Equipment Findings -COMISION FEDERAL DE ELECTRICIDAD

Equipment: 09MAV21
Type: 3PhaseAC
Name:
AUX DE LUBRICACION
Model:
Manufacturer:
Serial No:
Frame:
Size HP:
RPM:
kVA Code:
Ins. Class:

Enclosure:
Size KW:
30.05
Efficiency:
Power Fact:
Service Fact:

40.30

Phases:

TI: 12

Amps:
0
Volt:
Temp Rise:

TestDate: 2016 03 19 - 09:54

Resistance
Impedance
Inductance
Phase Angle
I/F

Impedance
Inductance

0.185

0.185

0.187

0.498

7.0
2.0
68
46

13.0
2.0
68
47

7.0
2.0
68
46

44.44
0.00
0
1

> 99 MegOhm
Findings:
- Possible contaminated or overheated winding,
evaluate Impedance and Inductance Pattern match.
- Recommend check at motor if tested from MCC.
Notes: