WARNING
for by
means of these Acts and Regulations.
AS/NZS
4801:2001
Occupational Health & Safety Management Systems
Note: Current ratings data contained in the cable selection category of this guide are based
on 18001:1999
Australian/New Zealand Standards (AS/NZS 3008.1.1).
OHSAS
Assessment Specification for Occupational
Health & Safety Management Systems
ISO 14001:2004
Environmental Management Systems
No worries. Regardless of what cables youre looking for, we have them for sure. A full market
offer ranging from construction, power and telecom cables. And if not, well invent them.
Plus, we provide you with all the services you might need before, during and after.
Australian made? Yes, of course.
2 WWW.PRYSMIANCABLE.COM.AU
Contents
Power Cables
8
PVC/PVC SDI
PVC/PVC Flat
PVC/PVC Flat
PVC/PVC Orange Circular
10
PVC Insulated Building Wire
PVC/PVC Orange Circular
PVC/PVC Orange Circular
PVC/SWA/PVC Orange Circular
PVC/SWA/PVC Orange Circular
15
Single Core
Flexible XLPE/PVC Copper SDI - X-90
Single Core
Flexible XLPE/PVC Copper SDI - RE-110
Single Core
XLPE/PVC Copper SDI
Single Core
XLPE/PVC Aluminium SDI
2 & 3 Core plus Earth
XLPE/PVC Circular
4 Core & 4 Core plus Earth XLPE/PVC Circular
3 Core plus Earth
XLPE/SWA/PVC Circular
4 Core plus Earth
XLPE/SWA/PVC Circular
Instrumentation Cables
21
25
Contents
Power Cables
Continued
27
PVC Insulated Aerial
PVC Insulated Aerial
PVC Insulated Aerial
Communication
Cables
29
Flexible FS110
FS90
FS90
FS110
FS110
33
XLPE/PVC Screened
XLPE/PVC Screened
34
36
LAN Cables
37
Optical Fibre
40
Indoor/Outdoor
Outdoor Loose Tube
Aerial Dielectric Self Supporting (ADSS) Cable & Ordering Information
Telephone Cables
45
Cable Selection
Cable Selection
4 WWW.PRYSMIANCABLE.COM.AU
52
Contents
Current Carrying
Capacities &
Voltage Drops
Current Ratings
58
75C
90C
90C
110C
75C
90C
90C
110C
75C
90C
110C
75C
90C
110C
90C
110C
75C
90C
Cable In Conduit
General Information
3 Phase Formulae 84
Motor Current Table Single Phase
Motor Current Table Three Phase
Short Circuit Capacity
Conductor Stranding, Resistance & Diameter
Wire Gauges
SWG/Metric/AWG
American Conductors
Imperial Conductors
Minimum Copper Earthing Conductor Size
Cable Installation
Recommended Minimum Bending Radii
Maximum Pulling Tensions
Safe Working Force - Flex
Insulation & Sheath Properties
Glossary of Terms
82
Weve been producing tailor-made cables in Australia since 1944. And we will continue
to do so. Our great staff of highly skilled and experienced people know what it takes to
make cables that withstand everything from termites to hazardous mine sites.
Just fair dinkum cables, mate.
Australian made? Yes, of course.
6 WWW.PRYSMIANCABLE.COM.AU
Power Cables
PVC Cables
en Star
Gre
POWER CABLES
en Star
Gre
CERTIFIED
CERTIFIED
GREEN
STAR
GREEN STAR
CERTIFIED
CERTIFIED
Single Core Cable, Copper Conductor, V-90 PVC Insulated and 3V-90 PVC Sheathed, to AS/NZS 5000.2.
Cable
description:
Single Core Cable, Aluminium Conductor,
X-90 XLPE Insulated, 5V-90
PVC Sheathed, to AS/NZS 5000.1.
Approx.
Nominal
Approx. Mass
Note:
Class 2 Compacted
Overall Diameter
Catalogue
Reference Conductor.
Conductor Area
kg/100m
mm
mm2
Approx.
Nominal
*1.0SSDI
1.0
4.1
2.9Mass
Approx.
Overall Diameter
Catalogue Reference
Conductor Area
1.5SDI
1.5
4.5
3.5
kg/100m
mm
mm2
2.5SDI
2.5
5.2
5.1
25CALXLP
25
10.9
15
4SDI
4.0
6.2
7.4
35CALXLP
35
11.9
18
6SDI
6.0
6.8
9.8
50CALXLP
50
13.1
23
10SDI
10
8.2
15
70CALXLP
16SDI
70
16
15.0
9.4
31
22
95CALXLP
95
16.9
*Single Wire Conductor.
120CALXLP 2
120
18.5
For conductors 25mm and above please refer to XLPE/PVC product pages.
150CALXLP
150
20.4
185CALXLP
185
Min. Installed
Bending Radius
mm
Min. Installed
15
Bending Radius
20
mm
20
85
25
95
25
105
35
22.6
120
40
40
135
48
145
58
165
73
180
200
240CALXLP
240
25.3
93
300CALXLP
300
28.0
114
225
400
31.5
145
250
500
35.2
180
280
400CALXLP
PVC FLAT
450/750V
500CALXLP
Cable description:
630CALXLP
630
39.6
230
2 & 3 Core Flat TPS Cable, Copper Conductor V-90, PVC Insulated and 3V-90 PVC Sheathed, to AS/NZS 5000.2.
315
Nominal
Conductor Area
mm2
Approx.
Overall Dimensions
mm
Approx. Mass
kg/100m
Min. Installed
Bending Radius
mm
2C
3C
2C
3C
2C
3C
2C
3C
*1.0ST
*1.0S3CF
1.0
6.6 x 4.3
9.0 x 4.3
5.2
7.3
15
20
1.5T
1.53CF
1.5
7.3 x 4.6
10.1 x 4.6
6.4
9.0
20
20
2.5T
2.53CF
2.5
8.9 x 5.5
12.4 x 5.5
9.9
15
20
20
4T
4.0
10.7 x 6.5
15
25
30
6T
6.0
11.9 x 7.1
20
10T
10
15.0 x 8.8
31
35
16T
16
17.3 x 10.0
45
40
The cables listed above are available in Green Star approved PVC or made to order Non PVC Low Smoke Zero Halogen.
10WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300
300 304
8
1300
300 304
en Star
Gre
en Star
Gre
POWER CABLES
CERTIFIED
GREEN
STAR
CERTIFIED
GREEN STAR
CERTIFIED
CERTIFIED
XLPE
ALUMINIUM
SDI 0.6/1KV
PVC FLAT
450/750V
Cable description:
Single
Coreplus
Cable,
Aluminium
X-90
XLPE Insulated,
5V-90
PVC Sheathed,
AS/NZS
5000.1.
2 & 3 Core
Earth
Flat TPS Conductor,
Cable, Copper
Conductor,
V-90 PVC
Insulated
and 3V-90toPVC
Sheathed,
to AS/NZS 5000.2.
Note: Class 2 Compacted Conductor.
2C+E
Approx.
Overall
Dimensions
Approx.
Overallmm
Diameter
2C+E mm 3C+E
Nominal
Nominal
Conductor Area
Conductor2 Area
mm
mm2
Catalogue Reference
Catalogue Reference
3C+E
Approx. Mass
kg/100m
Approx.
Mass
kg/100m
2C+E
3C+E
Min. Installed
Bending
Radius
Min. Installed
mm
Bending
Radius
2C+E mm 3C+E
25CALXLP
*1.0STE
*1.0S3CEF
25
1.0
15
10
20
85
20
1.5TE35CALXLP1.53CEF
1.5
35
18
12
20
95
20
2.5TE50CALXLP
2.53CEF
4TE70CALXLP43CEF
2.5
50
4.0
70
15
23
19
20
105
20
19
31
26
25
120
6TE
63CEF
95CALXLP
10TE
103CEF
120CALXLP
16TE
163CEF
150CALXLP
6.0
95
10
120
16
150
15.3 x 7.1
24
33
30
52
35
75
40
20.1 x 7.1
16.9
25.8 x 8.8
18.5
22.5 x 10.0
29.7 x 10.0
20.4
19.2 x 8.8
*Single Wire
Conductor.
185CALXLP
185
2C+E = 2 Core + Earth. 3C+E = 3 Core + Earth.
240CALXLP
240
38
54
22.6
40
48
58
135
145
165
73
180
200
25.3
93
300CALXLP
300
28.0
114
225
400CALXLP
400
31.5
145
250
500CALXLP
500
35.2
180
280
630CALXLP
630
39.6
230
315
25
30
35
40
Min. Installed
Bending Radius
mm
2C+E
3C+E
4C+E
Nominal
Conductor
Area
mm2
2C+E
3C+E
4C+E
2C+E
3C+E
4C+E
2C+E
3C+E
4C+E
1.52CEOC
1.53CEOC
1.54CEOC
1.5
8.3
9.0
10.0
11
13
16
35
40
40
2.52CEOC
2.53CEOC
2.54CEOC
2.5
10.0
10.9
11.9
17
20
24
40
45
50
42CEOC
43CEOC
44CEOC
4.0
11.2
12.3
13.7
22
27
34
45
50
55
62CEOC
63CEOC
64CEOC
6.0
12.2
13.6
15.1
27
35
44
50
55
60
102CEOC
103CEOC
104CEOC
10
15.7
17.5
19.4
40
53
65
65
70
80
162CEOC
163CEOC
164CEOC
16
18.0
19.8
22.2
57
75
94
75
80
90
Catalogue Reference
Approx. Mass
kg/100m
The cables listed above are available in Green Star approved PVC or made to order Non PVC Low Smoke Zero Halogen.
1300
300
|| WWW.PRYSMIAN.COM.AU
1300304
300304
304
WWW.PRYSMIAN.COM.AU 17
119
1300 300
WWW.PRYSMIANCABLE.COM.AU
en Star
Gre
en Star
Gre
POWER CABLES
CERTIFIED
GREEN
STAR
CERTIFIED
CERTIFIED
GREEN STAR
CERTIFIED
XLPE
ALUMINIUM
SDI 0.6/1KV
PVC INSULATED
0.6/1KV
Cable description:
Single
Conductor,
Insulated,
5V-90 PVC
Sheathed,
to AS/NZS 5000.1.
Single Core
Core Cable,
Cable, Aluminium
Copper Conductor,
V-90X-90
PVCXLPE
Insulated,
Unsheathed,
to AS/NZS
5000.1.
Note: Class 2 Compacted Conductor.
Approx. Mass
kg/100m
Approx.
Mass
kg/100m
1.7
Min. Installed
Bending
Radius
Min. Installed
mm
Bending
Radius
mm
10
10.9
3.2
15
2.2
85
15
3.7
11.9
3.3
18
15
95
4.0
50
6.0
70
4.6
13.1
5.2
15.0
5.3
23
7.4
31
20
105
20
120
10
95
16
120
25
150
35
185
50
6.2
16.9
7.3
18.5
8.9
20.4
10.1
22.6
11.9
12
40
18
48
28
58
37
73
50
25
135
30
145
35
165
40
180
50
200
55
*1.OSBW
Nominal
Conductor
NominalArea
mm2 Area
Conductor
2
mm
1.0
Approx.
Overall
Diameter
Approx.
