilated 800
 2500 2500 2500 natural ventilated 1000
 3150 3150 3150 natural ventilated 1000 1540 1650
 4000 4000 4000 forced ventilated 3) 1000

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 49 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

6.1.1 Panel types


basic rated panel type short busbar current 1) feeder current 1) panel design width depth depth
2)
ver- voltage circuit (A) (A) (with
sion breaking extended
current rated busbar rated rated rated CT) 6)
current current breaker panel
current current
(kV) (kA) (A) (A) (A) (A) (mm) (mm) (mm)
 ≤ 17.5 Switching 40 1250 1250 1250 1250 closed 800 1500 1500
device
 panel 2500 1250 1250 1250 closed 800
 with circuit 2000 2500 2000 natural ventilated 800
breaker
 or 2500 2500 2500 1000
disconnecting
 3150 1250 1250 1250 closed 800
link
 2000 2500 2000 natural ventilated 800
 2500 2500 2500 1000
 3150 3150 3150 natural ventilated 1000 1540 1650
 4000 1250 1250 1250 closed 800 1500 1500
 2000 2500 2000 natural ventilated 800
 2500 2500 2500 1000
 3150 3150 3150 natural ventilated 1000 1540 1650
 4000 4000 4000 forced ventilated 3) 1000
 ≤ 12 Contactor ≤ 31.5 1250 ≤ 450 450 450 closed 435 1400 n.a.
panel 5)
 2000 ≤ 450 450 450 closed 435
 2500 ≤ 450 450 450 closed 435
 3150 ≤ 450 450 450 closed 435 1500 n.a.
 4000 ≤ 450 450 450 closed 435
 40 1250 ≤ 450 450 450 closed 435 1500 n.a.
 2500 ≤ 450 450 450 closed 435
 3150 ≤ 450 450 450 closed 435
 4000 ≤ 450 450 450 closed 435
 ≤ 17,5 Metering ≤ 31.5 1250 - - - closed 600 1350 n.a.
panel
 2000
 2500
 3150 1500 n.a.
 4000
 40 1250 - - - closed 800 1500 n.a.
 2500
 3150
 4000
 ≤ 17,5 Busbar ≤ 31.5 3150 - - - natural ventilated 800 1500 n.a.
current

metering 4000 natural ventilated
 panel 40 1250 - - - closed 800 1500 n.a.
 2500 closed
 3150 natural ventilated
 4000 natural ventilated

1) permissible current values depending on ambient temperature values, degree of protection etc are included in chapter 15
2) rear side cable connection from above additional 600 mm in depth for duct
3) forced ventilation standard, optionally redundant system
4) ≤ 12 kV at 31,5 kA a 1600 A CB is used
5) can be used for motor feeder and transformer feeder (not for transformer incomer), insulation level of GOST standard for 7.2 kV rated voltage as an
option possible, permissible current limited by used type of fuse
6) extended ct only possible in switching device panel, restriction for duplex arrangement (see chapter 4 and 5); extended ct in duplex back-to-back
arrangement does have no influence of panel depth due to position of Ct at rear side (standard panel depth depending on technical data is valid)

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 50 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

6.1.1 Panel types


basic rated panel type short busbar current 1) feeder current 1) panel design width depth depth
ver- voltage circuit (A) (A) (with
sion breaking extended
current CT) 3)
Rated busbar Rated Rated Rated
current current breaker panel
(kV) (kA) current current (mm) (mm) (mm)
(A) (A) (A) (A)
5)
 Bus 25 1250 1250 1250 1250 closed 2x800 1350 1500
sectionalizer
2000 2000 2500 2000 natural ventilated 2x1000
type I
 consisting of: 2500 2500 2500 2500 natural ventilated 2x1000
 switching 3150 3150 3150 3150 natural ventilated 2x1000 1540 1650
device panel
 and 4000 4000 4000 4000 forced ventilated 2) 2x1000
5)
 bus riser 31.5 1250 1250 1250 1250 closed 2x800 1350 1500
panel with 2000 2000 2500 2000 natural ventilated 2x1000
disconnector
 module 2500 2500 2500 2500 natural ventilated 2x1000
 3150 3150 3150 3150 natural ventilated 2x1000 1540 1650
2)
 4000 4000 4000 4000 forced ventilated 2x1000
 40 1250 1250 1250 1250 closed 2x800 1500 1500
 2500 2500 2500 2500 natural ventilated 2x1000
 3150 3150 3150 3150 natural ventilated 2x1000 1540 1650
 4000 4000 4000 4000 forced ventilated 2) 2x1000
5)
 Bus 25 1250 1250 1250 1250 closed 2x800 1350 1500
sectionalizer
2000 2000 2500 2000 natural ventilated 1x1000+
type II
1x800
consisting of:
 switching 2500 2500 2500 2500 natural ventilated 1x1000+
device panel 1x800
 and 3150 3150 3150 3150 natural ventilated 2x1000 1540 1650
 bus riser 4000 4000 4000 4000 forced ventilated 2) 2x1000
panel
5)
 optionally with 31.5 1250 1250 1250 1250 closed 2x800 1350 1500
metering 2000 2000 2500 2000 natural ventilated 1x1000+
module 3) 1x800
 2500 2500 2500 2500 natural ventilated 1x1000+
1x800
 3150 3150 3150 3150 natural ventilated 2x1000 1540 1650
2)
 4000 4000 4000 4000 forced ventilated 2x1000
 40 1250 1250 1250 1250 closed 2x800 1500 1500
 2500 2500 2500 2500 natural ventilated 1x1000+
1x800
 3150 3150 3150 3150 natural ventilated 2x1000 1540 1650
 4000 4000 4000 4000 forced ventilated 2) 2x1000
 ≤ 17.5 Bus coupler 25 1250 1250 1250 1250 closed 800 1350 ---
 only for 2000 2000 2500 2000 natural ventilated 800 1350 ---
Duplex in
 back-to-back 2500 2500 2500 2500 natural ventilated 1000 1350 ---
 arrangement 3150 3150 3150 3150 natural ventilated 1000 1500 ---
4)
 4000 4000 4000 4000 forced ventilated 2) 1000 1500 ---
 31.5 1250 1250 1250 1250 closed 800 1350 ---
 2000 2000 2500 2000 natural ventilated 800 1350 ---
 2500 2500 2500 2500 natural ventilated 1000 1350 ---
 3150 3150 3150 3150 natural ventilated 1000 1500 ---
 4000 4000 4000 4000 forced ventilated 2) 1000 1500 ---
 40 1250 1250 1250 1250 closed 800 1500 ---
 2500 2500 2500 2500 natural ventilated 1000 1500 ---
 3150 3150 3150 3150 natural ventilated 1000 1500 ---
 4000 4000 4000 4000 forced ventilated 2) 1000 1500 ---

1) permissible current values depending on ambient temperature values, degree of protection etc are included in chapter 15
2) forced ventilation current relays controlled, optionally redundant version possible, bus riser panel natural ventilated
3) extended ct only possible in switching device panel, but not for bus coupler and bus sectionalizer for duplex in back-to-back arrangement
4) depth of a single panel. Total depth of a complete bus coupler 2850 mm (≤ 31.5 kA, ≤ 2500 A) and 3150 mm (≤ 31.5 kA for 3150 A / 4000 A) and
3150 mm for 40 kA)
5) switching device panel natural ventilated in combination with bushing type CT 4MD between circuit breaker and busbar

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 51 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

6.1.1 Panel types


basic rated panel type short busbar current 1) feeder current 1) panel design width depth depth
ver- voltage circuit (with
sion breaking (A) (A) extended
current CT)
Rated busbar Rated Rated Rated
current current breaker panel
(kV) (kA) current current (mm) (mm) (mm)
(A) (A) (A) (A)

 ≤ 17,5 Busbar 25 1250 1250 - 1250 closed 800 1350 n.a.


connecting

panel 2500 2500 - 2500 natural ventilated 800
 3150 3150 - 3150 natural ventilated 1000 1540 n.a.
 4000 4000 - 4000 1000
 31.5 1250 1250 - 1250 closed 800 1350 n.a.
 2500 2500 - 2500 natural ventilated 800
 3150 3150 - 3150 natural ventilated 1000 1540 n.a.
 4000 4000 - 4000 1000
 40 1250 1250 - 1250 closed 800 1500 n.a.
 2500 2500 - 2500 natural ventilated 800
 3150 3150 - 3150 natural ventilated 1000 1540 n.a.
 4000 4000 - 4000 1000
 ≤ 17,5 Switch- 25 1250 200 200 200 1.) closed 800 1350 n.a.
disconnector
 2500 200 200 200 1.) closed 800
panel with
 HRC fuses 3150 200 200 200 1.) closed 800 1500 n.a.
 4000 200 200 200 1.) closed 800
 31.5 1250 200 200 200 1.) closed 800 1350 n.a.
1.)
 2500 200 200 200 closed 800
 3150 200 200 200 1.) closed 800 1500 n.a.
 4000 200 200 200 1.) closed 800

1) depending on nominal current rating of the used HRC-fuse see chapter 15

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 52 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

7. Components
7.1 Capacitive voltage detection system (CVD)
Capacitive voltage indicator  at cable side

 at busbar side

 Separable VDIS

 OVI+S (comparable CAPDIS S1+)

 OVI+SR (comparable CAPDIS S2+)

 VOIS+

 CAPDIS S1+ (without wire supervision)

 CAPDIS S2+

7.1 CVD-system: Overview of products and supplier


Product VOIS+ OVI+S CAPDIS S1 + OVI+SR CAPDIS S2+

R4.5 R4.5

Supplier Kries Orion Kries Orion Kries

Standard IEC 61243-5 / IEC IEC 61243-5 / IEC IEC 61243-5 / IEC IEC 61243-5 / IEC IEC 61243-5 / IEC
62271-213 62271-213 62271-213 62271-213 62271-213

Voltage Level LRM LRM LRM LRM LRM

Display LCD Single level LCD 2 levels LCD 3 levels LCD 2 levels LCD 4 levels
+ +
2 LED 2 LED
Display levels

Front testing points Yes Yes Yes Yes Yes

Capable of Multiple No No Yes No Yes


C2m Modules

AMP Connection Yes Yes Yes Yes Yes


(New cable )

Self test No Yes Yes Yes Yes

Broken cable No No Yes No Yes


detection

Protection Class IP54 IP54 IP54 IP54 IP54

Relay output No No No Yes - 2 relays Yes - 2 relays

Contact Output -- -- -- 5A, 250VAC or 5A, 250VAC or


30VDC 30VDC

Auxiliary Power -- -- -- 24 – 230V AC/DC 24 – 230V AC/DC

Power Consumption -- -- -- Less than 2W Less than 1W

Released in option Pre-selected option Pre-selected option


NXTools+

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 53 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

7.2 Panel connection cable compartment 1)


Cable connection  From bottom, front
5)
 From bottom, rear (not for SDF panel)

 From above and rear 2) 5)

Number, type and size of cables  1 single core cable max. 630 mm² per phase

 2 single core cable max. 630 mm² per phase

 3 single core cable max. 630 mm² per phase

 4 single core cable max. 630 mm² per phase

 6 single core cable max. 630 mm² per phase for panel depth 1540 mm
3)
 up to 2 x three core cable max. 240 mm²
4)
Deep bottom pan  Without

 With

Copper bar connection  With ≤ 1250 A (1 x 80 mm x 10 mm)

 With for 2000 A (2 x 80 mm x 10 mm) (only for panels 40 kA)

 With for 2500 A (2 x 100 mm x 10 mm)

 With for 3150 A (3 x 120 mm x 10 mm)

 With for 4000 A (3 x 120 mm x 10 mm)

7.3 Panel connection busbar compartment 1)


Copper bar connection  With ≤ 1250 A (1 x 80 mm x 10 mm in 600 mm) and (1 x 100 mm x 10 mm in 800 mm)

 With for 2000 A (only for panels ≥ 3150 A busbar current)

 With for 2500 A (2 x 100 mm x 10 mm)

 With for 3150 A (3 x 120 mm x 10 mm)

 With for 4000 A (3 x 120 mm x 10 mm)

1) permissible combination of equipment in busbar and connection compartment, see also chapter chapter 15.9, 15.10
2) increased panel depth of 600 mm (not for vacuum contactor panels with 435mm), see also chapter 6.1
3) general only up to 2 three core cables and only if in combination with deep bottom pan, in 600 mm panel only 3 three core cables up to 185 mm²
4) always in combination with three-core cables necessary
 when having deep bottom pan in combination with zero CT assembled in deep the bottom pan only connetion of 1 three-core cable possible
 for 435 mm VCP assembly of zero CT in deep bottom not possible (zero CT always located outside deep bottom pan)
5) not possible for Duplex in back-to-back arrangement

7.4 Bushing-type insulators


installation  at busbar side (between breaker and busbar) and at cables side (between breaker and cable)
1)
 at busbar side (between circuit breaker and busbar) as bushing type CT

 at busbar side (between breaker and busbar) and at cables side (between breaker and cable)
with current and/or voltage sensors as LPITs 2)

 at busbar side (between breaker and busbar) with current and/or voltage sensors as LPITs 2) and
at cables side (between breaker and cable)

 at busbar side (between breaker and busbar) with current and/or voltage sensors as LPITs 2) and
at cables side (between breaker and cable) with current and/or voltage sensors as LPITs 2)

Rated short time current / Rated  ≤ 31.5 kA / 3 s, 1000 A


short circuit duration resp. rated
current  ≤ 40 kA / 3 s, 1250 A

 ≤ 31.5 kA / 3 s, 2000 A

 ≤ 40 kA / 3 s, 2500 A

 ≤ 40 kA / 3 s, 4000 A

 for capacitive voltage indication optionally

 Silicon free optionally

1) only for circuit breaker panels of bus sectionalizer 1250 A, 2000 A and 2500 A up to 31.5 kA
2) with cast-in rogowski coil for current measurement (LPCT) and / or cast-in resistive divider for voltage measurement (LPVT)

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 54 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

7.5 Earthing switch 1)


Type of earthing switch  Earthing switch with short circuit making capacity

Function of earthing switch  Feeder earthing

 Busbar earthing 2)

Rated short circuit withstand  Ik ≤ 25 kA, tk ≤ 3s


current rating (three-phase)
 Ik = 31.5 kA, tk ≤ 3s

 Ik = 40 kA, tk ≤ 3s

Rated short circuit withstand Solidly earthed neutral


current rating (single-phase)
 Ipe ≤ 65 kA; Ike ≤ 25 kA, tke ≤ 3s

 Ipe ≤ 82 kA; Ike = 31.5 kA, tke ≤ 3s

 Ipe ≤ 104 kA; Ike = 40 kA, tke ≤ 3s

Isolated, resonance or impedance earthed neutral

 Ipe ≤ 150 A; Ike = 60 A, tke ≤ 24 h


3)
Auxiliary switch  Feeder earthing 4 NO + 4 NC, busbar earthing 6 NO + 6 NC

 For Vacuum contactor panel in 435 mm: Feeder earthing 2 NO + 2 NC

 For SDF panel: Feeder earthing 4 NO + 4 NC

Mechanism  Manual operated

 Motor operated 4)

Electromagnetic interlock  With

Mechanical locking device  Without

 Padlock

Key interlocking  Key interlocking system for feeder earthing in circuit breaker panel, disconnecting link panel,
contactor panel

 1. Key free in closed  2. Key free in  1. Key free in closed position and 2.
position open position Key free in open position

 Key interlocking system for busbar earthing

 1. Key free in closed  2. Key free in  1. Key free in closed position and 2.
position open position Key free in open position

1) in SDF panel switching capacity of feeder earthing is limited to 40 kA peak values resp. 16 kA / 1s in contactor panel switching capacity of feeder
earthing is limited to 16,4 kA peak values resp. 6,3 kA / 1s for 435mm panel width due to cut off function of fuses, in case of using this contactor
panel for other consumers than motor, this must be considered (electrical interlocking with upstream breaker to be configurated)
2) for busbar earthing always extended low voltage compartment is used, low voltage compartment as advanced delivery not possible
3) number of free auxiliary switch contacts depending on kind of interlocking and are shown detailed in engineering drawings
4) if motor operated feeder earthing switch in combination with motor operated withdrawable part is needed both mechanism must have same rated
power supply voltage, motor mechanism not possible for earthing switch at cable side 600 mm panel and in contactor panel 435mm

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 55 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

7.6 Block-type current transformers 4MA72 standard version for current values 2500 A,
in connection compartment 1),
drawing number 4MA72: ≤ 1250 A: 110-0135.9; >1250 A / ≤ 2500 A: 110-0136.9
installation  one set at cable side, below breaker

Number of cores  1 x 1 core in L2  2 x 2 core in L1/L3 + 1 x 1 cores in L2

 2 x 1 core in L1/L3  3 x 2 core in L1/L2/L3

 3 x 1 core in L1/L2/L3  3 x 3 core in L1/L2/L3

 2 x 1 core in L1/L3 + 1 x 2 cores in L2  2 x 3 core in L1/L3 + 1 x 2 cores in L2

 2 x 2 core in L1/L3  2 x 2 core in L1/L3 + 1 x 3 cores in L2

Rated short time current / Rated  16 kA / 1s  40 kA / 1s  31.5 kA / 3s


short circuit duration
 20 kA / 1s  16 kA / 3s  40 kA / 3s

 25 kA / 1s  20 kA / 3s

 31.5 kA / 1s  25 kA / 3s

Rated primary current  50  200  750

(not reconectable on the secondary  60  250  1000


side)
 75  300  1250

 100  400  1500

 125  500  2000

 150  600  2500

Rated primary current  2 x 20  2 x 75  2 x 300

(reconnectable on the secondary  2 x 25  2 x 100  2 x 400


side)
 2 x 30  2 x 125  2 x 500

 2 x 40  2 x 150  2 x 600

 2 x 50  2 x 200

 2 x 60  2 x 250

Rated power  2.5 VA  10 VA  20 VA

 5 VA  15 VA  30 VA

Class  0.2 FS10  5P 10  5P 30

 0.2 SFS10  10P 10

 0.5 FS5  5P 15

 1 FS5  5P 20

Rated secondary current  1A  5A/1A  1A/5A/5A

 5A  1A/1A/1A  5A/5A/1A

 1A/1A  5A/5A/5A  5A/1A/5A

 5A/5A  1A/1A/5A  5A/1A/1A

 1A/5A  1A/5A/1A

Additional features  with approval  Short-duration power-frequency withstand


voltage 32 kV 1 min. for 7.2 kV, Standard GOST

 Current transformers silicon free  Short-duration power-frequency withstand


voltage 42 kV 1 min. for 12 kV, Standard GOST

 Secondary wiring halogen free  Language of name plate German / English

 Primary rated current 1.2 x In

1) extended cts only possible in circuit breaker panel, disconnector panel and bus sectionalizer type I and type II (circuit breaker and disconnector
panel), restriction for duplex arrangement (see chapter 3 and 4)

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 56 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

7.7 Block-type current transformers 4MA72, size 2, extended version for current values 2500 A,
panel depth 1500 mm,
in connection compartment 1)
installation  one set at cable side, below breaker

Number of cores  1 x 1 core in L2  2 x 2 core in L1/L3 + 1 x 1 cores in L2

 2 x 1 core in L1/L3  3 x 2 core in L1/L2/L3

 3 x 1 core in L1/L2/L3  3 x 3 core in L1/L2/L3

 2 x 1 core in L1/L3 + 1 x 2 cores in L2  2 x 3 core in L1/L3 + 1 x 2 cores in L2

 2 x 2 core in L1/L3  2 x 2 core in L1/L3 + 1 x 3 cores in L2

Rated short time current / Rated  16 kA / 1s  40 kA / 1s  31.5 kA / 3s


short circuit duration
 20 kA / 1s  16 kA / 3s  40 kA / 3s

 25 kA / 1s  20 kA / 3s

 31.5 kA / 1s  25 kA / 3s

Rated primary current  50  200  750

(not reconnectable on the  60  250  1000


secondary side)
 75  300  1250

 100  400  1500

 125  500  2000

 150  600  2500

Rated primary current  2 x 20  2 x 75  2 x 300

(reconnectable on the secondary  2 x 25  2 x 100  2 x 400


side)
 2 x 30  2 x 125  2 x 500

 2 x 40  2 x 150  2 x 600

 2 x 50  2 x 200

 2 x 60  2 x 250

Rated power  2.5 VA  10 VA  20 VA

 5 VA  15 VA  30 VA

Class  0.2 FS10  5P 10  5P 30

 0.2 SFS10  10P 10

 0.5 FS5  5P 15

 1 FS5  5P 20

Rated secondary current  1A  5A/1A  1A/5A/5A

 5A  1A/1A/1A  5A/5A/1A

 1A/1A  5A/5A/5A  5A/1A/5A

 5A/5A  1A/1A/5A  5A/1A/1A

 1A/5A  1A/5A/1A

Additional features  with approval  Short-duration power-frequency withstand


voltage 32 kV 1 min. for 7.2 kV, Standard GOST

 Current transformers silicon free  Short-duration power-frequency withstand


voltage 42 kV 1 min. for 12 kV, Standard GOST

 Secondary wiring halogen free  Language of name plate German / English

 Primary rated current 1.2 x In

1) extended cts only possible in circuit breaker panel, disconnector panel and bus sectionalizer type I and type II (circuit breaker and disconnector panel),
restriction for duplex arrangement (see chapter 3 and 4)

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 57 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

7.8 Block-type current transformers 4MA72 – size 4 (formerly CT 12I or CT 18I) only for panels
up 17.5kV, busbar current ≥ 3150 A, drawing number: 110-0583.9 (4MA72 – size 4);
panel depth 1500 resp. 1540 mm,
in connection compartment or in busbar current metering panel 1) + 2) + 3)

installation  one set at cable side, below breaker


Number of cores  1 x 1 core in L2  2 x 2 core in L1/L3 + 1 x 1 cores in L2
 2 x 1 core in L1/L3  3 x 2 core in L1/L2/L3
 3 x 1 core in L1/L2/L3  3 x 3 core in L1/L2/L3
 2 x 1 core in L1/L3 + 1 x 2 cores in L2  2 x 3 core in L1/L3 + 1 x 2 cores in L2
 2 x 2 core in L1/L3  2 x 2 core in L1/L3 + 1 x 3 cores in L2
Rated short time current / Rated  16 kA / 1s  16 kA / 3s
short circuit duration
 20 kA / 1s  20 kA / 3s
 25 kA / 1s  25 kA / 3s
 31.5 kA / 1s  31.5 kA / 3s
 40 kA / 1s  40 kA / 3s
Rated primary current  50  300  2000
(not reconnectable on the secondary  60  400  2500
side)
 75  500  3000 A
 100  600  3150 A
 125  750  3200 A
 150  1000  3600 A
 200  1250  4000 A
 250  1500

Rated primary current  2 x 20  2 x 100  2 x 500


(reconnectable on the secondary  2 x 25  2 x 125  2 x 600
side)
 2 x 30  2 x 150  2 x 750
 2 x 40  2 x 200  2 x 1000
 2 x 50  2 x 250  2 x 1250
 2 x 60  2 x 300  2 x 1500
 2 x 75  2 x 400  2 x 2000

Rated power  2.5 VA  10 VA  20 VA


 5 VA  15 VA  30 VA
Class  0.2 FS10  5P 10  5P 30
 0.2 SFS10  10P 10
 0.5 FS5  5P 15
 1 FS5  5P 20
Rated secondary current  1A  5A/1A  1A/5A/5A
 5A  1A/1A/1A  5A/5A/1A
 1A/1A  5A/5A/5A  5A/1A/5A
 5A/5A  1A/1A/5A  5A/1A/1A
 1A/5A  1A/5A/1A
Additional features  4.)
with approval
 Current transformers silicon free
 Secondary wiring halogen free
 Short-duration power-frequency withstand voltage 32 kV 1 min. for 7.2 kV, Standard
GOST
 Short-duration power-frequency withstand voltage 42 kV 1 min. for 12 kV, Standard GOST
 Language of name plate German / English
 Primary rated current 1.2 x In, only for 3150 A

Attention:
1) extended cts only possible in circuit breaker panel, disconnector panel and bus sectionalizer type I and type II (circuit breaker and disconnector panel),
restriction for duplex arrangement (see chapter 3 and 4)
2) only possible in panels with 800mm or 1000mm panel width
3) only primary ratings 3150A and 4000A in standard, rated primary currents ≤ 3000A, 3200A and 3600A must be asked as DTO
4) with approval on possible in combination with 1,2 In and for primary currents up to 3200 A

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 58 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

7.9 Block-type current transformers 4MA72 – size 6 (formely CT 12K or CT18K), extended
version only for panels up to 17.5 kV, busbar current ≥ 3150 A; drawing number: 110-0584.9
(4MA72 – size 6); panel depth 1650 mm,
in connection compartment 1) + 2) + 3)
to be blocked temporarily until the test by Zelisko passes
installation  one set at cable side, below breaker
Number of cores  1 x 1 core in L2  2 x 2 core in L1/L3 + 1 x 1 cores in L2
 2 x 1 core in L1/L3  3 x 2 core in L1/L2/L3
 3 x 1 core in L1/L2/L3  3 x 3 core in L1/L2/L3
 2 x 1 core in L1/L3 + 1 x 2 cores in L2  2 x 3 core in L1/L3 + 1 x 2 cores in L2
 2 x 2 core in L1/L3  2 x 2 core in L1/L3 + 1 x 3 cores in L2
Rated short time current / Rated  16 kA / 1s  16 kA / 3s
short circuit duration
 20 kA / 1s  20 kA / 3s
 25 kA / 1s  25 kA / 3s
 31.5 kA / 1s  31.5 kA / 3s
 40 kA / 1s  40 kA / 3s
Rated primary current  50  300  2000
(not reconectable on the secondary  60  400  2500
side)
 75  500  3000 A
 100  600  3150 A
 125  750  3200 A
 150  1000  3600 A
 200  1250  4000 A
 250  1500

Rated primary current  2 x 20  2 x 100  2 x 500


(reconnectable on the secondary  2 x 25  2 x 125  2 x 600
side)
 2 x 30  2 x 150  2 x 750
 2 x 40  2 x 200  2 x 1000
 2 x 50  2 x 250  2 x 1250
 2 x 60  2 x 300  2 x 1500
 2 x 75  2 x 400  2 x 2000

Rated power  2.5 VA  10 VA  20 VA


 5 VA  15 VA  30 VA
Class  0.2 FS10  5P 10  5P 30
 0.2 SFS10  10P 10
 0.5 FS5  5P 15
 1 FS5  5P 20
Rated secondary current  1A  5A/1A  1A/5A/5A
 5A  1A/1A/1A  5A/5A/1A
 1A/1A  5A/5A/5A  5A/1A/5A
 5A/5A  1A/1A/5A  5A/1A/1A
 1A/5A  1A/5A/1A
Additional features  4.)
with approval
 Current transformers silicon free
 Secondary wiring halogen free
 Short-duration power-frequency withstand voltage 32 kV 1 min. for 7.2 kV, Standard
GOST
 Short-duration power-frequency withstand voltage 42 kV 1 min. for 12 kV, Standard GOST
 Language of name plate German / English
 Primary rated current 1.2 x In, only for 3150 A

Attention:
1) extended cts only possible in circuit breaker panel, disconnector panel and bus sectionalizer type I and type II (circuit breaker and disconnector panel),
restriction for duplex arrangement (see chapter 3 and 4)
2) only possible in panels with 800mm or 1000mm panel width
3) rated primary currents ≤ 2500A must be asked as DTO
4) with approval on possible in combination with 1,2 In and for primary currents up to 2500 A

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 59 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

7.10 Block-type current transformers 4MB61 (size 2) for contactor panel 435mm
Installation  at cable side
 3 x 1 core in L1/L2/L3
 3 x 2 core in L1/L2/L3
Rated short time current / Rated  up to 25 kA / 3s
short circuit duration 1)
Rated primary current  25 A  75 A  250 A
 30 A  100 A  300 A
 40 A  125 A  400 A
 50 A  150 A
 60 A  200 A
Rated power  5 VA  15 VA
 10 VA  30 VA
Class  5 VA 10P 10  30 VA 10P 10  15 VA 1 FS5
 10 VA 10P 10  5 VA 1 FS5
 15 VA 10P 10  10 VA 1 FS5
Rated secondary current  1A  1A/1A  1A/5A
 5A  5A/5A  5A/1A
 with approval
 Current transformers silicon free
 Secondary wiring halogen free
 Short-duration power-frequency withstand voltage 32 kV 1 min. for 7.2 kV, Standard
GOST
 Language of name plate German / English
 Primary rated current 1.2 x In

1) due to current limiting function of fuses not relevant

7.11 Block-type current transformers 4MA72 (standard version) for SDF panel 800mm
Installation  at cable side
 1 x 1 core in L2
 3 x 1 core in L1/L2/L3
Rated short time current / Rated  up to 8 kA / 1 sec
short circuit duration 1)
Rated primary current  25 A  50 A  100 A
 30 A  60 A 
 40 A  75 A 

Rated power  5 VA  10 VA 15 VA

Class  0.2 FS10  0.5 FS5 1 FS5


 0.2 SFS10

Rated secondary current  1A  1A/1A  1A/5A


 5A  5A/5A  5A/1A

 Current transformers silicon free


 Secondary wiring halogen free
 Short-duration power-frequency withstand voltage 32 kV 1 min. for 7.2 kV, Standard
GOST
 Language of name plate German / English
 Primary rated current 1.2 x In

1) due to current limiting function of fuses not relevant

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 60 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

7.12 Bushing type current transformers 4MD17 for switching device panel of bus sectionalizer
type I and type II (only for 1250 A, 2000A and 2500 A up to 31.5 kA); drawing nr. 129-1804.3
(1250 A); drawing nr. 129-1563.3 (2000 A / 2500 A)
Installation  Between busbar and circuit breaker of switching device panel

nr of cores  On request

Rated short time current / Rated short circuit duration  up to 31.5 kA / 3 sec

Rated primary current  On request (max. 2500 A)

Rated secondary current  1A  5A

Rated power  On request

Class  On request

Remark: bushing type CT 4MD17 must be asked for as a “special” component in general all requirements like current transformers
silicon free, secondary wiring halogen free, language of name plate German / English, Primary rated current 1.2 x In are on request

7.13 Bushing type insulator 4ME17 as LPIT


7.13.1 Versions and Installation
Installation  between busbar and circuit breaker of switching device panel

 between circuit breaker and cable connection of switching device panel

7.13.2 Technical data


Rated short-time thermal current Ith up to 40 kA

Rated dynamic current Idyn up to 104 kA

Rated short circuit duration 3 sec

Rated frequency  50 Hz  60 Hz

With cast-in rogowski coil for current measuring (LPCT)

Range of primary current 80 A – 4000 A

Rated primary current Ipr 80 A

Rated continuous thermal current Icth 4000 A

Output signal 22.5 mV (at 80 A rated primary current and at 50 Hz)

27 mV (at 80 A rated primary current and 60 Hz)

Rated extended primary current factor Kpcr 50

Accuracy limit factor Kalf 630

Accuracy class 0.5 / 5P630

Output signal derivative

With cast-in restistor devider for voltage measuring (LPVT)

Range of operating voltage 3.0 kV – 15.4 kV

Output signal 3.25 V / √3 at 17.5 kV / √3 operating voltage

Burden Rbr ≤ 2 MOhm

Rated voltage factor and corresponding rated time 1.9 for 8h

Class 0,5 for measuring

3P for protection

Rated phase offset (phi) 0°

Connection

Wiring Ethernet cable (CAT 7), shielded, always halogen free

Connection RJ45-plug

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 61 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

7.13.3 Ordering code


Order number (MLFB)
1. 2. 3. 4. 5. 6. 7. 8. - 9. 10. 11.
 4 M E 1 7 - Bushing with current and / or voltage sensor up to 17.5 kV,
 6. pos.: current sensor (LPCT)
 0 Without
1 Primary current: 80 A – 4000 A
Output signal: 22.5 mV (at 80 A rated primary current and at 50 Hz) or
27 mV (at 80 A rated primary current and 60 Hz)
Accuracy class: 0.5 / 5P630
7. pos.: Voltage sensor (LPVT)
 0 Without
 1 Operating voltage: 3.0 kV – 15.4 kV
Output signal: 3.25 V / √3 at 17.5 kV/√3 operating voltage
Accuracy class: 0,5 for measuring and 3P for protection
8. pos.: version of bushing
 0 For 600 mm panel ≤ 31.5 kA, ≤ 1000 A (119-5080.3)
 1 For 800 mm panel ≤ 40 kA, 1250 A (119-5084.3)
 2 For 800 mm / 1000 mm panel ≤ 40 kA, 2000 A – 4000 A or
50 kA, 1250 A – 4000 A (119-5078.3)
9. pos.: layer for capacitive voltage detection system
 A Without
 B with
10. pos: type of secondary wiring
 A Standard
 B Halogen free (pre-selected); Ethernet cable (CAT 7), shielded with
RJ45 connection plug
11. position: threatment of surface
 0 Standard
 1 Silicon free

7.13.4 Bushing-type insulator 4ME17 as LPIT for switching device panels


1)
Continous rated current feeder ≤ 1000 A 1250 A 1250 A 2000 A 2500 A 3150 A 4000 A
Rated short time circuit current ≤ 31.5 kA ≤ 31.5 kA 40 kA ≤ 40 kA
Panel width 600 mm 800 mm 800 mm 800 mm 1000 mm 1000 mm 1000 mm
PCD 160 mm 210 mm 210 mm 210 mm 210 mm 210 mm 210 mm
Diameter fixed contact 40 mm 60 mm 40 mm 80 mm 80 mm 80 mm 80 mm
Drawing-nr. 119-5080.3 119-5084.3 119-5084.3 119-5078.3 119-5078.3 119-5078.3 119-5078.3

7.13.5 Bushing-type insulator 4ME17 as LPIT for bus sectionalizer type I


Panel type CB panel BR panel CB panel BR panel CB panel BR panel CB panel BR panel
Continous rated current feeder 1250 A 1250 A 2000 A / 2500 A 3150 A / 4000 A
Rated short time circuit current ≤ 31.5 kA 40 kA ≤ 40 kA ≤ 40 kA
Panel width 800 mm 800 mm 800 mm 800 mm 1000 mm 1000 mm 1000 mm 1000 mm
PCD 210 mm 210 mm 210 mm 210 mm 210 mm 210 mm 210 mm 210 mm
Diameter fixed contact 60 mm 60 mm 40 mm 60 mm 80 mm 80 mm 80 mm 80 mm
Drawing-nr. 119-5084.3 119-5084.3 119-5078.3 119-5078.3

7.13.6 Bushing-type insulator 4ME17 as LPIT for bus sectionalizer type II 2)

Panel type CB panel BR panel CB panel BR panel CB panel BR panel CB panel BR panel
Continous rated current feeder 1250 A 1250 A 2000 A / 2500 A 3150 A / 4000 A
Rated short time circuit current ≤ 31.5 kA 40 kA ≤ 40 kA ≤ 40 kA
Panel width 800 mm 800 mm 800 mm 800 mm 1000 mm 800 mm 1000 mm 1000 mm
PCD 210 mm --- 210 mm --- 210 mm --- 210 mm ---
Diameter fixed contact 60 mm --- 40 mm --- 80 mm --- 80 mm ---
Drawing-nr. 119-5084.3 119-5084.3 119-5078.3 119-5078.3

1) disconnector panels for 1250A 40 kA with 60 mm diameter of fixed contact


2) bus riser panel not equipped with bushing-type insulator

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 62 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

