Pilot Gas
361 XV 026
361 XV 048
361 XV 047
Fuel Gas
361 XV 025
361 XV 050
361 XV 049
Fuel Oil
361 XV 024
361 XV 051
361 XV 023 ( FO Return Valve )
Step 1 :- From " System Start " to " Ready For Purge "
Press " System Start "
" Leak Test In Progress " Lamp Flashing .
--> Close Pilot Bleed Valve ( Faliure of Action ---> " Pilot Valve Discrepancy / Energized " Lamp Flashing ) .
--> Close Main Gas Bleed Valve ( Failure of Action ---> " Main Gas Valve Discrepancy / Energized " Lamp Flashing ) .
--> Open Pilot Block Valves 1 & 2.
--> Open Main Gas Block Valves 1 & 2.
Lamp " Pilot Valve Discrepancy / Energized " ON
Lamp " Main Gas Valve Discrepancy / Energised " ON
X1 = 10
ON ;
--> Check whether Main Gas Line Pressure > 1.5 Kg / Cm2 ? ( Failure of the same --> Lamp " Main Gas Leak Test Failure " ON ;
"Leak Test In Progress / Complete " Lamp OFF ; Press " BMS Reset " PB. )
--> Open Second Block Valve on Pilot and Main Gas Lines for 8 secs.
--> At the End Of 8 secs
--> Close Second Block Valve on Pilot and Main Gas Lines.
Lamp " Leak Test In Progress / Complete " ON.
Lamp " Ready For Purge " ON.
Step 2 :- From " Purge Start " to " Pilot Ignition "
Press " Purge Start "
Signal From BMS to DCS for " Purge Start "
Lamp " Ready For Purge " OFF.
Permissive Signal from DCS Available ? ( If Not then Wait for 1 min ( Timer X10 ) ; if it becomes available within that period
then back to Ready For Purge Otherwise Halt the sequence and wait for the Permissive signal )
then back to Ready For Purge Otherwise Halt the sequence and wait for the Permissive signal )
Lamp " Purging In Progress / Complete " Flashing .
X3 = 300
X4 = 1800
Open Individual Pilot Isolation Valve and Press PB to Ignite Corresponding Pilot.
Corresponding Pilot receives a Spark for 10 secs for light Up.If Pilot is light Up and Flame is detected ; Corresponding Lamp will
glow on Panel indication " Pilot Flame X " ON.
Z = Total No. Of Burners ( 12 )
W = Total No Of Burners in Maintenance
n = Z -W
N = Total No of Burners Lit Up
Open Individual Main Gas Isolation Valve on Each Burner for Lighting Up of Burner.
Before Pressing " Fuel Oil Burner Start " ; Check --->
a ) All the Fuel Oil Related ESDs are Healthy ?
Press " Fuel Oil Burner Start " PB
--> Open Both Fuel Oil Block Valves ( Faliure of Action ---> " Fuel Oil Valve Discrepancy / Energized " Lamp Flashing ; Press
BMS reset for Restarting the sequence. )
Signal from BMS to ESD to open Fuel Oil Return Valve ( Keep FO Return Valve Open ; For Timer X6 = 600 secs then Close
the same after Tmer is Exhausted. )
--> Lamp " Fuel Oil Valve Discrepancy / Energised " ON .
Open Individual Fuel Oil Isolation Valve on Each Burner for Lighting Up of Burner.