Overallmm
Diameter
mm
2.8
25CALXLP
1.5BW
25
1.5
2.5BW
35CALXLP
2.5
35
4BW
50CALXLP
6BW
70CALXLP
10BW
95CALXLP
16BW
120CALXLP
25BW
150CALXLP
35BW
185CALXLP
50BW
Catalogue Reference
Catalogue Reference
240CALXLP
70BW
240
70
25.3
13.5
93
69
300CALXLP
95BW
300
95
28.0
15.9
114
96
225
65
120BW
400CALXLP
120
400
17.3
31.5
119
145
70
250
150BW
500CALXLP
185BW
630CALXLP
150
500
185
630
19.5
35.2
21.7
39.6
146
180
184
230
80
280
85
315
Catalogue Reference
Nominal
Conductor Area
mm2
Approx.
Overall Diameter
mm
Approx. Mass
kg/100m
Min. Installed
Bending Radius
mm
2C+E
3C+E
2C+E
3C+E
2C+E
3C+E
2C+E
1.52CEOC1KV
1.53CEOC1KV
1.5
10.1
11.0
15
18
40
3C+E
45
2.52CEOC1KV
2.53CEOC1KV
2.5
11.3
12.3
20
24
45
50
42CEOC1KV
43CEOC1KV
4.0
12.9
14.0
26
32
50
55
62CEOC1KV
63CEOC1KV
6.0
14.0
15.2
33
41
55
60
102CEOC1KV
103CEOC1KV
10
16.5
18.1
43
56
65
70
162CEOC1KV
163CEOC1KV
16
18.6
20.4
59
78
75
80
The cables listed above are available in Green Star approved PVC or made to order Non PVC Low Smoke Zero Halogen.
12 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
304
10
1300
300 304
17
en Star
Gre
en Star
Gre
POWER CABLES
CERTIFIED
GREEN
STAR
CERTIFIED
GREEN STAR
CERTIFIED
CERTIFIED
XLPE
ALUMINIUM
SDI 0.6/1KV
PVC MULTICORE
CIRCULAR
0.6/1KV
Cable description:
Single
Aluminium
Conductor,
X-90 XLPEV-90
Insulated,
5V-90 PVC
AS/NZS 5000.1.
4 Core Core
plus Cable,
Earth Circular
Cable,
Copper Conductor,
PVC Insulated
andSheathed,
5V-90 PVCtoSheathed,
to AS/NZS 5000.1.
Note: Class 2 Compacted Conductor.
Approx. Mass
kg/100m
Approx.
Mass
kg/100m
21
Min. Installed
Bending
Radius
Min. Installed
mm
Bending
Radius
mm
50
10.9
13.3
15
29
85
55
15.4
11.9
39
18
60
95
16.8
13.1
20.0
15.0
50
23
69
31
70
105
80
120
Nominal
Conductor
NominalArea
mm2 Area
Conductor
2
mm
1.5
Approx.
Overall
Diameter
Approx.
Overallmm
Diameter
mm
11.9
25CALXLP
2.54CEOC1KV
25
2.5
44CEOC1KV
35CALXLP
4.0
35
64CEOC1KV
50CALXLP
104CEOC1KV
70CALXLP
6.0
50
10
70
Catalogue Reference
Catalogue Reference
1.54CEOC1KV
164CEOC1KV
95CALXLP
16
95
22.6
16.9
92
40
90
135
120CALXLP
120
18.5
48
145
150CALXLP
150
20.4
58
165
185CALXLP
185
22.6
73
180
200
240CALXLP
240
25.3
93
300CALXLP
300
28.0
114
225
400CALXLP
400
31.5
145
250
500CALXLP
500
35.2
180
280
630CALXLP
630
39.6
230
315
Approx.
Overall Diameter
mm
Min. Installed
Bending Radius
mm
Nominal
Conductor
Area
mm2
2C+E
3C+E
2C+E
3C+E
2C+E
3C+E
2C+E
1.52CEOCA1KV 1.53CEOCA1KV
1.5
9.1
10.0
15.2
16.1
47
52
185
195
2.52CEOCA1KV 2.53CEOCA1KV
2.5
10.3
11.3
16.9
17.4
56
63
195
210
230
Catalogue Reference
2C+E
3C+E
Approx. Mass
kg/100m
3C+E
42CEOCA1KV
43CEOCA1KV
4.0
11.8
13.0
17.9
19.2
67
77
215
62CEOCA1KV
63CEOCA1KV
6.0
13.0
14.2
19.1
20.3
77
88
230
245
102CEOCA1KV 103CEOCA1KV
10
15.5
17.1
21.6
23.2
94
111
260
280
162CEOCA1KV 163CEOCA1KV
16
17.6
19.4
23.7
26.2
117
156
285
315
The cables listed above are available in Green Star approved PVC or made to order Non PVC Low Smoke Zero Halogen.
17
1300304
300 304
| WWW.PRYSMIAN.COM.AU 13
1300 300
WWW.PRYSMIANCABLE.COM.AU
11
en Star
Gre
en Star
Gre
POWER CABLES
CERTIFIED
GREEN
STAR
CERTIFIED
GREEN STAR
CERTIFIED
CERTIFIED
XLPE
ALUMINIUM
SDI CIRCULAR
0.6/1KV 0.6/1KV
PVC MULTICORE
SWA
Cable description:
Single
Aluminium
Conductor,
XLPE
Insulated,
5V-90
Sheathed,
AS/NZS
5000.1.
4 Core Core
plus Cable,
Insulated
Earth Circular
Cable,X-90
Copper
Conductor,
V-90
PVCPVC
Insulated
and to
PVC
Bedded,
Steel Wire Armoured, 5V-90
Note:
Class 2 Compacted
PVC Sheathed,
to AS/NZSConductor.
5000.1.
Catalogue
Reference
Catalogue
Reference
Approx. Approx.
Nominal Approx. Diameter
Nominal
Approx.Approx.
Mass Mass
Overall Diameter
Conductor
Overall Diameter
Conductor
Area Area Over Bedding
kg/100m
kg/100m
2
2
mm
mm
mm
mm mm
Min.
Installed
Min.
Installed
Bending
Radius
Bending
Radius
mm
mm
1.54CEOCA1KV
25CALXLP
1.5
25
10.9
10.9
17.0
15
59
85205
2.54CEOCA1KV
35CALXLP
44CEOCA1KV
50CALXLP
2.5
35
12.3
11.9
18.5
18
71
4.0
50
14.4
13.1
20.5
23
87
95225
105245
265
120
310
135
340
145
64CEOCA1KV
70CALXLP
104CEOCA1KV
95CALXLP
164CEOCA1KV
120CALXLP
6.0
10
16
15.8
70
15.0
19.0
95
16.9
21.6
120
18.5
21.9
31
25.8
40
28.4
48
102
145
184
The cables
listed above are available in
or made to order Non PVC Low
150CALXLP
150Green Star approved PVC20.4
58 Smoke Zero Halogen. 165
185CALXLP
185
22.6
73
180
240CALXLP
2
300CALXLP
240
25.3
93
200
400CALXLP
400
300
4MM TWIN SOLAR CABLE
Cable description:
28.0
114
225
31.5
145
250
500CALXLP
500
35.2
180
280
The cable complies with the requirements of 2 Pfg 1169/08.2007, Fire Performance: IEC60332-1, Smoke Density: IEC61034, EN50268-2,
39.6 Sizes available: Prysmian
230Product Codes: 4mm2 single
315 - 5749083,
Halogen630CALXLP
Acid Gas Emission: IEC60754-1,630
EN50267-2-1, Certificate: TUV,
4mm2 twin - 5749045, 6mm2 single - 5749090, 6mm2 twin - 5749069, Other sizes made to order, Colours available on request in either
Note: LSOH version available.
SDI or twin: red or blue.
Item
Conductor
Insulation
Sheath
Marking on cable
Specification
4mm2
Material
Size (mm)
56/(0.300.008)
Strand OD (mm)
2.590.01
Material
Nominal OD (mm)
4.450.15
Colour
Material
Nominal OD (mm)
5.80.10 x 12.000.20
Colour
Black
PRYSMIAN SOLAR CABLE (PV) PV1-F 4mm2 0.6/1KVAC -- 0.9/1.8KVDC -- FOR DC USE ONLY DO NOT
DISCONNECT UNDER LOAD -- 120C SOLAR DV
TUV Cert No R (Metre Marking)
Spread over the length of a metre in between metre markings
Nominal Voltage
Test Voltage
Temperature Rating
Ambient Temperature
-40C up to +125C
Max. Conductor
Temperature
+120C
Bending Radius
Conductor Resistance
Insulation Resistance
UV Resistant
6 x cable OD
>720h
14 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
12
1300304
300 304
17
See a star!
Were Green Star certified.
A lot of companies say they can make cables. But were the leading green star manufacturer
of cables. So if sustainable responsibility is part of your business you can count us in.
Australian made? Yes, of course.
13
Been in a tight spot lately, with almost no room to move? Our flexible cables will make it
a lot easier to get the job done. They can be used in both general and fire rated applications
and theyll save you both time and money.
Australian made? Yes, of course.
14 WWW.PRYSMIANCABLE.COM.AU
XLPE Cables
en Star
Gre
POWER CABLES
CERTIFIED
GREEN STAR
CERTIFIED
Flexible Single Core Cable, Class 5 Conductor, 5V-90 X-90 XLPE Insulated, PVC Sheathed, to AS/NZS 5000.1.
Cable
description:
Note: For fixed installation.
Single Core Cable, Aluminium Conductor, X-90 XLPE Insulated, 5V-90 PVC Sheathed, to AS/NZS 5000.1.
Note: Class 2 Compacted Conductor.
Conductor
Cable
Nominal
Product
Code
Catalogue
Reference
C.S.A.
mm2
25CALXLP
351CFF90
35CALXLP
501CFF90
50CALXLP
701CFF90
70CALXLP
951CFF90
95CALXLP
1201CFF90
120CALXLP
1501CFF90
150CALXLP
1851CFF90
185CALXLP
2401CFF90
35
Nominal
Nominal
Conductor Area
Diameter
mm2
mm
25
NominalApprox.
Overall Diameter
Approx. Mass
Insulation
Overall Diameter
kg/100m
Thickness mm Minimum
Maximum
mm
mm
mm
10.9
15
0.9
11.9
11.9
1.0
13.1
13.7
185
357.7
509.3
11.1
70
12.8
95
14.5
120
16.3
150
18.0
1.6
20.4
240
185
20.8
1.7
22.6
50
70
95
120
150
1.0
1.0
1.2
1.4
15.0
16.9
18.5
Min.
Installed
Min. Installed
Approx.