7.14 Zero sequence transformers -conventional


7.14.1 Zero sequence transformers 4MC96 (Split core type) 1)

Number  1

 2

 80 mm

 120 mm

Rated current  50 A / 1A

 60 A / 1A

 100 A / 1 A

Core data  1.25 VA, 1 FS10


3)
Assembly  inside deep bottom pan (installation of only 1 zero sequence CT possible)

 outside cable connection compartment (max. 2 zero sequence CT possible)

Additional features  Current transformers silicon free

7.14.2 Zero sequence transformers KAT/ZCT – 130 (closed core type) 1)

Number  1

 2

 130 mm (inner diameter)

Rated secondary current  60 A / 1 A

 100 A / 1A

Core data  1.25 VA, 1 FS10


3)
Assembly  inside deep bottom pan (installation of only 1 zero sequence CT possible)

 outside cable connection compartment (max. 2 zero sequence CT possible)

Additional features  Current transformers silicon free


2)
7.14.3 Zero sequence transformer 4MC4_40 (closed core type according to drawing 953-0005.3)
Number 1

Technical data Insulation level IL: 0,72 / 3.0 / - kV

Ith: 25 kA / 3 s

Icth: 1,2×Ir

300 mm (inner diameter), 100 mm height

frequency  50 Hz

 60 Hz

Rated current  60 A / 1 A

 60 A / 5 A

Primary rated current 1.2 x In

Core data 2,5 VA, 3 ext 120% FS5

Secondary wiring Halogen free of secondary wiring,4mm² cross section, 3,6 m length, cast-in wiring

Assembly Installation in cable connection compartment without deep bottom pan

Pressure resistant floor cover in cable Non-metallic cover as double layer without drillings
connection compartment

Additional features With routine test protocol (German or English)

 Current transformers silicon free

1) 1 zero CT per cable system needed, total outer diameter of cable system must be considered (max. 70, 110 or 120 mm)
2) not possible for assembly in vacuum contactor panel 435 mm, switch disconnector panel with HV-fuses (SDF-panel) in 800 mm, panels ≥ 2500 A with 1000
mm width and only possible in combination with single-core cables
3) for 435 mm VCP and feeder current ≥ 2000 A assembly of zero CT in deep bottom not possible (zero CT always located outside deep bottom pan), when
having deep bottom pan in combination with zero CT assembled in deep the bottom pan only connection of 1 three-core cable possible

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 63 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

7.15 Zero sequence transformers – with LPCT technology


1)
7.15.1 LPCT zero sequence transformers Zelisko GAE120/SENS-JW1003 (split core type)
Number  1

 2

 120 mm (inner diameter)

Output signal 60 A / 225 mV

Accuracy class  1 FS10

Core data  Class 1


3)
Assembly  inside deep bottom pan (installation of only 1 zero sequence CT possible)

 outside cable connection compartment (max. 2 zero sequence CT possible)

Additional features  current transformers silicon free

7.15.2 LPCT zero sequence transformer 4MC4_40 (closed core type according to drawing 953-0005.3) 2)

Number 1

Technical data Insulation level: IL: 0,72 / 3.0 / - kV

Ith: 25 kA / 1 s

Icth: 1.2×Ipr

300 mm (inner diameter), 50 mm height

Rated frequency  50 Hz

 60 Hz

Rated primary current Ipr 60 A (ext. 200%)

Output signal 225 mV (at 60 A rated primary current and at 50 Hz)

270 mV (at 60 A rated primary current and 60 Hz)

Accuracy class 0.5

Burden > 20 kOhm

Secondary wiring 2 pole shielded,0.34 mm² cross section, 7 m length, cast-in wiring

 Optionally halogen free

Connection RJ45-plug

Assembly Installation in cable connection compartment without deep bottom pan

Additional features With routine test protocol (German or English)

 Optionally current transformer and secondary wiring silicon free

1) 1 zero CT per cable system needed, total outer diameter of cable system must be considered (max. 70, 110 or 120 mm), attention: protection relay
SIPROTEC 7SY82 does only have an additional input for 1 set of zero type CT, so assembly of only one zero type CT is possible. If second zero sequence
transformer is needed a merger unit or the adapter and test box must be used.
2) not possible for assembly in vacuum contactor panel 435 mm, panels ≥ 2500 A with 1000 mm width and only possible in combination with single-core cables
3) for 435 mm VCP assembly of zero CT in deep bottom not possible (zero CT always located outside deep bottom pan), when having deep bottom pan in
combination with zero CT assembled in deep the bottom pan only connection of 1 three-core cable possible

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 64 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

7.16 Voltage transformers 4MR12 up to 17.5 kV


a.) fixed mounted type without fuses (in top box to busbar or cable connection compartment)
b.) mounted on cassette with fuses without any tripping mechanism (in metering panel or metering
modul in bus riser panel)
c.) as withdrawable VT with fuses without any tripping mechanism on feeder side
Type  3 x 1 pole
Installation  fix mounted without primary fuses (drawing number: 110-0523.9)
 on withdrawable part for busbar metering in metering panel or bus riser panel in bus sectionalizer type II with
fuses (details of used fuses see chapter 6.4)

 in separate compartment, withdrawable with fuses at feeder side (drawing number: 110-0235.9) 1)
(details of used fuses see chapter 6.4)

Rated voltage of Standard Insulation values Rated primary voltages Secondary winding
switchgear
Impulse/withstand Voltage level class Rated output
(kV) (kV/kV) (kV /√3) (V/√3) % (VA)
7.2  IEC 60/20 3.0, 3.3 100 or 110 0.2 20
 0.5 50
 1 100
115 or 120 0,2 20
 0,5 75
 4.16, 4.8, 5.0, 6, 6.3, 6.6 100 or 110 0.2 30
 0.5 75
 1 150
115 or 120 0,2 20
 0,5 75
 GOST 60/32 6.0, 6.3, 6.6 100 or 110 0.2 20
 0.5 50
 1 100
115 or 120 0,2 20
 0,5 75
12  IEC 75/28 6.0, 6.3, 6.6 100 or 110 0.2 20
 0.5 50
 1 100
115 or 120 0,2 20
 0,5 75
 10, 10.5, 11 100 or 110 0.2 30
 0.5 75
 1 150
115 or 120 0,2 20
 0,5 75
 GOST 75/42 10, 10.5, 11 100 or 110 0.2 20
 0.5 50
 1 100
115 or 120 0,2 20
 0,5 75
17.5  IEC 95/38 10, 10.5, 11, 12.8, 13.2, 13.8, 15, 15.4 100 or 110 0.2 20
 0.5 50
 1 100
115 or 120 0,2 20
 0,5 75
Earth fault winding for  without
above versions  with 100/3 3P/6P 90
 110/3 3P/6P 90
 115/3 3P/6P 90
 120/3 3P/6P 90
Damping resistor for  without
earth fault winding  with
Additional features  Voltage transformer silicon free
 Secondary wiring halogen free
 Language of name plate German / English
 With official certification
 With approval (only up to 12kV possible)
Rated voltage factor for rated time: 1,9 x Un for 8 h in standard

1) additional ordering code “F23 (110-0235.9)” due to primary integrated fuses; withdrawable not possible in CB-panels with 3150A with 1000mm width
(natural ventilated); additional ordering code “F23 (110-0235.9)” due to integrated primary fuses, truck type design for switching device not possible

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 65 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

1)
7.17 Surge devices 3EJ / 3EK
Type of surge device  Surge arresters with high energy discharge capabilities 3EJ (former “limiters”)
 Distribution class surge arresters 3EK (former “arresters”)
Max. operating voltage for surge arresters with  3.6 kV 3EJ0 003–6CB71-0
high energy discharge capabilities limiters
 4.8 kV 3EJ0 004–8CB71-0
 7.2 kV 3EJ0 007–2CB71-0
 12.0 kV 3EJ9012-0CC71-0B
Max. operating voltage for distribution class Compensated or Solidly earthed or low Resistive earthed
surge arresters isolated resistance earthed
 3.6 kV 3EK7060-4CB0 3EK7030-4CB0 3EK7030-4CB0
 5.5 kV 3EK7090-4CB0 3EK7060-4CB0 3EK7060-4CB0
 7.2 kV 3EK7090-4CB0 3EK7060-4CB0 3EK7090-4CB0
 9,6 kV 3EK7120-4CC0 3EK7090-4CB0 3EK7120-4CC0
 12 kV 3EK7150-4CC0 3EK7090-4CB0 3EK7120-4CC0
 15.5 kV 3EK7210-4CD0 3EK7120-4CC0 3EK7150-4CC0
 17.5 kV 3EK7220-4CD0 3EK7150-4CC0 3EK7180-4CD0
Neutral point  Compensated or isolated
 Solidly earthed or low resistance earthed
 Resistive earthed

7.18 Specification of withdrawable part 2)


Type of withdrawable part  for circuit breaker
 for disconnecting link
 for contactor with 1 fuse per phase, without fused control transformer
 for contactor with 2 fuses per phase, without fused control transformer
 for contactor with 1 fuse per phase, with fused control transformer
 for contactor with 2 fuses per phase, with fused control transformer
 metering unit with voltage transformers, with fuses without tripping mechanism
 metering unit with voltage transformers, with fuses with tripping mechanism and auxiliary
contact 1NC + 1NO
Mechanism  Manual operated
 Motor operated 3)
Auxiliary switch  6 NO + 6 NC
Mechanical locking devices  With mechanical interlocking of high voltage door
 With electromagnetic interlock
 With padlock
 With key interlocking system, key free in test position

1) silicon free to be clarified, surge arrestors should be used for stating currents of motors up to 600 A
2) withdrawable part on cassette is standard, truck type design as option possible (exception: feeder current 3150 A - natural ventilated, feeder with
withdrawable voltage transformers in connection compartment are excluded)
3) not possible for withdrawable part as metering function and for contactor panel, if motor operated feeder earthing switch in combination with motor
operated withdrawable part is needed both mechanism must have same rated power supply voltage possible combinations see table 1.6

1)
7.19 Portable earthing device
Feeder ratings Portable earthing device
Un IN Ik MLFB IK, max. Duration, max. Suitable for diameter of fixed contact
≤ 17.5 kV ≤ 1000 A ≤ 31,5 kA 8BX2043-1E 25 kA 1 sec Ø 40 mm
≤ 17.5 kV 1250 A 40 kA 8BX2043-1E 25 kA 1 sec Ø 40 mm
≤ 17.5 kV Metering panel ≤ 40 kA 8BX2043-1E 25 kA 1 sec Ø 40 mm
≤ 17.5 kV 1250 A ≤ 31,5 kA 8BX2045 25 kA 1 sec Ø 60 mm
≤ 17.5 kV ≥ 2000 A ≤ 40 kA 8BX2045-0C 25 kA 1 sec Ø 80 mm

1) the portable earthing device has to be selected in accessories and is only suitable and tested for 25 kA for 1 sec. It will be used normally for “grounding
for work” but is not a substitute for an earthing switch

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 66 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

8 Vacuum circuit breaker


8.1 Circuit breaker SION (3AE) 12 kV – 25 kA (tested acct. to IEC 62271-100)
Panel data Breaker data (MLFB) 1. 2. 3. 4. 5. 6. 7. - 8. 9.-14. 15. 16. - Z
1)
kV kA Busbar Feeder Width kV kA A
(A) (A) (mm)
 12 25 1250 630 600 12 25 800 3 A E 5 5 5 4 - 1
 1000 600 12 25 1250 3 A E 5 5 5 4 - 2
 1250 800 12 25 1600 3 A E 5 5 6 4 - 3
 2000 630 600 12 25 800 3 A E 5 5 5 4 - 1
2500
 1000 600 12 25 1250 3 A E 5 5 5 4 - 2
 1250 800 12 25 1600 3 A E 5 5 6 4 - 3
 2000 800 12 31.5 2500 3 A E 5 5 6 5 - 6
 2500 1000 12 31.5 2500 3 A E 5 5 6 5 - 6
 3150 630 600 12 25 800 3 A E 5 5 5 4 - 1
 1000 600 12 25 1250 3 A E 5 5 5 4 - 2
 1250 800 12 25 1600 3 A E 5 5 6 4 - 3
 2000 800 12 31,5 2500 3 A E 5 5 6 5 - 6
 2500 1000 12 31.5 2500 3 A E 5 5 6 5 - 6
 3150 1000 12 40 3150 3 A E 5 5 6 6 - 7
 4000 630 600 12 25 800 3 A E 5 5 5 4 - 1
 1000 600 12 25 1250 3 A E 5 5 5 4 - 2
 1250 800 12 25 1600 3 A E 5 5 6 4 - 3
 2000 800 12 31,5 2500 3 A E 5 5 6 5 - 6
 2500 1000 12 31.5 2500 3 A E 5 5 6 5 - 6
 3150 1000 12 40 3150 3 A E 5 5 6 6 - 7
 4000 1000 12 40 4000 3 A E 5 5 6 6 - 8
 Additional ordering code 9. - 14. position, shunt releases, auxiliary voltages configurated in NX-Tools+
Standard version for all 15. position new version: mechanical interlocking, auxiliary switch 12 NO + 12 NC, N
breakers with circuit breaker tripping signal, 64-pole plug
Switching duty O – 0,3 s – CO – 15 s – CO
Standard additional codes for Routine test certificate F 2 0
all breakers
Special low voltage connection and without upper part of plug W 6 3
 Additional ordering code, Secondary wiring halogen free and flame retardant A 1 0
optionally
Silicon free design A 3 1
circuit breaker for operation down to –25 °C A 4 0
GOST, specific higher insulation level Ud = 42 kV E 1 3
Switching duty O – 3 min – CO – 3 min – CO F 2 7
Switching duty O – 0,3 s – CO – 3 min – CO F 3 8

 Release combinations 9.-14.  “1 shunt release” or


and 16. position provided by
NX-Tools+  “2 shunt releases” or
 “3 shunt releases” or
 “1 shunt release+1 ct operated release 0,1 Ws / 20 Ohm” or
 “1 shunt release+1 undervoltage release” or
 “2 shunt release+1 undervoltage release” or
 “2 shunt release+1 ct operated release 0,1 Ws / 20 Ohm” or
 “1 shunt release+1 undervoltage release + 1 ct operated release 0,1 Ws / 20 Ohm”

1) due to temperature rise 31.5 kA breaker is used

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 67 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

8.2 Circuit breaker SION (3AE) 12 kV – 31,5 kA (tested acct. to IEC 62271-100)
Panel data Breaker data (MLFB) 1. 2. 3. 4. 5. 6. 7. - 8. 9.-14. 15. 16. - Z

kV kA Busbar Feeder Width kV kA A


(A) (A) (mm)

 12 31.5 1250 630 600 12 31.5 800 3 A E 5 5 5 5 - 1

 1000 600 12 31.5 1250 3 A E 5 5 5 5 - 2

 1250 800 12 31.5 1600 3 A E 5 5 6 5 - 3

 2000 630 600 12 31.5 800 3 A E 5 5 5 5 - 1


2500
 1000 600 12 31.5 1250 3 A E 5 5 5 5 - 2

 1250 800 12 31.5 1600 3 A E 5 5 6 5 - 3

 2000 800 12 31.5 2500 3 A E 5 5 6 5 - 6

 2500 1000 12 31.5 2500 3 A E 5 5 6 5 - 6

 3150 630 600 12 31,5 800 3 A E 5 5 5 5 - 1

 1000 600 12 31,5 1250 3 A E 5 5 5 5 - 2

 1250 800 12 31.5 1600 3 A E 5 5 6 5 - 3

 2000 800 12 31,5 2500 3 A E 5 5 6 5 - 6

 2500 1000 12 31.5 2500 3 A E 5 5 6 5 - 6

 3150 1000 12 40 3150 3 A E 5 5 6 6 - 7

 4000 630 600 12 31,5 800 3 A E 5 5 5 5 - 1

 1000 600 12 31,5 1250 3 A E 5 5 5 5 - 2

 1250 800 12 31.5 1600 3 A E 5 5 6 5 - 3

 2000 800 12 31,5 2500 3 A E 5 5 6 5 - 6

 2500 1000 12 31.5 2500 3 A E 5 5 6 5 - 6

 3150 1000 12 40 3150 3 A E 5 5 6 6 - 7

 4000 1000 12 40 4000 3 A E 5 5 6 6 - 8

 Additional ordering code 9. - 14. position, shunt releases, auxiliary voltages configurated in NX-Tools+

Standard version for all 15. position new version: mechanical interlocking, auxiliary switch 12 NO + 12 NC, N
breakers with circuit breaker tripping signal, 64-pole plug

Switching duty O – 0,3 s – CO – 15 s – CO

Standard additional codes for Routine test certificate F 2 0


all breakers
Special low voltage connection and without upper part of plug W 6 3

 Additional ordering code, Secondary wiring halogen free and flame retardant A 1 0
optionally
Silicon free design A 3 1

circuit breaker for operation down to –25 °C A 4 0

GOST, specific higher insulation level Ud = 42 kV E 1 3

Switching duty O – 3 min – CO – 3 min – CO F 2 7

Switching duty O – 0,3 s – CO – 3 min – CO F 3 8

 Release combinations 9.-14.  “1 shunt release” or


and 16. position provided by
NX-Tools+  “2 shunt releases” or

 “3 shunt releases” or

 “1 shunt release+1 ct operated release 0,1 Ws / 20 Ohm” or

 “1 shunt release+1 undervoltage release” or

 “2 shunt release+1 undervoltage release” or

 “2 shunt release+1 ct operated release 0,1 Ws / 20 Ohm” or

 “1 shunt release+1 undervoltage release + 1 ct operated release 0,1 Ws / 20 Ohm”

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 68 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

8.3 Circuit breaker SION (3AE) 12 kV – 40kA (tested acct. to IEC 62271-100)
Panel data Breaker data (MLFB) 1 2 3 4 5 6 7 - 8 9.-14. 15 16 - Z

kV kA Busbar Feeder Width kV kA A


(A) (A) (mm)

 12 40 1250 1250 800 12 40 1250 3 A E 5 5 6 6 - 2

 2500 1250 800 12 40 1250 3 A E 5 5 6 6 - 2

 2000 800 12 40 2500 3 A E 5 5 6 6 - 6

 2500 1000 12 40 2500 3 A E 5 5 6 6 - 6

 3150 1250 800 12 40 1250 3 A E 5 5 6 6 - 2

 2000 800 12 40 2500 3 A E 5 5 6 6 - 6

 2500 1000 12 40 2500 3 A E 5 5 6 6 - 6

 3150 1000 12 40 3150 3 A E 5 5 6 6 - 7

 4000 1250 800 12 40 1250 3 A E 5 5 6 6 - 2

 2000 800 12 40 2500 3 A E 5 5 6 6 - 6

 2500 1000 12 40 2500 3 A E 5 5 6 6 - 6

 3150 1000 12 40 3150 3 A E 5 5 6 6 - 7

 4000 1000 12 40 4000 3 A E 5 5 6 6 - 8

 Additional ordering code 9. - 14. position, shunt releases, auxiliary voltages configurated in NX-Tools+

Standard version for all 15. position new version: mechanical interlocking, auxiliary switch 12 NO + 12 NC, N
breakers with circuit breaker tripping signal, 64-pole plug

Switching duty O – 0,3 s – CO – 15 s – CO

Standard additional codes for Routine test certificate F 2 0


all breakers
Special low voltage connection and without upper part of plug W 6 3

 Additional ordering code, Secondary wiring halogen free and flame retardant A 1 0
optionally
Silicon free design A 3 1

circuit breaker for operation down to –25 °C A 4 0

GOST, specific higher insulation level Ud = 42 kV E 1 3

Switching duty O – 3 min – CO – 3 min – CO F 2 7

Switching duty O – 0,3 s – CO – 3 min – CO F 3 8

 Release combinations 9.-14.  “1 shunt release” or


and 16. position provided by
NX-Tools+  “2 shunt releases” or

 “3 shunt releases” or

 “1 shunt release+1 ct operated release 0,1 Ws / 20 Ohm” or

 “1 shunt release+1 undervoltage release” or

 “2 shunt release+1 undervoltage release” or

 “2 shunt release+1 ct operated release 0,1 Ws / 20 Ohm” or

 “1 shunt release+1 undervoltage release + 1 ct operated release 0,1 Ws / 20 Ohm”

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 69 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

8.4 Circuit breaker SION (3AE) 17.5 kV – 25 kA (tested acct. to IEC 62271-100)
Panel data Breaker data (MLFB) 1 2 3 4 5 6 7 - 8 9.-14. 15 16 - Z
1)
kV kA Busbar Feeder Width kV kA A
(A) (A) (mm)

 17.5 25 1250 630 600 17,5 25 800 3 A E 5 6 2 4 - 1 D 9 1

 1000 600 17,5 25 1250 3 A E 5 6 2 4 - 2 D 9 1

 1250 800 17,5 25 1600 3 A E 5 6 6 4 - 3 D 9 1

 2000 630 600 17,5 25 800 3 A E 5 6 2 4 - 1 D 9 1


2500
 1000 600 17,5 25 1250 3 A E 5 6 2 4 - 2 D 9 1

 1250 800 17,5 25 1600 3 A E 5 6 6 4 - 3 D 9 1

 2000 800 17,5 31.5 2500 3 A E 5 6 6 5 - 6 D 9 1

 2500 1000 17,5 31.5 2500 3 A E 5 6 6 5 - 6 D 9 1

 3150 630 600 17,5 25 800 3 A E 5 6 2 4 - 1 D 9 0

 1000 600 17,5 25 1250 3 A E 5 6 2 4 - 2 D 9 0

 1250 800 17,5 25 1600 3 A E 5 6 6 4 - 3 D 9 0

 2000 800 17,5 31.5 2500 3 A E 5 6 6 5 - 6 D 9 0

 2500 1000 17,5 31.5 2500 3 A E 5 6 6 5 - 6 D 9 0

 3150 1000 17,5 40 3150 3 A E 5 6 6 6 - 7 D 9 0

 4000 630 600 17,5 25 800 3 A E 5 6 2 4 - 1 D 9 0

 1000 600 17,5 25 1250 3 A E 5 6 2 4 - 2 D 9 0

 1250 800 17,5 25 1600 3 A E 5 6 6 4 - 3 D 9 0

 2000 800 17,5 31.5 2500 3 A E 5 6 6 5 - 6 D 9 0

 2500 1000 17,5 31.5 2500 3 A E 5 6 6 5 - 6 D 9 0

 3150 1000 17,5 40 3150 3 A E 5 6 6 6 - 7 D 9 0

 4000 1000 17,5 40 4000 3 A E 5 6 6 6 - 8 D 9 0

 Additional ordering code 9. - 14. position, shunt releases, auxiliary voltages configurated in NX-Tools+

Standard version for all 15. position new version: mechanical interlocking, auxiliary switch 12 NO + 12 NC, N
breakers with circuit breaker tripping signal, 64-pole plug

Switching duty O – 0,3 s – CO – 15 s – CO

Standard additional codes for Routine test certificate F 2 0


all breakers
Special low voltage connection and without upper part of plug W 6 3

 Additional ordering code, Secondary wiring halogen free and flame retardant A 1 0
optionally
Silicon free design A 3 1

circuit breaker for operation down to –25 °C A 4 0

GOST, specific higher insulation level Ud = 42 kV E 1 3

Switching duty O – 3 min – CO – 3 min – CO F 2 7

Switching duty O – 0,3 s – CO – 3 min – CO F 3 8

 Release combinations 9.-14.  “1 shunt release” or


and 16. position provided by
NX-Tools+  “2 shunt releases” or

 “3 shunt releases” or

 “1 shunt release+1 ct operated release 0,1 Ws / 20 Ohm” or

 “1 shunt release+1 undervoltage release” or

 “2 shunt release+1 undervoltage release” or

 “2 shunt release+1 ct operated release 0,1 Ws / 20 Ohm” or

 “1 shunt release+1 undervoltage release + 1 ct operated release 0,1 Ws / 20 Ohm”

1) due to temperature rise 31.5 kA breaker is used

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 70 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

8.5 Circuit breaker SION (3AE) 17.5 kV – 31,5 kA (tested acct. to IEC 62271-100)
Panel data Breaker data (MLFB) 1 2 3 4 5 6 7 - 8 9.-14. 15 16 - Z

kV kA Busbar Feeder Width kV kA A


(A) (A) (mm)

 17,5 31.5 1250 630 600 17,5 31.5 800 3 A E 5 6 2 5 - 1 D 9 7

 1000 600 17,5 31.5 1250 3 A E 5 6 2 5 - 2 D 9 7

 1250 800 17,5 31.5 1250 3 A E 5 6 6 5 - 2 D 9 1

 2000 630 600 17,5 31.5 800 3 A E 5 6 2 5 - 1 D 9 7


2500
 1000 600 17,5 31.5 1250 3 A E 5 6 2 5 - 2 D 9 7

 1250 800 17,5 31.5 1250 3 A E 5 6 6 5 - 2 D 9 1

 2000 800 17,5 31.5 2500 3 A E 5 6 6 5 - 6 D 9 1

 2500 1000 17.5 31.5 2500 3 A E 5 6 6 5 - 6 D 9 1

 3150 630 600 17,5 31.5 800 3 A E 5 6 2 5 - 1 D 9 7

 1000 600 17,5 31.5 1250 3 A E 5 6 2 5 - 2 D 9 7

 1250 800 17,5 31.5 1250 3 A E 5 6 6 5 - 2 D 9 0

 2000 800 17,5 31.5 2500 3 A E 5 6 6 5 - 6 D 9 0

 2500 1000 17.5 31.5 2500 3 A E 5 6 6 5 - 6 D 9 0

 3150 1000 17.5 40 3150 3 A E 5 6 6 6 - 7 D 9 0

 4000 630 600 17,5 31.5 800 3 A E 5 6 2 5 - 1 D 9 7

 1000 600 17,5 31.5 1250 3 A E 5 6 2 5 - 2 D 9 7

 1250 800 17,5 31.5 1250 3 A E 5 6 6 5 - 2 D 9 0

 2000 800 17,5 31.5 2500 3 A E 5 6 6 5 - 6 D 9 0

 2500 1000 17.5 31.5 2500 3 A E 5 6 6 5 - 6 D 9 0

 3150 1000 17.5 40 3150 3 A E 5 6 6 6 - 7 D 9 0

 4000 1000 17.5 40 4000 3 A E 5 6 6 6 - 8 D 9 0

 Additional ordering code 9. - 14. position, shunt releases, auxiliary voltages configurated in NX-Tools+

Standard version for all 15. position new version: mechanical interlocking, auxiliary switch 12 NO + 12 NC, N
breakers with circuit breaker tripping signal, 64-pole plug

Switching duty O – 0,3 s – CO – 15 s – CO

Standard additional codes for Routine test certificate F 2 0


all breakers
Special low voltage connection and without upper part of plug W 6 3

 Additional ordering code, Secondary wiring halogen free and flame retardant A 1 0
optionally
Silicon free design A 3 1

circuit breaker for operation down to –25 °C A 4 0

GOST, specific higher insulation level Ud = 42 kV E 1 3

Switching duty O – 3 min – CO – 3 min – CO F 2 7

Switching duty O – 0,3 s – CO – 3 min – CO F 3 8

 Release combinations 9.-14.  “1 shunt release” or


and 16. position provided by
NX-Tools+  “2 shunt releases” or

 “3 shunt releases” or

 “1 shunt release+1 ct operated release 0,1 Ws / 20 Ohm” or

 “1 shunt release+1 undervoltage release” or

 “2 shunt release+1 undervoltage release” or

 “2 shunt release+1 ct operated release 0,1 Ws / 20 Ohm” or

 “1 shunt release+1 undervoltage release + 1 ct operated release 0,1 Ws / 20 Ohm”

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 71 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

8.6 Circuit breaker SION (3AE) 17.5 kV – 40kA (tested acct. to IEC 62271-100)
Panel data Breaker data (MLFB) 1 2 3 4 5 6 7 - 8 9.-14. 15 16 - Z

kV kA Busbar Feeder Width kV kA A


(A) (A) (mm)

 17.5 40 1250 1250 800 17.5 40 1250 3 A E 5 6 6 6 - 2 D 9 0

 2500 1250 800 17.5 40 1250 3 A E 5 6 6 6 - 2 D 9 0

 2000 800 17.5 40 2500 3 A E 5 6 6 6 - 6 D 9 0

 2500 800 / 1000 17.5 40 2500 3 A E 5 6 6 6 - 6 D 9 0

 3150 1250 800 17.5 40 1250 3 A E 5 6 6 6 - 2 D 9 0

 2000 800 17.5 40 2500 3 A E 5 6 6 6 - 6 D 9 0

 2500 1000 17.5 40 2500 3 A E 5 6 6 6 - 6 D 9 0

 3150 1000 17.5 40 3150 3 A E 5 6 6 6 - 7 D 9 0

 4000 1250 800 17.5 40 1250 3 A E 5 6 6 6 - 2 D 9 0

 2000 800 17.5 40 2500 3 A E 5 6 6 6 - 6 D 9 0

 2500 1000 17.5 40 2500 3 A E 5 6 6 6 - 6 D 9 0

 3150 1000 17.5 40 3150 3 A E 5 6 6 6 - 7 D 9 0

 4000 1000 17.5 40 4000 3 A E 5 6 6 6 - 8 D 9 0

 Additional ordering code 9. - 14. position, shunt releases, auxiliary voltages configurated in NX-Tools+

Standard version for all 15. position new version: mechanical interlocking, auxiliary switch 12 NO + 12 NC, N
breakers with circuit breaker tripping signal, 64-pole plug

Switching duty O – 0,3 s – CO – 15 s – CO

Standard additional codes for Routine test certificate F 2 0


all breakers
Special low voltage connection and without upper part of plug W 6 3

 Additional ordering code, Secondary wiring halogen free and flame retardant A 1 0
optionally
Silicon free design A 3 1

circuit breaker for operation down to –25 °C A 4 0

GOST, specific higher insulation level Ud = 42 kV E 1 3

Switching duty O – 3 min – CO – 3 min – CO F 2 7

Switching duty O – 0,3 s – CO – 3 min – CO F 3 8

 Release combinations 9.-14.  “1 shunt release” or


and 16. position provided by
NX-Tools+  “2 shunt releases” or

 “3 shunt releases” or

 “1 shunt release+1 ct operated release 0,1 Ws / 20 Ohm” or

 “1 shunt release+1 undervoltage release” or

 “2 shunt release+1 undervoltage release” or

 “2 shunt release+1 ct operated release 0,1 Ws / 20 Ohm” or

 “1 shunt release+1 undervoltage release + 1 ct operated release 0,1 Ws / 20 Ohm”

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 72 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

8.7 Circuit breaker 3AE2 7,2 kV, 12 kV and 15 kV – 25 kA (tested acc. to IEC/IEEE 62271-37-013)
Panel data Breaker data 1) Ordering number of breaker (MLFB)
1 2 3 4 5 6 7 - 8 9-14 15 16 - Z
kV kA Busbar Feeder Width kV kA A
[A] [A] [mm]
 7.2 31.5 3150 1250 800 12 31,5 1250 3 A E 2 5 6 5 - 2
 2000 800 2500 3 A E 2 5 6 5 - 6
 2500 1000 2500 3 A E 2 5 6 5 - 6
 3150 1000 3150 3 A E 2 5 6 5 - 7
 7.2 31.5 4000 1250 800 12 31,5 1250 3 A E 2 5 6 5 - 2
 2000 800 2000 3 A E 2 5 6 5 - 6
 2500 1000 2500 3 A E 2 5 6 5 - 6
 3150 1000 3150 3 A E 2 5 6 5 - 7
 4000 1000 4000 3 A E 2 5 6 5 - 8
 12 31.5 3150 1250 800 12 31,5 1250 3 A E 2 5 6 5 - 2
 2000 800 2500 3 A E 2 5 6 5 - 6
 2500 1000 2500 3 A E 2 5 6 5 - 6
 3150 1000 3150 3 A E 2 5 6 5 - 7
 12 31.5 4000 1250 800 12 31,5 1250 3 A E 2 5 6 5 - 2
 2000 800 2000 3 A E 2 5 6 5 - 6
 2500 1000 2500 3 A E 2 5 6 5 - 6
 3150 1000 3150 3 A E 2 5 6 5 - 7
 4000 1000 4000 3 A E 2 5 6 5 - 8
 17.5 31.5 3150 1250 800 17.5 31,5 1250 3 A E 2 6 6 5 - 2 D 9 0
 2000 800 2500 3 A E 2 6 6 5 - 6 D 9 0
 2500 1000 2500 3 A E 2 6 6 5 - 6 D 9 0
 3150 1000 3150 3 A E 2 6 6 5 - 7 D 9 0
 17.5 31.5 4000 1250 800 17.5 31,5 1250 3 A E 2 6 6 5 - 2 D 9 0
 2000 800 2000 3 A E 2 6 6 5 - 6 D 9 0
 2500 1000 2500 3 A E 2 6 6 5 - 6 D 9 0
 3150 1000 3150 3 A E 2 6 6 5 - 7 D 9 0
 4000 1000 4000 3 A E 2 6 6 5 - 8 D 9 0
 Additional ordering code 9. - 14. position, shunt releases, auxiliary voltages configurated in NX-Tools+
Standard version for all 15. position: With mechanical interlocking Auxiliary switch 12NO+12NC and N
breakers 64-pole plug
Routine test certificate F 2 0
Special low voltage connection and without upper part of plug W 6 3
Switching duty: CO – 30 min – CO
 Additional ordering code 16. pos, language configurated in NX-Tools+
 optionally additional codes for optionally secondary wiring halogen free and flame retardent A 1 0
all breakers
Silicon free design A 3 1
circuit breaker for operation down to –25 °C A 4 0
GOST, specific higher insulation level Ud = 42 kV E 1 3

 Release combinations 9.-14.  “1 shunt release” or


and 16. position provided by
NX-Tools  “2 shunt releases” or
 “3 shunt releases” or
 “1 shunt release+1 undervoltage release” or
 “2 shunt release+1 undervoltage release”

Attention:
1) Rated insulation levels for rated voltage 17.5 kV acc. IEC 62271-1, range 1, series 1
 Rated short-duration power-frequency withstand voltage: 38 kV
 Rated lightning impulse withstand voltage: 95 kV

Due to dimensions of 3AE2 for generator circuit application in NXAIR 3AE2 fits only in standard panels with depth ≥ 1500 mm and panels with 800 mm or
1000 mm panel width.
For generator switch application 25 kA acc. IEC/IEEE 62271-37-013 (up to 69 kA peak current) NXAIR for 31,5 kA for busbar ratings 3150 A or 4000 A must
be selected in combination with 3AE2 for 31,5 kA
Remark: rated voltage 17,5 kV (IEC 62271); 15 kV (IEC/IEEE 62271-37-013)
Switchgear must be labeled correctly regarding short circuit current

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 73 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

8.8 Circuit breaker 3AE2 7,2 kV and 12 kV – 31,5 kA (tested acc. to IEC/IEEE 62271-37-013)
Panel data Breaker data Ordering number of breaker (MLFB)
1 2 3 4 5 6 7 - 8 9-14 15 16 - Z
kV kA Busbar Feeder Width kV kA A
[A] [A] [mm]
 7.2 40 1250 1250 800 12 31.5 1250 3 A E 2 5 6 5 - 2
 7.2 40 2500 1250 800 12 31.5 1250 3 A E 2 5 6 5 - 2
 2000 800 2500 3 A E 2 5 6 5 - 6
 2500 1000 2500 3 A E 2 5 6 5 - 6
 7.2 40 3150 1250 800 12 31.5 1250 3 A E 2 5 6 5 - 2
 2000 800 2500 3 A E 2 5 6 5 - 6
 2500 1000 2500 3 A E 2 5 6 5 - 6
 3150 1000 3150 3 A E 2 5 6 5 - 7
 7.2 40 4000 1250 800 12 31.5 1250 3 A E 2 5 6 5 - 2
 2000 800 2000 3 A E 2 5 6 5 - 6
 2500 1000 2500 3 A E 2 5 6 5 - 6
 3150 1000 3150 3 A E 2 5 6 5 - 7
 4000 1000 4000 3 A E 2 5 6 5 - 8
 12 40 1250 1250 800 12 31.5 1250 3 A E 2 5 6 5 - 2
 12 40 2500 1250 800 12 31.5 1250 3 A E 2 5 6 5 - 2
 2000 800 2500 3 A E 2 5 6 5 - 6
 2500 1000 2500 3 A E 2 5 6 5 - 6
 12 40 3150 1250 800 12 31.5 1250 3 A E 2 5 6 5 - 2
 2000 800 2500 3 A E 2 5 6 5 - 6
 2500 1000 2500 3 A E 2 5 6 5 - 6
 3150 1000 3150 3 A E 2 5 6 5 - 7
 12 40 4000 1250 800 12 31.5 1250 3 A E 2 5 6 5 - 2
 2000 800 2000 3 A E 2 5 6 5 - 6
 2500 1000 2500 3 A E 2 5 6 5 - 6
 3150 1000 3150 3 A E 2 5 6 5 - 7
 4000 1000 4000 3 A E 2 5 6 5 - 8
 Additional ordering code 9. - 14. position, shunt releases, auxiliary voltages configurated in NX-Tools+
Standard version for all 15. position: With mechanical interlocking Auxiliary switch 12NO+12NC and N
breakers 64-pole plug
Routine test certificate F 2 0
Special low voltage connection and without upper part of plug W 6 3
Switching duty: CO – 30 min – CO
 Additional ordering code 16. pos, language configurated in NX-Tools+
 optionally additional codes for optionally secondary wiring halogen free and flame retardent A 1 0
all breakers
Silicon free design A 3 1
circuit breaker for operation down to –25 °C A 4 0
GOST, specific higher insulation level Ud = 42 kV E 1 3

 Release combinations 9.-14.  “1 shunt release” or


and 16. position provided by
NX-Tools  “2 shunt releases” or
 “3 shunt releases” or
 “1 shunt release+1 undervoltage release” or
 “2 shunt release+1 undervoltage release”

Attention:
Due to dimensions of 3AE2 for generator circuit application in NXAIR 3AE2 fits only in standard panels with depth ≥ 1500 mm and panels with 800 mm or
1000 mm panel width.
For generator switch application 31,5 kA acc. IEC/IEEE 62271-37-013 (up to 87 kA peak current) NXAIR for 40 kA must be selected in combination with
3AE2 for 31,5 kA
Remark: Switchgear must be labeled correctly regarding short circuit current

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 74 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

8.9 Circuit breaker 3AE2 15 / 17,5 kV – 31,5 kA (tested acc. to IEC/IEEE 62271-37-013)
Panel data Breaker data 1) Ordering number of breaker (MLFB)
1 2 3 4 5 6 7 - 8 9-14 15 16 - Z
kV kA Busbar Feeder Width kV kA A -
[A] [A] [mm]
 17.5 40 1250 1250 800 17.5 31.5 1250 3 A E 2 6 6 5 - 2 D 9 0
 17,5 40 2500 1250 800 17.5 31.5 1250 3 A E 2 6 6 5 - 2 D 9 0
 2000 800 2500 3 A E 2 6 6 5 - 6 D 9 0
 2500 1000 2500 3 A E 2 6 6 5 - 6 D 9 0
 17.5 40 3150 1250 800 17.5 31.5 1250 3 A E 2 6 6 5 - 2 D 9 0
 2000 800 2500 3 A E 2 6 6 5 - 6 D 9 0
 2500 1000 2500 3 A E 2 6 6 5 - 6 D 9 0
 3150 1000 3150 3 A E 2 6 6 5 - 7 D 9 0
 17.5 40 4000 1250 800 17.5 31.5 1250 3 A E 2 6 6 5 - 2 D 9 0
 2000 800 2000 3 A E 2 6 6 5 - 6 D 9 0
 2500 1000 2500 3 A E 2 6 6 5 - 6 D 9 0
 3150 1000 3150 3 A E 2 6 6 5 - 7 D 9 0
 4000 1000 4000 3 A E 2 6 6 5 - 8 D 9 0
 Additional ordering code 9. - 14. position, shunt releases, auxiliary voltages configurated in NX-Tools+
Standard version for all 15. position: With mechanical interlocking Auxiliary switch 12NO+12NC and N
breakers 64-pole plug
Routine test certificate F 2 0
Special low voltage connection and without upper part of plug W 6 3
Switching duty: CO – 30 min – CO
 Additional ordering code 16. pos, language configurated in NX-Tools+
 optionally additional codes for optionally secondary wiring halogen free and flame retardent A 1 0
all breakers
Silicon free design A 3 1
circuit breaker for operation down to –25 °C A 4 0
GOST, specific higher insulation level Ud = 42 kV E 1 3

 Release combinations 9.-14.  “1 shunt release” or


and 16. position provided by
NX-Tools  “2 shunt releases” or
 “3 shunt releases” or
 “1 shunt release+1 undervoltage release” or
 “2 shunt release+1 undervoltage release”

Attention:
1) Rated insulation levels for rated voltage 17.5 kV acc. IEC 62271-1, range 1, series 1
 Rated short-duration power-frequency withstand voltage: 38 kV
 Rated lightning impulse withstand voltage: 95 kV

Due to dimensions of 3AE2 for generator circuit application in NXAIR 3AE2 fits only in standard panels with depth ≥ 1500 mm and panels with 800 mm or
1000 mm panel width.
For generator switch application 31,5 kA acc. IEC/IEEE 62271-37-013 (up to 87 kA peak current) NXAIR for 40 kA must be selected in combination with
3AE2 for 31,5 kA
Remark: rated voltage 17,5 kV (IEC 62271); 15 kV (IEC/IEEE 62271-37-013)
Switchgear must be labeled correctly regarding short circuit current

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 75 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

1)
9 Vacuum contactor fuse combination
9.1 Contactor 3TM3
Order number Rated Rated Standard BIL PFWV
voltage operational
current
kV A kV kV kV kV
phase/phase open contact phase/phase open contact
gap gap
 3 T M 3 2 3 1 - 1 7.2 450 IEC 60 60 20 20
 3 T M 3 3 3 1 - 1 7.2 450 GOST 60 60 32 32
 3 T M 3 4 3 1 - 1 12 450 IEC 75 75 28 28
 A 10. pos: without latching / delatching system
 F 10. pos: with latching / delatching + mechanical delatching +always in combination with Z J67
2 11. pos: 120 mm pole-centre distance
For operating voltage 24 V DC – 60 V DC:
T 9. pos. For operating voltage 24 - 32 V DC
U 9. pos. For operating voltage 48 - 60 V DC:
 0 12. pos: standard closing time (55 ms ± 15 ms) without delay
1 12. pos: additional closing delay: 50 ms ± 10 ms
 0 13. pos. standard opening time (35 ms ± 10 ms)
possible with or without closing latch and latch release
 1 13. pos. additional opening delay 50 ms ± 10 ms
only possible without closing latch and latch release
For operating voltage 110 - 125 V DC / 100 - 120 V AC and 220 - 250 V DC / 230 - 240 V AC
V 9. pos. For operating voltage 110 - 125 V DC / 100 - 120 V AC
W 9. pos. For operating voltage 220 - 250 V DC / 230 - 240 V AC
0 12. pos: standard closing time (55 ms ± 15 ms) without delay
1 12. pos: additional closing delay: 50 ms ± 10 ms
0 13. pos. standard opening time (40ms ± 10 ms)
2 13. pos. additional opening delay 30 ms ± 10 ms
only possible without closing latch and latch release
3 13. pos. additional opening delay 60 ms ± 10 ms
only possible without closing latch and latch release
5 13. pos. additional opening delay 90 ms ± 10 ms
only possible without closing latch and latch release
 C 15. pos: auxiliary switch 4NO+4NC without wiring
 D 15. pos.: auxiliary switch 6NO+6NC without wiring
0 16. pos: Operating manual in German
2 16. pos: Operating manual in English
6 16. pos: Operating manual in Spanish
9 16. pos: Operating manual in Portugese + order code R1C
 AC operating voltage of drive solenoid and closing latch
2)
 Fused control transformer secondary voltage 110 V AC
2)
 Fused control transformer secondary voltage 230 V AC
 1 HVRC fuse per phase, 442 mm length
 2 HVRC fuses per phase, 442 mm length
 2nd nameplate as consignment (Z B00)
 For operation in altitude > 2000m (Z R57)
 for heavy duty demands, high vibration and shock resistance >10g (Z R58)
Routine test protocol (Z F20) – language is defined by 16. position
 Mechanical delatching in direction A -push (Z J67) always in combination with “F” (pos. 10)
 Routine test protocol in English additionally incl. ratings of voltage drop test (Z F36)

1) can be used for motor feeder and transformer feeder (not for transformer incomer), insulation level of GOST standard for 7.2 kV rated voltage as an
option possible
2) control transformer (CPT) in contactor includes always wiring with silicone

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 76 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

9.2 Control transformer in contactor panel 1)


Primary voltage (kV)

 3.3  3.6  4.0  4.2  4.8  5.0  5.5  6.0

 6.3  6.6  6.9  7.2  10.0  10.5  11.0  11.4  12.0

Secondary voltage (V)  110 V AC  230 V AC

Frequency (Hz)  50  60

1) insulation level of control transformers 75 kV / 28 kV, 1 min, insulation level GOST 75 kV / 32 kV 1 min only possible for primary voltages ≥ 6 kV;
insulation level for CPT ≤ 3,6 kV is 40kV BIL and 10kV PFV

9.3 Fuses motor application of contactor panel


9.3.1 type SIBA
Ur In HV HRC fuse Dimension “e” HV HRC fuse-link

(kV) (A) (mm) Order no.: Type

 7.2 50 442 3010853.50 HHD - BM

 63 442 3010853.63 HHD - BM

 80 442 3010853.80 HHD - BM

 100 442 3010853.100 HHD - BM

 125 442 3010953.125 HHD - BM

 160 442 3010953.160 HHD - BM

 200 442 3011054.200 HHD - BM

 250 442 3011054.250 HHD - BM

 315 442 3011054.315 HHD - BM

 12 50 442 30 101 53.50 HHD - BM

 63 442 30 101 53.63 HHD - BM

 80 442 30 102 53.80 HHD - BM

 100 442 30 102 53.100 HHD - BM

 125 442 30 102 53.125 HHD - BM

 160 442 30 103 53.160 HHD - BM

9.3.2 type Inter-teknik


Ur In HV HRC fuse Dimension “e” HV HRC fuse-link

(kV) (A) (mm) Order no.:

 7.2 50 442 +S68T.12KV.442.050.08-7.2

 63 442 +S68T.12KV.442.063.08-7.2

 80 442 +S68T.12KV.442.080.08-7.2

 100 442 +S4T.12KV.442.100.08-7.2

 125 442 +S4T.12KV.442.125.08-7.2

 160 442 +S4T.12KV.442.160.08-7.2

 200 442 +S4T.12KV.442.200.08-7.2

 250 442 +S4T.12KV.442.250.08-7.2

 315 442 +S4T.12KV.442.315.08-7.2

 12 50 442 +S68T.12KV.442.050.08

 63 442 +S68T.12KV.442.063.08

 80 442 +S68T.12KV.442.080.08

 100 442 +S4T.12KV.442.100.08

 125 442 +S4T.12KV.442.125.08

 160 442 +S4T.12KV.442.160.08

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 77 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

9.4 Fuses for withdrawable voltage transformers resp. control transformer of contactor panel
application Voltage Rated current Length Design

 Metering panel for busbar metering 7,2 kV 3,15 A 142 mm type Bussmann (7,2 ABWNA)

12 kV 3,15 A 195 mm type Bussmann (12 ABCNA)

17,5 kV 2A 220 mm type Bussmann (17,5 CAV)

 Withdrawable voltage transformers at feeder side 7,2 kV 2A 192 mm Siba 3000211 for 7.2 kV or
fuses include inside voltage transformer housing
(drawing number: 110-0235.9) Inter-teknik S1Z1002 for 7.2 kV

12 kV 2A 192 mm Siba 3011911 for 12 kV or

Inter-teknik S1Z.12kV.192.002 for 12 kV

17,5 kV 2A 192 mm Siba 3017911 for 17.5 kV or

Inter-teknik S1Z.17.5kV.192.002 for 17.5 kV


2)
 Control transformer in contactor panel ≤ 7,2 kV 3A 142 mm type SIBA

12 kV 1,6 A 160 mm EFEN, order nr. 67036-0004

10 Switch-disconnector with HRC-fuses


10.1 Switch-disconnector - fuse combination
Manufacturer: Schneider electric

Order number Standard Rated BIL PFWV


voltage

L-TRI 5 F/24/200/250-UH-KS-A-EUI kV kV kV kV kV

phase/phase Open contact gap phase/phase open contact gap

IEC 62271-105 12 75 85 28 32

GOST 12 75 85 42 48

IEC 62271-105 17,5 95 110 38 45

standard

Length of shaft: 907 mm

Without shunt release AA

With auxiliary switches for the load break switch and earthing switch (provided by Siemens factory)

Interface to operating side for load break switch on the right side

With fuse holder for 1 HVRC fuse per phase, 442 mm length, 53mm diameter

Without capacitive voltage detection system

Blades of earthing switch bare

With clamping lever QW 7 for load break switch

With clamping lever QW 6 for earthing switch

Without interlocking between earthing switch and load break switch (VUI)

With earthing switch, interface to operating mechanism on the right side (EUI)

option

 With breaking-current shunt release (as option “AA”)

 With auxiliary switch for signal “fuse tripped” (option “MSKM”)

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 78 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

10.2 HV-fuses for switch-disconnector type SIBA


Type designation for all possible rated fuse currents for transformer application, fuse length “e”, order number

Ur Ur HRC-fuse In HV HRC fuse Length “e” Diameter “D” HV HRC fuse-link

[kV] [kV] [A] [mm] [mm] Order no.: Type

7.2 3/7,2 16 442 53 30.108.13.16 HHD-B

 20 442 53 30.108.13.20 HHD-B

 25 442 53 30.108.13.25 HHD-B

 31,5 442 53 30.108.13.31,5 HHD-B

 40 442 53 30.108.13.40 HHD-B

 50 442 53 30.108.13.50 HHD-B

 63 442 67 30.109.13.63 HHD-B

 80 442 67 30.109.13.80 HHD-B

 6/12 80 442 67 30.102.43.80 HHD-BSSK

 12 6/12 6,3 442 53 30.101.13.6,3 HHD-B

10 442 53 30.101.13.10 HHD-B

16 442 53 30.101.13.16 HHD-B

 20 442 53 30.101.13.20 HHD-B

 25 442 53 30.101.13.25 HHD-B

 31,5 442 53 30.101.13.31,5 HHD-B

 40 442 53 30.101.13.40 HHD-B

 50 442 53 30.101.13.50 HHD-B

 63 442 67 30.102.13.63 HHD-B

 80 442 67 30.102.43.80 HHD-BSSK

 17,5 10/17,5 6,3 442 53 30.231.13.6,3 HHD-B

 10 442 53 30.231.13.10 HHD-B

 16 442 53 30.231.13.16 HHD-B

 20 442 53 30.231.13.20 HHD-B

 25 442 53 30.231.13.25 HHD-B

 31,5 442 53 30.231.13.31,5 HHD-B

 40 442 53 30.231.13.40 HHD-B

 50 442 67 30.232.13.50 HHD-B

 10/24 63 442 67 30.014.43.63 HHD-BSSK

 80 442 67 30.014.43.80 HHD-BSSK

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 79 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

11 SIQuench (Arc Quenching Device)


Order number
1. 2. 3. 4. 5. 6. 7. - 8. 9. 10. 11. 12. - 13. 14. 15. 16. - Z

 3 A M 4 1 - - 3 phase SAQ power box


2 - 12 kV (BIL = 75 kV / PFV 42 kV)
3 - 17,5 kV (BIL = 95 kV / PFV 42 kV)
2 - - 170 mm pole distance for 600mm panels
(only up to 31,5 kA)
3 - - 210 mm pole distance for 800mm panels
6 - - 210 mm pole distance for use in module
compartment of 800 mm panels
- 1 - Up to 31,5 kA
- 2 - 40 kA
- C - 1 sec
- D - 3 sec
- A - Sensing: not specified
- 1 - With Siemens SAQ-Controller for MV
- 2 - Auxiliary voltage 110V-250V AC/DC for
controller
- - 0 w/o Connection harness
- - A w/o Communication protocols
- - B Communication interface USB at front
- - 2 language of operation manual and
nameplate in English
- - - Z A 3 1 Version free of silicone emissions incl.
evidence (certificate) as option

1) SIQuench 3AM41 always will delivered in standard:


 With routine test protocol
 With separate nameplate for fitting in LV compartment
 wiring: 1,5 mm² SIENOPYR (N)HX4GAF 110°C – 600/1000V – halogen free cable

2) selection of sensors, master unit and slave units depending on switchgear configuration:

Item Detail Brand Product Code

 1 pc. required per compartment --> 3 pcs. required per panel


(2 pcs. for metering panels)
 Sensors within a cubicle will be serially connected to reduce
Point light sensors down the required number of arc flash protection relays. With Arcteq AQ-01B
this type of connection, the indication in case of an internal arc
fault will be cubicle wise but not compartment wise.

 1 pc. required per SIQuench system.


 This is the relay triggering the controller of SIQuench.
 There are 4 light sensor inputs. When the 3 light sensors in a
cubicle are serially connected, this relay can accommodate the
Main arc flash protection relay light pickup of 4 panels.
 For overcurrent pickup, a parallel connection shall be made Arcteq AQ-110P-?ABA-S-E
(Master unit)
from the CTs of the incomers.
 In case of more than 1 incomer per bus, additionally, a
summation CT shall be used to sum up the current signal from
the CTs of the incomers.

 When all 4 inputs are used on the main arc flash relay, slave
Slave arc flash protection relay
units shall be utilized to increase the number of inputs. It has Arcteq AQ-101-?AA?-S-E
(Add-on unit) also 4 light sensor inputs.

 Required for connecting the light point sensors to arc flash


protection relays.
Shielded twisted pair cable for Size: 0.5 ~ 0.75mm2, AWG: 18 ~ 20
 Any brand NA
sensor connection Cable cover: Ø 4.5 ~6.0 mm
 In average 8 meters required per each panel.
 1 pc. required per each SIQuench system
Connection fiber  To connect the controller of SIQuench to the main arc flash Arcteq AX-001-5
relay for triggering

3) additional ARCTEQ make arc flash relays type AQ-110P as master unit and AQ-101 as add-on units must be selected with the browser for low-voltage,
following type with suffix “-S-E” are released for use in combination with SIQuench only:

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 80 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

Master unit (AQ 110P – Arc flash protection relay) – Ordering numbers

AQ 110P-XXXX-S-E Auxiliary power Trip relay T3 Additional sensor Binary inputs


supply characteristic channels nominal voltage
A 80…265 V AC / DC
A Normally open (NO) type
AQ-110P-AABA-S-E B Additional Fiber optic sensor channel for
triggering the controller
A 24 V DC
B 18…72 V DC
A Normally open (NO) type
AQ-110P-BABA-S-E B Additional Fiber optic sensor channel for
triggering the controller
A 24 V DC

Add-on unit (AQ 101- Arc flash protection relay) – Ordering numbers

AQ 101-XXXX-S-E Auxiliary power Trip relay T3 Additional sensor Binary inputs


supply characteristic channels nominal voltage
A 80…265 V AC / DC
A Normally open (NO) type
AQ-101-AAAA-S-E
A None
A 24 V DC
A 80…265 V AC / DC
A Normally open (NO) type
AQ-101-AAAB-S-E
A None
B 110 V DC
A 80…265 V AC / DC

AQ-101-AAAC-S-E A Normally open (NO) type


A None
C 220 V DC
B 18…72 V DC

AQ-101-BAAA-S-E A Normally open (NO) type


A None
A 24 V DC
B 18…72 V DC

AQ-101-BAAB-S-E A Normally open (NO) type


A None
B 110 V DC
B 18…72 V DC

AQ-101-BAAC-S-E A Normally open (NO) type


A None
C 220 V DC

4) remarks and explanations


 SIQuench could only be located in the panels without any busbar assembly (BB VT, BB CT, BB ES, Ventilation…). The electronic controller of SIQuench
and the main arc flash relay which is triggering the SIQuench will be located as flush-mounted on the LV door of the panel where the SIQuench will be
located in. The positioning of these two components with other secondaries needs to be checked. In case of space constraints, the main arc flash
protection unit AQ-110P can be located on the adjacent panel.
 The LV box of the panel to be equipped with SIQuench shall be extended/higher version.
 Each bus will require one SIQuench system.
 SIQuench could only be triggered with a dedicated arc flash protection relay. The Siemens certified arc flash protection relays and light point sensors
from Arcteq needs to be used.
 As it is not fast enough, an arc sensing with SIP5 or with other makes could not be used with SIQuench application.
 Arc flash protection relays and fiber connection cables between the relay and SIQuench controller shall be configured in the Browser.
 Busbar live signal is required for the controller to be able to distinguish and count the switching cycles under load and without load. That is why an LLI
with a change-over contact like CAPDIS S2+ is required on the panels where SIQuench will be located.
 Aux. voltage of the controller is in the range 110V-250V AC/DC.
 For charging the spring hand lever for moving the withdrawable part is needed (8BX3300-0LA00-0AB7)

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 81 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

12. Optical arc fault detection system


12.1 Location of sensors
Arcteq SIPROTEC

Location of point sensors 1) Location of point sensors 1)

BBC CC SDC BBC CC SDC

Single busbar and panels for duplex front-to-front arrangement

circuit breaker panel X X X X X X

disconnector panel X X X X X X

vacuum contactor panel X --- X X --- X

switch disconnector panel with HVR-fuses X X X X

CB-panel X X X X X X
bus sectionalizer type I
BR-panel with disconnector X X X X X X

CB-panel X X X X X X
bus sectionalizer type II
BR-panel X X

CB-panel X X X X X X
bus sectionalizer type II
BR-panel with metering module X X X X

metering panel X --- X X --- X

busbar current metering panel X --- --- X --- ---

busbar connecting panel X X

panels for duplex in back-to-back arrangement

circuit breaker panel X X X X X X

disconnector panel X X X X X X

bus coupler X X X X X X

One light point sensor mounted in each HV-compartment depending on compartmentalization and LSC-categorization per typical (position marked with a
cross in table 12.1). For some typicals special conditions are valid:
 for switch disconnector panel one sensor in busbar compartment and one common sensor mounted for combined switching device and connection
compartment
 for bus sectionalizer type II in bus riser panel with metering modul one sensor in switching compartment and one common sensor mounted for
combined busbar compartment and connection compartment
 for bus sectionalizer type II in bus riser panel and for bus bar connecting panel only one common sensor mounted for complete panel
 for bus coupler, circuit breaker panel and disconnector panel combined to one functional unit duplex in back-to-back arrangement one sensor per
busbar compartment of row A and row B, one sensor per switching device compartment of row A and row B and two sensors in combined
connection compartment between row a and row B mounted

12.2 ARCTEQ AQ-series


12.2.1 Systematic of sensor connection for tripping of circuit breakers
selective tripping typical Wiring of sensors

with outgoing feeder with cb The sensors located in the BBC&SDC will be wired in serial and connected to one common input of
the arc flash relay. The sensor in the CC shall be separately connected to the arc flash relay

incomer feeder with cb The sensor in BBC, in SDC and in the CC shall be separately connected to the arc flash relay

cb-panel of bus The sensor in BBC, in SDC and in the CC shall be separately connected to the arc flash relay
sectionalizer
bus riser panel of bus All sensors in a single functional unit will be wired in serial and connected to one common input of
sectionalizer the arc flash relay.

all other typicals All sensors in a single functional unit will be wired in serial and connected to one common input of
the arc flash relay.

without outgoing feeder with cb All sensors in a single functional unit will be wired in serial and connected to one common input of
the arc flash relay.

incomer feeder with cb The sensors located in the BBC&SDC will be wired in serial and connected to one common input of
the arc flash relay. The sensor in the CC shall be separately connected to the arc flash relay

cb-panel of bus The sensors located in the BBC&SDC will be wired in serial and connected to one common input of
sectionalizer the arc flash relay. The sensor in the CC shall be separately connected to the arc flash relay

bus riser panel of bus All sensors in a single functional unit will be wired in serial and connected to one common input of
sectionalizer the arc flash relay.

All other typicals All sensors in a single functional unit will be wired in serial and connected to one common input of
the arc flash relay.

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 82 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

12.2.2 Components for optical arc fault detection system

Brand Item Detail Product Code

 Only point light sensor w/o any wiring


Arcteq Point light sensors  Number of sensors depending on type of typical AQ-01B

 Required for connecting the light point sensors to arc flash


Shielded twisted pair protection relays.
Any brand cable for sensor  Size: 0.5 ~ 0.75mm2, AWG: 18 ~ 20 NA
connection Cable cover: Ø 4.5 ~6.0 mm
 In average 8 meters required per each panel for three sensors

 1 pc. required per bus section


 This is the relay with current inputs for overcurrent sensing
triggering the cb of the incomer
 There are 4 light sensor inputs. When the 3 light sensors in a
Main arc flash protection cubicle are serially connected, this relay can accommodate the
Arcteq relay light pickup of 4 panels. AQ-110P-XXXX-S-E
(Master unit)  For overcurrent pickup, a parallel connection shall be made
from the CTs of the incomers.
 In case of more than 1 incomer per bus, either additional
AQ-110P/s or summation CTs shall be considered to sum up
the current signal from the CTs of the different incomers.

Slave arc flash  When all 4 inputs are used on the main arc flash relay, slave
AQ-101-XXXX-S-E
Arcteq protection relay units shall be utilized to increase the number of inputs. It has
also 4 light sensor inputs. AQ-101D-XXXX-S-E
(Add-on unit)

 Only for busbar compartment as DTO


 1 pc. required per each busbar section
 Pre-manufactured length 1 – 40 m
Arcteq fiber optic loop sensor AQ07 or AQ08
 AQ-110P and/or AQ-101 arc flash protection relays must be
equipped with the additional sensor channel S5 “fiber optic
sensor channel” for the connection of fiber loop sensors.

12.3 Selection table for ARQTEC AQ-protection relays


12.3.1 AQ-101 arc flash protection relay AQ-101D arc flash protection (for DIN rail fixation)

12.3.2 AQ-101 P arc flash protection relay with overcurrent

Attention: Arteq relais with ending „S-E” are Siemens certified version and covered via frame agreement

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 83 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

12.4 SIPROTEC 5 – series


12.4.1 Systematic of sensor connection for tripping of circuit breakers
With Outgoing feeder with CB Each point sensor will be connected to the relay individually

Incomer feeder with CB Each point sensor will be connected to the relay individually

All other typicals Each point sensor will be connected to the relay individually

Without Outgoing feeder with CB Each point sensor will be connected to the relay individually

Incomer feeder with CB Each point sensor will be connected to the relay individually

All other typicals Each point sensor will be connected to the relay individually

Attention: Metal-enclosed compartments of AIS are not light tight hence nuisance tripping may occur depending on the density of light in the case of arcing
fault. So selective tripping of an outgoing feeder can not be guaranteed

12.4.2 Realization with SIPROTEC 5

Brand Item Detail Product Code

 Point sensor with line length of 3 m


Siemens SIP5 Point light sensors  number of sensors depending on type of typical P1X19
 type of connection: glass fibre cable

Arc Protection Plugin Module  Up to 3 optical point or line sensors per arc
Siemens SIP5 protection plug-in module can be connected P1Z1966
(ARC-CD-3FO)

 non-modular devices – 7xx81 and 7xx82 + arc


protection plugin module
Protection relay of  1 pc. required per panel in standard
Siemens SIP5 modular devices as DTO due to changed length of 7xx81 or 7xx82
SIPROTEC 5 series 
glass fibre cables for point sensors depending on
postion of protection relay

 Only for busbar compartment as DTO


P1X107 (5 m)
Siemens SIP5 line sensor  1 pc. per each busbar section
 Selection of length depending on switchgear length P1X143 (40 m)

 For connection of line sensor with arc protection P1X152 (3m)


Siemens SIP5 Supply line for line sensor plugin module needed P1X170 (10 m)

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 84 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

13. Accessories MLFB No.:


1 2 3 4 5 6 7 - 8 9 10 11 12 - 13 14 15 16
Standard accessory set consisting of (generally included in delivery): 8 B X 2 0 4 2 - 2 T C
1 hand crank for charging spring of circuit breaker,
1 push rod for actuating the ON/OFF push buttons
1 hand lever for moving withdrawable part
1 set shutter levers right/left
1 socket spanner for high voltage door
1 socket spanner for low voltage door
1 wall panel for accessories
1 set lifting bolts for panels width ≤ 800 mm
1 set lifting bolts for 1000 mm panel
1 operating manual
1 installation manual and
1set supplement drawings in english
Standard accessory set consisting of (generally included in delivery): 8 B X 2 0 4 2 - 2 T F
1 hand crank for charging spring of circuit breaker,
1 push rod for actuating the ON/OFF push buttons,
1 hand lever for moving withdrawable part,
1 set shutter levers right/left,
1 socket spanner for high voltage door,
1 socket spanner for low voltage door,
1 wall panel for accessories,
1 set lifting bolts for panels width ≤ 800 mm,
1 set lifting bolts for 1000 mm panel,
1 operating manual,
1 installation manual and
1set supplement drawings in german
Standard accessory set consisting of (generally included in delivery): 8 B X 2 0 4 2 - 2 T G
1 hand crank for charging spring of circuit breaker,
1 push rod for actuating the ON/OFF push buttons,
1 hand lever for moving withdrawable part,
1 set shutter levers right/left,
1 socket spanner for high voltage door,
1 socket spanner for low voltage door,
1 wall panel for accessories,
1 set lifting bolts for panels width ≤ 800 mm,
1 set lifting bolts for 1000 mm panel,
1 operating manual,
1 installation manual and
1set supplement drawings in spanish
1 hand crank for charging spring of circuit breaker 8 B X 2 0 4 2 - 2 U

1 push rod for actuating the ON/OFF push buttons 8 B X 2 0 7 2

1 push rod for actuating the ON/OFF push buttons and for “emergency OFF” for 3TM 8 B X 2 0 7 2
contactor (only for NXAIR up to 40 kA and NXAIR for 50 kA)

1 hand lever for moving withdrawable part 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A B 7

1 hand lever for for switch-disconnector in SDF panel (for NXAIR and NXAIR C) – 8 B X 2 0 4 2 - 1 C C 3 9
improved version

1 hand lever for earthing switch (NXAIR, NXAIR SEC, NXAIR M, NXAIR C) 8 B X 2 0 4 3 - 1 H B

1 adapter for earthing without withdrawable part 8 B X 2 0 4 4 - 1 A

1 hand lever for withdrawable voltage transformers 1) 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A B 8

1 socket spanner for high voltage door 8 B X 1 6 0 0

1 socket spanner for low voltage door 8 B X 1 6 0 1

1 ladder (three stairs) for operating busbar earthing switch 1) 8 B X 2 0 4 3 - 1 L


1)
1 drilling jig for seismic version ≤ 17.5 kV / ≤ 31.5 kA / ≤ 2500 A 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A C 2
1)
1 drilling jig for seismic version ≤ 17.5 kV / ≤ 31.5 kA / ≤ 3150 / 4000 A resp. ≤ 17.5 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A C 3
kV / 40 kA / ≤ 4000 A

1 set (4 pieces per panel) of lifting bolts for NXAIR ≤17.5 kV per panel of widths up to 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A C 6
800 mm or for 24kV up to 1000mm (included in standard delivery)

1 set (4 pieces per panel) of lifting bolts for NXAIR ≤ 17.5 kV, per panel of width 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A C 7
1000 mm, included in standard delivery

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 85 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

13. Accessories MLFB No.:


1 2 3 4 5 6 7 - 8 9 10 11 12 - 13 14 15 16
2)
Service truck , simplified 600 panel with instruction notes in German 8 B X 2 0 4 3 - 1 A A
version,
600 panel with instruction notes in English 8 B X 2 0 4 3 - 1 A B

600 panel with instruction notes in Spanish 8 B X 2 0 4 3 - 1 A C

800 / 1000 panel with instruction notes in German 8 B X 2 0 4 3 - 1 B A

800 / 1000 panel with instruction notes in English 8 B X 2 0 4 3 - 1 B B

800 / 1000 panel with instruction notes in Spanish 8 B X 2 0 4 3 - 1 B C

Height and width adjustable 600 / 800 / 1000 panel with instruction notes in German 8 B X 2 0 4 3 - 1 D A
service truck, (height
adjustment in 7 steps from 600 / 800 / 1000 panel with instruction notes in English 8 B X 2 0 4 3 - 1 D B
0 mm to 150 mm)
600 / 800 / 1000 panel with instruction notes in Spanish 8 B X 2 0 4 3 - 1 D C

Service truck for withdrawable voltage transformers at cable side for 800mm and 8 B X 3 4 0 0 - 0 A A 0 0 - 0 A A 8
1000 mm panels 2)

Service truck for withdrawable voltage transformers at cable side for 600 mm panels 2) 8 B X 3 4 0 0 - 0 A A 0 0 - 0 A B 5

Hand lever for shutter mechanism (set, included in standard accessories) 8 B X 2 0 4 2 - 2 F A

1 pc. hand lever for shutter mechanism (only for vacuum contactor panel 435mm with 8 B X 2 0 4 2 - 2 F D
3TM)

Terminal lug (copper bars) for connection of earthing bar to station earth for 600 mm, 8 B X 2 0 4 2 - 2 H C
800 mm and 1000 mm panels

Indicator for separable VDIS 1) 8 D X 1 6 2 0

Phase comparison measuring instrument for capacitive voltage indication system 8 D X 1 6 0 7


Type EPV-HR (Pfisterer incl. 2 HR-LRM Adapter and transport bag

KP Glow lamp voltage tester with operation rod (3 kV - 10 kV / 50 Hz) 8 B X 1 6 1 5 - 1 A

KP Glow lamp voltage tester with operation rod (10 kV - 20 kV / 50 Hz) 8 B X 1 6 1 5 - 1 B

KP Glow lamp voltage tester with operation rod (3 kV - 10 kV / 50 Hz - 60 Hz) 8 B X 1 6 1 5 - 1 D

KP Glow lamp voltage tester with operation rod (10 kV - 20 kV / 50 Hz - 60 Hz) 8 B X 1 6 1 5 - 1 E


1)
Testing equipment for pressure switch 8 A X 1 0 5 0

Coupling element for testing equipment for pressure switch 8 A X 1 0 5 1

Tool for connecting fibre optic cables 1) 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A E 7


4)
Portable earthing device 25 kA / 1s, diameter 40mm 8 B X 2 0 4 3 - 1 E
4)
Portable earthing device 25 kA / 1s, diameter 60mm 8 B X 2 0 4 5
4)
Portable earthing device 25 kA / 1s, diameter 80mm 8 B X 2 0 4 5 - 0 C

Tube of Vaseline (250 g) for connecting coppers 8 B X 2 0 4 1

Can of Longtherm 2 Grease (1 kg) for isolating and mating contacts 8 B X 1 0 2 2

Lubrications for 3AE 180 g of Klüber-Isoflex Topas L32 3 A X 1 1 3 3 - 3 H

1 kg of Klüber-Isoflex Topas L32 3 A X 1 1 3 3 - 3 E

1 kg of Molykote-Fett 3 A X 1 1 3 3 - 2 L

Wall panel for accessories (included in standard set of accessories) 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A C 0

