You are on page 1of 17

GUJARAT TECHNOLOGICAL

UNIVERSITY

PowerPoint Presentation on
“BUS-BAR ARRANGEMENT IN
SUBSTANTION”

Subject Code:
B. E. II, Semester – IV

SR.NO. NAME ENROLLMENT NUMBER


1 Rinkesh patel 180860109013

Submitted by
In partial fulfillment for the award of the degree
of
BACHELOR OF ENGINEERING
in
Electrical Engineering
Laxmi Institute of Technology
Sarigam– 396155
Gujarat Technological University
Ahmedabad
05/30/2020 Academic year: 2019-2020 1
Types of Busbar Arrangement
Single bus
Single busbar system with sectionalisation
Main and transfer busbar
 Double bus bar with double breaker
 One and half breaker busbar
 Ring busbar

05/30/2020 2
Single Bus arrangement

05/30/2020 3
Single Bus arrangement System
Advantage Disadvantage Remarks
1. Low cost 1. Fault of bus or any 1. Used for
circuit breaker results in distribution
shut-down of entire substations upto 33kV
substation
2. Simple to Operate 2. Difficult to do any 2. Not used for large
maintenance substations.
3. Simple Protection 3. Bus cannot be extended 3. Sectionalizing
without completely de- increases flexibility
energizing substations
4. Can be used only where
loads can be interrupted or
have other supply
arrangements.

05/30/2020 4
Main & Transfer Bus

05/30/2020 5
Main & transfer busbar system
Advantage Disadvantage Remarks
1. Low initial & ultimate 1. Requires one extra 1. Used for 110kV
cost breaker coupler substations where cost
of duplicate bus bar
system is not justified
2. Any breaker can be 2. Switching is
taken out of service for somewhat complex
maintenance. when maintaining a
breaker
3. Potential devices may 3. Fault of bus or any
be used on the main bus circuit breaker results in
shutdown of entire
substation.

05/30/2020 6
Double Busbar with Double breaker

05/30/2020 7
Double Bus Bar Double Breaker system

Advantage Disadvantage Remarks


1. Each has two 1. Most expensive 1. Not used for usual
associated breakers EHV substations due to
high cost.
2. Has flexibility in 2. Would lose half of 2. Used only for very
permitting feeder the circuits for breaker important, high power,
circuits to be connected fault if circuits are not EHV substations.
to any bus connected to both the
3. Any breaker can be buses.
taken out of service for
maintenance.
4. High reliability

05/30/2020 8
One & half breaker scheme

05/30/2020 9
One & half breaker scheme
Advantage Disadvantage Remarks
1. Flexible operation for breaker 1. One and half 1. Used for 400kV
maintenance breakers per circuit, & 220kV
hence higher cost substations.
2. Any breaker can be removed 2. Protection and 2. Preferred.
from maintenance without auto-reclosing more
interruption of load. complex since
3. Requires 1 1/2 breaker per middle breaker must
feeder. be responsive to
both associated
circuits.
4. Each circuit fed by two
breakers.
5. All switching by breaker.
6. Selective tripping

05/30/2020 10
Ring Bus

05/30/2020 11
Mesh (Ring) busbar system
Advantage Disadvantage Remarks
1. Busbars gave 1. If fault occurs during bus 1. Most widely
some operational maintenance, ring gets separated used for very
flexibility into two sections. large power
2.Auto-reclosing and protection stations having
complex. large no. of
incoming and
3. Requires VT’s on all circuits outgoing lines
because there is no definite voltage and high power
reference point. transfer.
These VT’s may be required in all
cases for synchronizing live line or
voltage indication
4. Breaker failure during fault on one
circuit causes loss of additional
circuit because of breaker failure.

05/30/2020 12
Given:-
 A generating station with 14 generator

Design two alternative way of busbar arrangement of


the station
Solution
I assume each generator generates 300MW with
voltage 11kv and power factor 0.9
 14x300=4200MW
Auxiliary service 10%=420MW=14x30MW

Base on this it is done as shown below


05/30/2020 13
Option 1

05/30/2020 14
Option 2

05/30/2020 15
Auxiliary Service

05/30/2020 16
THANK
YOU
05/30/2020