Bending
Bending Radius
Mass
mmRadius
kg/100m
mm
85
23.8
12.7
18
14.5
23
16.5
31
18.4
40
20.3
48
22.7
58
24.8
178.0
26.9
73
28.0
231.8
165 149
180 168
200 186
15.7
17.5
19.4
21.7
38.7
95
76
53.5
105
87
72.9
94.2
118.6
147.4
120
135
145
99
110
122
136
240CALXLP
3001CFF90
300
240
23.4
1.8
25.3
29.8
93
30.9
288.3
4001CFF90
300CALXLP
400
26.8
300
2.0
28.0
33.8
35.0
114
376.2
225 210
5001CFF90
400CALXLP
6301CFF90
500CALXLP
500
30.3
400
35.1
500
2.2
31.5
37.8
474.5
35.2
43.2
39.1
145
44.6
180
250 235
280 268
630
630CALXLP
630
2.4
39.6
230
628.9
315
1300
300 304
| WWW.PRYSMIAN.COM.AU 15
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
15
en Star
Gre
en Star
Gre
POWER CABLES
CERTIFIED
GREEN
STAR
CERTIFIED
GREEN STAR
CERTIFIED
CERTIFIED
XLPE
ALUMINIUM
SDI 0.6/1KV
FLEXIBLE
XLPE COPPER
SDI 0.6/1KV
Cable description:
Single
Core
Cable,
Aluminium
Conductor,
X-90RE-110
XLPE Insulated,
PVC Sheathed,
AS/NZS
5000.1. 5000.1.
Flexible
Single
Core
Cable, Class
5 Conductor,
Insulated, 5V-90
HFS-110-TP
Sheathed,toLSOH,
to AS/NZS
Note:
2 Compacted
Conductor.
Note: Class
For fixed
installation.
Nominal
Conductor
Conductor Area
mm2
Nominal
Nominal
25
C.S.A.
Diameter
mm2
35mm
Catalogue Reference
Product Code
25CALXLP
35CALXLP
Approx.
Cable Approx. Mass
Overall Diameter
kg/100m
Nominal mm
Overall Diameter
Insulation
10.9
15
Thickness
Maximum
Minimum
11.9
18
mm
mm
mm
50CALXLP
351CFF110
70CALXLP
501CFF110
50
50
7.7
709.3
1.4
15.0
14.5
95CALXLP
701CFF110
70
9511.1
1.4
16.9
16.4
23
13.3
31
15.3
40
17.2
35
1.2
13.1
12.5
Min. Installed
Min.
Bending Radius
mmInstalled
Approx.
Bending
85 Radius
Mass
kg/100m
95 mm
105
40.3
80
120
55.9
75.0
92
135 103
951CFF110
120CALXLP
95
12.8
120
1.6
18.5
18.6
19.4
48
97.9
145 116
1201CFF110
150CALXLP
1501CFF110
185CALXLP
120
14.5
150
16.3
185
1.6
20.4
20.2
122.0
1.8
22.6
22.6
21.1
58
23.6
73
1851CFF110
240CALXLP
2401CFF110
300CALXLP
3001CFF110
400CALXLP
4001CFF110
500CALXLP
5001CFF110
630CALXLP
6301CFF110
150
185
2.0
500
18.0
240
20.8
300
23.4
400
26.8
500
30.3
2.8
35.2
630
630
35.1
2.8
39.6
240
300
400
2.2
2.4
2.6
25.3
28.0
31.5
290.0
39.3
25.8
93
29.3
114
31.1
145
36.5
180
40.6
485.7
165 127
180 141
155
200
176
225
186
250
219
280 244
44.1
230
45.6
637.3
315 273
24.8
28.2
29.9
35.2
151.1
183.1
239.0
386.2
Catalogue Reference
Nominal
Conductor Area
mm2
Approx.
Overall Diameter
mm
Approx. Mass
kg/100m
Min. Installed
Bending Radius
mm
40
16CUXLP
16
9.5
21
25CUXLP
25
11.2
31
45
35CUXLP
35
12.4
41
50
50CUXLP
50
13.9
54
55
70CUXLP
70
15.8
73
65
95CUXLP
95
17.9
100
75
120CUXLP
120
19.6
124
80
150CUXLP
150
21.9
153
90
185CUXLP
185
24.1
190
100
240CUXLP
240
27.1
246
165
300CUXLP
300
30.0
307
180
400CUXLP
400
33.5
388
200
*500CCUXLP
*500
35.2
489
280
*630CCUXLP
*630
39.7
625
315
* Compacted Conductor.
Note: LSOH version available.
16 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
16
1300304
300 304
17
een Star
Gr
POWER CABLES
CERTIFIED
GREEN STAR
CERTIFIED
Min. Installed
Bending Radius
mm
10.9
15
85
11.9
18
95
50
13.1
23
105
120
Catalogue Reference
Nominal
Conductor Area
mm2
Approx.
Overall Diameter
mm
25CALXLP
25
35CALXLP
35
50CALXLP
70CALXLP
70
15.0
31
95CALXLP
95
16.9
40
135
120CALXLP
120
18.5
48
145
150CALXLP
150
20.4
58
165
185CALXLP
185
22.6
73
180
200
240CALXLP
240
25.3
93
300CALXLP
300
28.0
114
225
400CALXLP
400
31.5
145
250
500CALXLP
500
35.2
180
280
630CALXLP
630
39.6
230
315
1300
300 304
| WWW.PRYSMIAN.COM.AU 17
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
17
een Star
Gr
POWER CABLES
CERTIFIED
GREEN STAR
CERTIFIED
XLPE ALUMINIUM
SDI 0.6/1KV
MULTICORE CIRCULAR
0.6/1KV
Cable description:
Single
Coreplus
Cable,
Aluminium
Conductor,
X-90
XLPE Insulated,
5V-90
PVC Sheathed,
to AS/NZS
5000.1.
2 & 3 Core
Earth
Circular Cable,
Copper
Conductor,
X-90 XLPE
Insulated,
5V-90 PVC
Sheathed,
to AS/NZS 5000.1.
Note:
2 Compacted
Conductor.
Note: Class
Non Compacted
Conductor.
Catalogue
Catalogue Reference
Reference
2C+E25CALXLP3C+E
Nominal
Nominal
Conductor
Area
Conductor
mm2 Area
mm2
25
1.52CEXLP
35CALXLP
2.52CEXLP
50CALXLP
42CEXLP
70CALXLP
62CEXLP
95CALXLP
102CEXLP
120CALXLP
162CEXLP
1.5
35
2.5
50
4.0
70
6.0
95
10
120
16
150CALXLP
252CEXLP
150
25
253CEXLP
185CALXLP
353CEXLP
240CALXLP
25
185
35
240
503CEXLP
300CALXLP
703CEXLP
400CALXLP
953CEXLP
500CALXLP
1203CEXLP
630CALXLP
1503CEXLP
50
300
70
400
95
500
120
630
150
1853CEXLP
Note: LSOH version available.
2403CEXLP
3003CEXLP
Approx.
Approx.
Overall
Overall Diameter
Diameter
mm
mm
2C+E 10.9
10.1
11.3
12.2
13.2
15.1
3C+E
11.9
20.4
18
29
16.9
21.0
15
14
23
15.0
18.5
2C+E
19
13.1
17.4
Approx.
Approx. Mass
Mass
kg/100m
kg/100m
41
3C+E
58
95
53
40
75.4
85
41
49
31
48
2C+E
46
23
54
Min.
Min. Installed
Installed
Bending
Bending Radius
Radius
mm
mm
61
70
85
3C+E
105
120
135
145
165
22.6
22.4
73
102
180
90
25.3
25.0
93
136
200
150
28.0
31.5
35.2
39.6
28.5
33.0
37.0
41.0
46.0
114
145
180
230
183
254
336
422
525
225
250
280
315
170
200
220
245
275
185
51.6
665
310
240
58.1
868
350
300
64.4
1084
385
18 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
18
1300304
300 304
17
een Star
Gr
POWER CABLES
CERTIFIED
GREEN STAR
CERTIFIED
XLPE ALUMINIUM
SDI 0.6/1KV
MULTICORE CIRCULAR
0.6/1KV
Cable description:
Single
Cable,
Aluminium
Conductor,
X-90 XLPE
Insulated,
5V-90
Sheathed,
to AS/NZS
5000.1.to AS/NZS 5000.1.
4 Core Core
& 4 Core
plus
Earth Circular
Cable, Copper
Conductor,
X-90
XLPEPVC
Insulated,
5V-90
PVC Sheathed,
Note:
2 Compacted
Conductor.
Note: Class
Non Compacted
Conductor.
Min.
Min. Installed
Installed
Bending
Bending Radius
Radius
mm
mm
Catalogue
Catalogue Reference
Reference
Nominal
Nominal
Conductor
Conductor Area
Area
mm
mm22
Approx.
Approx.
Overall
Overall Diameter
Diameter
mm
mm
Approx.
Approx. Mass
Mass
kg/100m
kg/100m
164CEXLP
25CALXLP
16
25
21.0
10.9
87.5
15
85
85
254CEXLP
35CALXLP
354CEXLP
50CALXLP
25
35
35
50
24.9
11.9
27.8
13.1
130
18
173
23
150
95
165
105
504CEXLP
70CALXLP
704CEXLP
95CALXLP
954CEXLP
120CALXLP
1204CEXLP
150CALXLP
1504CEXLP
50
70
70
95
95
120
120
150
150
32.0
15.0
37.1
16.9
41.8
18.5
46.2
20.4
52.0
235
31
325
40
437
48
547
58
680
190
120
225
135
250
145
280
165
310
185CALXLP
1854CEXLP
185
185
22.6
58.3
73
857
180
350
240CALXLP
2404CEXLP
240
240
25.3
65.8
93
1122
200
395
3004CEXLP
300CALXLP
300
300
72.9
28.0
1400
114
440
225
400CALXLP
400
31.5
145
250
500CALXLP
500
35.2
180
280
630CALXLP
630
39.6
230
315
Approx. Mass
kg/100m
Min. Installed
Bending Radius
mm
28.2
187
340
30.8
229
370
Approx.
Overall Diameter
mm
Catalogue Reference
Nominal
Conductor Area
mm2
253CEXLPA
25
21.4
353CEXLPA
35
24.0
503CEXLPA
50
27.5
34.5
291
415
703CEXLPA
70
31.8
40.0
406
480
530
953CEXLPA
95
35.6
44.0
504
1203CEXLPA
120
39.3
47.9
608
575
1503CEXLPA
150
44.4
54.4
783
655
1853CEXLPA
185
49.6
59.8
949
720
2403CEXLPA
240
56.4
67.0
1198
805
3003CEXLPA
300
62.3
73.3
1447
880
17
1300
300 304
| WWW.PRYSMIAN.COM.AU 19
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
19
een Star
Gr
POWER CABLES
CERTIFIED
GREEN STAR
CERTIFIED
XLPE ALUMINIUM
SDI 0.6/1KV
MULTICORE SWA
CIRCULAR 0.6/1KV
Cable description:
Single
Aluminium
Conductor,
X-90 XLPEX-90
Insulated,
5V-90 PVCPVC
Sheathed,
AS/NZS
4 Core Core
plus Cable,
Earth Circular
Cable,
Copper Conductor,
XLPE Insulated,
Bedded,toSteel
Wire5000.1.
Armoured, 5V-90 PVC Sheathed,
Note:
Class 5000.1.
2 Compacted Conductor.
to AS/NZS
Note: Non Compacted Conductor.
Catalogue Reference
Catalogue Reference
25CALXLP
254CEXLPA
35CALXLP
354CEXLPA
50CALXLP
504CEXLPA
70CALXLP
704CEXLPA
Approx.
Nominal
Approx. Mass
Nominal
Overall DiameterApprox.