Sealing compound for IP4X (Sikaflex) 8 B X 2 0 4 2 - 2 L

Coupling cable connector 64 pin for connection withdrawable part for function tests 8 B X 2 0 5 0 - 0 A

Fixing material (1 set per panel included in standard delivery) 8 B X 2 0 6 0

cable clamp small (26 mm - 38 mm) 8 A X 2 2 3 3 - 1 A

cable clamp middle (36 mm - 52 mm) 8 A X 2 2 3 3 - 1 B

cable clamp large (50 mm - 75 mm) 8 A X 2 2 3 3 - 1 C

cable clamp extra large (66 mm - 90 mm) 8 A X 2 2 3 3 - 1 D

Spare assembly parts for wiring on site (1 set included in standard delivery) 8 D X 1 6 2 1

to Phoenix Standard terminals, consisting of Type UPCV3K, 12 Bus wiring terminals,


4 plugs PCC4/6-ST-MTN 1.5-2.5, Type VBSTB 4-FS: 12 Terminals, 4 Modul plugs
with sockets, 50 contact sockets (single pins), 50 insulating coverings

cable entry plate FL 21 prepared for use with special cable glands for LV cables 8 B X 1 0 2 3

1 set of x cable glands (4 x PG12, 4 x PG16, 2 x PG20 and 2 x PG25) 8 B X 1 0 2 8

Installation manual German 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A A 0

Operation manual German 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A B 0

Installation manual English 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A A 1

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 86 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

13. Accessories MLFB No.:


1 2 3 4 5 6 7 - 8 9 10 11 12 - 13 14 15 16

Operation manual English 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A B 1

Installation manual Spanish 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A A 3

Operation manual Spanish 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A B 3

Installation manual Turkish 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A A 9

Operation manual Turkish 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A B 9

Supplement drawings for installation manual (english / german) 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A E 0


1)
Supplementary Instructions - Installation of the low-voltage compartment for NXAIR 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A F 7

Supplement drawings for installation manual Turkish 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A G 8

Installation manual for IP roof (IPX1 / IPX2) English 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A E 1

Installation manual for IP roof (IPX1 / IPX2) German 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A E 2

Installation manual for IP roof (IPX1 / IPX2) Turkish 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A E 3

Supplement instructions for SIQuench English 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A J 1


3)
Additional adapter channels to lead internal arc fault gases outside of switchgear room (quantity of channel parts depends on dimensions of switchgear
room and required channel for both sides lateral or one side lateral or rear side, see also chapter 8.26

pressure relief channel for IP4X, length 0,26 m 1) 8 B X 3 4 0 0 - 0 A A 0 0 - 0 A B 0

pressure relief channel, length 0,8 m 3) 8 B X 3 4 0 0 - 0 A A 0 0 - 0 A B 1

pressure relief channel, length 0,6 m 3) 8 B X 3 4 0 0 - 0 A A 0 0 - 0 A B 2

pressure relief channel, flexible length 0400 to 0,435 m in 17,5 mm steps 3) 8 B X 3 4 0 0 - 0 A A 0 0 - 0 A B 3


1)
pressure relief channel for IP3XD, length 0,26 m 8 B X 3 4 0 0 - 0 A A 0 0 - 0 A B 4
3)
pressure relief channel, length 1 m, 8 B X 3 4 0 0 - 0 A A 0 0 - 0 A A 0
3)
pressure relief channel, 45° angle up/down 8 B X 3 4 0 0 - 0 A A 0 0 - 0 A A 1
3)
pressure relief channel, 45° angle right/left 8 B X 3 4 0 0 - 0 A A 0 0 - 0 A A 2

pressure relief channel, length 0.5 m 3) 8 B X 3 4 0 0 - 0 A A 0 0 - 0 A A 3

pressure relief channel, flexible length 0.595 to 0,76 m in 20 mm steps 3) 8 B X 3 4 0 0 - 0 A A 0 0 - 0 A A 4

pressure relief channel, wall outlet box, length 0.40 m with flap for wall of switchgear 8 B X 3 4 0 0 - 0 A A 0 0 - 0 A A 5
room 3)

pressure relief channel, wall outlet box, length 0.224 m with flap for wall of switchgear 8 B X 3 4 0 0 - 0 A A 0 0 - 0 A B 6
room 3)

outlet flap (weatherproof) 8 B X 3 4 0 0 - 0 A A 0 0 - 0 A B 7


3)
fixing ledges, (2 pieces) 8 B X 3 4 0 0 - 0 A A 0 0 - 0 A A 6
3)
fixing angles, (2 pieces) 8 B X 3 4 0 0 - 0 A A 0 0 - 0 A A 7

1) included in standard delivery when relevant version must be ordered


2) at least 1 service truck device for withdrawable voltage transformers resp.1 service truck depending on ordered panel width included in standard delivery,
trucks are not needed, when truck type version is selected (exception contactor panel)
3) to be used when channel system is required from technical data or in combination with IP50/IP51 up to 17.5 kV / ≤ 31.5 kA, see chapter 1.3
4) selection criteria for portable earthing device depending on feeder ratings see chapter 4.17

14. Spare parts Ordering No.:


On withdrawable part for busbar metering in metering panel or bus riser panel
in bus sectionalizer type II with fuses
7,2 kV: 3,15 A, 142 mm length type Bussmann (7,2 ABWNA3.15) BSD:7.2ABWNA3.15

12 kV: 3,15 A, 195 mm length type Bussmann (12 ABCNA3.15) BSD:12ABCNA3.15

17,5 kV: 2 A, 220 mm length type Bussmann (17,5 CAV2) BSD:17.5CAV2

in separate compartment, withdrawable with fuses at feeder side

7,2 kV: 2 A, 192 mm length type SIBA 3000211 SIB:3000211.2

12 kV: 2 A, 192 mm length type SIBA 3011911 SIB:3011911.2

17,5 kV: 2 A, 192 mm length type SIBA 3017911 SIB:3017911.2

7,2 kV 2 A, 192 mm length type Inter-teknik S1Z1002 INT: S1Z1002

12 kV 2 A, 192 mm length type Inter-teknik S1Z.12kV.192.002 INT: S1Z12kv192.2

17,5 k 2 A, 192 mm length type Inter-teknik S1Z.17.5kV.192.002 INT: S1Z17.5kv192.2

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 87 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

15. Additional tables

15.1 Technical standards

IEC 62271-1 Common clauses for high-voltage switchgear and controlgear standards VDE 0671 – 1
Gemeinsame Bestimmungen für Hochspannungsschaltgeräte
IEC 60071 – 1 Insulation co-ordination for equipment in three-phase systems above 1 VDE 0111 – 1
kV
Isolationskoordination für Betriebsmittel in Drehstromnetzen über 1 kV
IEC 62271-200 A.C. metal-enclosed switchgear and controlgear for rated voltages VDE 0670 – 6
above 1 kV and up to and including 52 kV
Metallgekapselte Wechselstrom-Schaltanlagen für Nennspannungen
über 1 kV bis 52 kV
IEC 62271-100 High-voltage alternating current circuit-breakers VDE 0671-100
Hochspannungs-Wechselstrom-Leistungsschalter
IEC 62271-102 Alternating current disconnectors (isolators) and earthing switches VDE 0671-102
Wechselstromtrennschalter und Erdungsschalter
IEC 62271-103 Switches for rated voltages above 1 kV and including 52 kV VDE 0671-103
Lastschalter für Bemessungsspannungen über 1 kV bis einschließlich
52 kV
IEC 62271-105 High-voltage alternating current switch-fuse combinations VDE 0671-105
Hochspannungs-Lastschalter-Sicherungskombinationen
IEC 62271-106 Contactors VDE 0671-106
Schütze
IEC 60529 Degree of protection provided by enclosures (IP-code) VDE 0470 – 1
Schutzarten durch Gehäuse (IP-Code)
IEC 61243-5 Working under voltage – Voltage detectors – VDE 0682 – 415
Part 5: Voltage detection systems
Arbeiten unter Spannung – Spannungsprüfer –
Teil 5: Spannungsprüfsysteme
IEC 61271-213 Voltage detecting and indicating system VDE 0671-213
Spannungsprüf- und anzeigesysteme
IEC 60282 – 1 Current limiting fuses VDE 0670 – 4
Strombegrenzende Sicherungen
IEC 61869 -1 Instrument transformers - Part 1: General requirements VDE 0414 – 9-1
Messwandler – Teil 1: Allgemeine Anforderungen
IEC 61869 -2 Instrument transformers - Part 2: Additional requirements for current VDE 0414 – 9-2
transformers / Applies in conjunction with IEC 61869-1 (2007-10)
Messwandler – Teil 2: Zusätzliche Anforderungen für induktive
Stromwandler
IEC 61869-3 Instrument transformers - Part 3: Additional requirements for inductive VDE 0414 – 9-3
voltage transformers / Applies in conjunction with IEC 61869-1 (2007-
10)
Messwandler – Teil 3: Zusätzliche Anforderungen für induktive
Spannungswwandler
IEC 61869-6 Instrument transformers – Part 6: Additional general requirements for VDE 0414-9-6
low-power instrument transformers
Messwandler – Teil 6: Zusätzliche allgemeine Anforderungen an
Kleinsignal-Messwandler
IEC 61869-10 Instrument transformers – Part 10: Additional requirements for low- VDE 0414-9-10
power passive current transformers
Messwandler – Teil 10: Zusätzliche Anforderungen an passive
Kleinsignal-Stromwandler
IEC 61869-11 Instrument transformers – Part 11: Additional requirements for low- VDE 0414-9-11
power passive voltage transformers
Messwandler – Teil 11: Zusätzliche Anforderungen an passive
KleinsignalSpannungswandler
IEC 60721-3-3 Classification of environmental conditions DIN EN 60721-3-3
Klassifizierung von Umweltbedingungen

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 88 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

15.2 Dimensions
15.2.1 Dimension of switchgear (standard)
With standard LV- With extended LV-
compartment compartment or top box
at busbar compartment
Height Standard panel incl. pressure relief ≤ 17,5 kV / ≤ 25 kA mm 2300 2350
channel
≤ 17,5 kV / > 25 kA mm 2300 2350
Standard panel incl. absorber ≤ 12 kV / ≤ 25 kA mm 2300 2350
≤ 12 kV / > 25kA mm 2500 2500
17,5 kV / ≤ 40kA mm 2500 2500
Forced ventilated panel ≤ 17,5 kV / ≤ 40kA mm 2450 2450
Height incl. roof Standard panel incl. pressure relief ≤ 17,5 kV / ≤ 25 kA mm 2600 2600
for IPX1 / IPX2 channel
≤ 17,5 kV / > 25 kA mm 2600 2600
Standard panel incl. absorber ≤ 12 kV / ≤ 25 kA mm 2600 2600
≤ 12 kV / > 25kA mm 2600 2600
17,5 kV / ≤ 40kA mm 2600 2600
Forced ventilated panel ≤ 17,5 kV / ≤ 40kA mm 2600 2600
Width Depending on panel type mm Details see chapter 6.1
depth Depending on panel type and type of CT mm Details see chapter 6.1

15.2.2 Dimensions of switchgear room (standard)


Ceiling height with pressure release channel to ≤ 17.5 kV / ≤ 40 kA 1s or 0.1 s mm ≥ 2500
lead gases outside
without pressure release channel ≤ 12 kV / ≤ 25 kA 1s or 0.1 s mm ≥ 2800
to lead gases outside (with
≤ 12 kV / 31.5 kA 1s or 0.1 s mm ≥ 3000
absorbers)
≤ 12 kV / 40 kA 1s or 0.1 s mm ≥ 3500
≤ 17.5 kV / ≤ 31.5 kA 1s or 0.1 s mm ≥ 3500
≤ 17.5 kV / 40 kA 1s or 0.1 s mm ≥ 3500
Ceiling height with pressure release channel to ≤ 17.5 kV / ≤ 40 kA 1s or 0.1 s mm ≥ 2800
incl. roof for lead gases outside
IPX1 / IPX2
without pressure release channel ≤ 12 kV / ≤ 25 kA 1s or 0.1 s mm ≥ 3000
to lead gases outside (with ≤ 12 kV / 31.5 kA 1s or 0.1 s mm ≥ 3000
absorbers)
≤ 12 kV / 40 kA 1s or 0.1 s mm ≥ 3500
≤ 17.5 kV / ≤ 31.5 kA 1s or 0.1 s mm ≥ 3500
≤ 17.5 kV / 40 kA 1s or 0.1 s mm ≥ 3500
Distances behind switchgear to wall, cable connection from front (minimum) mm ≥ 150
behind switchgear to wall, cable connection from rear (minimum) mm ≥ 500
beside switchgear to wall, (minimum) mm ≥ 150 at one side of switchgear row,
≥ 100 for contactor panel,

when pressure release duct is used (at lateral


or back side) at least at that side of switchgear
row ≥ 500 mm for installation recommended
aisles for operating in front of switchgear mm ≥ 1250
for panel replacement mm ≥ 1700

15.2.3 Dimension of switchgear (NXAIR for marine application)


with standard LV-compartment, with extended
LV-compartment or top box at busbar
compartment
Height Standard panel incl. exhaust pipe ≤ 12 kV / 25 kA mm 2600 2600
and IP-roof for IPX1 / IPX2 for
≤ 12 kV / 31,5kA mm 2600 2600
busbar currents ≤ 2500 A
≤ 12 kV / 40kA mm 2600 2600
Width Depending on panel type mm Details see chapter 6.1
Depth Depending on panel type and type of CT mm Details see chapter 6.1

15.2.4 Dimensions of switchgear room (NXAIR for marine application)


Height with exhaust pipe to lead gases ≤ 12 kV / 25 kA 1s or 0.1 s mm ≥ 2800
into switchgear room ≤ 12 kV / 31.5 kA 1s or 0.1 s mm ≥ 2800
≤ 12 kV / 40 kA 1s or 0.1 s mm ≥ 2800
Distances behind switchgear to wall, cable connection from front (minimum) mm ≥ 150
behind switchgear to wall, cable connection from rear (minimum) mm ≥ 500
beside switchgear to wall, (minimum) mm ≥ 150 at one side of switchgear row
≥ 100 for contactor panel,
Aisles for operating in front of switchgear mm ≥ 1250
for panel replacement mm ≥ 1750

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 89 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

15.2.5 Dimension of switchgear (duplex in back-to-back arrangement)


With standard LV- With extended LV-
compartment compartment or top box
at busbar compartment

Height Standard panel incl. pressure ≤ 17,5 kV / ≤ 25 kA mm 2300 2350


relief channel
≤ 17,5 kV / > 25 kA mm 2300 2350

Standard panel incl. absorber ≤ 12 kV / ≤ 25 kA mm 2300 2350

≤ 12 kV / > 25kA mm 2500 2500

17,5 kV / ≤ 40kA mm 2500 2500

Forced ventilated panel ≤ 17,5 kV / ≤ 40kA mm 2450 2450

Width Depending on panel type mm Details see chapter 3.2.1

Depth Un Ik busbar current feeder current Standard panels Panels with extended CT

≤ 17.5 kV ≤ 31.5 kA ≤ 2500 A ≤ 2500 A mm 2850 2850

≤ 17.5 kV ≤ 31.5 kA 3150 A / 4000 A ≤ 2500 A mm 3150 3150

≤ 17.5 kV ≤ 31.5 kA 3150 A / 4000 A 3150 A / 4000 A mm 3150 3150

≤ 17.5 kV 40 kA ≤ 4000 A ≤ 2500 A mm 3150 3150

≤ 17.5 kV 40 kA ≤ 4000 A 3150 A / 4000 A mm 3150 3150

15.2.6 Dimensions of switchgear room (duplex in back-to-back arrangement)


Ceiling height with pressure release channel to ≤ 17.5 kV / ≤ 40 kA 1s or 0.1 s mm ≥ 2500
lead gases outside

without pressure release channel ≤ 12 kV / ≤ 25 kA 1s or 0.1 s mm ≥ 2800


to lead gases outside (with
absorbers) ≤ 12 kV / 31.5 kA 1s or 0.1 s mm ≥ 3000

≤ 12 kV / 40 kA 1s or 0.1 s mm ≥ 3500

≤ 17.5 kV / ≤ 31.5 kA 1s or 0.1 s mm ≥ 3500

≤ 17.5 kV / 40 kA 1s or 0.1 s mm ≥ 3500

Distances behind switchgear to wall, cable connection from front (minimum) mm n.a.

beside switchgear to wall, (minimum) mm ≥ 150 at one side of switchgear row,

≥ 100 for contactor panel,

when pressure release duct is used (at lateral or


back side) at least at that side of switchgear row
≥ 500 mm for installation recommended

aisles for operating in front of switchgear mm ≥ 1250

for panel replacement mm ≥ 1700

15.3 Loss of service continuity class acc. IEC62271-200 Edition 3


Panels with connection compartment Switching device panel with CB LCS 2B

Switching device panel with disconnector link LSC 2B

Contactor panel LCS 2B

Switch-disconnector panel with fixed mounted load-break switch LSC 2

Busbar connecting panel LSC 1

Panels without connection compartment Busbar current metering panel No LSC category

Metering panel No LSC category

Bus sectionalizer Type 1 (CB panel + bus riser panel with disconnecting module No LSC category

Bus sectionalizer type 2 (CB panel + bus riser) No LSC category

Bus sectionalizer type 2 (CB panel + bus riser with metering module) No LSC category

15.4 Partition class


For feeders with withdrawable parts PM Partition of metal

For switch-disconnector panel with fixed mounted load-break switch PI Partition of insulating material

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 90 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

15.5 Access to compartments


compartment Type of accessibility

Busbar compartment Tool-based

Switching-device compartment Interlock-controlled

Voltage transformer compartment (withdrawable voltage Tool-based


transformer at cable side)

Connection compartment Access from the front side Interlock-controlled and tool-based

Access from the rear side Tool-based

HV-fuses in SDF-panel Interlock-controlled

Low voltage box Tool-based

1)
15.6 Degree of protection
enclosure Standard IP 3XD

optional IP 4X

optional IP 50, (only for non ventilated panels and in combination with additional pressure relief channel to lead the gases
outside the switchgear room)

optional IP 51, (only for non ventilated panels and in combination with additional pressure relief channel to lead the gases
outside the switchgear room)

optional IP 31

optional IP 32

optional IP 41

optional IP 42

partitions Standard IP 2X

1. degree of protection IPX1 or IPX2 not possible


 in combination with pressure relief duct at the top
 with cable connection or bar connection in top box at the busbar
 for Duplex in back-to-back arrangement

15.7 Creepage distances, clearances in air


contactor panel SDF panel circuit breaker panel and others typicals

435 mm panel 800 mm panel 600 mm panel, 600 mm panel, 800 mm panel, 800 and 1000 mm
panel
≤ 630 A 1000 A 1250 A
≥ 2000 A, ≤ 4000 A

phase to phase ≥ 55 mm ≥ 160 mm ≥ 80 mm ≥ 80 mm ≥ 105 mm ≥ 90 mm

phase to earth ≥ 55 mm ≥ 155 mm ≥ 75 mm ≥ 75 mm ≥80 mm ≥ 80 mm


1) 1)
creepage distance ≥ 135 mm ≥ 187 mm ≥ 179 mm ≥ 179 mm ≥ 220 mm ≥ 220 mm

1) creepage distance will be reduced to 195mm when panel or typical is equipped with rear cable box for cable entry from the top or busbar
earthing switch

A main benefit of type tested switchgear in accordance to IEC 62271-200 is saving space in order to minimize volume of switchgear room. NXAIR
switchgear are type tested and fulfill the following requirements with required values as shown in table 8.8, such as:

rated short-duration power frequency withstand voltage, Phase/phase, phase/earth, open contact gap,

rated short-duration power frequency withstand voltage, Disconnecting distance

rated lightning impulse withstand voltage, Phase/phase, phase/earth, open contact gap

rated lightning impulse withstand voltage, Disconnecting distance

Due to this special dimension between phases and to earth are no criteria for quality of isolation capacity. Important criteria are only fulfilling the
required test values.

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 91 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

15.8 Internal arc fault classification


Standard design IAC A FLR up to 40kA 1sec

IAC = internal arc classification


A = 300 mm distance of indicators,
F/L/R accessibility from F = front, L = lateral and R = rear,
40 kA = short circuit current of switchgear,
1 sec = duration of tested arc fault current

(version of pressure relief system see table in chapter 1.3, special duct devices see also in chapter 3,
accessories)
3) 1.)
Optional design Additional with pressure switch system without testing device, duration 0.1 s
1.)
Additional with pressure switch system with testing device, duration 0.1 s
2.)
Additional with optical system, duration 0.1 s

Additional to Standard IEC 62271-200 Confinement of internal arc within a compartment

arc in connection definition of confinement of internal arc:


compartment no burn-through, no re-ignition in adjacent compartments,
no loss of dielectrical properties of adjacent compartments,
and neighbouring panels up to 80% of power frequency withstand voltage after
cleaning
applies up to 17.5kV 31.5 kA/1s

evidence:
documentation and observation of internal arc fault tests

remarks:
on request confirmation will be worked by R&D
busbar shutdown necessary for cleaning
partitions of withdrawable VT with fuses are not pressure resistant

arc in breaker definition of confinement of internal arc:


compartment no burn-through, no re-ignition in adjacent compartments,
no loss of dielectrical properties in busbar compartment and neighbouring panels up
to 80% power frequency withstand voltage after cleaning and removing shutters
upper contact system of affected panel needs to be cleaned,
applies up to 17.5kV 31.5 kA/1s

evidence:
documentation and observation of internal arc fault tests

remarks:
on request confirmation will be worked by R&D
busbar shutdown necessary for cleaning
failure in incoming feeder requires shutdown of upstream breaker feeder

arc in busbar definition of confinement of internal arc:


compartment
no burn-through, no re-ignition in adjacent compartments incl. partition plate in bus
sectionalizer (between breaker and riser panel in busbar compartment),
transverse partition (optionally) in busbar compartment may break,
No partition between top box and busbar compartment,
applies up to 17.5kV 31.5 kA/1s

evidence:
documentation and observation of internal arc fault tests

remarks:
on request confirmation will be worked by R&D

1) when using pressure switch a throw-over relay type (e.g. 7PA22/23) is needed per switchgear section and has to be configured additionally in browser for
LV equipment.
2) When using an optical arc detection system a control unit ARCTEQ is needed per panel. This control unit is included automatically in NXTools+ when
“optical system” is selected and no configuration in the Browser is required.
3) NXAIR always IAC tested with 1 sec, 0.1 sec only with additional arc fault limitation systems possible (switchgear design the same as for 1 sec)

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 92 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

15.9 Type tests in accordance to IEC 62271-1 resp. IEC 62271-200


Following type tests will be carried out mandatory:
chapter Type test
6.2 Test to verify the insulation level of main circuits and low voltage circuits

test values:
Rated lightning impulse withstand voltage depending on rated voltage of switchgear, see also 1.1
rated short duration power frequency withstand voltage depending on rated voltage, see also 1.1
6.4, 6.5 Tests to prove temperature rise of any part of equipment and measurement of the resistance of circuits
test values:
rated current of busbar and feeder, maximum temperature rise values for main parts depending on material of contacts and
materials based on 40°C ambient temperature in OG (oxidizing gases):
silver coated contacts: temperature rise 75°K
bolted connections bare copper: temperature rise 60°K
bolted connections silver-coated copper: temperature rise 75°K
materials used as insulation: temperature rise 50°K for class Y, 65°K for class A and 80°K for class E
surfaces to be touched in normal operation but not to be held continuously in the hand: temperature rise 30°K
surfaces not to be touched in normal operation: temperature rise 40°K
6.6 Tests to prove capability of the main circuits and earthing circuits
test values:
short time withstand current for 1 or 3 s, see also 1.1, multiplied with 2.5 = peak withstand current for 50 Hz applications
short time withstand current for 1 or 3 s, see also 1.1, multiplied with 2.6 = peak withstand current for 60 Hz applications
6.101 Tests to prove the making and breaking capacity of the included devices
test values:
short circuit breaking current, see also 1.1, multiplied with 2.5 = short circuit making current for 50 Hz applications
short circuit breaking current, see also 1.1, multiplied with 2.6 = peak circuit making current for 60 Hz applications
6.102 Tests to prove satisfactory operation of the included switching devices and removable parts
test values:
1000 mechanical cycle for withdrawable part and earthing switch
6.7 Test to verify the protection of persons against access to hazardous parts and the protection of the equipment against solid
foreign objects
test values: IP2X, IP3XD, IP 4X; IP50, IP51. IPX1 and IPX2 depending on version
Following type tests will be carried out generally (in standard required mandatory, where applicable):
6.106 Test to verify internal arc classification
test values: IAC A FLR Isc 1s or 0.1 s, see also 8.7
6.9 Test to verify electromagnetic compatibility (EMC)
Following mandatory type tests where applicable will not be carried out
6.104 Test to verify protection of persons against dangerous not applicable due to partition class PM
electrical effects non-metallic partitions and shutters are used in SDF panel
6.103 Test to verify strength of gas-filled compartments not applicable due air insulation
6.8 Tightness test of gas-filled compartments not applicable due air insulation
Following optional type tests will not be carried out
6.105 Test to verify the protection of the equipment against effects not applicable due to indoor switchgear
due to weather
6.2.9 Test to evaluate the insulation of the equipment by As mentioned in Annex B of standard it is not yet possible to
measurement of partial discharge establish a reliable relationship between the results of partial
discharge measurements and the life expectancy of switchgear.
Due to this testing values and testing procedure are not defined in
standard. Calculation of partial discharge values for switchgear
with different components is not possible.
6.2.8 Artificial pollution tests switchgear is designed and tested for normal service conditions as
defined in IEC 62271-200
6.2.101 Dielectric tests on cable testing circuits testing values and testing procedure are not defined in standard

15.10 Routine tests in accordance to IEC 62271-1 resp. IEC 62271-200


Following routine tests will be carried out mandatory:
7.1 Dielectric test with power frequency voltage of main circuits
test values:
rated short duration power frequency withstand voltage depending on rated voltage, see also 1.1
7.2 Dielectric test of auxiliary circuits
test values: 1 kV, 1 s
7.5 Design and visual checks
7.102 Mechanical operation tests
7.104 Test of auxiliary devices, verification of the correct wiring
Following routine tests are subject of agreement between manufacturer and user:
7.3 Measurement of the resistance of the main circuit
7.4 Tightness test not applicable due air insulation
7.101 Partial discharge measurement As mentioned in Annex B of standard it is not yet possible to
establish a reliable relationship between the results of partial
discharge measurements and the life expectancy of switchgear.
Due to this testing values and testing procedure are not defined in
standard. Calculation of partial discharge values for switchgear with
different components is not possible.
7.103 Pressure tests of gas-filled components not applicable due air insulation

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 93 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16 NXAIR – permissible current values

16.1 NXAIR, ≤ 12 kV, 50 Hz, 25/31.5 kA, ≤ 2500 A, permissible current values
Rated fre- Short busbar width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- temperature
ency current tion (A /°C)
(A / °C)

degree panel panel cb (A /°C) bus- (A /°C)


of pro- bar
tection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55
1)
≤ 12 50 ≤ 25 without 600 all closed 630 800 680 655 630 605 575 545 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235


1)
600 all closed 1000 1250 1080 1045 1005 965 925 880 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235


1)
800 all closed 1250 1600 1330 1290 1250 1205 1165 1115 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235

800 IP3XD, nat. vent 2000 2500 2210 2145 2075 2005 1930 1855 2000 2130 2065 2000 1930 1860 1790
IP31,
IP32 2210 2145 2075 2005 1930 1855 2500 2660 2580 2500 2415 2325 2235

800 IP4X, nat. vent 2000 2500 2100 2040 1970 1905 1835 1760 2000 2130 2065 2000 1930 1860 1790
IP41,
IP42 2100 2040 1970 1905 1835 1760 2500 2660 2580 2500 2415 2325 2235

1000 IP3XD, nat. vent 2500 2500 2765 2680 2595 2510 2415 2270 2500 2660 2580 2500 2415 2325 2235
IP31,
IP32

1000 IP4X, nat. vent 2500 2500 2625 2545 2465 2380 2295 2155 2500 2660 2580 2500 2415 2325 2235
IP41,
IP42
1)
31.5 without 600 all closed 630 800 680 655 630 605 575 545 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235


1)
600 all closed 1000 1250 1125 1090 1050 1010 965 920 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235


1)
800 all closed 1250 1600 1380 1330 1285 1235 1180 1125 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235

800 IP3XD, nat. vent 2000 2500 2210 2145 2075 2005 1930 1855 2000 2130 2065 2000 1930 1860 1790
IP31,
IP32 2210 2145 2075 2005 1930 1855 2500 2660 2580 2500 2415 2325 2235

800 IP4X, nat. vent 2000 2500 2100 2040 1970 1905 1835 1760 2000 2130 2065 2000 1930 1860 1790
IP41,
IP42 2100 2040 1970 1905 1835 1760 2500 2660 2580 2500 2415 2325 2235

1000 IP3XD, nat. vent. 2500 2500 2765 2680 2595 2510 2415 2270 2500 2660 2580 2500 2415 2325 2235
IP31,
IP32

1000 IP4X, nat. vent. 2500 2500 2625 2545 2465 2380 2295 2155 2500 2660 2580 2500 2415 2325 2235
IP41,
IP42

1) All = IP3XD, IP31, IP32, IP4X, IP41, IP42, IP50, IP51

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 94 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.1 NXAIR, ≤ 12 kV, 50 Hz, 25/31.5 kA, ≤ 2500 A, permissible current values
Rated fre- Short busbar width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- temperature
ency current tion (A /°C)
(A / °C)

degree panel panel cb (A /°C) bus- (A /°C)


of pro- bar
tection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55
1)
≤ 12 50 ≤ 25 with 600 all closed 630 800 680 655 630 605 575 545 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235


1)
600 all closed 1000 1250 1060 1025 985 945 905 865 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235


1)
800 all closed 1250 1600 1330 1290 1250 1205 1165 1115 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235

800 IP3XD, nat. vent 2000 2500 2210 2145 2075 2005 1930 1855 2000 2130 2065 2000 1930 1860 1790
IP31,
IP32 2210 2145 2075 2005 1930 1855 2500 2660 2580 2500 2415 2325 2235

800 IP4X, nat. vent 2000 2500 2100 2040 1970 1905 1835 1760 2000 2130 2065 2000 1930 1860 1790
IP41,
IP42 2100 2040 1970 1905 1835 1760 2500 2660 2580 2500 2415 2325 2235

1000 IP3XD, nat. vent. 2500 2500 2765 2680 2595 2510 2415 2270 2500 2660 2580 2500 2415 2325 2235
IP31,
IP32

1000 IP4X, nat. vent. 2500 2500 2625 2545 2465 2380 2295 2155 2500 2660 2580 2500 2415 2325 2235
IP41,
IP42
1)
31.5 with 600 all closed 630 800 680 655 630 605 575 545 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235


1)
600 all closed 1000 1250 1105 1065 1030 985 945 900 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235


1)
800 all closed 1250 1600 1350 1305 1260 1210 1155 1105 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235

800 IP3XD, nat. vent 2000 2500 2210 2145 2075 2005 1930 1855 2000 2130 2065 2000 1930 1860 1790
IP31,
IP32 2210 2145 2075 2005 1930 1855 2500 2660 2580 2500 2415 2325 2235

800 IP4X, nat. vent 2000 2500 2100 2040 1970 1905 1835 1760 2000 2130 2065 2000 1930 1860 1790
IP41,
IP42 2100 2040 1970 1905 1835 1760 2500 2660 2580 2500 2415 2325 2235

1000 IP3XD, nat. vent. 2500 2500 2765 2680 2595 2510 2415 2270 2500 2660 2580 2500 2415 2325 2235
IP31,
IP32

1000 IP4X, nat. vent. 2500 2500 2625 2545 2465 2380 2295 2155 2500 2660 2580 2500 2415 2325 2235
IP41,
IP42

1) All = IP3XD, IP31, IP32, IP4X, IP41, IP42, IP50, IP51

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 95 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.2 NXAIR, ≤ 12 kV, 60 Hz, 25 / 31.5 kA, ≤ 2500 A, permissible current values
Rated fre- Short busbar width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- temperature
ency current tion (A /°C)
(A / °C)

degree panel panel cb (A /°C) bus- (A /°C)


of pro- version bar
tection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55
1)
≤ 12 60 ≤ 25 without 600 all closed 630 800 680 655 630 605 575 545 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235


1)
600 all closed 1000 1250 1080 1045 1005 965 925 880 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235


1)
800 all closed 1250 1600 1295 1260 1220 1175 1135 1085 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235

800 IP3XD, nat. vent 2000 2500 2150 2085 2015 1950 1880 1805 2000 2070 2010 1945 1880 1810 1740
IP31,
IP32 2150 2085 2015 1950 1880 1805 2500 2660 2580 2500 2415 2325 2235

800 IP4X, nat. vent 2000 2500 2045 1985 1915 1850 1785 1715 2000 2070 2010 1945 1880 1810 1740
IP41,
IP42 2045 1985 1915 1850 1785 1715 2500 2660 2580 2500 2415 2325 2235

1000 IP3XD, natural 2500 2500 2685 2610 2525 2440 2350 2260 2500 2660 2580 2500 2415 2325 2235
IP31, ventilated
IP32

1000 IP4X, natural 2500 2500 2555 2480 2395 2315 2230 2150 2500 2660 2580 2500 2415 2325 2235
IP41, ventilated
IP42
1)
31.5 without 600 all closed 630 800 680 655 630 605 575 545 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235


1)
600 all closed 1000 1250 1110 1075 1035 995 955 910 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235


1)
800 all closed 1250 1600 1365 1320 1270 1220 1170 1115 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235

800 IP3XD, nat. vent 2000 2500 2150 2085 2015 1950 1880 1805 2000 2070 2010 1945 1880 1810 1740
IP31,
IP32 2150 2085 2015 1950 1880 1805 2500 2660 2580 2500 2415 2325 2235

800 IP4X, nat. vent 2000 2500 2045 1985 1915 1850 1785 1715 2000 2070 2010 1945 1880 1810 1740
IP41,
IP42 2045 1985 1915 1850 1785 1715 2500 2660 2580 2500 2415 2325 2235

1000 IP3XD, natural 2500 2500 2685 2610 2525 2440 2350 2260 2500 2660 2580 2500 2415 2325 2235
IP31, ventilated
IP32

1000 IP4X, natural 2500 2500 2555 2480 2395 2315 2230 2150 2500 2660 2580 2500 2415 2325 2235
IP41, ventilated
IP42

1) All = IP3XD, IP31, IP32, IP4X, IP41, IP42, IP50, IP51

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 96 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.2 NXAIR, ≤ 12 kV, 60 Hz, 25 / 31.5 kA, ≤ 2500 A, permissible current values
Rated fre- Short busbar width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- temperature
ency current tion (A /°C)
(A / °C)

degree panel panel cb (A /°C) bus- (A /°C)


of pro- version bar
tection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55
1)
≤ 12 60 ≤ 25 with 600 all closed 630 800 680 655 630 605 575 545 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235


1)
600 all closed 1000 1250 1060 1025 985 945 905 865 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235


1)
800 all closed 1250 1600 1295 1260 1220 1175 1135 1085 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235

800 IP3XD, nat. vent 2000 2500 2150 2085 2015 1950 1880 1805 2000 2070 2010 1945 1880 1810 1740
IP31,
IP32 2150 2085 2015 1950 1880 1805 2500 2660 2580 2500 2415 2325 2235

800 IP4X, nat. vent 2000 2500 2045 1985 1915 1850 1785 1715 2000 2070 2010 1945 1880 1810 1740
IP41,
IP42 2045 1985 1915 1850 1785 1715 2500 2660 2580 2500 2415 2325 2235

