KK MAYA LIKAS

ATTACHMENT B2

B2-1

TITTLE: SUMMARY OF SPRINKLER PUMPS


No

Pump
Designation

Level

Description

SPP-1

UG

Sprinkler Pump (Duty)

SPP-2

UG

Sprinkler Pump (Standby)

SPJ

UG

Sprinkler Pump (Jockey)

Type

End Suction
End Suction
Vertical InLine

Flow
Rate
(L/min)

Estimated
Pump Head
(bar)

Speed
(RPM)

Estimated
Power Input
(kW)

Control
Panel

Elec
Char
(V/Ph/Hz)

2250

1.4

2900

11.0

CP-SPP-1

415/3/50

2250

1.4

2900

11.0

CP-SPP-1

415/3/50

50

3.6

2900

0.8

CP-SPP-1

415/3/50

KK MAYA LIKAS

Standards

ATTACHMENT B2

Remarks

MS 1910 & LPC

OH3 15m

MS 1910 & LPC

OH3 15m

B2-1

PROJECT: MAYA LIKAS


SERVICES: FIRE PROTECTION SERVICES
REVISION : REV 00
Date: 19 NOVEMBER 2015
Sprinkler Pump (Single Stage)

1. Designed to all the rules of the 'Loss Prevention Council' (LPC) for precalculated installations.
2. Below are the hazard class classification
Lower Ground Floor (3.0 m)
-

Ordinary Hazard Group III based on 15m height

Calculations
-

Duty and standby pump characteristic data


SPP-1 and SPP-2
Nominal flowrate :
High flowrate :
Low flowrate :

2250
1350
1100

l/min
l/min
l/min

Head =
Head =
Head =

1.4
2.9
3.2

Jockey pump sizing


SPJ
Flow rate across one sprinkler point,
Q = k x (P)1/2

where k= 80

P=

0.35 bar

Q = 80 x (0.35)1/2
Q
=
47.33 l/min
say
Therefore, select jockey pump flow rate as 50 l/min

50.00 l/min

The jockey pump head is approximately 10% higher than the duty pump head.
Head = 1.1 x head of low flow rate
Head = 1.1 x
3.2 bars
Head =
3.52 bars
say
3.6
Thus, flow rate =

50.0 l/min

Head =

3.6

PROJECT: MAYA LIKAS


SERVICES: FIRE PROTECTION SERVICES
REVISION : REV 00
Date: 19 NOVEMBER 2015

ed installations.

on 15m height

bars
bars
bars

duty pump head.

bars