Conductor AreaApprox. Diameter
Approx. Mass
2
Over Bedding mm Overall Diameter kg/100m
Conductor Area
mm
kg/100m
mm
mm
mm2
25
10.9
15
25
23.8
30.6
223
35
11.9
18
35
26.8
33.8
278
50
13.1
23
50
30.8
38.8
379
70
15.0
31
70
35.7
44.1
493
Min. Installed
Min. Installed
Bending
Radius
Bending
mm Radius
mm
85
370
95
405
105
465
120530
95CALXLP
954CEXLPA
95
95
40.0
16.9
48.6
40
624
135585
120CALXLP
1204CEXLPA
120
120
44.6
18.5
54.6
48
804
145655
1504CEXLPA
150CALXLP
150
150
50.0
20.4
60.4
58
970
165725
1854CEXLPA
185CALXLP
2404CEXLPA
240CALXLP
185
185
56.4
22.6
67.0
73
1184
240
63.5
25.3
74.5
180805
200895
3004CEXLPA
300CALXLP
240
300
300
70.2
400CALXLP
400
Note: LSOH
version available on request.
28.0
81.6
93
114
1487
1804
980
225
31.5
145
250
500CALXLP
500
35.2
180
280
630CALXLP
630
39.6
230
315
20 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
20
1300304
300 304
17
POWER CABLES
Instrumentation Cables
INFORM@X
Cable description:
P50-P56 cables are intrinsically safe electrically to as 2380.7 & AS 2381.7. Construction design standard according to EN 50288-7.
Instrumentation cables are used in a broad range of operational conditions, they are primarily allocated to control applications where
optimal protection from electrical noise is required. These cables can be used for digital and analogue data transmission at 110V in PLC
and SCADA systems.
Pairs
Nominal O.D
Approx.Mass
Plain
SWA
Plain
SWA
Plain
SWA
Plain
SWA
mm
mm
mm
mm
kg/km
kg/km
P5001CS
6.8
41
70
55
P5002CS
10.3
14.4
62
173
140
1390
121
344
P5004CS
11.8
16.6
71
200
280
2060
162
516
P5006CS
14.0
18.8
84
226
420
2520
196
631
P5008CS
14.4
19.3
87
231
560
2950
256
679
P5010CS
10
17.5
23.1
105
277
700
3360
304
972
P5012CS
12
18.0
23.6
108
284
840
4010
344
1031
P5016CS
16
19.9
25.6
120
307
1120
5060
431
1178
P5020CS
20
22.1
27.7
132
332
1400
6180
519
1343
P5024CS
24
25.0
30.6
150
367
1680
6960
634
1544
P5036CS
36
28.5
35.0
171
420
2520
9450
882
2153
Pairs
Nominal O.D
Approx.Mass
Plain
SWA
Plain
SWA
Plain
SWA
Plain
SWA
mm
mm
mm
mm
kg/km
kg/km
P5002ESCS
11.5
15.6
69
187
140
1550
146
391
P5004ESCS
13.3
18.1
80
218
280
2310
200
598
P5006ESCS
16.4
21.4
98
256
420
2890
266
772
P5008ESCS
16.8
21.7
101
261
560
3390
312
831
P5010ESCS
10
19.7
25.3
118
304
700
4170
384
1129
P5012ESCS
12
20.3
25.9
122
311
840
4980
437
1203
1393
P5016ESCS
16
22.5
28.2
135
338
1120
5900
551
P5020ESCS
20
25.4
31.1
153
373
1400
6860
691
1618
P5024ESCS
24
28.3
34.7
170
417
1680
8000
814
2084
P5036ESCS
36
32.4
39.3
194
471
2520
11160
1141
2626
1300
300 304
| WWW.PRYSMIAN.COM.AU 21
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
21
POWER CABLES
Pairs
Nominal O.D
Approx.Mass
Plain
SWA
Plain
SWA
Plain
SWA
Plain
SWA
mm
mm
mm
mm
kg/km
kg/km
P5102ES
1 Pair
8.1
12.4
48
149
210
1390
85
265
P5103ES
1 Triple
8.5
12.9
51
155
315
1480
107
309
Triples
Nominal O.D
Approx.Mass
Plain
SWA
Plain
SWA
Plain
SWA
Plain
SWA
mm
mm
mm
mm
kg/km
kg/km
P5304CS
13.4
18.2
80
219
420
2520
212
610
P5306CS
16.5
21.5
99
258
630
3150
297
803
P5312CS
12
20.1
25.7
121
309
1260
5450
471
1233
P5316CS
16
22.3
28.0
134
335
1680
6570
596
1435
P5336CS
36
32.1
38.9
192
467
3780
13480
1249
2698
Triples
Nominal O.D
Approx.Mass
Plain
SWA
Plain
SWA
Plain
SWA
Plain
SWA
mm
mm
mm
mm
kg/km
kg/km
P5304ESCS
15.2
19.5
91
234
420
2920
266
680
P5306ESCS
18.1
23.7
109
285
630
3940
346
1034
P5308ESCS
18.6
24.2
112
291
840
4980
399
1105
P5312ESCS
12
22.6
28.2
135
338
1260
6470
562
1405
P5316ESCS
16
25.5
31.2
153
374
1680
8050
739
1683
P5336ESCS
36
36.2
43.1
217
517
3780
15360
1504
3140
Pairs
Nominal O.D
Approx.Mass
Plain
SWA
Plain
SWA
Plain
SWA
Plain
SWA
mm
mm
mm
mm
kg/km
kg/km
P5502CS
12.4
17.3
75
207
420
1900
193
547
P5504CS
14.5
19.3
87
231
840
2700
272
686
1059
P5506CS
17.9
23.5
107
282
1260
3430
373
P5508CS
18.4
24.0
110
288
1680
4360
436
1141
P5510CS
10
21.6
27.2
130
327
2100
5320
536
1340
P5512CS
12
22.3
27.9
134
335
2520
5950
617
1458
22 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
22
1300304
300 304
POWER CABLES
Pairs
Nominal O.D
Approx.Mass
Plain
SWA
Plain
SWA
Plain
SWA
Plain
SWA
mm
mm
mm
mm
kg/km
kg/km
P5502ESCS
13.3
18.1
80
217
420
2140
215
589
P5504ESCS
16.7
21.6
100
260
840
3090
331
803
P5506ESCS
19.9
25.6
120
307
1260
4200
426
1173
P5508ESCS
20.4
26.1
123
313
1680
5360
501
1266
P5510ESCS
10
24.5
30.2
147
362
2100
6180
640
1546
P5512ESCS
12
25.3
31.0
152
372
2520
6960
736
1662
Pairs
Nominal O.D
Approx.Mass
Plain
SWA
Plain
SWA
Plain
SWA
Plain
SWA
mm
mm
mm
mm
kg/km
kg/km
P5604CS
17.1
22.0
102
264
1260
1260
390
868
P5606CS
20.4
26.1
122
313
1890
1890
512
1272
P5612CS
12
25.4
31.1
153
373
3780
3780
957
1816
P5604ESCS
18.3
24.0
110
288
1260
1260
425
1073
P5606ESCS
22.0
27.6
132
332
1890
1890
556
1380
P5612ESCS
12
28.1
34.5
168
414
3780
3780
989
2234
Units
P50 CS
P50 ESCS
P51 ES
P53 CS
P53 ESCS
P55 CS
P55 ESCS
mm
0.5
0.5
1.5
0.5
0.5
1.5
1.5
1.5
ohms/100m
3.84
3.84
1.36
3.84
3.84
1.36
1.36
1.36
Conductor Size
P56 CS
mohms/km
10
10
10
10
10
10
10
10
3.2
3.2
12
3.2
3.2
12
12
12
kV
pF/m
250
250
250
250
250
Capacitance Unbalanced
between pairs
pF/100m
100
100
100
100
L/R Ratio
H/ohms
25
25
40
25
25
40
40
40
Capacitance of pairs
1300
300 304
| WWW.PRYSMIAN.COM.AU 23
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
23
POWER CABLES
24 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
304
24
1300
300 304
Control Cables
en Star
Gre
POWER CABLES
CERTIFIED
Copper Conductor, V-90 PVC Insulated and 5V-90 Sheathed Control Cable, to AS/NZS 5000.1.
GREEN STAR
CERTIFIED
Min. Installed
Bending Radius
mm
1.53CECON
Catalogue
Reference
1.54CECON
2
Nominal
3 Area
Conductor
42
mm
10.1
Approx.
Overall10.9
Diameter
11.9
mm
15
Approx.
18 Mass
kg/100m
21
40
Min. Installed
45Radius
Bending
50
mm
1.55CECON
25CALXLP
1.56CECON
35CALXLP
1.57CECON
50CALXLP
1.58CECON
70CALXLP
1.510CECON
5
25
6
35
7
50
8
70
10
13.5
10.9
13.5
11.9
14.4
13.1
15.4
15.0
16.6
23
15
25
18
28
23
31
31
36
55
85
55
95
60
105
60
120
65
1.512CECON
95CALXLP
1.515CECON
120CALXLP
1.520CECON
150CALXLP
1.525CECON
185CALXLP
1.530CECON
12
95
15
120
20
150
25
185
30
17.3
16.9
19.2
18.5
21.1
20.4
23.3
22.6
24.6
41
40
49
48
61
58
73
73
85
70
135
75
145
85
165
95
180
100
200
170
240CALXLP
1.540CECON
240
40
25.3
28.0
93
110
1.550CECON
300CALXLP
50
300
31.4
28.0
135
114
190
225
400CALXLP
2
400
31.5
145
250
500CALXLP
500
35.2
180
280
630
39.6
230
315
Multicore Circular with Earth, 2.5mm2 Copper Conductor, V-90 PVC Insulated and 5V-90 PVC Sheathed Control Cable, to AS/NZS 5000.1.
Note: LSOH version available.
Approx.
Min. Installed
Approx. Mass
Catalogue Reference
No. Of Power Cores
Overall Diameter
Bending Radius
kg/100m
mm
mm
2.52CECON
11.3
20
2.53CECON
12.3
25
50
50
2.54CECON
13.3
30
60
2.55CECON
15.0
31
60
2.56CECON
15.0
36
60
2.57CECON
16.1
39
70
2.58CECON
17.2
43
80
2.510CECON
10
18.6
50
80
2.512CECON
12
19.5
58
80
2.515CECON
15
21.6
70
90
2.520CECON
20
23.8
89
100
160
2.525CECON
25
26.3
107
2.530CECON
30
27.4
124
170
2.540CECON
40
32.0
163
200
2.550CECON
50
35.9
201
220
een Star
Gr
POWER CABLES
CERTIFIED
GREEN STAR
CERTIFIED
2
XLPE
0.6/1KV
1.5MMALUMINIUM
MULTICORESDI
PVC
CONTROL SWA 0.6/1KV
Cable description:
2
Single
CoreCircular
Cable, Aluminium
Conductor,
X-90Conductor,
XLPE Insulated,
5V-90
PVC Sheathed,
AS/NZS
5000.1.
Multicore
with Earth, 1.5mm
Copper
V-90 PVC
Insulated
and PVCto
Bedded,
Steel
Wire Armoured, 5V-90 PVC
Note:
ClassControl
2 Compacted
Conductor.
Sheathed
Cable, to
AS/NZS 5000.1.
Approx. Approx.
Nominal Approx. Diameter
Approx.Approx.