1000 IP3XD, natural 2500 2500 2685 2610 2525 2440 2350 2260 2500 2660 2580 2500 2415 2325 2235
IP31, ventilated
IP32

1000 IP4X, natural 2500 2500 2555 2480 2395 2315 2230 2150 2500 2660 2580 2500 2415 2325 2235
IP41, ventilated
IP42
1)
31.5 with 600 all closed 630 800 680 655 630 605 575 545 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235


1)
600 all closed 1000 1250 1090 1055 1015 975 935 890 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235


1)
800 all closed 1250 1600 1335 1290 1245 1195 1145 1090 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235

800 IP3XD, nat. vent 2000 2500 2150 2085 2015 1950 1880 1805 2000 2070 2010 1945 1880 1810 1740
IP31,
IP32 2150 2085 2015 1950 1880 1805 2500 2660 2580 2500 2415 2325 2235

800 IP4X, nat. vent 2000 2500 2045 1985 1915 1850 1785 1715 2000 2070 2010 1945 1880 1810 1740
IP41,
IP42 2045 1985 1915 1850 1785 1715 2500 2660 2580 2500 2415 2325 2235

1000 IP3XD, natural 2500 2500 2685 2610 2525 2440 2350 2260 2500 2660 2580 2500 2415 2325 2235
IP31, ventilated
IP32

1000 IP4X, natural 2500 2500 2555 2480 2395 2315 2230 2150 2500 2660 2580 2500 2415 2325 2235
IP41, ventilated
IP42

1) All = IP3XD, IP31, IP32, IP4X, IP41, IP42, IP50, IP51

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 97 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.3 NXAIR, 17.5 kV, 50 Hz, 25 / 31.5 kA, ≤ 2500 A, permissible current values
Rated fre- Short busbar width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- temperature
ency current tion (A /°C)
(A / °C)

degree panel panel cb (A /°C) bus- (A /°C)


of pro- version bar
tection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55
1)
17.5 50 ≤ 25 without 600 all closed 630 800 680 655 630 605 575 545 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235


1)
600 all closed 1000 1250 1105 1070 1030 990 945 900 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235


1)
800 all closed 1250 1600 1390 1340 1290 1240 1190 1135 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235

800 IP3XD, nat. vent 2000 2500 2170 2105 2035 1965 1895 1820 2000 2130 2065 2000 1930 1860 1790
IP31,
IP32 2170 2105 2035 1965 1895 1820 2500 2660 2580 2500 2415 2325 2235

800 IP4X, nat. vent 2000 2500 2060 1995 1930 1865 1800 1725 2000 2130 2065 2000 1930 1860 1790
IP41,
IP42 2060 1995 1930 1865 1800 1725 2500 2660 2580 2500 2415 2325 2235

1000 IP3XD, natural 2500 2500 2710 2630 2545 2460 2370 2280 2500 2660 2580 2500 2415 2325 2235
IP31, ventilated
IP32

1000 IP4X, natural 2500 2500 2570 2495 2415 2335 2250 2165 2500 2660 2580 2500 2415 2325 2235
IP41, ventilated
IP42
1)
31.5 without 600 all closed 630 800 680 655 630 605 575 545 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235


1)
600 all closed 1000 1250 1105 1065 1025 980 935 885 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235


1)
800 all closed 1250 1250 1330 1290 1250 1205 1160 1115 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235

800 IP3XD, nat. vent 2000 2500 2170 2105 2035 1965 1895 1820 2000 2130 2065 2000 1930 1860 1790
IP31,
IP32 2170 2105 2035 1965 1895 1820 2500 2660 2580 2500 2415 2325 2235

800 IP4X, nat. vent 2000 2500 2060 1995 1930 1865 1800 1725 2000 2130 2065 2000 1930 1860 1790
IP41,
IP42 2060 1995 1930 1865 1800 1725 2500 2660 2580 2500 2415 2325 2235

1000 IP3XD, natural 2500 2500 2710 2630 2545 2460 2370 2280 2500 2660 2580 2500 2415 2325 2235
IP31, ventilated
IP32

1000 IP4X, natural 2500 2500 2570 2495 2415 2335 2250 2165 2500 2660 2580 2500 2415 2325 2235
IP41, ventilated
IP42

1) All = IP3XD, IP31, IP32, IP4X, IP41, IP42, IP50, IP51

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 98 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.3 NXAIR, 17.5 kV, 50 Hz, 25 / 31.5 kA, ≤ 2500 A, permissible current values
Rated fre- Short busbar width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- temperature
ency current tion (A /°C)
(A / °C)

degree panel panel cb (A /°C) bus- (A /°C)


of pro- version bar
tection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55
1)
17,5 50 ≤ 25 with 600 all closed 630 800 680 655 630 605 575 545 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235


1)
600 all closed 1000 1250 1105 1070 1030 990 945 900 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235


1)
800 all closed 1250 1600 1390 1340 1290 1240 1190 1135 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235

800 IP3XD, nat. vent 2000 2500 2170 2105 2035 1965 1895 1820 2000 2130 2065 2000 1930 1860 1790
IP31,
IP32 2170 2105 2035 1965 1895 1820 2500 2660 2580 2500 2415 2325 2235

800 IP4X, nat. vent 2000 2500 2060 1995 1930 1865 1800 1725 2000 2130 2065 2000 1930 1860 1790
IP41,
IP42 2060 1995 1930 1865 1800 1725 2500 2660 2580 2500 2415 2325 2235

1000 IP3XD, natural 2500 2500 2710 2630 2545 2460 2370 2280 2500 2660 2580 2500 2415 2325 2235
IP31, ventilated
IP32

1000 IP4X, natural 2500 2500 2570 2495 2415 2335 2250 2165 2500 2660 2580 2500 2415 2325 2235
IP41, ventilated
IP42
1)
31.5 with 600 all closed 630 800 680 655 630 605 575 545 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235


1)
600 all closed 1000 1250 1105 1065 1025 980 935 885 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235


1)
800 all closed 1250 1250 1330 1290 1250 1205 1160 1115 1250 1330 1290 1250 1210 1165 1120

2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235

800 IP3XD, nat. vent 2000 2500 2170 2105 2035 1965 1895 1820 2000 2130 2065 2000 1930 1860 1790
IP31,
IP32 2170 2105 2035 1965 1895 1820 2500 2660 2580 2500 2415 2325 2235

800 IP4X, nat. vent 2000 2500 2060 1995 1930 1865 1800 1725 2000 2130 2065 2000 1930 1860 1790
IP41,
IP42 2060 1995 1930 1865 1800 1725 2500 2660 2580 2500 2415 2325 2235

1000 IP3XD, natural 2500 2500 2710 2630 2545 2460 2370 2280 2500 2660 2580 2500 2415 2325 2235
IP31, ventilated
IP32

1000 IP4X, natural 2500 2500 2570 2495 2415 2335 2250 2165 2500 2660 2580 2500 2415 2325 2235
IP41, ventilated
IP42

1) All = IP3XD, IP31, IP32, IP4X, IP41, IP42, IP50, IP51

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 99 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.4 NXAIR, 17.5 kV, 60 Hz, 25 / 31.5 kA, ≤ 2500 A, permissible current values
Rated fre- Short busbar width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- temperature
ency current tion (A /°C)
(A / °C)

degree panel panel cb (A /°C) bus- (A /°C)


of pro- version bar
tection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55
1)
17.5 60 ≤ 25 without 600 all closed 630 800 680 655 630 605 575 545 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235


1)
600 all closed 1000 1250 1090 1050 1015 975 935 890 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235


1)
800 all closed 1250 1600 1315 1270 1220 1175 1125 1070 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235

800 IP3XD, nat. vent 2000 2500 2110 2045 1975 1910 1840 1770 2000 2070 2010 1945 1880 1810 1740
IP31,
IP32 2110 2045 1975 1910 1840 1770 2500 2660 2580 2500 2415 2325 2235

800 IP4X, nat. vent 2000 2500 2000 1940 1875 1810 1750 1675 2000 2070 2010 1945 1880 1810 1740
IP41,
IP42 2000 1940 1875 1810 1750 1675 2500 2660 2580 2500 2415 2325 2235

1000 IP3XD, natural 2500 2500 2635 2555 2475 2390 2305 2215 2500 2660 2580 2500 2415 2325 2235
IP31, ventilated
IP32

1000 IP4X, natural 2500 2500 2500 2425 2350 2270 2185 2100 2500 2660 2580 2500 2415 2325 2235
IP41, ventilated
IP42
1)
31.5 without 600 all closed 630 800 680 655 630 605 575 545 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235


1)
600 all closed 1000 1250 1075 1040 1000 955 910 860 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235


1)
800 all closed 1250 1250 1295 1260 1220 1175 1130 1085 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235

800 IP3XD, nat. vent 2000 2500 2110 2045 1975 1910 1840 1770 2000 2070 2010 1945 1880 1810 1740
IP31,
IP32 2110 2045 1975 1910 1840 1770 2500 2660 2580 2500 2415 2325 2235

800 IP4X, nat. vent 2000 2500 2000 1940 1875 1810 1750 1675 2000 2070 2010 1945 1880 1810 1740
IP41,
IP42 2000 1940 1875 1810 1750 1675 2500 2660 2580 2500 2415 2325 2235

1000 IP3XD, natural 2500 2500 2635 2555 2475 2390 2305 2215 2500 2660 2580 2500 2415 2325 2235
IP31, ventilated
IP32

1000 IP4X, natural 2500 2500 2500 2425 2350 2270 2185 2100 2500 2660 2580 2500 2415 2325 2235
IP41, ventilated
IP42

1) All = IP3XD, IP31, IP32, IP4X, IP41, IP42, IP50, IP51

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 100 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.4 NXAIR, 17.5 kV, 60 Hz, 25 / 31.5 kA, ≤ 2500 A, permissible current values
Rated fre- Short busbar width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- temperature
ency current tion (A /°C)
(A / °C)

degree panel panel cb (A /°C) Bus- (A /°C)


of pro- version bar
tection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55
1)
17.5 60 ≤ 25 with 600 all closed 630 800 680 655 630 605 575 545 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235


1)
600 all closed 1000 1250 1090 1050 1015 975 935 890 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235


1)
800 all closed 1250 1600 1315 1270 1220 1175 1125 1070 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235

800 IP3XD, nat. vent 2000 2500 2110 2045 1975 1910 1840 1770 2000 2070 2010 1945 1880 1810 1740
IP31,
IP32 2110 2045 1975 1910 1840 1770 2500 2660 2580 2500 2415 2325 2235

800 IP4X, nat. vent 2000 2500 2000 1940 1875 1810 1750 1675 2000 2070 2010 1945 1880 1810 1740
IP41,
IP42 2000 1940 1875 1810 1750 1675 2500 2660 2580 2500 2415 2325 2235

1000 IP3XD, natural 2500 2500 2635 2555 2475 2390 2305 2215 2500 2660 2580 2500 2415 2325 2235
IP31, ventilated
IP32

1000 IP4X, natural 2500 2500 2500 2425 2350 2270 2185 2100 2500 2660 2580 2500 2415 2325 2235
IP41, ventilated
IP42
1)
31.5 with 600 all closed 630 800 680 655 630 605 575 545 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235


1)
600 all closed 1000 1250 1075 1040 1000 955 910 860 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235


1)
800 all closed 1250 1250 1295 1260 1220 1175 1130 1085 1250 1300 1260 1220 1180 1135 1090

2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235

800 IP3XD, nat. vent 2000 2500 2110 2045 1975 1910 1840 1770 2000 2070 2010 1945 1880 1810 1740
IP31,
IP32 2110 2045 1975 1910 1840 1770 2500 2660 2580 2500 2415 2325 2235

800 IP4X, nat. vent 2000 2500 2000 1940 1875 1810 1750 1675 2000 2070 2010 1945 1880 1810 1740
IP41,
IP42 2000 1940 1875 1810 1750 1675 2500 2660 2580 2500 2415 2325 2235

1000 IP3XD, natural 2500 2500 2635 2555 2475 2390 2305 2215 2500 2660 2580 2500 2415 2325 2235
IP31, ventilated
IP32

1000 IP4X, natural 2500 2500 2500 2425 2350 2270 2185 2100 2500 2660 2580 2500 2415 2325 2235
IP41, ventilated
IP42

1) All = IP3XD, IP31, IP32, IP4X, IP41, IP42, IP50, IP51

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 101 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.5 NXAIR, ≤ 12 kV, 50 Hz, 40 kA, ≤ 4000 A or 25/31,5 kA with 3150/4000 A busbar, permissible current
values
Rated fre- Short busbar width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- temperature
ency current tion (A / °C) (A /°C)

Degree of panel version panel cb (A /°C) busbar (A /°C)


protection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55
1)
≤ 12 50 25 with / 600 all closed 630 800 680 655 630 605 575 545 3150 4470 4335 4195 4050 3905 3750
without
4000 4470 4335 4195 4050 3905 3750
1)
600 all closed 1000 1250 1080 1045 1005 965 925 880 3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750


1)
800 all closed 1250 1600 1330 1290 1250 1205 1165 1115 3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750

800 IP3XD, nat. vent. 2000 2500 2190 2125 2060 1990 1920 1845 3150 4470 4335 4195 4050 3905 3750
IP31, IP32
4000 4470 4335 4195 4050 3905 3750

800 IP4X, IP41,nat. vent. 2000 2500 2085 2020 1960 1890 1825 1750 3150 4470 4335 4195 4050 3905 3750
IP42
4000 4470 4335 4195 4050 3905 3750

1000 IP3XD, nat. vent. 2500 2500 2765 2680 2595 2510 2415 2325 3150 4470 4335 4195 4050 3905 3750
IP31, IP32
4000 4470 4335 4195 4050 3905 3750

3150 3150 3440 3340 3230 3120 3005 2890 3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750

1000 IP3XD, forc. Vent.2) 4000 4000 4000 4000 4000 4000 3905 3750 4000 4470 4335 4195 4050 3905 3750
IP31, IP32

1000 IP4X, IP41,nat. vent. 2500 2500 2625 2545 2465 2380 2295 2210 3150 4470 4335 4195 4050 3905 3750
IP42
4000 4470 4335 4195 4050 3905 3750

3150 3150 3270 3170 3070 2965 2855 2745 3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750


2)
1000 IP4X, IP41,forc. Vent. 4000 4000 4000 4000 3985 3850 3710 3565 4000 4470 4335 4195 4050 3905 3750
IP42
1)
31.5 with / 600 all closed 630 800 680 655 630 605 575 545 3150 4470 4335 4195 4050 3905 3750
without
4000 4470 4335 4195 4050 3905 3750
1)
600 all closed 1000 1250 1125 1090 1050 1010 965 920 3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750


1)
800 all closed 1250 1600 1380 1330 1285 1235 1180 1125 3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750

800 IP3XD, nat. vent. 2000 2500 2190 2125 2060 1990 1920 1845 3150 4470 4335 4195 4050 3905 3750
IP31, IP32
4000 4470 4335 4195 4050 3905 3750

800 IP4X, IP41,nat. vent. 2000 2500 2085 2020 1960 1890 1825 1750 3150 4470 4335 4195 4050 3905 3750
IP42
4000 4470 4335 4195 4050 3905 3750

1000 IP3XD, nat. vent. 2500 2500 2765 2680 2595 2510 2415 2325 3150 4470 4335 4195 4050 3905 3750
IP31, IP32
4000 4470 4335 4195 4050 3905 3750

3150 3150 3440 3340 3230 3120 3005 2890 3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750


2)
1000 IP3XD, forc. Vent. 4000 4000 4000 4000 4000 4000 3905 3750 4000 4470 4335 4195 4050 3905 3750
IP31, IP32

1000 IP4X, IP41,nat. vent. 2500 2500 2625 2545 2465 2380 2295 2210 3150 4470 4335 4195 4050 3905 3750
IP42
4000 4470 4335 4195 4050 3905 3750

3150 3150 3270 3170 3070 2965 2855 2745 3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750

1000 IP4X, IP41,forc. Vent.2) 4000 4000 4000 4000 3985 3850 3710 3565 4000 4470 4335 4195 4050 3905 3750
IP42

1) All = IP3XD, IP31, IP32, IP4X, IP41, IP42, IP50, IP51 for busbar rating up to 2500 A also possible
2) standard version current relays controlled, optionally current relays controlled and redundant version

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 102 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.5 NXAIR, ≤ 12 kV, 50 Hz, 40 kA, ≤ 4000 A or 25/31,5 kA with 3150/4000 A busbar, permissible current
values
Rated fre- Short busbar width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- temperature
ency current tion (A / °C) (A /°C)

Degree of panel version panel cb (A /°C) busbar (A /°C)


protection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55
1)
≤ 12 50 40 with / 800 all closed 1250 1250 1340 1300 1260 1220 1175 1125 1250 1340 1300 1260 1220 1175 1125
without
2500 2730 2650 2565 2480 2390 2295

3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750

800 IP3XD, nat. vent. 2000 2500 2165 2100 2035 1965 1895 1820 2500 2730 2650 2565 2480 2390 2295
IP31, IP32
3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750

800 IP4X, IP41,nat. vent. 2000 2500 2055 1995 1930 1865 1800 1725 2500 2730 2650 2565 2480 2390 2295
IP42
3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750

1000 IP3XD, nat. vent. 2500 2500 2730 2650 2565 2480 2390 2295 2500 2730 2650 2565 2480 2390 2295
IP31, IP32
3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750

1000 IP3XD, nat. vent. 3150 3150 3440 3340 3230 3120 3005 2890 3150 4470 4335 4195 4050 3905 3750
IP31, IP32
4000 4470 4335 4195 4050 3905 3750
2)
1000 IP3XD, forc. vent. 4000 4000 4000 4000 4000 4000 3905 3750 4000 4470 4335 4195 4050 3905 3750
IP31, IP32

1000 IP4X, IP41,natural 2500 2500 2590 2515 2435 2355 2270 2180 2500 2730 2650 2565 2480 2390 2295
IP42 ventilated
3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750

1000 IP4X, IP41,natural 3150 3150 3270 3170 3070 2965 2855 2745 3150 4470 4335 4195 4050 3905 3750
IP42 ventilated
4000 4470 4335 4195 4050 3905 3750
2)
1000 IP4X, IP41,forc. vent. 4000 4000 4000 4000 3985 3850 3710 3565 4000 4470 4335 4195 4050 3905 3750
IP42

1) All = IP3XD, IP31, IP32, IP4X, IP41, IP42, IP50, IP51 for busbar rating up to 2500 A also possible
2) standard version current relays controlled, optional current relays controlled and redundant version

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 103 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.6 NXAIR, ≤ 12 kV, 60 Hz, 40 kA, ≤ 4000 A or 25/31,5 kA with 3150/4000 A busbar, permissible current
values
Rated fre- Short busbar width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- temperature
ency current tion (A / °C) (A /°C)

Degree of panel version panel cb (A /°C) busbar (A /°C)


protection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55
1)
≤12 60 25 with / 600 all closed 630 800 680 655 630 605 575 545 3150 4335 4200 4065 3925 3785 3635
without
4000 4335 4200 4065 3925 3785 3635
1)
600 all closed 1000 1250 1080 1045 1005 965 925 880 3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635


1)
800 all closed 1250 1600 1295 1260 1220 1175 1135 1085 3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635

800 IP3XD, nat. vent. 2000 2500 2130 2070 2005 1935 1865 1795 3150 4335 4200 4065 3925 3785 3635
IP31, IP32
4000 4335 4200 4065 3925 3785 3635

800 IP4X, IP41,nat. vent. 2000 2500 2025 1965 1905 1840 1775 1705 3150 4335 4200 4065 3925 3785 3635
IP42
4000 4335 4200 4065 3925 3785 3635

1000 IP3XD, nat. vent. 2500 2500 2685 2610 2525 2440 2350 2260 3150 4335 4200 4065 3925 3785 3635
IP31, IP32
4000 4335 4200 4065 3925 3785 3635

3150 3150 3335 3235 3130 3025 2910 2800 3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635


2
1000 IP3XD, forc. vent. 4000 4000 4000 4000 4000 3930 3785 3635 4000 4335 4200 4065 3925 3785 3635
IP31, IP32

1000 IP4X, IP41,nat. vent. 2500 2500 2555 2480 2395 2315 2230 2150 3150 4335 4200 4065 3925 3785 3635
IP42
4000 4335 4200 4065 3925 3785 3635

3150 3150 3165 3075 2970 2870 2770 2655 3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635

1000 IP4X, IP41,forc. vent.2 4000 4000 4000 4000 3875 3735 3595 3450 4000 4335 4200 4065 3925 3785 3635
IP42
1)
31.5 with / 600 all Closed 630 800 680 655 630 605 575 545 3150 4335 4200 4065 3925 3785 3635
without
4000 4335 4200 4065 3925 3785 3635
1)
600 all closed 1000 1250 1110 1075 1035 995 955 910 3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635


1)
800 all closed 1250 1600 1365 1320 1270 1220 1170 1115 3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635

800 IP3XD, nat. vent. 2000 2500 2130 2070 2005 1935 1865 1795 3150 4335 4200 4065 3925 3785 3635
IP31, IP32
4000 4335 4200 4065 3925 3785 3635

800 IP4X, IP41,nat. vent. 2000 2500 2025 1965 1905 1840 1775 1705 3150 4335 4200 4065 3925 3785 3635
IP42
4000 4335 4200 4065 3925 3785 3635

1000 IP3XD, nat. vent. 2500 2500 2685 2610 2525 2440 2350 2260 3150 4335 4200 4065 3925 3785 3635
IP31, IP32
4000 4335 4200 4065 3925 3785 3635

3150 3150 3335 3235 3130 3025 2910 2800 3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635


2)
1000 IP3XD, forc. vent. 4000 4000 4000 4000 4000 3930 3785 3635 4000 4335 4200 4065 3925 3785 3635
IP31, IP32

1000 IP4X, IP41,nat. vent. 2500 2500 2555 2480 2395 2315 2230 2150 3150 4335 4200 4065 3925 3785 3635
IP42
4000 4335 4200 4065 3925 3785 3635

3150 3150 3165 3075 2970 2870 2770 2655 3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635


2)
1000 IP4X, IP41,forc. vent. 4000 4000 4000 4000 3875 3735 3595 3450 4000 4335 4200 4065 3925 3785 3635
IP42

1) All = IP3XD, IP31, IP32, IP4X, IP41, IP42, IP50, IP51 for busbar rating up to 2500 A also possible
2) standard version current relays controlled, optional current relays controlled and redundant version

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 104 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.6 NXAIR, ≤ 12 kV, 60 Hz, 40 kA, ≤ 4000 A or 25/31,5 kA with 3150/4000 A busbar, permissible current
values
Rated fre- Short busbar width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- temperature
ency current tion (A / °C) (A /°C)

Degree of panel version panel cb (A /°C) busbar (A /°C)


protection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55
1)
≤12 60 40 with / 800 all closed 1250 1250 1295 1260 1220 1180 1135 1090 1250 1295 1260 1220 1180 1135 1090
without
2500 2645 2570 2485 2405 2315 2225

3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635

800 IP3XD, nat. vent. 2000 2500 2100 2035 1970 1905 1835 1765 2500 2645 2570 2485 2405 2315 2225
IP31, IP32
3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635

800 IP4X, IP41,nat. vent. 2000 2500 1995 1930 1870 1805 1740 1675 2500 2645 2570 2485 2405 2315 2225
IP42
3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635

1000 IP3XD, nat. vent. 2500 2500 2645 2570 2485 2405 2315 2225 2500 2645 2570 2485 2405 2315 2225
IP31, IP32
3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635

1000 IP3XD, nat. vent. 3150 3150 3335 3235 3130 3025 2910 2800 3150 4335 4200 4065 3925 3785 3635
IP31, IP32
4000 4335 4200 4065 3925 3785 3635
2)
1000 IP3XD, forc. vent. 4000 4000 4000 4000 4000 3930 3785 3635 4000 4335 4200 4065 3925 3785 3635
IP31, IP32

1000 IP4X, IP41,natural 2500 2500 2510 2440 2360 2280 2195 2110 2500 2645 2570 2485 2405 2315 2225
IP42 ventilated
3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635

1000 IP4X, IP41,natural 3150 3150 3165 3075 2970 2870 2770 2655 3150 4335 4200 4065 3925 3785 3635
IP42 ventilated
4000 4335 4200 4065 3925 3785 3635
2)
1000 IP4X, IP41,forc. vent. 4000 4000 4000 4000 3875 3735 3595 3450 4000 4335 4200 4065 3925 3785 3635
IP42

1) All = IP3XD, IP31, IP32, IP4X, IP41, IP42, IP50, IP51 for busbar rating up to 2500 A also possible
2) standard version current relays controlled, optional current relays controlled and redundant version

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 105 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.7 NXAIR, 17.5 kV, 50 Hz, 40 kA, ≤ 4000 A or 25/31,5 kA with 3150/4000 A busbar, permissible current
values
Rated fre- Short busbar width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- temperature (A / °C) (A /°C)
ency current tion

Degree of Panel version panel cb (A /°C) busbar (A /°C)


protection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55
1)
17.5 50 25 with / 600 all closed 630 800 680 655 630 605 575 545 3150 4470 4335 4195 4050 3905 3750
without
4000 4470 4335 4195 4050 3905 3750
1)
600 all closed 1000 1250 1105 1070 1030 990 945 900 3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750


1)
800 all closed 1250 1600 1390 1340 1290 1240 1190 1135 3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750

800 IP3XD, nat. vent. 2000 2500 2170 2105 2040 1970 1900 1825 3150 4470 4335 4195 4050 3905 3750
IP31, IP32
4000 4470 4335 4195 4050 3905 3750

800 IP4X, IP41,nat. vent. 2000 2500 2060 2000 1940 1870 1805 1735 3150 4470 4335 4195 4050 3905 3750
IP42
4000 4470 4335 4195 4050 3905 3750

1000 IP3XD, nat. vent. 2500 2500 2710 2630 2545 2460 2370 2280 3150 4470 4335 4195 4050 3905 3750
IP31, IP32
4000 4470 4335 4195 4050 3905 3750

3150 3150 3375 3275 3170 3060 2950 2835 3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750


2)
1000 IP3XD, forc. vent. 4000 4000 4000 4000 4000 3975 3830 3680 4000
IP31, IP32 4470 4335 4195 4050 3905 3750

1000 IP4X, IP41,nat. vent. 2500 2500 2570 2495 2415 2335 2250 2165 3150 4470 4335 4195 4050 3905 3750
IP42
4000 4470 4335 4195 4050 3905 3750

3150 3150 3205 3110 3010 2905 2800 2690 3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750

1000 IP4X, IP41,forc. vent.2) 4000 4000 4000 4000 3905 3775 3635 3495 4000 4470 4335 4195 4050 3905 3750
IP42
1)
31.5 with / 600 all closed 630 800 680 655 630 605 575 545 3150 4470 4335 4195 4050 3905 3750
without
4000 4470 4335 4195 4050 3905 3750
1)
600 all closed 1000 1250 1105 1065 1025 980 935 885 3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750


1)
800 all closed 1250 1250 1330 1290 1250 1205 1160 1115 3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750

800 IP3XD, nat. vent. 2000 2500 2170 2105 2040 1970 1900 1825 3150 4470 4335 4195 4050 3905 3750
IP31, IP32
4000 4470 4335 4195 4050 3905 3750

800 IP4X, IP41,nat. vent. 2000 2500 2060 2000 1940 1870 1805 1735 3150 4470 4335 4195 4050 3905 3750
IP42
4000 4470 4335 4195 4050 3905 3750

1000 IP3XD, nat. vent. 2500 2500 2710 2630 2545 2460 2370 2280 3150 4470 4335 4195 4050 3905 3750
IP31, IP32
4000 4470 4335 4195 4050 3905 3750

3150 3150 3375 3275 3170 3060 2950 2835 3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750


2)
1000 IP3XD, forc. vent. 4000 4000 4000 4000 4000 3975 3830 3680 4000 4470 4335 4195 4050 3905 3750
IP31, IP32

1000 IP4X, IP41,nat. vent. 2500 2500 2570 2495 2415 2335 2250 2165 3150 4470 4335 4195 4050 3905 3750
IP42
4000 4470 4335 4195 4050 3905 3750

3150 3150 3205 3110 3010 2905 2800 2690 3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750


2)
1000 IP4X, IP41,forc. vent. 4000 4000 4000 4000 3905 3775 3635 3495 4000 4470 4335 4195 4050 3905 3750
IP42

1) All = IP3XD, IP31, IP32, IP4X, IP41, IP42, IP50, IP51 for busbar rating up to 2500 A also possible
2) standard version current relays controlled, optional current relays controlled and redundant version

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 106 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.7 NXAIR, 17.5 kV, 50 Hz, 40 kA, ≤ 4000 A or 25/31,5 kA with 3150/4000 A busbar, permissible current
values
Rated fre- Short busbar width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- temperature (A / °C) (A /°C)
ency current tion

Degree of Panel version panel cb (A /°C) busbar (A /°C)


protection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55
1)
17.5 50 40 with / 800 all closed 1250 1250 1340 1300 1260 1220 1175 1125 1250 1340 1300 1260 1220 1175 1125
without
2500 2730 2650 2565 2480 2390 2295

3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750

800 IP3XD, nat. vent. 2000 2500 2165 2100 2035 1965 1895 1820 2500 2730 2650 2565 2480 2390 2295
IP31, IP32
3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750

800 IP4X, IP41,nat. vent. 2000 2500 2055 1995 1930 1865 1800 1725 2500 2730 2650 2565 2480 2390 2295
IP42
3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750

1000 IP3XD, nat. vent. 2500 2500 2730 2650 2565 2480 2390 2295 2500 2730 2650 2565 2480 2390 2295
IP31, IP32
3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750

1000 IP3XD, nat. vent. 3150 3150 3375 3275 3170 3060 2950 2835 3150 4470 4335 4195 4050 3905 3750
IP31, IP32
4000 4470 4335 4195 4050 3905 3750
2)
1000 IP3XD, forc. vent. 4000 4000 4000 4000 4000 3975 3830 3680 4000 4470 4335 4195 4050 3905 3750
IP31, IP32

1000 IP4X, IP41,natural 2500 2500 2590 2515 2435 2355 2270 2180 2500 2730 2650 2565 2480 2390 2295
IP42 ventilated
3150 4470 4335 4195 4050 3905 3750

4000 4470 4335 4195 4050 3905 3750

1000 IP4X, IP41,natural 3150 3150 3205 3110 3010 2905 2800 2690 3150 4470 4335 4195 4050 3905 3750
IP42 ventilated
4000 4470 4335 4195 4050 3905 3750
2)
1000 IP4X, IP41,forc. vent. 4000 4000 4000 4000 3905 3775 3635 3495 4000 4470 4335 4195 4050 3905 3750
IP42

1) All = IP3XD, IP31, IP32, IP4X, IP41, IP42, IP50, IP51 for busbar rating up to 2500 A also possible
2) standard version current relays controlled, optional current relays controlled and redundant version

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 107 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.8 NXAIR, 17.5 kV, 60 Hz, 40 kA, ≤ 4000 A or 25/31,5 kA with 3150/4000 A busbar, permissible current
values
Rated fre- Short busbar width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- temperature
ency current tion (A / °C) (A /°C)

Degree of Panel version panel cb (A /°C) busbar (A /°C)


protection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55
1)
17.5 60 25 with / 600 all closed 630 800 680 655 630 605 575 545 3150 4335 4200 4065 3925 3785 3635
without
4000 4335 4200 4065 3925 3785 3635
1)
600 all closed 1000 1250 1090 1050 1015 975 935 890 3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635


1)
800 all closed 1250 1600 1315 1270 1220 1175 1125 1070 3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635

800 IP3XD, nat. vent. 2000 2500 2110 2050 1985 1915 1850 1775 3150 4335 4200 4065 3925 3785 3635
IP31, IP32
4000 4335 4200 4065 3925 3785 3635

800 IP4X, IP41,nat. vent. 2000 2500 2005 1945 1885 1820 1755 1685 3150 4335 4200 4065 3925 3785 3635
IP42
4000 4335 4200 4065 3925 3785 3635

1000 IP3XD, nat. vent. 2500 2500 2635 2555 2475 2390 2305 2215 3150 4335 4200 4065 3925 3785 3635
IP31, IP32
4000 4335 4200 4065 3925 3785 3635

3150 3150 3270 3175 3070 2965 2860 2745 3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635


2)
1000 IP3XD, forc. vent. 4000 4000 4000 4000 4000 3855 3715 3565 4000 4335 4200 4065 3925 3785 3635
IP31, IP32

1000 IP4X, IP41,nat. vent. 2500 2500 2500 2425 2350 2270 2185 2100 3150 4335 4200 4065 3925 3785 3635
IP42
4000 4335 4200 4065 3925 3785 3635

3150 3150 3105 3015 2915 2815 2715 2605 3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635

1000 IP4X, IP41,forc. vent.2) 4000 4000 4000 3915 3785 3660 3525 3385 4000 4335 4200 4065 3925 3785 3635
IP42
1)
31.5 with / 600 all Closed 630 800 680 655 630 605 575 545 3150 4335 4200 4065 3925 3785 3635
without
4000 4335 4200 4065 3925 3785 3635
1)
600 all Closed 1000 1250 1075 1040 1000 955 910 860 3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635


1)
800 all Closed 1250 1250 1295 1260 1220 1175 1130 1085 3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635

800 IP3XD, nat. vent. 2000 2500 2110 2050 1985 1915 1850 1775 3150 4335 4200 4065 3925 3785 3635
IP31, IP32
4000 4335 4200 4065 3925 3785 3635

800 IP4X, IP41,nat. vent. 2000 2500 2005 1945 1885 1820 1755 1685 3150 4335 4200 4065 3925 3785 3635
IP42
4000 4335 4200 4065 3925 3785 3635

1000 IP3XD, nat. vent. 2500 2500 2635 2555 2475 2390 2305 2215 3150 4335 4200 4065 3925 3785 3635
IP31, IP32
4000 4335 4200 4065 3925 3785 3635

3150 3150 3270 3175 3070 2965 2860 2745 3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635


2)
1000 IP3XD, forc. vent. 4000 4000 4000 4000 4000 3855 3715 3565 4000 4335 4200 4065 3925 3785 3635
IP31, IP32

1000 IP4X, IP41,nat. vent. 2500 2500 2500 2425 2350 2270 2185 2100 3150 4335 4200 4065 3925 3785 3635
IP42
4000 4335 4200 4065 3925 3785 3635

3150 3150 3105 3015 2915 2815 2715 2605 3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635


2)
1000 IP4X, IP41,forc. vent. 4000 4000 4000 3915 3785 3660 3525 3385 4000 4335 4200 4065 3925 3785 3635
IP42

1) All = IP3XD, IP31, IP32, IP4X, IP41, IP42, IP50, IP51 for busbar rating up to 2500 A also possible
2) standard version current relays controlled, optional current relays controlled and redundant version

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 108 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.8 NXAIR, 17.5 kV, 60 Hz, 40 kA, ≤ 4000 A or 25/31,5 kA with 3150/4000 A busbar, permissible current
values
Rated fre- Short busbar width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- temperature
ency current tion (A / °C) (A /°C)

Degree of Panel version panel cb (A /°C) busbar (A /°C)


protection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55
1)
17.5 60 40 with / 800 all closed 1250 1250 1295 1260 1220 1180 1135 1090 1250 1295 1260 1220 1180 1135 1090
without
2500 2645 2570 2485 2405 2315 2225

3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635

800 IP3XD, nat. vent. 2000 2500 2100 2035 1970 1905 1835 1765 2500 2645 2570 2485 2405 2315 2225
IP31, IP32
3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635