Mass Mass
Overall Diameter
Catalogue
Reference
CoresArea Over Bedding
Overall Diameter
Catalogue
Reference No. Of Power
Conductor
kg/100m
kg/100m
2
mm
mm
mm
mm
Min.
Installed
Min.
Installed
Bending
Radius
Bending
Radius
mm
mm
1.52CECONA
25CALXLP
1.53CECONA
35CALXLP
25
9.1
10.9
15.2
15
48
35
9.9
11.9
16.1
18
52
1.54CECONA
50CALXLP
1.55CECONA
70CALXLP
1.56CECONA
95CALXLP
1.57CECONA
120CALXLP
1.58CECONA
150CALXLP
1.510CECONA
10
150
15.6
20.4
21.7
58
87
185CALXLP
1.512CECONA
12
185
16.3
22.6
22.4
73
94
180270
1.515CECONA
240CALXLP
15
240
18.2
25.3
24.3
93
108
200290
1.520CECONA
300CALXLP
1.525CECONA
400CALXLP
20
300
20.1
28.0
26.9
114
141
25
400
22.3
31.5
29.1
145
160
225340
250350
370
280
410
315
460
5
6
7
8
1.530CECONA
500CALXLP
1.540CECONA
630CALXLP
1.550CECONA
30
40
50
50
10.9
12.4
70
12.4
95
13.4
120
14.4
23.1
500
630
27.1
30.3
13.1
15.0
16.9
18.5
35.2
39.6
17.0
18.5
18.5
19.5
20.5
29.9
34.1
38.5
23
31
40
48
180
230
59
65
66
73
79
175
216
280
85190
95200
210
105
230
120
230
135
250
145
260
165260
Min. Installed
Bending Radius
mm
16.4
57
200
17.4
65
210
18.4
72
220
240
Catalogue Reference
Approx. Diameter
Over Bedding
mm
Approx.
Overall Diameter
mm
2.52CECONA
10.3
2.53CECONA
11.3
2.54CECONA
12.3
2.55CECONA
14.0
20.1
80
2.56CECONA
13.5
19.6
82
240
2.57CECONA
15.1
21.2
95
260
2.58CECONA
16.2
22.3
103
270
2.510CECONA
10
17.6
23.7
109
290
300
2.512CECONA
12
18.5
25.3
133
2.515CECONA
15
20.6
27.4
151
330
2.520CECONA
20
22.8
29.6
183
360
2.525CECONA
25
25.3
32.3
207
390
2.530CECONA
30
26.4
33.4
234
400
2.540CECONA
40
30.9
39.1
313
470
2.550CECONA
50
34.6
43.0
361
520
26 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
26
1300304
300 304
17
Aerial Cables
en Star
Gre
POWER CABLES
CERTIFIED
GREEN STAR
CERTIFIED
Single Core Aerial Cable, Hard Drawn Copper Conductor, V-90 PVC Insulated, Unsheathed, to AS/NZS5000.1.
Cable
description:
Single Core Cable, Aluminium Conductor,
X-90 XLPE Insulated, 5V-90
PVC Sheathed, to AS/NZS 5000.1.
Approx.
Nominal
Approx. Mass
Note:
Class 2 Compacted
Overall Diameter
Catalogue
Reference Conductor.
Conductor Area
kg/100m
mm
mm2
Approx.
Nominal
Single Core
Approx. Mass
Overall Diameter
Catalogue Reference
Conductor Area
61CAER
6.0
5.2
8
kg/100m
mm
mm2
101CAER
10
6.2
12
25CALXLP
25
10.9
15
161CAER
16
7.2
18
35CALXLP
35
11.9
18
251CAER
25
9.3
28
50CALXLP
50
13.1
23
351CAER
35
10.2
38
Min. Installed
Bending Radius
mm
Min. Installed
Bending Radius
20
mm
20
85
30
95
40
105
40
70CALXLP
501CAER
70
50
15.0
11.9
31
51
701CAER
95CALXLP
70
95
13.7
16.9
72
40
60
135
951CAER
120CALXLP
1201CAER
150CALXLP
95
120
120
150
15.9
18.5
17.4
20.4
98
48
120
58
60
145
70
165
1501CAER
185CALXLP
1851CAER
240CALXLP
150
185
185
240
19.5
22.6
21.7
25.3
148
73
189
93
80
180
90
200
300CALXLP
300
28.0
400CALXLP PARALLEL
400
31.5
PVC AERIAL
WEBBED 0.6/1KV
500CALXLP
Cable description:
500
35.2
120
50
114
225
145
250
180
280
630CALXLP
630
39.6
230
315
2 Core Parallel Webbed Aerial Cable, Hard Drawn Copper Conductor, V-90 PVC Insulated, Unsheathed, to AS/NZS 5000.1.
Note: LSOH version available.
Approx. Mass
kg/100m
Min. Installed
Bending Radius
mm
11.2x5.2
15
20
10
13.2x6.2
24
25
16
15.3x7.2
37
30
Catalogue Reference
Nominal
Conductor Area
mm2
Approx.
Overall Diameter
mm
6FIG8AER
6.0
10FIG8AER
16FIG8AER
2 Core
1300
300 304
| WWW.PRYSMIAN.COM.AU 27
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
27
een Star
Gr
POWER CABLES
CERTIFIED
GREEN STAR
CERTIFIED
XLPE
ALUMINIUM
SDI 0.6/1KV
PVC TWISTED
AERIAL
Cable description:
Single
Aluminium
Conductor,
X-90 XLPE
Insulated,
5V-90
AS/NZS 5000.1.
2, 3 & 4Core
CoreCable,
Twisted
Aerial Cable,
Hard Drawn
Copper
Conductor,
V-90PVC
PVCSheathed,
Insulated,toUnsheathed,
to AS/NZS 5000.1.
Note: Class 2 Compacted Conductor.
Min. Installed
Approx.
Nominal
Approx. Mass
Bending
Radius
Overall
Diameter
Catalogue Reference
Conductor
Min. Installed
Approx.
NominalArea
kg/100m
Approx.
Mass
2
mm
mm Area
Bending
Radius
Overallmm
Diameter
Catalogue Reference
Conductor
kg/100m
2
mm
mm
2mm
Core
25CALXLP
62CTAER
25
6.0
10.9
10.3
15
15
102CTAER
35CALXLP
10
35
12.3
11.9
24
18
85
60
70
95
162CTAER
50CALXLP
252CTAER
70CALXLP
16
50
25
70
37
23
57
31
90
105
110
120
95CALXLP
63CTAER
120CALXLP
103CTAER
150CALXLP
163CTAER
185CALXLP
253CTAER
95
6.0
120
10
150
16
185
25
14.4
13.1
18.5
15.0
3 Core
16.9
11.1
18.5
13.3
20.4
15.5
22.6
20.0
40
23
48
36
58
55
73
85
135
70
145
80
165
95
180
120
200
240CALXLP
240
425.3
Core
93
64CTAER
300CALXLP
6.0
300
12.4
28.0
30
114
75
225
104CTAER
400CALXLP
164CTAER
500CALXLP
10
400
16
500
14.9
31.5
17.4
35.2
48
145
73
180
90
250
105
280
254CTAER
630CALXLP
25
630
22.3
39.6
112
230
135
315
28 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
28
1300304
300 304
17
Firestop Cables
POWER CABLES
en Star
Gre
CERTIFIED
en Star
Gre
CERTIFIED
GREEN
STAR
CERTIFIED
GREEN STAR
CERTIFIED
Multicore Circular, Copper Conductor, Mica Glass Taped, X-90 XLPE Insulation, HFS-90-TP Sheathed, 0.6/1kV, to AS/NZS 5000.1 and
Cable
description:
AS/NZS 3013 WS Rating.
Single Core Cable, Aluminium Conductor, X-90 XLPE Insulated, 5V-90 PVC Sheathed, to AS/NZS 5000.1.
Note: Class 2 Compacted Conductor. Nominal
Approx.
Approx. Mass
Overall Diameter
Code
Conductor Area
kg/100m
mm
mm2
Approx.
Nominal
Approx. Mass
Overall2 Core
Diameter
Catalogue Reference
Conductor Area
kg/100m
mm
mm
*1.02CFS90
1.0 2
11.3
16
1.52CFS90
1.5
11.9
18
25CALXLP
25
10.9
15
2.52CFS90
2.5
12.9
22
35CALXLP
35
11.9
18
2 Core + Earth
50CALXLP
50
13.1
23
1.52CEFS90
1.5
11.9
19
2.52CEFS90
2.5
13.4
25
70CALXLP
70
15.0
31
42CEFS90
4.0
14.2
29
95CALXLP
95
16.9
40
62CEFS90
6.0
15.3
35
120CALXLP
120
48
318.5
Core
150CALXLP
150
20.4
58
1.03CFS90
1.0
11.9
17
1.53CFS90
1.5
12.5
20
185CALXLP
185
22.6
73
2.53CFS90
2.5
13.6
25
240CALXLP
240
25.3
93
3 Core + Earth
300CALXLP
300
28.0
114
1.53CEFS90
1.5
13.4
23
2.53CEFS90
2.5
14.6
29
400CALXLP
400
31.5
145
43CEFS90
4.0
15.6
35
500CALXLP
500
35.2
180
63CEFS90
6.0
16.8
43
630CALXLP
630
39.6
230
4 Core
*1.04CFS90
1.0
12.9
20
Note: LSOH version available.
1.54CFS90
1.5
13.6
23
2.54CFS90
2.5
14.8
30
4 Core + Earth
1.54CEFS90
1.5
14.6
26
2.54CEFS90
2.5
16.0
34
44CEFS90
4.0
16.8
42
64CEFS90
6.0
18.5
53
6 Core + Earth
1.56CFS90
1.5
16.1
28
1.56CEFS90
1.5
16.1
29
2.56CEFS90
2.5
17.6
39
7 Core
1.57CFS90
1.5
16.1
29
10 Core + Earth
1.510CEFS90
1.5
20.2
42
2.510CEFS90
2.5
22.2
57
20 Core + Earth
1.520CEFS90
1.5
25.7
72
2.520CEFS90
2.5
28.4
99
AS/NZS 3013
WS Rating
Min. Installed
Bending Radius
mm
WS51W
WS52W
85
WS52W
95
105
WS52W
WS52W
120
WS52W
135
WS52W
145
165
WS51W
WS52W
180
WS52W
200
225
WS52W
WS52W
250
WS52W
280
WS52W
315
WS51W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
en Star
Gre
en Star
Gre
POWER CABLES
CERTIFIED
GREEN
STAR
CERTIFIED
CERTIFIED
GREEN STAR
CERTIFIED
XLPE
ALUMINIUM
SDI250/450V
0.6/1KV & 0.6/1KV
FIRESTOP
FS90 FLAT
Cable description:
Single
Cable,Conductor,
AluminiumMica
Conductor,
X-90 XLPE Insulated,
PVC Sheathed,
Figure Core
8, Copper
Glass Taped,
Insulation,5V-90
HFS-90-TP
Sheathed,totoAS/NZS
AS/NZS5000.1.
5000.1 and AS/NZS 3013 WS Rating.
Note: Class 2 Compacted Conductor.
Approx.
Nominal
Approx. Mass
AS/NZS 3013
Overall
Dimensions
Code
Conductor
Min.
Approx.
NominalArea
kg/100m
WSInstalled
Rating
Approx.
Mass
2
mm Area
Bending Radius
Overallmm
Diameter
Catalogue Reference
Conductor
kg/100m
2
mm
mm
2 COREmm
250/450V
25CALXLP
*1.02CFF90LD
25
1.0
10.9
5.5x9.0
15
7.2
85
WS51W
*1.52CFF90LD
35CALXLP
1.5
35
5.7x9.6
11.9
8.5
18
WS51W
95
50CALXLP
*1.02CFF90HD
70CALXLP
*1.52CFF90HD
95CALXLP
50
1.0
70
1.5
95
2 CORE
0.6/1KV
13.1
7.7x11.2
15.0
8.0x11.8
16.9
23
10.3
31
12.0
40
105
WS52W
120
WS52W
135
120
18.5
48
145
150
20.4
58
165
73
180
93
200
120CALXLP
* Complies
to AS/ACIF S 008.
150CALXLP
SINGLE
CORE FIRESTOP
185CALXLP
185 FS110 0.6/1KV22.6
Cable240CALXLP
description:
240
25.3
300CALXLP
300 Glass Taped, R-HF-11028.0
114 to AS/NZS 5000.1. 225
Single Core
Circular, Copper Conductor, Mica
Insulation, HF-110-R Sheathed,
400CALXLP
400
31.5
145
250
Approx.
Nominal
500CALXLP
500
35.2
180 Mass
280 3013
Approx.
AS/NZS
Overall Diameter
Code
Conductor Area
kg/100m
WS315
Rating
630CALXLP
630 2
39.6
230
mm
mm
101CFS110
Note: LSOH
version available.
161CFS110
10
9.9
1.9
WS51W
16
10.9
25
WS52W
WS52W
251CFS110
25
13.1
38
351CFS110
35
14.2
47
WS52W
501CFS110
50
16.0
62
WS52W
701CFS110
70
17.6
82
WS52W
Nominal C.S.A.
mm2
251CFFFS110
25
13.7
36.0
WS52W
351CFFFS110
35
14.8
46.0
WS52W
501CFFFS110
50
16.4
61.0
WS52W
701CFFFS110
70
18.2
81.0
WS52W
WS52W
Approx. Mass
kg/100m
AS/NZS 3013
WS Rating
951CFFFS110
95
20.1
103.0
1201CFFFS110
120
21.8
128.0
WS52W
1501CFFFS110
150
24.0
157.0
WS52W
1851CFFFS110
185
26.1
189.0
WS52W
2401CFFFS110
240
29.3
245.0
WS52W
3001CFFFS110
300
32.2
303.0
WS52W
4001CFFFS110
400
36.3
394.0
WS52W
5001CFFFS110
500
40.4
495.0
WS52W
6301CFFFS110
630
45.9
654.0
WS52W
30 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
30
1300304
300 304
17
en Star
Gre
en Star
Gre
POWER CABLES
CERTIFIED
GREEN
STAR
CERTIFIED
CERTIFIED
GREEN STAR
CERTIFIED
XLPE
ALUMINIUM
SDI 0.6/1KV
MULTICORE
FIRESTOP
FS110 0.6/1KV
Cable description:
Single
CoreCircular,
Cable, Aluminium
Conductor,
XLPE
Insulated,
5V-90
PVC Sheathed,
AS/NZS 5000.1.
Multicore
Copper Conductor,
MicaX-90
Glass
Taped,
R-HF-110
Insulation,
HF-110-RtoSheathed,
to AS/NZS 5000.1 and AS/NZS 3013
Note:
Class 2 Compacted Conductor.
WS Rating.
Code
Catalogue
Reference
25CALXLP
103CEFS110
35CALXLP
163CEFS110
50CALXLP
253CEFS110
70CALXLP
353CEFS110
95CALXLP
503CEFS110
120CALXLP
703CEFS110
150CALXLP
953CEFS110
Nominal
Nominal
Conductor Area
Area
Conductor
mm22
mm
Approx.
Approx.
Overall Diameter
Diameter
Overall
mm
mm
25
10
35
3 Core
+ Earth
10.9
Approx. Mass
Mass
Approx.
kg/100m
kg/100m
Min. Installed
AS/NZS 3013
Bending Radius
WS Rating
mm
16
50
25
70
35
95
50
120
70
150
95
20.1
11.9
22.4
13.1
27.0
15.0
29.2
16.9
33.3
18.5
37.4
20.4
42.3
15
75
18
100
23
144
31
183
40
244
48
325
58
429
85
WS52W
95
WS52W
105
WS52W
120
WS52W
135
WS52W
145
WS52W
165
WS52W
185CALXLP
1203CEFS110
185
120
22.6
46.0
73
527
180
WS52W
1503CEFS110
240CALXLP
150
240
51.1
25.3
651
93
WS52W
200
1853CEFS110
300CALXLP
2403CEFS110
400CALXLP
185
300
240
400
56.4
28.0
63.8
31.5
818
114
1066
145
WS52W
225
WS52W
250
500CALXLP
104CEFS110
630CALXLP
164CEFS110
500
10
630
16
4 Core + Earth
35.2
22.2
39.6
24.8
180
94
230
126
280
WS52W
315
WS52W
254CEFS110
Note: LSOH
version available.
25
30.0
183
WS52W
354CEFS110
35
33.0
222
WS52W
504CEFS110
50
37.4
315
WS52W
704CEFS110
70
42.0
419
WS52W
954CEFS110
95
47.2
550
WS52W
1204CEFS110
120
51.2
676
WS52W
1504CEFS110
150
57.2
837
WS52W
1854CEFS110
185
63.7
1063
WS52W
2404CEFS110
240
72.2
1386
WS52W
17
1300
300 304
| WWW.PRYSMIAN.COM.AU 31
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
31
Its when the flames consume everything around them and the heat becomes intolerable
that our fire-resistance cable, Firestop, displays its best qualities. In intense heat conditions
it continues to supply all the critical functions such as fire alarm, emergency lighting and fans.
Low smoke and halogen-free like all the other cables in our Afumex series. Welcome to
our safe and secure cable family, Firestop.
Australian made? Yes, of course.
32 WWW.PRYSMIANCABLE.COM.AU
een Star
Gr
POWER CABLES
CERTIFIED
GREEN STAR
CERTIFIED
XLPE
ALUMINIUM
SDI 0.6/1KV
VaSTEC
EMC/VARIABLE
SPEED DRIVE 0.6/1KV
Cable description:
2
Single
Cable,2 Aluminium
X-90and
XLPE
Insulated,
PVC Sheathed,
to AS/NZS
1.5mmCore
& 2.5mm
cables are aConductor,
flexible, 3 core
earth
copper 5V-90
construction,
X-90 XLPE
insulated5000.1.
and 5V-90 PVC sheathed to
Note:
Class
2 Compacted
Conductor.
AS/NZS
5000.1
incorporating
a heavy duty tinned copper braid screen over metallised tape.
73
180
93
200
300CALXLP
300
28.0
114
225
400CALXLP
400
31.5
145
250
500CALXLP
500
35.2
180
280
630CALXLP
630
39.6
230
315
Code
Nominal
Conductor Area
mm2
Nominal Combined
Earth Area
mm2
Nominal Overall
Diameter
mm
Weight
kg/100m
10REMC
10
4.5
19.5
60
16REMC
16
7.5
22
90
25REMC
25
12
25.6
130
35REMC
35
18
28.1
170
50REMC
50
30
31.6
220
70REMC
70
30
35.3
290
95REMC
95
48
39.9
390
120REMC
120
48
43.6
470
150REMC
150
75
48.8
590
185REMC
185
75
54.1
720
240REMC
240
105
60.8
930
300REMC
300
150
66.9
1160
1300
300
304 || WWW.PRYSMIAN.COM.AU
WWW.PRYSMIAN.COM.AU 37
17
1300
300
1300 300
304
304
WWW.PRYSMIANCABLE.COM.AU
33
34 WWW.PRYSMIANCABLE.COM.AU
Communication Cables
35
COMMUNICATION CABLES
Fibre Size
Type Of Cable/
Construction
Jacket
Special Sheath
LT
F = Fibre
Optional
Mode
Armour
C
LAN CABLE
Product
Pair Count
Category
5E
L = Lan
4 = 4 pair
25 = 25 pair etc
Optional
Patch/Outdoor
Screening
Special Materials
CS
LS
P = Patch
P for Pair 3 = Cat 3
5E = Cat 5E O = Outdoor
6 = Cat 6
6A = Cat 6A
CS = Screened
ES = Element Screened
Colour
BL
J = Jelly
LS = low smoke zero halogen
(LSOH) flame retardant
BU = Blue
GR = Grey
RD = Red
GN = Green
WH = White
YE = Yellow
BK = Black
INTERNAL TELEPHONE
Product
Pair Count
T = Telephone
2 = 2 pair
10 = 10 pair etc
Optional
Internal
Screened or ISDN
CS
I for internal
P for pair
T for triple
C for core
CS = Screened
SDN = Balanced Pair
Station Cable
EXTERNAL TELEPHONE
Product
Pair Count
Conductor Size
Description
40
PE
T = Telephone
2 = 2 pair
10 = 10 pair etc
P for pair
40 = 0.40
64 = 0.64
90 = 0.90
PE = Polyethylene
IB = Integral Bearer
LI = Lead In
Optional
Jelly
Jacket
J = Jelly
Screened
M
N = Nylon
M = Moisture Barrier
CJMP
40 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
36
1300304
300 304
Optional
Colour
RDWH
RDWH = Red White
BLWH = Blue White
GNWH = Green White
LAN Cables
LAN CABLE M@XLAN
Category 6
Cable description:
Cat 6 - 1/0.57mm 24 AWG PACW, Polyolefin Insulated, Twisted Pair, Flame Retardant Low Smoke Sheath. ACMA and UL Listed.
Nominal Impedance 100 ohm. Tested up to 250MHz, (Tested up to 600MHz on request). Velocity of propogation 67%. Grey Sheath.
Category6
Code
No. Of Pairs
Description
Overall
Diameter
mm
L4P6
Unscreened
6.2
Max.
Min.
Bending Radius Pulling Tension
N
mm
50
190
Mass
kg/km
40
Category 6A
Cable description:
Cat 6A - 1/0.57mm 23 AWG PACW, Polyolefin Insulated, Twisted Pair, Flame Retardant Low Smoke Sheath. ACMA and UL Verified &
Listed. Nominal Impedance 100 ohm. Tested up to 500MHz, (Tested up to 750MHz on request). Velocity of propogation 67%. Grey or
Blue Sheath.
Category6A
Code
No. Of Pairs
Description
Overall
Diameter
mm
L4P6A
Screened
7.3
Max.
Min.
Bending Radius Pulling Tension
N
mm
60
180
Mass
kg/km
68
Category 5E
Cable description:
Cat 5E - 1/0.5mm 24 AWG PACW, Polyolefin Insulated, Twisted Pair, Flame Retardant Low Smoke Sheath. ACMA and UL Verified.
Nominal Impedance 100 ohm. Tested up to 100MHz, (Tested up to 450MHz on request). Velocity of propagation 67%. Blue Sheath.