800 IP4X, IP41,nat. vent. 2000 2500 1995 1930 1870 1805 1740 1675 2500 2645 2570 2485 2405 2315 2225
IP42
3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635

1000 IP3XD, nat. vent. 2500 2500 2645 2570 2485 2405 2315 2225 2500 2645 2570 2485 2405 2315 2225
IP31, IP32
3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635

1000 IP3XD, nat. vent. 3150 3150 3270 3175 3070 2965 2860 2745 3150 4335 4200 4065 3925 3785 3635
IP31, IP32
4000 4335 4200 4065 3925 3785 3635
2)
1000 IP3XD, forc. vent. 4000 4000 4000 4000 4000 3855 3715 3565 4000 4335 4200 4065 3925 3785 3635
IP31, IP32

1000 IP4X, IP41,natural 2500 2500 2510 2440 2360 2280 2195 2110 2500 2645 2570 2485 2405 2315 2225
IP42 ventilated
3150 4335 4200 4065 3925 3785 3635

4000 4335 4200 4065 3925 3785 3635

1000 IP4X, IP41,natural 3150 3150 3105 3015 2915 2815 2715 2605 3150 4335 4200 4065 3925 3785 3635
IP42 ventilated
4000 4335 4200 4065 3925 3785 3635
2)
1000 IP4X, IP41,forc. vent. 4000 4000 4000 3915 3785 3660 3525 3385 4000 4335 4200 4065 3925 3785 3635
IP42

1) All = IP3XD, IP31, IP32, IP4X, IP41, IP42, IP50, IP51 for busbar rating up to 2500 A also possible
2) standard version current relays controlled, optional current relays controlled and redundant version

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 109 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.9 NXAIR, ≤ 12 kV, 50 Hz, 25 / 31.5 kA, ≤ 2500 A, permissible current values for bus sectionalizer with
bushing type CT 4MD17 between busbar and circuit breaker
Rated fre- Short busbar Width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- 1) temperature
ency current tion (A / °C) (A /°C)
degree panel panel cb (A /°C) bus- (A /°C)
of pro- version bar
tection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55

≤12 50 ≤ 25 with / 2x IP3XD, nat. vent + 1250 1600 1330 1290 1250 1210 1165 1120 1250 1330 1290 1250 1210 1165 1120
without 800 IP31, closed
IP32 2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235

2x IP4X, nat. vent + 1250 1600 1330 1290 1250 1210 1165 1120 1250 1330 1290 1250 1210 1165 1120
800 IP41, closed
IP42 2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235

2x IP3XD, nat. vent 2000 2500 2130 2065 2000 1930 1860 1790 2000 2130 2065 2000 1930 1860 1790
1000 IP31,
IP32 2500 2660 2580 2500 2415 2325 2235

2x IP4X, nat. vent 2000 2500 2130 2065 2000 1930 1860 1790 2000 2130 2065 2000 1930 1860 1790
1000 IP41,
IP42 2500 2660 2580 2500 2415 2325 2235

2x IP3XD, nat. vent 2500 2500 2660 2580 2500 2415 2325 2235 2500 2660 2580 2500 2415 2325 2235
1000 IP31,
IP32

2x IP4X, nat. vent 2500 2500 2560 2485 2410 2325 2240 2155 2500 2660 2580 2500 2415 2325 2235
1000 IP41,
IP42

31.5 with / 2x IP3XD, nat. vent + 1250 1250 1330 1290 1250 1210 1165 1120 1250 1330 1290 1250 1210 1165 1120
without 800 IP31, closed
IP32 2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235

2x IP4X, nat. vent + 1250 1250 1330 1290 1250 1210 1165 1120 1250 1330 1290 1250 1210 1165 1120
800 IP41, closed
IP42 2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235

2x IP3XD, nat. vent 2000 2500 2130 2065 2000 1930 1860 1790 2000 2130 2065 2000 1930 1860 1790
1000 IP31,
IP32 2500 2660 2580 2500 2415 2325 2235

2x IP4X, nat. vent 2000 2500 2130 2065 2000 1930 1860 1790 2000 2130 2065 2000 1930 1860 1790
1000 IP41,
IP42 2500 2660 2580 2500 2415 2325 2235

2x IP3XD, nat. vent 2500 2500 2660 2580 2500 2415 2325 2235 2500 2660 2580 2500 2415 2325 2235
1000 IP31,
IP32

2x IP4X, nat. vent 2500 2500 2560 2485 2410 2325 2240 2155 2500 2660 2580 2500 2415 2325 2235
1000 IP41,
IP42

1) for 2000 A and 2500 A: 2 x 1000 for bus sectionalizer type I or 1 x 1000 mm + 1 x 800 mm for bus sectionalizer type II

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 110 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.10 NXAIR, ≤ 12 kV, 60 Hz, 25 / 31.5 kA, ≤ 2500 A, permissible current values for bus sectionalizer with
bushing type CT 4MD17 between busbar and circuit breaker
Rated fre- Short busbar Width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- 1) temperature
ency current tion (A / °C) (A /°C)
degree panel panel cb (A /°C) bus- (A /°C)
of pro- version bar
tection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55

≤12 60 ≤ 25 with / 2x IP3XD, nat. vent + 1250 1600 1300 1260 1220 1180 1135 1090 1250 1300 1260 1220 1180 1135 1090
without 800 IP31, closed
IP32 2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235

2x IP4X, nat. vent + 1250 1600 1300 1260 1220 1180 1135 1090 1250 1300 1260 1220 1180 1135 1090
800 IP41, closed
IP42 2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235

2x IP3XD, nat. vent 2000 2500 2070 2010 1945 1880 1810 1740 2000 2070 2010 1945 1880 1810 1740
1000 IP31,
IP32 2500 2660 2580 2500 2415 2325 2235

2x IP4X, nat. vent 2000 2500 2070 2010 1945 1880 1810 1740 2000 2070 2010 1945 1880 1810 1740
1000 IP41,
IP42 2500 2660 2580 2500 2415 2325 2235

2x IP3XD, nat. vent 2500 2500 2625 2545 2465 2385 2295 2205 2500 2660 2580 2500 2415 2325 2235
1000 IP31,
IP32

2x IP4X, nat. vent 2500 2500 2490 2420 2345 2265 2180 2095 2500 2660 2580 2500 2415 2325 2235
1000 IP41,
IP42

31.5 with / 2x IP3XD, nat. vent + 1250 1250 1300 1260 1220 1180 1135 1090 1250 1300 1260 1220 1180 1135 1090
without 800 IP31, closed
IP32 2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235

2x IP4X, nat. vent + 1250 1250 1300 1260 1220 1180 1135 1090 1250 1300 1260 1220 1180 1135 1090
800 IP41, closed
IP42 2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235

2x IP3XD, nat. vent 2000 2500 2070 2010 1945 1880 1810 1740 2000 2070 2010 1945 1880 1810 1740
1000 IP31,
IP32 2500 2660 2580 2500 2415 2325 2235

2x IP4X, nat. vent 2000 2500 2070 2010 1945 1880 1810 1740 2000 2070 2010 1945 1880 1810 1740
1000 IP41,
IP42 2500 2660 2580 2500 2415 2325 2235

2x IP3XD, nat. vent 2500 2500 2625 2545 2465 2385 2295 2205 2500 2660 2580 2500 2415 2325 2235
1000 IP31,
IP32

2x IP4X, nat. vent 2500 2500 2490 2420 2345 2265 2180 2095 2500 2660 2580 2500 2415 2325 2235
1000 IP41,
IP42

1) for 2000 A and 2500 A: 2 x 1000 for bus sectionalizer type I or 1 x 1000 mm + 1 x 800 mm for bus sectionalizer type II

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 111 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.11 NXAIR, 17.5 kV, 50 Hz, 25 / 31.5 kA, ≤ 2500 A, permissible current values for bus sectionalizer with
bushing type CT 4MD17 between busbar and circuit breaker
Rated fre- Short busbar Width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- 1) temperature
ency current tion (A / °C) (A /°C)
degree panel panel cb (A /°C) bus- (A /°C)
of pro- version bar
tection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55

17.5 50 ≤ 25 with / 2x IP3XD, nat. vent + 1250 1600 1330 1290 1250 1210 1165 1120 1250 1330 1290 1250 1210 1165 1120
without 800 IP31, closed
IP32 2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235

2x IP4X, nat. vent + 1250 1600 1330 1290 1250 1210 1165 1120 1250 1330 1290 1250 1210 1165 1120
800 IP41, closed
IP42 2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235

2x IP3XD, nat. vent 2000 2500 2130 2065 2000 1930 1860 1790 2000 2130 2065 2000 1930 1860 1790
1000 IP31,
IP32 2500 2660 2580 2500 2415 2325 2235

2x IP4X, nat. vent 2000 2500 2130 2065 2000 1930 1860 1790 2000 2130 2065 2000 1930 1860 1790
1000 IP41,
IP42 2500 2660 2580 2500 2415 2325 2235

2x IP3XD, nat. vent 2500 2500 2660 2580 2500 2415 2325 2235 2500 2660 2580 2500 2415 2325 2235
1000 IP31,
IP32

2x IP4X, nat. vent 2500 2500 2535 2460 2385 2305 2220 2135 2500 2660 2580 2500 2415 2325 2235
1000 IP41,
IP42

31.5 with / 2x IP3XD, nat. vent + 1250 1250 1330 1290 1250 1210 1165 1120 1250 1330 1290 1250 1210 1165 1120
without 800 IP31, closed
IP32 2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235

2x IP4X, nat. vent + 1250 1250 1330 1290 1250 1210 1165 1120 1250 1330 1290 1250 1210 1165 1120
800 IP41, closed
IP42 2000 2130 2065 2000 1930 1860 1790

2500 2660 2580 2500 2415 2325 2235

2x IP3XD, nat. vent 2000 2500 2130 2065 2000 1930 1860 1790 2000 2130 2065 2000 1930 1860 1790
1000 IP31,
IP32 2500 2660 2580 2500 2415 2325 2235

2x IP4X, nat. vent 2000 2500 2130 2065 2000 1930 1860 1790 2000 2130 2065 2000 1930 1860 1790
1000 IP41,
IP42 2500 2660 2580 2500 2415 2325 2235

2x IP3XD, nat. vent 2500 2500 2660 2580 2500 2415 2325 2235 2500 2660 2580 2500 2415 2325 2235
1000 IP31,
IP32

2x IP4X, nat. vent 2500 2500 2535 2460 2385 2305 2220 2135 2500 2660 2580 2500 2415 2325 2235
1000 IP41,
IP42

1) for 2000 A and 2500 A: 2 x 1000 for bus sectionalizer type I or 1 x 1000 mm + 1 x 800 mm for bus sectionalizer type II

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 112 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.12 NXAIR, 17.5 kV, 60 Hz, 25 / 31.5 kA, ≤ 2500 A, permissible current values for bus sectionalizer with
bushing type CT 4MD17 between busbar and circuit breaker
Rated fre- Short busbar Width panel version Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
voltage qu- circuit insula- 1) temperature
ency current tion (A / °C) (A /°C)
degree panel panel cb (A /°C) bus- (A /°C)
of pro- version bar
tection
(kV) (Hz) (kA) (mm) (A) (A) 30 35 40 45 50 55 (A) 30 35 40 45 50 55

17.5 60 ≤ 25 with / 2x IP3XD, nat. vent + 1250 1600 1300 1260 1220 1180 1135 1090 1250 1300 1260 1220 1180 1135 1090
without 800 IP31, closed
IP32 2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235

2x IP4X, nat. vent + 1250 1600 1300 1260 1220 1180 1135 1090 1250 1300 1260 1220 1180 1135 1090
800 IP41, closed
IP42 2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235

2x IP3XD, nat. vent 2000 2500 2070 2010 1945 1880 1810 1740 2000 2070 2010 1945 1880 1810 1740
1000 IP31,
IP32 2500 2660 2580 2500 2415 2325 2235

2x IP4X, nat. vent 2000 2500 2070 2010 1945 1880 1810 1740 2000 2070 2010 1945 1880 1810 1740
1000 IP41,
IP42 2500 2660 2580 2500 2415 2325 2235

2x IP3XD, nat. vent 2500 2500 2595 2520 2440 2360 2270 2185 2500 2660 2580 2500 2415 2325 2235
1000 IP31,
IP32

2x IP4X, nat. vent 2500 2500 2470 2395 2320 2240 2160 2075 2500 2660 2580 2500 2415 2325 2235
1000 IP41,
IP42

31.5 with / 2x IP3XD, nat. vent + 1250 1250 1300 1260 1220 1180 1135 1090 1250 1300 1260 1220 1180 1135 1090
without 800 IP31, closed
IP32 2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235

2x IP4X, nat. vent + 1250 1250 1300 1260 1220 1180 1135 1090 1250 1300 1260 1220 1180 1135 1090
800 IP41, closed
IP42 2000 2070 2010 1945 1880 1810 1740

2500 2660 2580 2500 2415 2325 2235

2x IP3XD, nat. vent 2000 2500 2070 2010 1945 1880 1810 1740 2000 2070 2010 1945 1880 1810 1740
1000 IP31,
IP32 2500 2660 2580 2500 2415 2325 2235

2x IP4X, nat. vent 2000 2500 2070 2010 1945 1880 1810 1740 2000 2070 2010 1945 1880 1810 1740
1000 IP41,
IP42 2500 2660 2580 2500 2415 2325 2235

2x IP3XD, nat. vent 2500 2500 2595 2520 2440 2360 2270 2185 2500 2660 2580 2500 2415 2325 2235
1000 IP31,
IP32

2x IP4X, nat. vent 2500 2500 2470 2395 2320 2240 2160 2075 2500 2660 2580 2500 2415 2325 2235
1000 IP41,
IP42

1) for 2000 A and 2500 A: 2 x 1000 for bus sectionalizer type I or 1 x 1000 mm + 1 x 800 mm for bus sectionalizer type II

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 113 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.13 Permissible combination of components in connection compartment of switching device panel resp.
busbar connecting panel, detailed configuration NX-Tools+
Rated Short Rated width Cable venti- current earthing voltage Surge Surge Connection in cable compartment
voltage circuit feeder access lation trans- switch transformers 1) arrestor
arrestor
withstand current from: formers
current fixed With- 3EJ 3EK from bottom, front or rear from top, rear 2)
drawable
number and cross section of number and
cables 3) / bars cross section of
single-core
single-core per three-core per cables per
phase panel phase 3) / bars

(kV) (kA) (A) (mm) (mm2) (mm2) (mm2)

Circuit breaker or disconnector panel

≤ 17.5 ≤ 31.5 630 600 front / without 3 1 3 - - - ≤2 x ≤300 ≤2 x ≤240 ≤3 x ≤300


rear
3 1 3 - - 3 ≤2 x ≤300 ≤2 x ≤240 ≤3 x ≤300

3 1 - - - - ≤3 x ≤300 ≤3 x ≤185 ≤3 x ≤300

3 1 - - 3 - ≤2 x ≤300 ≤2 x ≤240 ≤3 x ≤300

3 1 - 3 - - ≤2 x ≤300 ≤2 x ≤240 ≤3 x ≤300

3 1 - 3 - 3 ≤2 x ≤300 ≤2 x ≤240 ≤3 x ≤300

3 1 - 3 3 - ≤2 x ≤300 ≤2 x ≤240 ≤3 x ≤300

≤ 31.5 1000 600 front / without 3 1 3 - - - ≤2 x ≤300 ≤2 x ≤240 ≤3 x ≤300


rear
3 1 3 - - 3 ≤2 x ≤300 ≤2 x ≤240 ≤3 x ≤300

3 1 - - - - ≤3 x ≤300 ≤3 x ≤185 ≤3 x ≤300

3 1 - - 3 - ≤2 x ≤300 ≤2 x ≤240 ≤3 x ≤300

3 1 - 3 - - ≤2 x ≤300 ≤2 x ≤240 ≤3 x ≤300

3 1 - 3 - 3 ≤2 x ≤300 ≤2 x ≤240 ≤3 x ≤300

3 1 - 3 3 - ≤2 x ≤300 ≤2 x ≤240 ≤3 x ≤300

≤ 40 1250 800 front / without 3 1 3 - - - ≤2 x ≤630 / ≤2 x ≤240 ≤4 x ≤500


rear
7)
3 / 4 x ≤630

3 1 3 - - - bars per phase, 1 x 80x10 -

3 1 3 - 3 - ≤2 x ≤630 / ≤2 x ≤240 4) ≤4 x ≤500

3 / 4 x ≤300 4)

3 1 3 - 3 - bars per phase, 1 x 80x10 -


5)
3 1 3 - - 3 ≤2 x ≤630 / ≤2 x ≤240 ≤4 x ≤500

3 / 4 x ≤300 5)

3 1 3 - - 3 bars per phase, 1 x 80x10 -

3 1 - 3 - - ≤2 x ≤630 / ≤2 x ≤240 ≤4 x ≤500

3 / 4 x ≤300

3 1 - 3 - - bars per phase, 1 x 80x10 -

3 1 - 3 3 - ≤2 x ≤630 / ≤2 x ≤240 ≤4 x ≤500

3 / 4 x ≤300

3 1 - 3 3 - bars per phase, 1 x 80x10 -

3 1 - 3 - 3 ≤2 x ≤630 / ≤2 x ≤240 ≤4 x ≤500

3 / 4 x ≤300

3 1 - 3 - 3 bars per phase, 1 x 80x10 -

1) surge arrestors are only used for up to 12 kV, and should be used for starting currents of motors up to 600 A
2) rear side cable box up to ≤ 17.5 kV / ≤ 40 kA / ≤ 4000 A, additional depth for rear side cable box: + 600 mm; service aisle of minimum 500 mm needed
and so only possible in freestanding design, not possible for duplex version in back-to-back arrangement
3) ≤1250A, screw size on connection copper: M12, > 1250 A up to 4000A, screw size on connection copper: M16
4) only ≤ 2 cables in version for 12 kV, up to 31.5 kA with panel depth 1350 mm
5) only ≤ 2 cables up to 17.5 kV up to 31.5 kA with panel depth 1350 mm
6) only possible in panel depth ≥ 1500 mm
7) 3 cables / phase for = 12 kV, 4 cables / phase for = 17.5 kV

Hint:
a. For duplex in back-to-back arrangement only cable connection from front is possible
b. For duplex in front-to-front arrangement cables connected in row A with max. 3 single core cables per phase resp. 1 three core cable per phase to
consumer and max. 3 single core cable per phase resp. 1 three core cable per phase to opposite side on row B

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 114 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.13 Permissible combination of components in connection compartment of switching device panel resp.
busbar connecting panel, detailed configuration NX-Tools+
Rated Short Rated width Cable venti- current earthing voltage Surge Surge Connection in cable compartment
voltage circuit feeder access lation trans- switch transformers 1) arrestor
arrestor
withstand current from: formers
current fixed With- 3EJ 3EK from bottom, front or rear from top, rear 2)
drawable
number and cross section of number and
cables 3) / bars cross section of
single-core
single-core per three-core per cables per
phase panel phase 3) / bars

(kV) (kA) (A) (mm) (mm2) (mm2) (mm2)


Circuit breaker or disconnector panel
≤ 17.5 ≤ 40 2000 800 front / natural 3 1 3 - - - 3 / 4 x ≤630 - 3 / 4 x ≤500
rear
3 1 3 - - - bars per phase, 2 x 80x10 -

3 1 3 6) - - 3 3 / 4 x ≤630 - 3 / 4 x ≤500

3 1 3 - - 3 bars per phase, 2 x 80x10 -

3 1 - 3 - - 3 / 4 x ≤630 - 3 / 4 x ≤500

3 1 - 3 - - Bar, 2 x 80x10 -

3 1 - 3 - 3 3 / 4 x ≤630 - 3 / 4 x ≤500

3 1 - 3 - 3 bars per phase, 2 x 80x10 -

2500 1000 front / natural 3 1 3 - - - 3 / 4 x ≤630 - 3 / 4 x ≤500


rear
3 1 3 - - - bars per phase, 2 x 100x10 -

3 1 3 6) - - 3 3 / 4 x ≤630 - 3 / 4 x ≤500

3 1 3 - - 3 bars per phase, 2 x 100x10 -

3 1 - 3 - - 3 / 4 x ≤630 - 3 / 4 x ≤500

3 1 - 3 - - bars per phase, 2 x 100x10 -

3 1 - 3 - 3 3 / 4 x ≤630 - 3 / 4 x ≤500

3 1 - 3 - 3 bars per phase, 2 x 100x10 -

3150 1000 front / natural 3 1 3 - - - 6 x ≤630 - 6 x ≤500


rear
3 1 3 - - - bars per phase, 3 x 120x10 -

3 1 - - - 3 6 x ≤630 - 6 x ≤500

3 1 3 - - 3 bars per phase, 3 x 120x10 -

4000 1000 front / forced 3 1 3 - - - 6 x ≤630 - 6 x ≤500


rear
3 1 3 - - - bars per phase, 3 x 120x10 -

3 1 - - - 3 6 x ≤630 - 6 x ≤500

3 1 3 - - 3 bars per phase, 3 x 120x10 -

3 1 - 3 - - 6 x ≤630 - 6 x ≤500

3 1 - 3 - - bars per phase, 3 x 120x10 -

3 1 - 3 - 3 6 x ≤630 - 6 x ≤500

3 1 - 3 - 3 bars per phase, 3 x 120x10 -

1) surge arrestors are only used for up to 12 kV, and should be used for starting currents of motors up to 600 A
2) rear side cable box up to ≤ 17.5 kV / ≤ 40 kA / ≤ 4000 A, additional depth for rear side cable box: + 600 mm; service aisle of minimum 500 mm needed
and so only possible in freestanding design, not possible for duplex version in back-to-back arrangement
3) ≤ 1250A, screw size on connection copper: M12, > 1250 A up to 4000A, screw size on connection copper: M16
4) only ≤ 2 cables in version for 12 kV, up to 31.5 kA with panel depth 1350 mm
5) only ≤ 2 cables up to 17.5 kV up to 31.5 kA with panel depth 1350 mm
6) only possible in panel depth ≥ 1500 mm

Hint:
a. For duplex in back-to-back arrangement only cable connection from front is possible
b. For duplex in front-to-front arrangement cables connected in row A with max. 3 single core cables per phase resp. 1 three core cable per phase to
consumer and max. 3 single core cable per phase resp. 1 three core cable per phase to opposite side on row B

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 115 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.13 Permissible combination of components in connection compartment of switching device panel resp.
busbar connecting panel, detailed configuration NX-Tools+
Rated Short Rated width Cable venti- current earthing voltage Surge Surge Connection in cable compartment
voltage circuit feeder access lation trans- switch transformers 1) arrestor
arrestor
withstand current from: formers
current fixed With- 3EJ 3EK from bottom, front or rear from top, rear 2)
drawable
number and cross section of number and
cables 3) / bars cross section of
single-core
single-core per three-core per cables per
phase panel phase 3) / bars

(kV) (kA) (A) (mm) (mm2) (mm2) (mm2)

Contactor panel

≤12 ≤ 40 ≤ 450 435 front / without 3 1 - - - - ≤2 x ≤240 ≤2 x ≤240 -


rear
3 1 - - 3 - 1 x ≤240 1 x ≤240 -

Busbar connecting panel

≤ 17.5 ≤ 40 1250 800 front / without 3 - 3 - - - ≤2 x ≤500 / ≤2 x ≤240 -


rear 3 / 4 x ≤300

3 - - 3 - - ≤2 x ≤500 / ≤2 x ≤240 -
3 / 4 x ≤300

2000 800 front / natural 3 - 3 - - - 3 / 4 x ≤500


rear

2500 800 front / without 3 - 3 - - - 3 / 4 x ≤500 -


rear
3 - - 3 - - 3 / 4 x ≤500 -

3150 / 1000 front / natural 3 - - 3 - - 6 x ≤630 -


4000 rear

Switch-disconnector panel with HRC fuses

≤ 17,5 ≤ 31,5 200 800 front without 3 1 - - - - ≤2 x ≤300 ≤2 x ≤100 -

rear without 3 1 - - - - - - ≤2 x ≤300

16.13 Number of connectable cables for panels with ring core CT type 4MC4_40 in cable connection
compartment (only for circuit breaker panel and disconnector panel)
Connection in cable compartment

Rated Short circuit Rated feeder from bottom, front or rear from top, rear 1)
width ventilation
voltage withstand current current number and cross section of cables 2)
single-core per phase three-core per panel
(kV) (kA) (A) (mm) (mm2) (mm2) (mm2)
≤17.5 ≤ 40 630 600 closed ≤ 3 x ≤ 300 --- ---
1000 600 ≤ 3 x ≤ 300 --- ---
1250 800 3 / 4 x ≤ 300 --- ---
≤ 2 x ≤ 500
2000 800 natural 3 / 4 x ≤ 300 --- ---
3)
2500 800 without 3 / 4 x ≤ 300 --- ---

1) rear side cable box up to ≤ 17.5 kV / ≤ 40 kA / ≤ 4000 A, additional depth for rear side cable box: + 600 mm; service aisle of minimum 500 mm needed
and so only possible in freestanding design
2) ≤1250A, screw size on connection copper: M12, > 1250 A up to 4000A, screw size on connection copper: M16
3) Only for busbar connecting panel

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 116 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.14 Permissible combination of components in busbar compartment of switching device panel,


detailed configuration NX-Tools+
Rated Short circuit Rated Width Ventilation Rated Bushing Voltage Surge Earthing SIQuench Bar or cable connection
voltage with-stand feeder busbar type transformers arresters switch in top in top box to busbar 4)
current current current insulators in top box in top box box

number and cross


section of single-core
cables per phase / bars
per phase
(kV) (kA) (A) (mm) (A) (mm2)

Contactor panel

≤12 ≤ 40 ≤ 450 435 without ≤ 4000 3 - - - - -

All other panel types 2)

≤ 17.5 ≤ 31.5 630 600 without 1250 3 - - - - -


3 3 - - - -
3 - - 1 - -
3 - 3 - -
3 - - - 1 -
3 - - - - 3 x 300
3)
3 - - - - bar 1 x 80 x 10
2500 3 - - - - -
3 3 - - - -
3 - - 1 - -
3 - 3 - - -
3 - - - 1
3150 3 - - - - -
4000 3 - - - - -
1000 600 without 1250 3 - - - - -
3 3 - - - -
3 - - 1 - -
3 - 3 - - -
3 - - - 1 -
3 - - - - 3 x 300
3 - - - - bar 1 x 80 x 10 3)
2500 3 - - - - -
3 3 - - - -
3 - - 1 - -
3 - 3 - - -
3 - - - 1 -
3150 3 - - - - -
4000 3 - - - - -
≤ 40 1250 800 without 1250 3 - - - - -
3 3 - - - -
3 - - 1 - -
3 - 3 - - -
3 - - - 1 -
3 - - - - 1 / 2 x ≤500 resp.
3 / 4 x ≤300
3 - - - - bar, 1 x 100x10 3)
2500 3 - - - - -
3 3 - - - -
3 - - 1 - -
3 - 3 - - -
3 - - - 1 -
3 - - - - 3 / 4 x ≤500
3 - - - - bar, 2 x 100x10 3)
3150 / 3 - - - - -
4000 3 3 - - - -
3 - - 1 - -
3 - 3 - - -
3 - - - 1 -
3 - - - - 6 x ≤500
3 - - - - bar, 3 x 120x10 3)
2000 800 natural ≤ 4000 3 - - - - -
2500 1000 natural ≤ 4000 3 - - - - -
3150 1000 natural ≤ 4000 3 - - - - -
4000 1000 forced 1) ≤ 4000 3 - - - - -

1) standard version current relay controlled, optionally current relay controlled and redundant version
2) No components on busbar side for SDF panel possible
3) current carrying capacity of busbar connection
 1 x 80 mm x 10 mm and 1 x 100 mm x 10 mm only suitable for max. current of 1250 A
 2 x 100 mm x 10 mm only suitable for max. current of 2500 A
 3 x 120 mm x 10 mm only suitable for max. current of 4000 A
4) No cable connection or bar connection in top box at the busbar for Marine application or in combination with degree of protection IPX1 or IPX2 possible

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 117 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.15 Type of cable lugs

16.15.1 Cable lug for compression connection

MV- cable Cable lug for compression connection


Cross section Diameter of inner For copper conductors acc. DIN 46 235 For alloy conductors acc. DIN 46 329
conductor
Al / Cu Al / Cu Cable lug Inner Outer Cable lug Inner Outer
type diameter d1 diameter d4 type diameter d1 diameter d4
[mm²] [mm] [mm] [mm] [mm] [mm]
95 11,0 – 12,0 12/16-95 13,5 19 12-95 13,2 22
120 12,5 – 13,5 12/16/-120 15,5 21 12/16-120 14,7 23
150 13,9 – 15,0 12/16-150 17 23,5 12/16-150 16,3 25
185 15,5 – 16,8 12/16-185 19 25,5 12/16-185 18,3 28,5
240 17,8 – 19,2 12/16-240 21,5 29 12/16-240 21 32
300 20,0 – 21,6 16/20-300 24,5 32 12/16-300 23,3 34
400 22,9 – 24,6 16/20-400 27,5 38,5 12/16-400 26 38,5
500 25,7 – 27,6 20-500 31 42 12/16-500 29 44
630 29,9 20-625 34,5 44 --- --- ---

16.15.2 Cable lug for compression connection - ELPRESS

MV- cable Aluminium-copper terminals for compression connection

Cross section Diameter of inner Only for alloy conductors


conductor
Al / Cu Al / Cu Cable lug type Inner diameter d Outer diameter D
[mm²] [mm] [mm] [mm]
95 11,0 – 12,0 AKK95-12 / -16 12,5 25
120 12,5 – 13,5 AKK120-12 / -16 14,0 25
150 13,9 – 15,0 AKK150-12 / -16 15,8 25
185 15,5 – 16,8 AKK185-12 / -16 17,6 32
240 17,8 – 19,2 AKK240-12 / -16 19,8 32
300 20,0 – 21,6 AKK300-12 / -16 22,0 36
400 22,9 – 24,6 AKK400-12 / -16 25,0 40
500 25,7 – 27,6 AKK500B-16 / -20 28,0 44
630 29,9 --- --- ---

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 118 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.15.3 Cable lug with shear-off-head bolts - NEXANS

MV- cable Cable lug with shear-off-head bolts acc. IEC 61238-1
Cross section Diameter of inner conductor NEXANS - for alloy and copper conductors
Al / Cu Al / Cu Cable lug type Inner diameter d1 Outer diameter d4
[mm²] [mm] [mm] [mm]
95 11,0 – 12,0 C16-95 - 12/16 12,5 24
120 12,5 – 13,5 C50-150 - 12/16 15,5 30
150 13,9 – 15,0 C50-150 - 12/16 15,5 30
185 15,5 – 16,8 C95-240 - 12/16 20 33
240 17,8 – 19,2 C95-240 - 12/16 20 33
300 20,0 – 21,6 C120-300 - 12/16 25 38
400 22,9 – 24,6 C185-400 - 12/16 26 42
500 25,7 – 27,6 C300-500 - 12/16 34 52
630 29,9 C400-630 - 12/16 34 52

16.15.4 Cable lug with shear-off-head bolts - HAUPA

MV- cable Cable lug with shear-off-head bolts


Cross section Diameter of inner conductor HAUPA - for alloy conductors
Al / Cu Al / Cu Cable lug type Inner diameter d1 Outer diameter d4
[mm²] [mm] [mm] [mm]
95 11,0 – 12,0 293140 x 12 12,5 24
293142 x 12
120 12,5 – 13,5 15,5 30
293144 x 16
293142 x 12
150 13,9 – 15,0 15,5 30
293144 x 16
293146 x 12
185 15,5 – 16,8 20 33
293148 x 16
293146 x 12
240 17,8 – 19,2 20 33
293148 x 16
293150 x 12
300 20,0 – 21,6 25 38
293152 x 16
293154 x 12
400 22,9 – 24,6 26 42
293156 x 16
500 25,7 – 27,6 --- --- ---
630 29,9 --- --- ---

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 119 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.15.5 Cable lug with shear-off-head bolts – PFISTERER SICON

MV- cable Cable lug with shear-off-head bolts


Cross section Diameter of inner conductor PFISTERER - for alloy and copper conductors
Al / Cu Al / Cu Cable lug type Inner diameter d1 Outer diameter d4
[mm²] [mm] [mm] [mm]
95 11,0 – 12,0 332 604 012 13 24
120 12,5 – 13,5 332 599 012 16.5 28
150 13,9 – 15,0 332 599 012 16.5 28
185 15,5 – 16,8 332 595 012/022 20 33
240 17,8 – 19,2 332 595 012/022 20 33
300 20,0 – 21,6 332 605 012/022 24 38
400 22,9 – 24,6 332 625 012/022 26,4 42
500 25,7 – 27,6 332 606 012/022 33,5 52
630 29,9 332 606 012/022 33,5 52

16.15.6 Cable lug with shear-off-head bolts – BBC Cellpack

MV- cable Cable lug with shear-off-head bolts


Cross section Diameter of inner conductor Cellpack - for alloy and copper conductors
Al / Cu Al / Cu Cable lug type Inner diameter d1 Outer diameter d4
[mm²] [mm] [mm] [mm]
95 11,0 – 12,0 CSK 16-95 – 12 12,5 22
120 12,5 – 13,5 CSK 50-150 – 12 16,0 28
150 13,9 – 15,0 CSK 50-150 - 12 16,0 28
185 15,5 – 16,8 CSK 95-240 - 12 20 33
240 17,8 – 19,2 CSK 95-240 - 12 20 33
300 20,0 – 21,6 CSK 240-400 – 16 26 40
400 22,9 – 24,6 CSK 240-400 - 16 26 40
500 25,7 – 27,6 --- --- ---
630 29,9 --- --- ---

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 120 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

16.15.7 Fixing of cable lugs

device screw Fixing moment


Termination of M12 for feeder currents ≤ 1250A 70
cables Connections elements per phase: 1x bolt size M12 plus 2 x flat washer; ISO 7093 plus 2x
(see also strain washer 12 plus 1x nut M12
installation M16 for feeder currents >1250A 170
manual) Connections elements per phase: 1x bolt size M16 plus 2x strain washer; 16 plus 1x nut M16

16.15.8 Surface (treatment) of the connection bar of the panel

copper aluminum tin coated nickel coated silver coated


2)
copper  X   
1) 2) 2)
surface of cable lugs aluminum X   X X
or external bars
2) 2)
(connection area) 3) tin coated    X X
2) 2)
nickel coated  X X  
2) 2)
silver coated  X X  
: possible combination X: critical in combination with humidity and can cause galvanic corrosion

1) For connecting of aluminum conductors to copper bi-metallic washers (CUPAL), bi-metallic transition joints or special compression cable lugs Al/Cu
must be used to avoid galvanic corrosion
2) Connection only possible when using bi-metallic washer or bi-metallic transition joints in between
3) Combination of material of wire of the HV-cable and surface of cable lug must be considered additional

Example: Cupal bi-metallic washer Example: bi-metallic transition joint Example: compression cable lugs Al/Cu

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 121 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17 Technical data of components