Category5E
Code
No. Of Pairs
Description
Overall
Diameter
mm
L4P5E
Unscreened
5.2
Max.
Min.
Bending Radius Pulling Tension
N
mm
40
150
Mass
kg/km
30.5
1300
300 304
| WWW.PRYSMIAN.COM.AU 41
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
37
COMMUNICATION CABLES
Insulation
Thickness
mm
Twist
Pitch
mm
Buffer
Diameter
mm
Sheath
Diameter
mm
Sheath
Thickness
Cable
Diameter
25
0.9 0.05 mm
2.5 0.1 mm
Nominal 0.6mm
6.1 0.2 mm
Cable weight
approximate
Kg/km
40
Optical Unit
Insulation
Diameter
mm
Temperature Range
C
Flame
Resistance
Without Tension
Under Maximum
Tension
Installation
Transport and
Storage
Operation
10 x Cable-
15 x Cable-
IEC60332-1
Electrical Characteristics
Mean
Conductor
Resistance
Characteristc
DC resistance
Unbalance
Impedance
(20 C)
95 /km
2%
100 15
(100MHz)
Mutual
Capacitance
Insulation
Resistance
(20 5 C,
500 VDC)
56 nF/Km
5000M .km
Propagation
Delay
Delay skew
Velocity
propagation
Dielectric
Strength
(1.5kVdc)
approx 67%
1KV DC 1min
(core-core)
534+36/sqrt(f)
45 ns/100m
ns/100m
Attenuation
dB/100m
NEXT
dB/100m
PS-NEXT
(only for 4pairs)
dB/100m
ELFEXT
dB/100m
PS-ELFEXT
(only for 4pairs)
dB/100m
Return Loss
dB
Max
Min
Min
Min
Min
Min
2.1
65
62
64
61
20
4.1
56
53
52
49
23
10
6.5
50
47
44
41
25
16
8.2
47
44
41
37
25
20
9.2
46
43
38
35
25
23.5
31.25
11.7
43
40
34
31
62.5
17.0
38
35
28
25
21.5
100
22.0
35
32
24
21
20.0
42 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
38
1300304
300 304
Terminate the rat battle with heavy armour. Our all dielectric ARM@CORE fibre optic cables
are fully protected against ruthless Australian rodents. Despite the solid hardware these
loose tube cables are still surprisingly light-weight, flexible and easy to handle.
Australian made? Yes, of course.
39
Optical Fibre
OPTICAL FIBRE DESCRIPTION
Single Mode (S) OS2 (G652.d)
Fibre Size
Fibre Core/Cladding
(nom)
Code
m
S
9/125
Outside
Acrylate
Coated
mm
Attenuation
Effective
dB/km (max) @
Cable Cut-Off
Wavelength
1310 1385 1550 1625
nm
nm nm nm nm
0.25
1260
0.35
0.35
0.21
Mode Field
Diameter @
0.24
Refractive
Index (nom) @
1310nm
m
Chromomatic
Dispersion
ps/nm.km (max) @
9.2
1.467
1.468
3.5
1550
nm
1625
nm
18
22
Attenuation
dB/km (max) @
Coating Diameter
(m)
9/125
OS1/OS2
1310nm
1550nm
0.40
0.30
900
Fibre
Code
Fibre Size
Core/Cladding
(nom)
m
Outside
Acrylate
Coated
mm
Numerical
Aperture
(nom)
Overfilled Launch
Bandwidth
MHz. km (min) @
Attenuation
dB/km (max) @
850nm
1300nm
850nm
1300nm
Refractive Index
(nom) @
850nm
1300nm
M1
OM1
62.5/125
0.25
0.275
3.2
1.0
200
500
1.496
1.491
M3
OM3
50/125
0.25
0.200
2.5
0.7
1500*
500
1.482
1.477
M4
OM4
50/125
0.25
0.200
2.5
0.7
3500**
500
1.482
1.477
Fibre
Code
Core/Cladding
Diameters
(m)
Jacket Diameter
(m)
850nm
1300nm
850nm
M1
62.5/125
900
3.5
1.0
200
500
M3
50/125
900
3.5
1.0
1500*
500
M4
50/125
900
3.5
1.0
1300nm
40 WWW.PRYSMIANCABLE.COM.AU
43
COMMUNICATION CABLES
Code
Description
OD Mass
mm kg/km
Max.
Min. Bend Tensile
Strength
Radius
Install.
mm
kN
Operating
Temp
C
Tight Jacket
Crush
Resistance Coating Dia.
m
kN/100mm
F1M1PAT
Simplex 2mm
2.0
3.6
30
0.1
0 to 60
0.5
900
F1SPAT
Simplex 2mm
2.0
3.6
30
0.1
0 to 60
0.5
900
F1M1PAT24
Simplex
2.4
5.6
30
0.1
0 to 60
0.5
900
F1SPAT24
Simplex
2.4
5.6
30
0.1
0 to 60
0.5
900
Crush
Resistance
kN/100mm
Tight
Jacket
Coating
Dia.
m
Mass
kg/km
Max.
Min. Bend Tensile
Strength
Radius
Install.
mm
kN
Operating
Temp
C
Code
Description
F2M1Z1P
2.0 x 4.2
6.6
30
0.2
0 to 60
0.5
900
F2SZ1P
Zip-Cord 2mm
2.0 x 4.2
6.6
30
0.2
0 to 60
0.5
900
F2M1Z1P24
Zip-Cord
2.4 x 5.0
11.0
30
0.2
0 to 60
0.5
900
F2SZ1P24
Zip-Cord
2.4 x 5.0
11.0
30
0.2
0 to 60
0.5
900
44
41
COMMUNICATION CABLES
OPTICAL INDOOR/OUTDOOR
Light & Heavy Duty Riser.
Cable description:
Black UV Stabilised LSOH Sheath.
Features Tetracote for Easy Stripping, Tight Buffered 900 micron fibre, reinforced with water swellable aramid yarns and sheathed with
Flame retardant, Low Smoke, Zero Halogen compound (LSOH). Black Sheath. Nylon jacket is an option.
Description
OD
mm
Mass
kg/km
Min. Bend
Radius
Full Load
mm
Max. Tensile
Strength
Install.
kN
Operating
Temp
C
Crush
Resistance
kN/100mm
(Short term)
F2M1IOR
5.8
28
120
0.6
-10 to 70
0.5
F4M1IOR
5.8
28
120
0.6
-10 to 70
0.5
F6M1IOR
6.2
33
125
0.6
-10 to 70
0.5
F8M1IOR
6.8
36
140
0.6
-10 to 70
0.5
F12M1IOR
7.2
41
145
0.6
-10 to 70
0.5
F24M1IOR
8.0
58
160
0.9
-10 to 70
0.5
F48M1IOR
10.5
96
210
1.2
-10 to 70
0.5
Description
OD
mm
Mass
kg/km
Min. Bend
Radius
Full Load
mm
Max. Tensile
Strength
Install.
kN
Operating
Temp
C
Crush
Resistance
kN/100mm
F6SIOR
6.2
33
125
0.6
-10 to 70
0.5
F12SIOR
7.2
41
145
0.6
-10 to 70
0.5
F24SIOR
8.0
58
160
0.9
-10 to 70
0.5
Description
OD
mm
Mass
kg/km
Min. Bend
Radius
Full Load
mm
Max. Tensile
Strength
Install.
kN
Operating
Temp
C
Crush
Resistance
kN/100mm
F4M1IOB
8.0
80
180
0.7
-10 to 70
1.0
F6M1IOB
8.0
80
180
0.7
-10 to 70
1.0
F8M1IOB
9.9
95
200
1.2
-10 to 70
1.0
F12M1IOB
12.5
150
250
1.2
-10 to 70
1.0
Description
OD
mm
Mass
kg/km
Min. Bend
Radius
Full Load
mm
Max. Tensile
Strength
Install.
kN
Operating
Temp
C
Crush
Resistance
kN/100mm
F2SIOB
8.0
82
180
0.7
-10 to 70
1.0
OM2 & OM3 fibre types also available for Riser and Breakout cables.
42 WWW.PRYSMIANCABLE.COM.AU
45
COMMUNICATION CABLES
Description
OD
mm
Mass
kg/km
Min. Bend
Radius
Full Load
mm
Max. Tensile
Strength
Install.
kN
Operating
Temp
C
Crush
Resistance
kN/100mm
F6SLTN
10.0
73
200
2.0
-10 to 70
2.0
F12SLTN
10.0
73
200
2.0
-10 to 70
2.0
F24SLTN
10.0
74
200
2.0
-10 to 70
2.0
F48SLTN
10.0
76
200
2.0
-10 to 70
2.0
46
43
COMMUNICATION CABLES
OPTICAL ADSS
ADSS - All Dielectric Self Supporting Aerial Optic Fibre Cable.
In order to determine your cable requirements, please supply the following data:
- Maximum Span (metres)
- Maximum Ice Load (mm)
- Maximum Wind Loading (km/hr)
- Every day sag (metres or %)
If Maximum Span only is supplied the following characteristics are assumed:
- 1% normal sag, maximum 100 km/hr wind speed and 5mm radial ice load
Metrosp@n - 80 metre Span for Metropolitan Environments
80m Span - up to 60 fibres in water blocked loose tubes, dummy fillers (If needed), laid up around a Glass Reinforced Plastic (GRP)
Central Strength Member, aramid yarns reinforced & polyethylene overall sheathed.
Code
Description
OD
mm
Max.
Min. Bend Min. Bend
Radius Everyday
Radius
Mass
kg/km No Load Full Load Tension
kN
mm
mm
Max.
Working
Tension
kN
Operating
Temp
C
Crush
Resistance
kN/100mm
F12SAD80
Singlemode 12 Core
10.8
80
300
400
0.8
4.2
-10 to +70
F24SAD80
Singlemode 24 Core
10.8
80
300
400
0.8
4.2
-10 to +70
F36SAD80
Singlemode 36 Core
10.8
80
300
400
0.8
4.2
-10 to +70
F48SAD80
Singlemode 48 Core
10.8
80
300
400
0.8
4.2
-10 to +70
F60SAD80
Singlemode 60 Core
10.8
80
300
400
0.8
4.2
-10 to +70
Black UV Stabilised Sheath is standard. A Grey UV Resistant Sacrificial Sheath is available on request.
Code
Description
OD
mm
Max.
Min. Bend Min. Bend
Radius Everyday
Radius
Mass
kg/km No Load Full Load Tension
kN
mm
mm
Max.
Working
Tension
kN
Operating
Temp
C
Crush
Resistance
kN/100mm
F12SAD150
Singlemode 12 Core
10.5
76
300
400
1.4
4.1
-10 to +70
F24SAD150
Singlemode 24 Core
10.5
77
300
400
1.4
4.1
-10 to +70
F36SAD150
Singlemode 36 Core
10.5
79
300
400
1.4
4.1
-10 to +70
F48SAD150
Singlemode 48 Core
10.5
80
300
400
1.4
4.1
-10 to +70
F60SAD150
Singlemode 60 Core
10.5
81
300
400
1.4
4.1
-10 to +70
Code
Description
OD
mm
Max.
Min. Bend Min. Bend
Radius Everyday
Radius
Mass
kg/km No Load Full Load Tension
kN
mm
mm
Max.