17.1 Technical data of circuit breaker 3AE5 (acc. to IEC 62271-100)
Rated voltage kV 12 17.5

Rated frequency Hz 50 / 60 50 / 60
Rated short-duration power frequency kV 28, IEC 38, IEC
withstand voltage 42, GOST
Phase/phase, phase/earth, open contact gap
Rated lightning impulse withstand voltage kV 75, IEC, GOST 95, IEC
Phase/phase, phase/earth, open contact gap
Rated short-time withstand current of main kA 25 31.5 40 25 31.5 40
circuits
Rated duration of short circuit s 1, 3 1, 3
Rated peak withstand current kA 63 / 65 80 / 82 100 / 104 63 / 65 80 / 82 100 / 104
Rated short circuit breaking current kA 25 31.5 40 25 31.5 40
Rated short circuit making current kA 63 / 65 80 / 82 100 / 104 63 / 65 80 / 82 100 / 104
Rated normal current A 800 800 1250 800 800 1250
1250 1250 2500 1250 1250 2500
1600 2500 3150 1600 2500 3150
4000 4000
Asymmetrical breaking current kA 30.6 38.6 49.0 30.6 38.6 49.0
DC component at rated short circuit breaking % 50 50 50 50 50 50
current
Rate-of-rise (RRRV) kV/μs 0.34 0.34 0.34 0.42 0.42 0.42
Voltage (TRV) peak value kV 20.6 20.6 20.6 30 30 30
Switching duty (up to 40kA) Standard: O – 0.3 s – CO – 3 min. – CO
Option F27: O – 3 min – CO – 3 min – CO
Option F28: O – 0,3 sec – CO – 15 s – CO

Operating times at rated voltage of the secondary circuit 3AE5


Closing time ms ≤ 60
Opening time 1st shunt release ms ≤ 30
Opening time 2nd and 3rd release ms ≤ 45
Arcing time ms < 15
Break time 1st shunt release ms ≤ 45
Break time 2nd and 3rd release ms ≤ 60
Dead time ms 300
Close-/ Open contact time 1st shunt release ms ≤ 45
Close-/ Open contact time 2nd and 3rd release ms ≤ 60
Minimum command duration for closing solenoid ms 45
Minimum command duration for 1st shunt release ms 40
Minimum command duration for 2nd and 3rd release ms 20
Pulse time for breaker tripping signal for 1st shunt release ms > 10
Pulse time for breaker tripping signal for 2nd and 3rd release ms >6
Spring-charging time for electrical operation s < 15
Synchronous operation error between the poles ms ≤2

Consumption data for releases 3AE5


Tripping ranges Power consumption
Release Tripping voltage DC Tripping voltage / Order no of at DC operation at AC 50/60 Hz
tripping current release operation

(50/60 Hz AC) appr. W appr. VA

Closing solenoid 85 to 110 % U 85 to 110 % U 3AY1410 300 - 370 300 – 370


1 st shunt release (without energy store) 70 to 110 % U 85 to 110 % U 3AY1410 300 300
2 nd shunt release (with energy store) 70 to 110 % U 85 to 110 % U 3AX1101 70 50
Undervoltage release 35 to 100 % U 35 to 100 % U 3AY1103 20 20
CT operated release (tripping pulse≥ 0.1Ws - - 3AX1104 - -
Power consumption of motor DC 100 W to 140 W
AC 170 VA to 200 VA

Switch classification electrically mechanically Capacitive switching capability


E2 M2 C2
contacts of auxiliary switch of breaker 12 NC+12NO

1) detailed information see also customer catalog HG11.02

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 122 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17.2 Technical data of circuit breaker 3AE2 (up to 31,5 kA acc. to IEC/IEEE 62271-37-013)
Rated voltage kV 15 1)

Rated frequency Hz 50 / 60
Rated short-duration power frequency withstand voltage kV 36 / (38) 2)

Phase/phase, phase/earth, open contact gap


Rated lightning impulse withstand voltage kV 95
Phase/phase, phase/earth, open contact gap
Rated normal current 1250, 2000, 2500, 3150, 4000 (forced ventilated)
Generator-source System-source interrupting
interrupting capability G1 capability
Rated short-time withstand current of main circuits kA 25 31,5
Rated duration of short circuit s 3 3
Rated short circuit breaking current kA 25 31,5
Rated peak withstand current 50 / 60Hz kA 69 87
Rated short circuit making current 50 / 60Hz kA 69 87
Asymmetrical breaking current kA 46 43
DC component at rated short circuit breaking current % 110 65
Rate-of-rise (RRRV) kV/μs 1,8 4,0
Voltage (TRV) peak factor 1,5 1,5
Closing time ms ≤ 60
Opening time 1st shunt release ms ≤ 30
Opening time 2nd and 3rd release ms ≤ 45
Arcing time ms < 15
Break time 1st shunt release ms ≤ 45
Break time 2nd and 3rd release ms ≤ 60
Dead time ms 300
Close-/ Open contact time 1st shunt release ms ≤ 45
Close-/ Open contact time 2nd and 3rd release ms ≤ 60
Minimum command duration for closing solenoid ms 45
Minimum command duration for 1st shunt release ms 40
Minimum command duration for 2nd and 3rd release ms 20
Pulse time for breaker tripping signal for 1st shunt release ms > 10
Pulse time for breaker tripping signal for 2nd and 3rd release ms >6
Spring-charging time for electrical operation s < 15
Synchronous operation error between the poles ms ≤2
Rated operating sequence For short-circuit breaking current (up to 30 short-circuit CO – 30 min – CO /) 3)

breaking operations)
For operating current (up to 10,000 operating cycles) O – 3 min – CO – 3 min – CO
Release Order no of release Power consumption Tripping ranges

DC operation AC (50/60 Hz) Tripping Tripping voltage


appr. W operation appr. VA voltage DC (50/60 Hz AC)
Closing solenoid 3AY1410 300 - 370 300 – 370 85 to 110 % U 85 to 110 % U
1st shunt release 3AY1410 300 300 70 to 110 % U 85 to 110 % U
(without energy store)
2nd and 3rd shunt release 3AX1101 70 50 70 to 110 % U 85 to 110 % U
(with energy store)
Undervoltage release 3AY1103 20 20 35 to 100 % U 35 to 100 % U
Power consumption of motor DC 100 W to 140 W
Power consumption of motor AC 170 VA to 200 VA
Switch classification electrically E2
mechanically M2
capacitive switching capability C2
circuit-breaker intended to be used in S1
a cable system class
generator circuit-breaker class G1 / G2
contacts of auxiliary switch of breaker 12 NC+12 NO Free contacts for external use

1) use suitable for rated voltages 7,2kV up to 15kV acc. to IEC/IEEE 62271-37.013
2) 36kV acc. to IEC/IEEE 62271-37.013 but tested for 38kV
3) CO – 30 min – CO acc. to IEEE
4) detailed information see also chapter 9.23 and customer catalogue HG11.08

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 123 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17.2 Technical data of circuit breaker 3AE2 and 3AE5

Operating times at rated voltage of the secondary circuit of 3AE2 and 3AE5 depending on release combinations

9. position opening break Power Spare part


release combination
of MLFB time time consumption

A 1st shunt release ≤ 30 ms ≤ 45 ms 300 W 3AY1410-0x

1st shunt release + ≤ 30 ms ≤ 45 ms 300 W 3AY1410-0x


B
2nd shunt release ≤ 45 ms ≤ 60 ms 70 W 3AX1101-xx

1st shunt release + ≤ 30 ms ≤ 45 ms 300 W 3AY1410-0x


B – Z G39
2nd shunt release ≤ 30 ms ≤ 45 ms 300 W 3AY1410-0x

1st shunt release + ≤ 30 ms ≤ 45 ms 300 W 3AY1410-0x


B - Z F15 2nd shunt release + ≤ 45 ms ≤ 60 ms 70 W 3AX1101-xx
3rd shunt release ≤ 45 ms ≤ 60 ms 70 W 3AX1101-xx

1st shunt release + ≤ 30 ms ≤ 45 ms 300 W 3AY1410-0x


C
C.t.-operated release with tripping pulse = 0.1 Ws (20 Ω) ≤ 45 ms ≤ 60 ms --- 3AX1104-2B

1st shunt release + ≤ 30 ms ≤ 45 ms 300 W 3AY1410-0x


F
undervoltage release ≤ 45 ms ≤ 60 ms 20 W 3AX1103-xx

1st shunt release + ≤ 30 ms ≤ 45 ms 300 W 3AY1410-0x


S 2nd shunt release + ≤ 45 ms ≤ 60 ms 70 W 3AX1101-xx
undervoltage release ≤ 45 ms ≤ 60 ms 20 W 3AX1103-xx

1st shunt release + ≤ 30 ms ≤ 45 ms 300 W 3AY1410-0x


T - Z A45 2nd shunt release + ≤ 45 ms ≤ 60 ms 70 W 3AX1101-xx
C.t.-operated release with tripping pulse = 0.1 Ws (20 Ohm) ≤ 45 ms ≤ 60 ms --- 3AX1104-2B

1st shunt release + ≤ 30 ms ≤ 45 ms 300 W 3AY1410-0x


V - Z A45 undervoltage release + ≤ 45 ms ≤ 60 ms 20 W 3AX1103-xx
C.t.-operated release with tripping pulse = 0.1 Ws (20 Ω) ≤ 45 ms ≤ 60 ms --- 3AX1104-2B

Ordering code “B + Z-G39” at 9. position of MLFB only possible for 3AE5

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 124 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17.3 Technical data of contactor 3TM3


Rated voltage kV 7.2 12
Ordering 3TM32 3TM33 3TM34
number
Rated frequency Hz 50/60 50/60 50/60
Rated short-duration power frequency phase/phase, kV 20 32 28
withstand voltage phase/earth
open contact kV 20 32 28
gap
Rated lightning impulse withstand voltage Phase/phase, kV 60 60 75
phase/earth
open contact kV 60 60 75
gap
Rated short-time withstand current [Ik] kA / s 8/1 8/1 8/1
Rated operational current according to IEC62271-106 A 450 450 450
Rated making current A 4500 4500 4500
Rated breaking current A 3600 3600 3600
Rated short-circuit breaking current A 5000 5000 5000
Rated single capacitor bank breaking current A --- --- 315 – back to back
Contactor class --- --- C2
Rated making current for capacitor switching (back to back) kA --- --- 10
Mechanical endurance of contactor cycles 1.000.000 1.000.000 1.000.000
Electrical endurance of vacuum interrupter of contactor while cycles 500.000 500.000 250.000
breaking the continuous current
Switching rate without mechanical closing latching cycles / h 1200 1200 1200
Minimum closing command for drive solenoid ms 100 100 100
Mechanical closing latch, operating cycles cycles 200.000 200.000 200.000
Mechanical closing latch, switching rate cycles / h 60 60 60
Mechanical closing latch, power consumption of the latch W 160 160 160
release solenoid
Voltage range of drive solenoid, operating voltage V 24 V DC … 250 V DC
100 V AC … 240 V AC
For operating voltage 24 V DC – 60 V DC and 110 - 125 V DC /
100 - 120 V AC and 220 - 250 V DC / 230 - 240 V AC
Closing time (interval of time between closing command and 55 ms ± 15 ms at 1,0 x Ua
the instant when the contacts touch for the first time)
Opening time (interval of time between opening command and 40 ms ± 10 ms at 1,0 x Ua
the instant when the contacts start to separate) without latching
system
Opening time (interval of time between opening command and 31 ms ± 13 ms at 1,0 x Ua (3TM32 and 3TM33)
the instant when the contacts start to separate) with latching
35 ms ± 10 ms at 1,0 x Ua (3TM34)
system
Power consumption of drive solenoid, making capacity 700 VA for 10 ms
Power consumption of drive solenoid, holding power 10 – 20 VA
Mechanical closing latch, voltage range of the latch release V 24 V DC … 250 V DC,
solenoid
100 V AC … 240 V AC
Mechanical closing latch, opening pulse maximum s 100 - 500ms
Contacts of auxiliary switch of contactor - 4NO + 4NC or 6NO + 6NC

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 125 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17.4 Technical data of contactor fuse combination for motor or transformer application
17.4.1 Technical data of fuses type SIBA / Inter-teknik for motor application of
contactor panel 435mm - 3TM32 – 450A
Current carrying capacity of fuses in contactor panel
Un Ith f Type SIBA (S) Number In HV HRC fuse Current carrying capacity in A
Inter-teknik (IT) per phase at ambient temperature in °C
kV kA Hz (A) 25°C 30°C 35°C 40°C 45°C 50°C 55°C
7.2 ≤ 40 50 3011054.250 S 2 250 351 340 328 316 304 291 278
+S4T.12KV.442.250.08-7.2 IT -- -- -- -- -- -- --
3011054.200 S 2 200 304 294 284 274 263 252 240
+S4T.12KV.442.200.08-7.2 IT 217 211 203 196 188 180 172
3010953.160 S 2 160 257 249 241 232 223 213 203
+S4T.12KV.442.160.08-7.2 IT 200 193 187 180 173 166 185
3011054.315 S 1 315 274 265 256 247 237 227 217
+S4T.12KV.442.315.08-7.2 IT 196 190 183 177 170 162 155
3011054.250 S 1 250 242 236 227 219 210 201 192
+S4T.12KV.442.250.08-7.2 IT 179 173 167 161 155 148 141
3011054.200 S 1 200 193 189 182 174 168 161 153
+S4T.12KV.442.200.08-7.2 IT 142 137 133 128 123 118 112
3010953.160 S 1 160 160 160 160 156 150 144 137
+S4T.12KV.442.160.08-7.2 IT 130 126 121 117 112 108 103
3010953.125 S 1 125 125 125 125 121 117 109 105
+S4T.12KV.442.125.08-7.2 IT 115 112 108 104 100 96 91
3010853.100 S 1 100 100 100 100 100 100 100 97
+S4T.12KV.442.100.08-7.2 IT 100 100 100 97 93 89 85
3010853.80 S 1 80 80 80 80 80 80 80 80
+S68T.12KV.442.080.08-7.2 IT 80 80 80 80 80 80 79
3010853.63 S 1 63 63 63 63 63 63 63 63
+S68T.12KV.442.063.08-7.2 IT 63 63 63 63 63 63 63
3010853.50 S 1 50 50 50 50 50 50 50 50
+S68T.12KV.442.050.08-7.2 IT 50 50 50 50 50 50 50
For rated fuse currents < 80 A, no current reduction must be considered
due to the ambient temperature
60 3011054.250 S 2 250 344 333 321 310 298 285 272
+S4T.12KV.442.250.08-7.2 IT -- -- -- -- -- -- --
3011054.200 S 2 200 298 288 278 269 258 247 235
+S4T.12KV.442.200.08-7.2 IT 203 207 199 192 184 176 169
3010953.160 S 2 160 252 244 236 227 219 209 199
+S4T.12KV.442.160.08-7.2 IT 196 189 183 176 170 163 155
3011054.315 S 1 315 269 260 251 242 232 222 213
+S4T.12KV.442.315.08-7.2 IT 192 186 179 173 167 159 152
3011054.250 S 1 250 237 231 222 215 206 197 188
+S4T.12KV.442.250.08-7.2 IT 175 170 164 158 152 145 138
3011054.200 S 1 200 189 185 178 171 165 158 150
+S4T.12KV.442.200.08-7.2 IT 139 134 130 125 121 116 110
3010953.160 S 1 160 154 154 154 153 147 141 134
+S4T.12KV.442.160.08-7.2 IT 127 123 119 115 110 106 101
3010953.125 S 1 125 121 121 121 119 115 107 103
+S4T.12KV.442.125.08-7.2 IT 113 110 106 102 98 94 89
3010853.100 S 1 100 100 100 100 100 100 96 95
+S4T.12KV.442.100.08-7.2 IT 98 98 98 95 91 87 83
3010853.80 S 1 80 80 80 80 80 80 80 80
+S68T.12KV.442.080.08-7.2 IT 78 78 78 78 78 78 77
3010853.63 S 1 63 63 63 63 63 63 63 63
+S68T.12KV.442.063.08-7.2 IT 63 63 63 63 63 63 63
3010853.50 S 1 50 50 50 50 50 50 50 50
+S68T.12KV.442.050.08-7.2 IT 50 50 50 50 50 50 50
For rated fuse currents < 63 A, no current reduction must be considered
due to the ambient temperature

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 126 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17.4.2 Technical data of fuses type SIBA / Inter-teknik for motor application of
contactor panel 435mm - 3TM33 – 450A
Current carrying capacity of fuses in contactor panel
Un Ith f Type SIBA (S) Number In HV HRC fuse Current carrying capacity in A
Inter-teknik (IT) per phase at ambient temperature in °C
kV kA Hz (A) 25°C 30°C 35°C 40°C 45°C 50°C 55°C
7.2 ≤ 40 50 3011054.250 S 2 250 351 340 328 316 304 291 278
+S4T.12KV.442.250.08-7.2 IT -- -- -- -- -- -- --
3011054.200 S 2 200 304 294 284 274 263 252 240
+S4T.12KV.442.200.08-7.2 IT 217 211 203 196 188 180 172
3010953.160 S 2 160 257 249 241 232 223 213 203
+S4T.12KV.442.160.08-7.2 IT 200 193 187 180 173 166 185
3011054.315 S 1 315 274 265 256 247 237 227 217
+S4T.12KV.442.315.08-7.2 IT 196 190 183 177 170 162 155
3011054.250 S 1 250 242 236 227 219 210 201 192
+S4T.12KV.442.250.08-7.2 IT 179 173 167 161 155 148 141
3011054.200 S 1 200 193 189 182 174 168 161 153
+S4T.12KV.442.200.08-7.2 IT 142 137 133 128 123 118 112
3010953.160 S 1 160 160 160 160 156 150 144 137
+S4T.12KV.442.160.08-7.2 IT 127 123 119 115 110 106 101
3010953.125 S 1 125 125 125 125 121 117 109 105
+S4T.12KV.442.125.08-7.2 IT 113 110 106 102 98 94 89
3010853.100 S 1 100 100 100 100 100 100 100 97
+S4T.12KV.442.100.08-7.2 IT 100 100 100 97 93 89 85
3010853.80 S 1 80 80 80 80 80 80 80 80
+S68T.12KV.442.080.08-7.2 IT 80 80 80 80 80 80 79
3010853.63 S 1 63 63 63 63 63 63 63 63
+S68T.12KV.442.063.08-7.2 IT 63 63 63 63 63 63 63
3010853.50 S 1 50 50 50 50 50 50 50 50
+S68T.12KV.442.050.08-7.2 IT 50 50 50 50 50 50 50
For rated fuse currents < 80 A, no current reduction must be considered due
to the ambient temperature
60 3011054.250 S 2 250 344 333 321 310 298 285 272
+S4T.12KV.442.250.08-7.2 IT -- -- -- -- -- -- --
3011054.200 S 2 200 298 288 278 269 258 247 235
+S4T.12KV.442.200.08-7.2 IT 203 207 199 192 184 176 169
3010953.160 S 2 160 252 244 236 227 219 209 199
+S4T.12KV.442.160.08-7.2 IT 196 189 183 176 170 163 155
3011054.315 S 1 315 269 260 251 242 232 222 213
+S4T.12KV.442.315.08-7.2 IT 192 186 179 173 167 159 152
3011054.250 S 1 250 237 231 222 215 206 197 188
+S4T.12KV.442.250.08-7.2 IT 175 170 164 158 152 145 138
3011054.200 S 1 200 189 185 178 171 165 158 150
+S4T.12KV.442.200.08-7.2 IT 139 134 130 125 121 116 110
3010953.160 S 1 160 154 154 154 153 147 141 134
+S4T.12KV.442.160.08-7.2 IT 127 123 119 115 110 106 101
3010953.125 S 1 125 121 121 121 119 115 107 103
+S4T.12KV.442.125.08-7.2 IT 113 110 106 102 98 94 89
3010853.100 S 1 100 100 100 100 100 100 96 95
+S4T.12KV.442.100.08-7.2 IT 98 98 98 95 91 87 83
3010853.80 S 1 80 80 80 80 80 80 80 80
+S68T.12KV.442.080.08-7.2 IT 78 78 78 78 78 78 77
3010853.63 S 1 63 63 63 63 63 63 63 63
+S68T.12KV.442.063.08-7.2 IT 63 63 63 63 63 63 63
3010853.50 S 1 50 50 50 50 50 50 50 50
+S68T.12KV.442.050.08-7.2 IT 50 50 50 50 50 50 50
For rated fuse currents < 63 A, no current reduction must be considered due
to the ambient temperature

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 127 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17.4.3 Technical data of fuses type SIBA / Inter-teknik for motor application of
contactor panel 435mm - 3TM34 – 450A
Current carrying capacity of fuses in contactor panel

Un Ith f Type SIBA (S) Number In HV HRC fuse Current carrying capacity in A
at ambient temperature in °C
Inter-teknik (IT) per phase

kV kA Hz (A) 25°C 30°C 35°C 40°C 45°C 50°C 55°C

12 ≤ 40 50 30 103 53.160 S 2 160 224 217 209 202 194 185 177

+S4T.12KV.442.160.08 IT 200 193 187 180 173 766 158

30 103 53.160 S 1 160 136 132 128 123 118 113 108

+S4T.12KV.442.160.08 IT 130 126 121 117 112 108 103

30 102 53.125 S 1 125 105 102 99 95 91 87 83

+S4T.12KV.442.125.08 IT 115 112 108 104 100 96 91

30 102 53.100 S 1 100 84 82 79 76 73 70 67

+S4T.12KV.442.100.08 IT 100 100 100 97 93 89 85

30 102 53.80 S 1 80 69 67 64 62 60 57 54

+S68T.12KV.442.080.08 IT 80 80 80 80 80 80 79

30 101 53.63 S 1 63 59 57 55 53 51 49 46

+S68T.12KV.442.063.08 IT 63 63 63 63 63 63 63

30 101 53.50 S 1 50 47 45 44 42 40 39 37

+S68T.12KV.442.050.08 IT 50 50 50 50 50 50 50

For rated fuse currents < 50 A, no current reduction must be considered due
to the ambient temperature

60 30 103 53.160 S 2 160 211 205 198 190 183 175 167

+S4T.12KV.442.160.08 IT 196 189 183 176 180 163 155

30 103 53.160 S 1 160 132 128 124 119 115 110 105

+S4T.12KV.442.160.08 IT 127 123 119 115 110 106 101

30 102 53.125 S 1 125 102 99 96 92 88 85 81

+S4T.12KV.442.125.08 IT 113 110 106 102 98 94 89

30 102 53.100 S 1 100 82 79 76 74 71 68 65

+S4T.12KV.442.100.08 IT 98 98 98 95 91 87 83

30 102 53.80 S 1 80 67 65 62 60 58 55 53

+S68T.12KV.442.080.08 IT 80 78 78 78 78 78 77

30 101 53.63 S 1 63 57 55 53 51 49 47 45

+S68T.12KV.442.063.08 IT 63 63 63 63 63 63 63

30 101 53.50 S 1 50 45 44 42 40 39 37 36

+S68T.12KV.442.050.08 IT 50 50 50 50 50 50 50

For rated fuse currents < 50 A, no current reduction must be considered due
to the ambient temperature

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 128 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

Type designation for all possible rated fuse currents for motor application, fuse length “e”, order number

Ur In HV HRC fuse Dimension “e” HV HRC fuse-link

(kV) (A) (mm) Order no.: Type SIBA

Inter-teknik

7.2 50 442 3010853.50 HHD – BM SIBA

+S68T.12KV.442.050.08- ------ Inter-teknik


7.2

63 442 3010853.63 HHD - BM SIBA

+S68T.12KV.442.063.08- ------ Inter-teknik


7.2

80 442 3010853.80 HHD - BM SIBA

+S68T.12KV.442.080.08- ------ Inter-teknik


7.2

100 442 3010853.100 HHD - BM SIBA

+S4T.12KV.442.100.08-7.2 ------ Inter-teknik

125 442 3010953.125 HHD - BM SIBA

+S4T.12KV.442.125.08-7.2 ------ Inter-teknik

160 442 3010953.160 HHD - BM SIBA

+S4T.12KV.442.160.08-7.2 ------ Inter-teknik

200 442 3011054.200 HHD - BM SIBA

+S4T.12KV.442.200.08-7.2 ------ Inter-teknik

250 442 3011054.250 HHD - BM SIBA

+S4T.12KV.442.250.08-7.2 ------ Inter-teknik

315 442 3011054.315 HHD - BM SIBA

+S4T.12KV.442.315.08-7.2 ------ Inter-teknik

12 50 30 101 53.50 HHD - BM SIBA


442
+S68T.12KV.442.050.08 ------ Inter-teknik

63 30 101 53.63 HHD - BM SIBA


442
+S68T.12KV.442.063.08 ------ Inter-teknik

80 30 102 53.80 HHD - BM SIBA


442
+S68T.12KV.442.080.08 ------ Inter-teknik

100 30 102 53.100 HHD - BM SIBA


442
+S4T.12KV.442.100.08 ------ Inter-teknik

125 30 102 53.125 HHD - BM SIBA


442
+S4T.12KV.442.125.08 ------ Inter-teknik

160 30 103 53.160 HHD - BM SIBA


442
+S4T.12KV.442.160.08 ------ Inter-teknik

Required extension tubes for fuses with “e” < 442 mm

Order no.: SIBA HV HRC fuse-link with dimension “e”

3400602 192 mm

3400601 292 mm

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 129 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

Table for selection fuses depending on starting conditions of motor – type SIBA / Inter-teknik

Starting Number Maximum permissible motor starting current in A at rated current and number of HV HRC fuse-links per phase in A
time of of starts
motor per hour SIBA (S) / Inter-teknik (IT)

1 x 50 1 x 63 1 x 80 1 x 100 1 x 125 1 x 160 1 x 200 1 x 250 1 x 315 2 x 160 2 x 200 2 x 250

4s 2 S 131 165 210 310 418 566 765 1283 1600 1132 1530 2566

IT 90 130 180 250 300 400 470 615 750 720 846 -

4 S 118 148 190 278 375 509 687 1153 1450 1018 1374 2306

IT 81 117 162 225 270 355 425 550 680 639 765 -

8 S 107 134 170 252 340 461 622 1044 1350 922 1244 2088

IT 73 105 146 195 240 310 375 485 590 558 675 -

16 S 95 120 155 225 304 413 557 935 1200 826 1114 1870

IT 66 95 131 180 225 290 345 435 535 522 621 -

32 S 87 109 140 205 276 374 505 848 1080 748 1010 1696

IT 59 85 118 165 195 275 310 410 500 495 558 -

15 s 2 S 112 139 190 254 344 459 641 1007 1300 918 1282 2014

IT 81 117 162 240 275 355 425 530 630 639 765 -

4 S 101 125 165 228 309 412 575 905 1180 824 1150 1810

IT 73 105 146 205 250 315 380 475 575 567 684 -

8 S 91 113 148 207 280 374 521 819 1080 748 1048 1638

IT 66 95 131 185 220 275 335 420 500 495 603 -

16 S 82 102 138 185 251 335 467 734 950 670 934 1468

IT 59 85 118 170 205 250 310 385 455 450 558 -

32 S 74 92 121 168 228 303 423 666 880 606 846 1332

IT 53 77 106 155 185 230 285 355 420 414 513 -

30 s 2 S 99 126 165 229 303 406 552 865 1150 812 1104 1730

IT 69 99 138 185 230 300 360 440 520 540 648 -

4 S 89 113 150 206 272 365 496 777 1040 730 992 1554

IT 62 90 124 170 205 265 325 400 455 477 585 -

8 S 81 102 138 186 247 330 449 704 920 660 898 1408

IT 56 81 112 150 180 240 290 350 410 432 522 -

16 S 72 92 130 167 221 296 403 630 860 592 806 1260

IT 50 72 100 140 165 210 260 310 370 378 468 -

32 S 65 83 115 151 200 268 365 572 760 536 730 1144

IT - - - - - - - - - - - -

60 s 2 S 91 114 145 204 273 357 501 777 950 714 1102 1554

IT 59 85 117 155 196 255 306 374 442 459 551 -

4 S 82 103 135 183 246 321 450 698 860 642 900 1369

IT 53 76 105 145 174 225 276 340 387 405 497 -

8 S 74 93 123 166 222 291 407 632 790 582 814 1264

IT 47 68 95 130 153 204 247 298 349 367 444 -

16 S 66 83 115 149 199 260 365 566 740 520 730 1132

IT - - - - - - - - - - - -

32 S 60 76 100 135 181 236 331 514 660 472 662 1028

IT - - - - - - - - - - - -

Detailed information regarding fuses also in intranet:

https://intranet.wss02.ptd.siemens.de/content/00001122/AIS_Common/HH-SiSchuetz_Kennlinien.pdf

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 130 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

Table selection of short-circuit current ratings of current transformer Type 4MB61 in contactor panel depending on used HV-
fuse
Calculation example given in table below (ID = cut off current of fuse) – Type SIBA (S) / Inter-teknik (IT)

Ur HV HRC fuse-link Dimension Number In HV HRC fuse ID for Ik = ID for Ik = ID for Ik =


“e” per phase 25kA 31,5kA 40kA

(kV) Order no.: Type (mm) (A) (kA) (kA) (kA)

7.2 3010853.50 S HHM 442 1 50 5,3 5,8 6,3

+S68T.12KV.442.050.08- IT --- 7,3 7,9 8,6


7.2

3010853.63 S HHM 442 1 63 6 6,6 7,1

+S68T.12KV.442.063.08- IT --- 8,3 8,9 9,7


7.2

3010853.80 S HHM 442 1 80 6,5 7 7,6

+S68T.12KV.442.080.08- IT --- 10,8 11,7 12,7


7.2

3010853.100 S HHM 442 1 100 8,4 9,1 10

+S4T.12KV.442.100.08-7.2 IT --- 13,3 14,4 15,6

3010953.125 S HHM 442 1 125 10 11 12

+S4T.12KV.442.125.08-7.2 IT --- 14,2 15,3 16,6

3010953.160 S HHM 442 1 160 14 15 16

+S4T.12KV.442.160.08-7.2 IT --- 16,6 17,9 19,4

3011054.200 S HHM 442 1 200 17 18 20

+S4T.12KV.442.200.08-7.2 IT --- 17,7 19,1 20,7

3011054.250 S HHM 442 1 250 23 24 26

+S4T.12KV.442.250.08-7.2 IT --- 25,5 27,5 29,8

3011054.315 S HHM 442 1 315 29 31 33

+S4T.12KV.442.315.08-7.2 IT --- 28,7 31 33,5

3010953.160 S HHM 442 2 160 22 24 27

+S4T.12KV.442.160.08-7.2 IT --- 26,4 28,5 30,9

3011054.200 S HHM 442 2 200 27 29 32

+S4T.12KV.442.200.08-7.2 IT --- 28,1 30,4 32,9

3011054.250 S HHM 442 2 250 37 39 42

+S4T.12KV.442.250.08-7.2 IT --- 40,5 43,7 47,3

Table selection of short-circuit current ratings of current transformer Type 4MB61 in contactor panel depending on used HV-fuse
Calculation example given in table below (ID = cut off current of fuse) – Type SIBA (S) / Inter-teknik (IT)

Ur HV HRC fuse-link Dimension Number In HV HRC fuse ID for Ik = ID for Ik = ID for Ik =


“e” per phase 25kA 31,5kA 40kA

(kV) Order no.: Type (mm) (A) (kA) (kA) (kA)

12 30 101 53.50 S HHM 1 50 5,3 5,8 6,3


442
+S68T.12KV.442.050.08 IT --- 7,3 7,9 8,6

30 101 53.63 S HHM 1 63 6,2 6,7 7,2


442
+S68T.12KV.442.063.08 IT --- 8,3 8,9 9,7

30 102 53.80 S HHM 1 80 6,6 7,2 7,7


442
+S68T.12KV.442.080.08 IT --- 10,8 11,7 12,7

30 102 53.100 S HHM 1 100 8,5 9,3 10


442
+S4T.12KV.442.100.08 IT --- 13,3 14,4 15,6

30 102 53.125 S HHM 1 125 10 11 12


442
+S4T.12KV.442.125.08 IT --- 14,2 15,3 16,6

30 103 53.160 S HHM 1 160 14 15 17


442
+S4T.12KV.442.160.08 IT --- 16,6 17,9 19,4

30 103 53.160 S HHM 2 160 22 24 27


442
+S4T.12KV.442.160.08 IT --- 26,4 28,5 30,9

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 131 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

Design example for selection of fuses and current transformer depending on motor data
Motor data, example Motor data, example
Ub = 6 kV
Ik” = 25 kA In = P / Ubx√3x cos φx η = 900 kW / 6 kVx√3x0.85x0.85 = 120 A
P = 900 kW
cos φ = 0.85 Ia = 6 x In = 720 A
η = 0.85
Ia = 6 x In The rated operating current of the HV HRC fuse should be read from the above shown table
max. 2 starts per hour using the data given: 200 A
max. starting time 5s
Definitions Selection of current transformers

Ia = starting current of motor The cut-off current of a fuse with 200 A rated current is for Ik” = 25 kA short circuit value: 18 kA
Idyn = max. peak current of current transformer (depending on characteristic of fuse for these values, see also above mentioned link to
ID = cut-off current of fuse intranet)
Ik” = short circuit current (r.m.s. value)
In = rated current of motor Thermal stressing of current transformer by the short time current rating Ith is negligible as a
Ith = short time withstand current result of current limiting by the HV HRC fuses. The current transformer must be capable of
P = rated motor power withstanding mechanical stress due only to the cut-off current ID. In this connection the cut-off
cos φ = Power factor of motor current ID is equivalent to the peak current of current transformer Idyn.
η = motor efficiency
Idyn ≥ ID

Ith = Idyn / 2.5 = 18 kA / 2.5 = 7,2 kA

The current transformer must be designed for an Ith of ≥ 7,2 kA


selection guide according to contactor or circuit breaker for motor switching applications
Selection of switching device for motors is influenced by following key factors:

 rated voltage of network and motor


 frequency of network
 rated power of motor
 rated current of motor
 required switching cycles based on application of motor in production process
 power factor cos φ of motor
 motor efficiency factor η
 starting current of motor
 number of starts per hour
 starting time of motor
 max. number and rated current of fuses which can be installed in panel when contactor is used,
 ambient temperature of switchgear room
 for contactors lower rated lightning impulse withstand voltages across the open contact gap as circuit breakers are required based on
different standards
(at 7.2 kV: 40 kV instead of 60 kV, at 12 kV: 60 kV instead of 75 kV)

Additional to above mentioned key factors protection and primary cable philosophy have to be considered. Protection philosophy is influenced by
significance and importance of motor in process while using differential protection relays in combination with circuit breakers or over current
protection in combination with fuses and contactors.
Due to current limiting function of fuses in combination with contactors cross section of primary cables can be optimized.

Based on above mentioned key factors following advice for selecting contactor with fuses can be given:

Max. fuses which can be installed in contactor panels:

NXAIR switchgear: 7.2 kV: single fuse per phase 1 x 315 A, parallel fuses per phase 2 x 250 A
12 kV: single fuse per phase 1 x 160 A, parallel fuses per phase 2 x 160 A

NXAIR P switchgear: 7.2 kV: single fuse per phase 1 x 315 A, parallel fuses per phase 2 x 250 A

Depending on max. permissible current values of complete contactor panel including fuses with above mentioned ratings in NXAIR and NXAIR P
switchgear,
based on 35° C ambient temperature of switchgear room,
rated voltage of motor for 7.2 kV application: 6.6 kV
rated voltage of motor for 12 kV application: 11 kV
power factor cos φ = 0,9
motor efficiency η = 0,9
following average power values of motors can be switched with fused contactor units:

7.2 kV: ≈ 3000 kW


12 kV: ≈ 3000 kW

For higher power values of motors circuit breakers should be checked.

Detailed calculation based on precise figures and specific conditions on site can vary above mentioned result.

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 132 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17.5 Technical data of switch-disconnector- fuse combination L-TRI 5F


17.5.1 Switching device (Schneider L-TRI 5 F/24/200/250-UH-KS-A EUI)
1.)
Rated voltage kV 24
Rated frequency Hz 50 / 60
Rated short-duration power frequency withstand voltage kV 38, IEC
Phase/phase, phase/earth, open contact gap 42, GOST

Rated lightning impulse withstand voltage kV 95, IEC, GOST


Phase/phase, phase/earth, open contact gap
Rated short-duration power frequency withstand voltage kV 45, IEC
Over open disconnecting distance 48, GOST
Rated lightning impulse withstand voltage kV 110, IEC, GOST
Over open disconnecting distance
Rated short-time withstand current of main circuits kA 16
Rated duration of short circuit s 1
Rated peak withstand current kA 40
Rated short circuit making current kA 40
2.)
Rated normal current Ir A 200
Number of operations with short-circuit making current Ima / Classification 2 / E1
Rated mainly active load breaking current Iload (20 x ) A 200
Rated mainly active load breaking current Iload (200 x ) A 32
Rated transformer breaking current A 10
Rated cable-charging breaking current and line-charging breaking current A 50
3.)
Mechanical operation cycles 1500
contacts of auxiliary switch of breaker 4NC+4NO

Earthing switch
Rated short-time withstand current kA 16
Rated duration of short circuit s 1
Rated peak withstand current kA 40
Rated short circuit making current kA 40
Number of operations with short-circuit making current Ima / Classification 2 / E1
contacts of auxiliary switch of earthing switch 4NC+4NO

HV-fuses
Dimension “e” of HV-fuse mm 442
Ratings (depending on transformer rating) A 6,3 - 80

1) 24 kV type load break switch assembled in SDF, but operated max. Up to 17,5 kV
2) general the rated current of a switch disconnector-fuse combination is lower than the rated current specified by the fuse manufacture
3) 1000 mechanical operation cycles when assembled in SDF

17.5.2 Selection table of the fuses for protection of transformers


Transformer Transformer rated output (kVA) Fuse
rated voltage rated voltage
[kV] [kV]
50 100 160 200 250 315 400 500 630 800 1000 1250 1600

Rated current of SIBA HHD Fuse-link In [A]

3 25 40 63 80 80 --- --- --- --- --- --- --- ---


5 16 20 40 40 50 63 80 80 --- --- --- --- --- 3,6 / 7,2
BSSK types 6/12
6 16 20 31,5 40 50 63 80 80 --- --- --- --- ---
BSSK BSSK

10 10 16 20 25 31,5 40 50 63 80 80 --- --- ---


BSSK BSSK
6/12
12 6,3 16 20 25 31,5 40 50 50 63 80 --- --- ---
BSSK

15 6,3 10 16 20 20 25 31,5 40 40 50 63 80 --- 10/17,5


BSSK BSSK
BSSK types
10/24

Protection plan without using a LV fuse-link on the low voltage side for overload protection of the transformer; the individual cable exits are protected with a
LV Fuse-Link operating class gL/gG

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 133 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17.6 Technical data of SIQuench (Arc Quenching Device)


Rated voltage kV 12 17,5
Rated frequency Hz 50 / 60 50 / 60
Rated short-duration power frequency withstand voltage kV 28, IEC 38, IEC
32, GOST 42, GOST
Phase/phase, phase/earth, open contact gap
Rated lightning impulse withstand voltage kV 75, IEC, GOST 95, IEC, GOST
Phase/phase, phase/earth, open contact gap
Rated short-time withstand current of main circuits kA 40 40
Rated duration of short circuit s 1/3 1/3
Rated peak withstand current kA 104 104
Rated short circuit making current kA 104 104
Number of operation with short-circuit making current Ima / Classification 5 / E2 5 / E2
Mechanical operation cycles 30 30

17.7 Technical data of earthing switches with short circuit making capacity
Circuit breaker panel Contactor panel SDF panel
Technical data 435 mm
Rated voltages kV up to 17,5 up to 12 up to 17,5
Rated frequency Hz 50 / 60 50 / 60 50 / 60
Rated short-duration power frequency withstand voltage kV 38, IEC 28, IEC 38, IEC
Phase/phase, phase/earth 42, GOST
Rated lightning impulse withstand voltage kV 95, IEC 75, IEC, GOST 95, IEC
Phase/phase, phase/earth
3)
Rated short-time withstand current Ik kA ≤ 40 6,3 16
3)
Rated short time duration tk s 3 1 1
3)
Rated peak withstand current Ip kA ≤ 100 at 50 Hz, ≤ 15,8 at 50 Hz, ≤ 40 at 50 Hz,
104 at 60 Hz 16,4 at 60 Hz 42 at 60 Hz
Rated short-circuit making current 3) kA ≤ 100 at 50 Hz, ≤ 15,8 at 50 Hz, ≤ 40 at 50 Hz,
104 at 60 Hz 16,4 at 60 Hz 42 at 60 Hz
Solidly earthed neutral (single phase)
Rated short-time withstand current Ike 3) kA ≤ 40 n.a. n.a.
3)
Rated short time duration tke s 3 n.a. n.a.
Rated peak withstand current Ipe 3) kA ≤ 100 at 50 Hz, n.a. n.a.
104 at 60 Hz
Isolated, resonance or impedance earthed neutral (single
phase)
Rated short-time withstand current Ike 3) A 60 n.a. n.a.
Rated short time duration tke 3) h 24 n.a. n.a.
Rated peak withstand current Ipe 3) A 150 at 50 Hz, n.a. n.a.
150 at 60 Hz
Operating mechanism
Hand operated Standard Standard Standard
Motor operated option not possible not possible
Interlockings
Cable earthing Mechanical to withdrawable part Standard Standard Standard
Mechanical and electrically option Not possible option
Busbar earthing padlockable Standard --- ---
electrically option --- ---
Power consumption of motor mechanism 30 W
Motor running time for switching “ON” or “OFF” appr. 9 s up to 14 s (depending on STC rating)
Switch classification 2) electrically mechanically
E1 M0
contacts of auxiliary switch of earthing switch 4) 4 NC+4 NO

1) cassette design is standard, truck type design as option possible (then withdrawable voltage transformers in connection compartment are excluded)
2) see also chapter 16.9
3) in contactor panel and SDF panel limited due to cut off function of fuses
4) number of free auxiliary switch contacts depending on kind of interlocking and are shown detailed in engineering drawings

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 134 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17.8 Technical data of withdrawable part for circuit breaker, disconnector link, metering module
Mechanism 1) hand operated Standard
motor operated optionally for withdrawable part with
circuit breaker or disconnector
interlockings Mechanical to circuit Standard
breaker position
padlockable option
key interlocking device option
Switch classification 2) mechanically
M0
contacts of auxiliary switch of withdrawable part 4) 6 NC+6 NO free contacts for external use
contacts “fuse tripped indication” for metering unit 1 NC + 1NO
Power consumption motor mechanism auxiliary voltage DC 35 W
Time for moving withdrawable part from test to service position or vice versa appr. 22 s up to 37 s (depending on weight of withdrawable
part)

17.9 Switching classifications of breaker, withdrawable part, earthing switch


Circuit breaker Withdrawable Earthing switch SIQuench
part
Electrically mechanically Capacitive mechanically electrically mechanically electrically mechanicall
switching y
capability
E2 M2 C2 M0 E1 M0 E2 ---
56xIp, 130x10% 10.000 cycles very low 1.000 cycles 2 x Ima 1.000 cycles 5 x Ima 30 cycles
Isc probability Ima=making Ima=making
130x30% Isc, of restrikes current (peak current (peak
8x60% Isc value) value)
6x100% isc
Ip= peak current
Isc=short circuit
breaking current

17.10 Position indication of electrical devices


Circuit breaker Mechanical indication through high voltage door, included in single line
Withdrawable part Mechanical indication ON / OFF, included in single line 1)

Earthing switch feeder Mechanical indication ON / OFF, included in single line


Earthing switch busbar Mechanical indication ON / OFF
Switch fixed mounted not released for sales
Contactor Mechanical indication ON / OFF

1) except 435 mm wide vacuum contactor panel, where position of withdrawable part is seen through high voltage door

17.11 Power consumptions of electrical devices


device power consumption
Circuit breaker 3AE2 and 3AE5 Motor for spring charging, DC 100 W to 140 W
Motor for spring charging, AC 170 VA to 200 VA
Running time of motor 10 s
Contactor 3TM Drive solenoid, making capacity 700 VA
Drive solenoid, holding power 10 -20 VA
Mechanical closing latch, power consumption of the 160 VA
latch release solenoid
Withdrawable part Motor mechanism DC 35 W
Running time of motor Appr. 25 s
Earthing switch busbar or feeder Motor mechanism DC 35 W
Running time of motor appr. 25 s
Electrical interlocking magnets Only active in releasing function 10 W, suitable for continuos energisation

SIQuench Controller Max. 20 W / 50 VA; type: 10 W / 20 VA

heaters Circuit breaker compartment 100 W


Cable compartment 100 W
Low voltage compartment 20 W
fan above circuit breaker compartment 500 W at 50/60 Hz

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 135 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17.12 Configuration information pressure release system


17.12.1 Application of pressure release channel to lead gases due to internal arc out of the switchgear (for standard and for
duplex in back-to-back arrangement)
Rated voltage IAC-classification Arc fault current Arc fault Height of switchgear room Pressure relief system
duration
≤ 12 kV IAC A FLR ≤ 25 kA 1 s or 0.1 s ≥ 2500 mm duct to outside
≥ 2800 mm absorbers
31.5 kA 1 s or 0.1 s ≥ 2500 mm duct to outside
≥ 3000 mm absorbers
40 kA 1 s or 0.1 s ≥ 2500 mm duct to outside
≥ 3500 mm absorbers
17.5 kV IAC A FLR ≤ 25 kA 1 s or 0.1 s ≥ 2500 mm duct to outside
> 3500 mm absorbers
31.5 kA 1 s or 0.1 s ≥ 2500 mm duct to outside
≥ 3500 mm absorbers
40 kA 1 s or 0.1 s ≥ 2500 mm duct to outside
≥ 3500 mm absorbers

17.12 Configuration information pressure release system


17.12.2 Application of pressure release channel system to lead gases due to internal arc out of the switchgear in
combination with roof for IPX1 or IP X2 – also IP51 (not for duplex in back-to-back arrangement)
Rated voltage IAC-classification Arc fault current Arc fault Height of switchgear room Pressure relief system
2)
duration
≤ 12 kV IAC A FLR ≤ 25 kA 1 s or 0.1 s ≥ 2800 mm duct to outside
≥ 3000 mm absorbers
31.5 kA 1 s or 0.1 s ≥ 2800 mm duct to outside
≥ 3000 mm absorbers
40 kA 1 s or 0.1 s ≥ 2800 mm duct to outside
≥ 3500 mm absorbers
17.5 kV IAC A FLR ≤ 25 kA 1 s or 0.1 s ≥ 2800 mm duct to outside
> 3500 mm absorbers
31.5 kA 1 s or 0.1 s ≥ 2800 mm duct to outside
≥ 3500 mm absorbers
40 kA 1 s or 0.1 s ≥ 2800 mm duct to outside
≥ 3500 mm absorbers

17.12 Configuration information pressure release system (NXAIR for marine application)
17.12.3 Application of pressure release channel system to lead gases due to internal arc out of the switchgear
Rated voltage IAC-classification Arc fault current Arc fault Height of switchgear room Pressure relief system 1.)
2)
duration
≤ 12 kV IAC A FLR ≤ 25 kA 1 s or 0.1 s ≥ 2800 mm exhaust pipe
31.5 kA 1 s or 0.1 s ≥ 2800 mm exhaust pipe
40 kA 1 s or 0.1 s ≥ 2800 mm exhaust pipe

1) without pressure release channel to lead gases out of the switchgear room (only in combination with exhaust pipe to lead the hot gases into the
switchgear room)
2) NXAIR always IAC tested with 1 sec, 0.1 sec only with additional arc fault limitation systems possible (switchgear design the same as for 1 sec)

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 136 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17.12 Configuration information pressure release system (standard)


17.12.4 Channel devices of pressure release channel system to lead gases due to internal arc outside switchgear room
General all type tests in accordance to IEC 62271-200 will be made on representative functional units. As mentioned in this IEC it is not
practicable to make for all arrangements of switchgear special type tests. Because of the variety of types, ratings and possible combinations of
components it is possible in accordance to standard that the performance of any particular arrangement may be substantiated by test data or
simulation calculations of comparable arrangements. Due to this and the fact that each switchgear room never will have exactly same
dimensions, installed equipment etc., the functionality of this channel system has been evaluated by type tests in combination with simulation
calculations.

All parts of channel system are included in accessories of NXAIR, chapter 7, and can be configurated with NX-Tools+ and will be delivered
together with switchgear.

Channel parts consists of zinc coated steel, thickness 2 mm, screws M8, following parts can be plugged and screwed together, cross section
530 mm x 245 mm:
 Adapter device at standard pressure relief channel to left, will be configurated with NX-Tools+
 Adapter device at standard pressure relief channel to right, will be configurated with NX-Tools+
 Adapter device at standard pressure relief channel to rear, will be configurated with NX-Tools+
 Adapter device at standard pressure relief channel to the top, will be configurated with NX-Tools+
 Channel, length 1000 mm, ordering number 8BX3400-0AA00-0AA0
 Angle channel 45° up / down, ordering number 8BX3400-0AA00-0AA1
 Angle channel 45° right / left, ordering number 8BX3400-0AA00-0AA2
 Channel, length 500 mm, ordering number 8BX3400-0AA00-0AA3
 Channel length extendable from 595 mm to 760 mm in 20 mm steps, ordering number 8BX3400-0AA00-0AA4
 Channel, length 400 mm for wall outgoing, powder coated RAL 7035, ordering number 8BX3400-0AA00-0AA5
 Channel, length 224 mm for wall outgoing, powder coated RAL 7035, ordering number 8BX3400-0AA00-0AB6
 Fixing ledges, ordering number per set 8BX3400-0AA00-0AA6
 Fixing angles, ordering number per set 8BX3400-0AA00-0AA7
 Channel, length 800 mm, ordering number 8BX3400-0AA00-0AB1
 Channel, length 600 mm, ordering number 8BX3400-0AA00-0AB2
 Channel, length extendable from 400 mm to 435 mm in 17,5 mm steps, ordering number 8BX3400-0AA00-0AB3
 Outlet flap (weatherproof), ordering number 8BX3400-0AA00-0AB7

Additional fixing parts must be organized on site.


Channel device Ordering number Drawing number Channel type

8BX3400-0AA00-0AA0 110-0523.3 Channel length 1000 mm

8BX3400-0AA00-0AA1 110-0533.3 Angle 45° rotatable


upwards or downwards

8BX3400-0AA00-0AA2 110-0534.3 Angle 45 ° rotatable right


or left

8BX3400-0AA00-0AA3 110-0540.3 Channel length 500 mm

8BX3400-0AA00-0AA4 110-0541.3 Channel extendable 595


mm to 760 mm in 20 mm
steps

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 137 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

Channel device Ordering number Drawing number Channel type

8BX3400-0AA00-0AA5 110-0537.3 Wall outlet box,


length 400 mm

8BX3400-0AA00-0AB6 129-2926.3 Wall outlet box,


length 224 mm

8BX3400-0AA00-0AA6 110-0535.3 Fixing ledges,


consisting of two parts

8BX3400-0AA00-0AA7 110-0536.3 Fixing angles,


Consisting of two parts

Channel length 800mm


8BX3400-0AA00-0AB1 119-0935.3

8BX3400-0AA00-0AB2 119-0936.3 Channel length 600mm

Channel extendable
8BX3400-0AA00-0AB3 119-0937.3
400 mm to 435 mm in 17,5
mm steps

8BX3400-0AA00-0AB0 110-0539.3 Channel length 260 mm,


IP4X

8BX3400-0AA00-0AB4 110-0538.3 Channel length 260 mm,


IP3XD

8BX3400-0AA00-0AB7 129-4325.3 Outlet flap (weatherproof)

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 138 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17.12.5 Principle version of pressure release channels, detailed drawing see intranet
A. Pressure relief to lateral side (left or right)

Front view

Top view

distance at rear side between switchgear and wall > = 150 mm for cable connection from front resp. >= 500 mm for cable
connection from rear
distance lateral > 150 mm resp. >=100 mm for contactor panel at one side of switchgear row resp. 500 mm at opposite side
of switchgear row where pressure relief duct is located

B. Pressure relief to rear side

Front view

Top view

distance at rear side between switchgear and wall > = 150 mm for cable connection from front resp. >= 500 mm for cable
connection from rear and for fixing of the rear duct at the back side
distance lateral > 150 mm resp. >=100 mm for contactor panel at one side of switchgear row resp. 500 mm at opposite side
of switchgear row

C. Pressure relief to the top

Front view

Top view

distance at rear side between switchgear and wall > = 150 mm for cable connection from front resp. >= 500 mm for cable
connection from rear
distance lateral > 150 mm resp. >=100 mm for contactor panel at one side of switchgear row resp. 500 mm at opposite side
of switchgear row
when pressure release duct is used at the top side at least between ceiling and switchgear row ≥ 500 mm for installation of
first duct element is recommended

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 139 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17.12.6 Configuration information pressure release channel system (dimensions for 31,5 kA as example)

Pressure release channel to left or right side, detailed drawings see intranet

Front view of switchgear, channel to lateral side view of switchgear, channel to lateral

Pressure release channel to rear side, detailed drawing see intranet

537
2248.5

2248.5
2000

2000

600
800
1000

Side view of switchgear, channel to rear Rear side of switchgear with channel to rear,
e.g. three panels

Pressure release channel to the top, detailed drawing see intranet

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 140 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17.12.7 Pressure relief - possible combinations depending on technical options


pressure relief to outside absorber
Panel configuration component To lateral (left To rear side To the top
or right side)
Top box with Voltage transformer --- --- --- ---
Earthing switch --- --- --- ---
SiQuench --- --- --- ---
Arresters --- --- --- ---

Ventilation system Closed X X X X


Natural ventilated X X --- ---
Forced ventilated X X --- ---

Connection at the busbar Cables --- --- --- ---


(through top box) Bars --- --- --- ---

Rear box for cable entry from the top Cables X --- X X

In combination with IP-roof IPX1 / IPX2 X X --- X

Duplex Back-to-back X --- X X


Front-to-front X X X X
Remarks In generall  pressure relief channel should be realized to lateral side, rear side or top side
 At least one panel of each busbar section (when bus sectionalizer is included)
must have one connected channel system to the top, lateral or rear side.
Length of switchgear and number of busbar device have no impact on
configuration of channel system

Rear side direction of  adaption to one single contactor panel is not possible, but in the middle of two
channel system: contactor panels possible, for all other panel types as mentioned above is
possible

Assembly  for fixing of the first element of the pressure relief duct to the adapter device
(delivered with the panel in standard) a space of minimum 500 mm is
recommended between ceiling and top of the panel or wall and side or rear of
the panel to get access to all bolting points

Absorber  At least one panel of each busbar section (when bus sectionalizer is included)
must have an absorber. Length of switchgear and number of busbar device
have no impact on configuration of channel system. NXTools+ generates
automatically the position of the absorber when starting the “switchgear check”

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 141 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17.13 Climate and ambient influences


In accordance to IEC 62271-200, IEC 62271-1

Ambient temperature does not exceed 40° C

Average value, measured over 24 h does not exceed 35°C

Minimum ambient temperature -5°C / -15°C / -25°C

Ambient air Not significantly polluted by dust, corrosive and/or flammable


gases, vapours or salt

Average value of relative humidity, measured over 24 h ≤ 95%

Average value of relative humidity, measured over 1 month ≤ 90%

Other special required ambient conditions in accordance to IEC 60721, 3-3

Conditions in switchgear room1) Additional measure to standard design of switchgear 1)

Climate in Ambient Relative Conden- Special heater Degree of Bolted All metal partitions Movable
switchgear tempe- humidity sation ambient protection joints inside panel contacts of
2)
room, Class rature conditions with painted in main circuits Additional
of climate special standard color all nickel-plated measures for
grease galvanized parts circuit breaker
treated specially 3) and current
transformers
resp. bushings

3K3 +5°C - 5 – 95% - - - IP3XD - -- -- --


+40°C
- - IP4X -
4)
3K5 -5°C - 5 – 95% occasionally, - yes IP3XD - -- -- yes
+45°C
1 per month - yes 4) IP4X -
for 2h
dust yes 4) IP50 5) -
4) 5)
vermin proof yes IP50 -

1) transport and commissioning not included

2) temperatures < - 5°C requires special measures (e.g. -25°C on request)

3) „DTO-design“ on special request

4) heaters are required for panels with ventilation (≥ 2000 A), for panels without ventilation not necessary

5) only possible for panels with rated current ≤ 1250 A and in combination with pressure relief duct to lead hot gases to outside

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 142 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17.14 Protection of voltage transformers with fuses, technical argumentation


Voltage transformer faults are – after cable termination faults – one of the most frequent sources of failure and cause of arcing faults of
switchboard. For this reason, appropriate protection measure needs to be taken into account. In order to avoid overloading at the secondary
winding the standard IEC 61936-1 requires protection on the secondary side.
IEC 61936-1, § 6.2.4.2.”The secondary side of voltage transformers shall be protected against the effects of short-circuits, and it is
recommended that protective devices (i.e. their tripping) be monitored.
The secondary cables of voltage transformers (like any other auxiliary and control wires) must be laid so that they are protected against
electrical and mechanical interference (see IEC/EN 62271-1, § 5.4.4.5.1). Protection with fuses on the primary side of voltage transformers
in not required in standards, nevertheless in some customer specification included.
Following technical reasons show that fuses on primary side of voltage transformers will not protect voltage transformers itself:
Failure: short circuit at secondary terminals of voltage transformers or secondary equipment:
Rated current on primary side at rated power: I1 = max. 100 mA at ≤ 12 kV; I1 = 50 mA at ≤ 24 kV
highest current on primary side at secondary terminal short circuit: I1 = max. 1 A
lowest rated current of fuses: IrHRC = 6 A
lowest breaking current of fuses: Imin HRC ≈ 25 A
fuses of primary side will not trip, due to: I1 << Imin HRC

Failure: short circuit within voltage transformer itself:


leads rapidly to thermal overload of voltage transformers, this leads to explosion of voltage transformer, this leads to arc fault outside voltage
transformer with current value depending on earthing of neutral point with ionising of air in the same compartment, depending on value of
this arc fault current and ionising rate of air fuse will trip and minimize damages of compartment or upstream circuit breaker have to trip this
internal arc, destruction of voltage transformers will not be avoided
Failure: short circuit on primary side of voltage transformers:
leads to arc fault outside voltage transformers with same effect as described one topic before
Conclusion:
HRC fuses on primary side of voltage transformers will not avoid destruction of voltage transformers. Secondary circuit fuses are sensible
and are recommended by VDE: Attention must be given to careful selection and installation so that their additional contact and internal
resistance do not lead to false measurement due to voltage drop. Resistance and limiting reactors fitted to a da-dn winding (former e-n
winding) to damp ferroresonances shall not be fitted with fuses, detailed information also:

17.15 Application of surge arrestors


Surge arrestors limit overvoltages by diverting thermal overvoltages which can be caused as external overvoltages by lightning strikes in
overhead lines or as internal overvoltages in the form of switching overvoltages or earth fault. They are normally installed in cable
compartment, please check table of max. possible installation combinations in cable compartment.
Surge arrestors are used to protect high voltage motors which are switched by vacuum circuit breakers or vacuum contactors with starting
current up to 600 A. For higher starting current these surge arrestors are not necessary. They are normally installed in cable compartment,
please check table of max. possible installation combinations in cable compartment.
Installation of surge arresters also possible at busbar in an additional top box (only for non-ventilated panels possible)

17.16 Packing dimensions and transport weights (tare) of packing 1)


switchgear data ≤ 17.5 kV, ≤ 31.5 kA, ≤ 2500 A
packing type Domestic transport, transport within Europe Seaworthy packaging
panel width (mm) 435 600 800 4) 1000 435 600 800 4) 1000
rated current feeder (A) ≤400 630 - 1250 - 2000 >1250 ≤400 630 - 1250 - 2000 >1250
1000 1000
packing depth 2) (mm) 1610 1610 1610 1610 1830 1830 1830 1830
packing width (mm) 800 800 1000 1200 820 820 1020 1220
packing height 2) (mm)
≤ 25 kA with/without absorber, 2510 2510 2510 2510 2541 2541 2541 2541
with extended low voltage box, 2560 2560 2560 2560 2541 2541 2541 2541
busbar devices
31.5 kA without absorber 2510 2510 2510 2510 2541 2541 2541 2541
without absorber, with extended 2560 2560 2560 2560 2541 2541 2541 2541
low voltage box, busbar devices
with absorber 2710 2710 2710 2710 2691 2691 2691 2691
packing weight 3) (kg) 29 32 34 37 130 130 144 155
switchgear data ≤ 17.5 kV, ≤ 31.5 kA, 3150/4000 A resp. ≤ 17.5 kV, 40 kA, ≤ 4000 A
packing type Domestic transport, transport within Europe Seaworthy packaging
panel width (mm) 435 800 800 4) 1000 435 800 800 4) 1000
rated current feeder (A) ≤400 ≤2000 ≥2500 >2000 ≤400 ≤2000 ≥2500 >2000
packing depth 2) (mm) 1700 1700 1700 1700 1722 1722 1722 1722
packing width (mm) 700 900 900 1100 820 1020 1020 1220
packing height (mm) 2510 2510 2510 2510 2531 2531 2531 2531
packing weight 3) (kg) 29 34 34 37 130 144 144 155

1) pressure release channel devices to outside to be checked separately


2) for panels in extended versions due to extended current transformers (1500 mm instead of 1350 mm resp. 1650 mm instead of 1500 mm) app. 150 mm
increased depth and for panels with rear side box for feeder connection from above additional to before mentioned appr. 600 mm increased depth have
to be considered,
3) for panels in extended versions due to extended current transformers (1500 mm instead of 1350 mm resp. 1650 mm instead of 1500 mm) appr. 10 kg per
panel must be added, for panels with rear side box for feeder connection from above appr. 20 kg have to be added for domestic transport / transport
within Europe resp. 40 kg have to be added for seaworthy packing
4) incl. SDF panel

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 143 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17.17 Weights of panels (appr., net weight)


≤ 17.5 kV, ≤ 31.5 kA, ≤ 2500 A ≤ 17.5 kV, ≤ 31.5 kA, 3150/4000 A
resp. ≤ 17.5 kV, 40 kA, ≤ 4000 A
contactor panel, 435 mm width ~ 680 - 750 kg ~ 700 - 770 kg
SDF panel, 800 mm width (without HV fuses) ~ 500 – 650 kg ~ 550 – 700 kg
Breaker panel, 600 mm width, 1000 A ~ 800 – 950 kg ---
Breaker or disconnecting panel, 800 mm width 1), 1250 A ~ 960 – 1170 kg ~ 1020 – 1320 kg
Breaker or disconnecting panel, 800 mm width 1), ≤ 2500 A ~ 1100 – 1250 kg ~ 1230 – 1650 kg
Breaker or disconnecting panel, 1000 mm width 1), ≤ 2500 A ~ 1100 – 1250 kg ~ 1230 – 1650 kg
Breaker or disconnecting panel, 800 mm width 1), 3150 A - ~ 1230 – 1650 kg
Breaker or disconnecting panel, 1000 mm width 1), 3150 A - ~ 1230 – 1650 kg
Breaker or disconnecting panel, 1000 mm width 1), 4000 A - ~ 1230 – 1650 kg
Bus riser panel of bus sectionalizer, 800 mm width ~ 800 kg ~ 1260 kg
Bus riser panel of bus sectionalizer, 800 mm width, 2500 A ~ 1100 kg ~ 1270 kg
Bus riser panel of bus sectionalizer, 1000 mm width, 2500 A ~ 1100 kg ~ 1320 kg
Bus riser panel of bus sectionalizer, 800 mm width, 3150 A - ~ 1470 kg
Bus riser panel of bus sectionalizer, 1000 mm width, 3150 A - ~ 1570 kg
Bus riser panel of bus sectionalizer, 1000 mm width, 4000 A - ~ 1590 kg
Metering panel, 800 mm width ~ 700 kg ~ 840 kg
Metering panel, 600 mm width ~ 650 kg ~ 750 kg
Busbar connecting panel, 800/1000 width ~ 1000 kg ~ 1180 kg

17.18 Transport and storage information


Temperature limits for transportation and storage - 25° C - +70° C for primary part
Electronic components in secondary part to be checked separately
Storage location (check also Packaging for domestic In original unpacked packing, in closed rooms,
detailed information in installation transport, transport within
manual) Europe
Seaworthy packaging If possible in closed room,
(6 months) Outdoor storage in original packaging for 12 month period

17.19 Painting, surface treatment


Front and endwalls Standard Powder coated RAL 7035 Preliminary treatment of steel:
of switchgear and Alkaline-acid spray degreasing and alkaline phosphatization,
optionally rear side Gardobond A 4932, forming a layer of 0.2 to 0.5 g/m²
wall Surface coating setup: powder coating baking 180°C – 200°C
Thickness: appr.: 75 to 125 μm
other steal parts Standard Zinc plated Standard: DIN EN 10327, DIN EN ISO 2081, Zn8/C
Thickness: appr: 20 μm resp. 275 g/m² zinc plated
complete optionally Powder coated RAL 7035 as discription above
switchgear
Parts of mechanism Chromium coated Parts of mechanism
Primary contacts movable contacts: Standard: DIN EN ISO 2819,
silver plated 20 + 6 μm Tested with temperature shock 250°C / 30 min.
fixed contacts: Fixed contacts if necessary: 3 +/- 2 μm
silver plated 25 + 6 μm

17.20 Cross section of earthing bar


Rated voltage (kV) Rated short-time withstand current (kA) Cross section (mm)
7.2 / 12 / 17.5 ≤ 31,5 kA 40 x 5
40 kA 40 x 10

17.21 Thickness of used steel sheets


Frame 2 mm
High voltage door 2.5 mm
Low voltage door 2 mm
Pressure release flaps 1 mm
Partitions between compartments 2 mm
Partition wall between panels 2 x 2 mm
Ground plate 2 mm
Rear side cover plates 2 mm / 2.5 mm at 40kA
End walls 2 mm

1) for panels with rear side box for feeder connection from above appr. 200 kg must be added

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 144 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17.22 Material of bottom plate in cable connection compartment

Panel rating Material 1 Material 2 Thickness


630-800 A (all nr of cables) galvanized galvanized 2mm
1000 A and higher current galvanized stainless 2mm
(all nr of cables)
All ratings Non-metallic (UPM-S16-Durostone) Non-metallic (UPM-S16-Durostone) 2 layers each of 5mm
Bottom plates consist of a combination of galvanized sheet metal and stainless sheets. The background is the heating effect of eddy
current around cables. Therefore half of the materials are used as non-magnetic (stainless steel). That is the reason why both materials
(galvanized and stainless) are used. This logic is valid for all currents except 630 A-800 A.
The eddy current at 630-800A is so low that no heating occurs. Therefore no nonmagnetic (stainless) sheet is needed for 630-800 A ratings.

17.23 Interlocks
device Interlocked with: Method
Withdrawable part Position of switching device on Standard: mechanically
withdrawable part
Feeder earthing switch Standard: mechanically
Circuit breaker Position of withdrawable part Standard: mechanically
Withdrawable part with disconnector link - Option: padlocked, Option: electrically
Feeder earthing switch Position of withdrawable part Standard: mechanically
Busbar earthing switch - Standard: padlocked, Option: electrically
High voltage door Position of withdrawable part Option: mechanically
Rear side cover of cable compartment when Feeder earthing switch Standard: with screws
cable connection from rear Option: padlocked

17.24 Used materials (average values)


Material / panel width 435 mm 600 mm 800 mm 1000 mm 800 mm (SDF)
steel ~ 500 kg ~ 600 kg ~ 700 kg ~ 800 kg ~ 450 kg
copper ~ 80 kg ~ 100 kg ~ 140 kg ~ 160 kg ~ 30 kg
Insulation material for current transformers, cast resin ~ 60 kg ~ 75 kg ~ 75 kg ~ 75 kg ~ 75 kg
Insulation material for bushing type insulators, cast resin ~ 40 kg ~ 50 kg ~ 50 kg ~ 50 kg ~ 5 kg
Aluminium ~ 5 kg ~ 15 kg ~ 15 kg ~ 20 kg 0 kg
Optional insulation of busbar, ~ 5 kg ~ 8 kg ~ 8 kg ~ 10 kg ~ 5 kg
material: fibre-glass reinforced insulation tubes
optionally insulation of busbar joints, ~5 kg ~8 kg ~8 kg ~10 kg ~ 2 kg
material: polyurethane, sealing compound PV5
optionally busbar transverse partition, ~3 kg ~3 kg ~3 kg ~3 kg ~ 5 kg
material plate: Durostone, UPM S14 (grey)
material bushings: cast resin ~ 3 kg ~ 3 kg ~3 kg ~3 kg
Insulation of control wiring Standard, H07V ~10 kg ~10 kg ~10 kg ~10 kg ~ 3 kg
Insulation of control wiring optional, HX4GAF, halogen free ~10 kg ~10 kg ~10 kg ~10 kg ~ 3 kg
Low voltage devices ~20 kg ~20 kg ~20 kg ~20 kg ~ 2 kg

17.25 Fire loads


panel width 435 mm 600 mm 800 mm 1000 mm 800 mm (SDF)
~ 1600 MJ ~ 1800 MJ ~ 2000 MJ ~ 2500 MJ ~ 645 MJ

17.26 Dynamic loads


Circuit breaker panel Impact load due to switching devices are negligible
Contactor panel

17.27 Fixing hardware


device screw Fixing moment
Main busbar M12 70
Earthing bar M12 70
Termination of cables M12 for feeder currents ≤ 1250A 70
(see also installation manual) Connections elements per phase: 1x bolt size M12 plus 2 x flat
washer; ISO 7093 plus 2x strain washer 12 plus 1x nut M12
M16 for feeder currents >1250A 170
Connections elements per phase: 1x bolt size M16 plus 2x
strain washer; 16 plus 1x nut M16
Between frames M8 30
Between panel and foundation rails M10 / M12 105 / 260

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 145 / 146 -
for internal use only, © by Siemens AG, SI EA PLM MV-AIS PRI

17.28 Heat losses at rated current


Panel ≤ 630 A ~ 220 W
Panel 1000 A ~ 500 W
Panel 1250 A ~ 800 W
Panel 2000 A ~ 1350 W
Panel 2500 A ~ 2000 W

Panel 3150 A ~ 2650 W

Panel 4000 A ~ 4300 W

Metering panel ~ 150 W

Busbar current metering panel ~ 150 W

17.29 Maintenance
visual inspection Every year or at the operator`s discretion, see also operation instructions

maintenance Every ten years or depending on operational facts, or at operator`s description, see also
operation instructions
Greases to be used Longtherm 2 for fixed contacts of main circuits in bushings and fixed contacts of earthing
switch, see also operation instructions
Isoflex Topas L32 for moving rails of withdrawable part, see also operation instructions

17.30 Spare parts


List for 1-year operation Depends on client requirements, parts from accessories, spare parts for breaker catalogue HG
11.02 can be offered
List for 5-year operation Depends on client requirements, parts from accessories, spare parts for breaker catalogue HG
11.02 can be offered

17.31 Fan (used for forced ventilation)


Fan manufacturer Delta Electronics, Inc.

type GTB031FUC20R N1

Nominal voltage 1~ 230Vac 50/60Hz

Power input (max. Load) 530 W

Noise level @ Qmax. 79 (dB-A)

Operating hours of fan 60,000 hrs at 40°C / 15 ~ 65 % RH

Operating instructions GTB031FUC20R N1

Restricted / SI EA PLM MV-AIS PRI, Ralf Weichert NXAIR ≤ 17.5 kV, up to 40 kA issued: 10.10.2023 / V61.0 - 146 / 146 -