Working
Tension
kN
Operating
Temp
C
Crush
Resistance
kN/100mm
2
F12SADD150
Singlemode 12 Core
13.5
13.5
400
500
1.3
5.5
-10 to +70
F24SADD150
Singlemode 24 Core
13.5
13.5
400
500
1.3
5.5
-10 to +70
F36SADD150
Singlemode 36 Core
13.5
13.5
400
500
1.3
5.5
-10 to +70
F48SADD150
Singlemode 48 Core
13.5
13.5
400
500
1.3
5.5
-10 to +70
F60SADD150
Singlemode 60 Core
13.5
13.5
400
500
1.3
5.5
-10 to +70
ADSS Cables also available in Multimode, higher fibre counts & Spans up to 500 metres.
Black UV Stabilised Sheath is standard. A Grey UV Resistant Sacrificial Sheath is available on request.
44 WWW.PRYSMIANCABLE.COM.AU
47
Telephone Cables
TELEPHONE INTERNAL/CAT 3 M@XTEL
Cable description:
M@XTEL INTERNAL/Cat 3. 1/0.50 PACW, Polyethylene Insulated, Twisted Pair, Unit Construction, Polyester Core Wrapped, PVC
Sheathed, ACMA Approved. Cream Coloured Sheath.
OD
mm
Code
Description
T2PI
2 pair
3.9
T3PI
3 pair
4.8
Max.
Pulling
Tension
N
Mass
kg/km
40
75
20
323/00165
50
110
27
323/00166
-
Min.
Bending
Radius
mm
T6PI
6 pair
6.8
70
230
52
T10PI
10 pair
8.4
85
380
75
T25PI
25 pair
11.5
115
950
152
323/00167
T50PI
50 pair
15.8
160
1900
280
T100PI
100 pair
21.3
215
3800
540
323/00168
Std. Pack Size: T2PI & T3PI 305M and 500m Box - T6PI 500m Reel - T10PI-T100PI 500 & 1000m Drum.
ISDN/STATION M@XDN
(Suitable for ISDN and DSL applications)
Cable description:
Internal Telephone Cable for 2 Mbit/s rate and 120 ohm @ 1 MHz.
1/0.5 PACW, Polyolefin Insulated, Twisted Pair, Aluminium/Laminate Screen with a 1/0.50mm Tinned Annealed Copper Drain Wire,
LSOH Thermoplastic Sheathed, ACMA Approved. Off White Coloured Sheath.
Code
OD
mm
Description
Min.
Bending
Radius
mm
Max.
Pulling
Tension
N
Mass
kg/km
24
ISDN/Station Cables
T1PISDN
ISDN 1
1 pair
4.5
50
40
T2PISDN
ISDN 2
2 pair
4.9
60
75
31
T4PISDN
ISDN 4
4 pair
7.2
100
150
53
T8PISDN
ISDN 8
8 pair
8.9
130
300
82
T16PISDN
ISDN 16
16 pair
12.2
180
600
142
T32PISDN
ISDN 32
32 pair
16.2
235
1200
238
25 pair available on request. Larger Pair Counts available on request. Std. Pack Size: 250m Reel or Drum.
The above Internal Telephone Cables can be supplied with Low Smoke Zero Halogen Flame Retardant (LSOHFR) Sheath.
48
45
COMMUNICATION CABLES
Code
Number Of Pairs
Max.
Pulling Tension
N
Min.
Bending Radius
mm
Overall Diameter
mm
Mass
kg/km
L25P30J
25
11.1
110
950
170
L50P30J
50
14.9
150
1900
320
L100P30J
100
20.2
200
3800
600
Code
Number Of Pairs
Overall Diameter
mm
Min.
Bending Radius
mm
Max.
Pulling Tension
N
Mass
kg/km
Telstra Version
for Approved
Contractors
Telstra Part No.
0.40 mm Conductor - Max Resistance 139.3 ohm/km, Max Capacitance Unbalance Pair to Pair 150pF/500m @ 800Hz
T10P40PEJ
10
7.5
120
240
60
467/05021
T30P40PEJ
30
11.6
190
720
145
467/05023
T50P40PEJ
50
14.2
230
1200
225
467/05024
T100P40PEJ
100
19.3
310
2400
425
467/05026
0.64 mm Conductor - Max Resistance 56.4 ohm/km, Max Capacitance Unbalance Pair to Pair 150pF/500m @ 800Hz
T10P64PEJ
10
10.2
165
600
115
T30P64PEJ
30
15.9
270
1800
300
T50P64PEJ
50
20.2
325
3100
485
T100P64PEJ
100
26.9
430
6200
915
0.90 mm Conductor - Max Resistance 27.9 ohm/km, Max Capacitance Unbalance Pair to Pair 150pF/500m @ 800Hz
T10P90PEJ
10
13.4
220
1200
210
T30P90PEJ
30
21.8
350
3600
580
T50P90PEJ
50
27.7
450
6000
950
T100P90PEJ
100
36.0
580
12100
1760
Note:
1. Nylon jacket can be supplied as protection against ants and termites. (Code = N).
2. A Sacrificial Sheath is optional (Code = 5).
3. Moisture Barrier version available (Code = M).
4. Mutual Capacitance max 49 nF/km.
46 WWW.PRYSMIANCABLE.COM.AU
49
COMMUNICATION CABLES
TELEPHONE TELSTRA
External Telephone Cable
Cable description:
External Telephone Cable - Telstra - For Approved Contractors Only.
Nominal Drum
Dimensions
mm
Max
Hauling
Tension
N
Stock
LW1 600/250/480
240
1000
Stock
LW1 600/250/480
240
11.7
1000
Stock
LW2 750/250/600
720
245
12.2
1000
Stock
LW2 750/250/600
720
225
230
14.2
1000
Stock
LW3 1000/350/600
1200
50
240
300
14.8
1000
Stock
LW3 1000/350/600
1200
100
425
310
19.3
1000
Stock
LW4 1100/400/600
2400
5432794
100
465
400
20.0
1000
Stock
LW4 1100/400/600
2400
467/09226
5441178
100
495
440
21.9
1000
8 weeks
STEEL 1200/600/1000
2400
467/07028
5412222
200
770
380
23.8
1000
Stock
STEEL 1200/600/1000
4800
467/09228
5442083
200
850
520
25.8
1000
8 weeks
STEEL 1200/600/1000
4800
467/07328
5414721
200
860
525
26.2
500
8 weeks
STEEL 1200/600/1000
4800
467/07030
5412239
400
1480
530
32.7
500
6 weeks
STEEL 1600/800/900
9600
400
1535
690
34.4
500
8 weeks
STEEL 1800/1000/900
9600
400
1595
705
35.1
500
8 weeks
STEEL 1800/1000/900
9600
Standard
Min
Overall
Stock/
Pack
Bending
Diameter
MTO
Length
Diameter
mm
mm
mm
Telstra
Serial/
Item
Number
Prysmian
Material
Code
Material
Description
Number
of Pairs
kg/
km
467/05021
5412055
10
60
120
7.5
1000
467/08121
5432763
10
65
165
8.1
467/05023
5412116
30
145
190
467/08123
5432770
30
160
467/05024
5412123
50
467/08124
5432787
467/05026
5412130
467/08226
467/09230
5442069
467/07330
5414738
467/07032
5412253
800
2915
750
46.6
100
6 weeks
STEEL 2400/1400/1000
19200
467/07332
5414745
800
3100
985
49.1
100
8 weeks
STEEL 1800/1000/900
19200
50
47
COMMUNICATION CABLES
Nominal Drum
Dimensions
mm
Max
Hauling
Tension
N
Stock
LW2 750/250/600
600
1000
Stock
LW3 1000/350/600
1800
21.4
1000
Stock
LW5 1250/450/600
3000
575
28.7
1000
Stock
STEEL 1600/800/900
6100
1006
600
29.9
1000
8 weeks
STEEL 1600/800/900
6100
200
1760
580
35.7
500
6 weeks
STEEL 1800/1000/900
12200
200
1825
750
37.4
1000
8 weeks
STEEL 2000/1200/1000
12200
200
1885
760
38.1
500
8 weeks
STEEL 2000/1200/1000
12200
400
3520
830
51.4
500
6 weeks
STEEL 2400/1200/1000
24500
400
3615
1060
53.0
500
8 weeks
STEEL 2400/1200/1000
24500
400
3715
1080
54.0
500
8 weeks
STEEL 2400/1200/1000
24500
10
245
290
14.5
1000
Stock
LW3 1000/350/600
1200
5432855
30
640
460
22.9
500
6 weeks
STEEL 1200/600/1000
3600
467/08264
5414943
50
1025
580
29.0
500
6 weeks
STEEL 1600/800/900
6000
467/08266
5414950
100
1885
760
37.9
500
6 weeks
STEEL 2000/1200/1000
12000
Standard
Min
Overall
Stock/
Pack
Bending
Diameter
MTO
Length
Diameter
mm
mm
mm
Telstra
Serial/
Item
Number
Prysmian
Material
Code
Material
Description
Number
of Pairs
kg/
km
467/08241
5432800
10
145
230
11.4
1000
467/08243
5432817
30
340
340
17.1
467/08244
5432824
50
540
430
467/08246
5432831
100
980
467/09246
5442106
100
467/07048
5414813
467/09248
5442113
467/07348
5414882
467/07050
5414820
467/09250
5442076
467/07350
5414899
467/08261
5432848
467/08263
48 WWW.PRYSMIANCABLE.COM.AU
51
COMMUNICATION CABLES
TELEPHONE AERIAL IB
Aerial IB - Integral Bearer Wire - Dry Core.
Cable description:
Solid PACW, Solid PE Insulated, Unit Twin Construction, Core wrapped, Al/Laminate Tape Screened plus Drain Wire, PE Sheathed,
Integral Bearer Construction with High Tensile Galvanised Steel Bearer Wire. ACMA Approved. Black UV Stabilised Sheath.
Code
Number Of
Pairs
Bearer Wire
No./mm
Overall
Diameter*
mm
Min.
Bending Radius
mm
Max.
Pulling**
Tension
N
Mass
kg/km
Telstra Version
for Approved
Contractors
Telstra Part No.
0.40 mm Conductor - Max Resistance 139 ohm/km, Max Capacitance Unbalance Pair to Pair 150pF/500m @ 800Hz
T10P40IB
10 Quad
1/2.50
7.8
160
2000
115
465/05221
T50P40IB
50
1/2.50
13.9
280
2000
260
465/05224
100
7/1.25
19.7
400
3500
510
465/05226
T100P40IB
0.64 mm Conductor - Max Resistance 56.4 ohm/km, Max Capacitance Unbalance Pair to Pair 120pF/1000m @ 800Hz
T10P64IB
10
1/2.50
10.4
210
2000
165
465/05241
T30P64IB
30
7/1.25
16.7
340
3500
390
465/05243
T50P64IB
50
7/1.25
21.0
420
3500
570
465/05244
T100P64IB
100
7/1.60
29.2
580
5800
1080
465/05246
0.90 mm Conductor - Max Resistance 27.9 ohm/km, Max Capacitance Unbalance Pair to Pair 150pF/500m @ 800Hz
T10P90IB
10
1/2.50
12.0
240
2000
240
T30P90IB
30
7/1.25
20.6
420
3500
650
T50P90IB
50
7/1.60
27.8
560
5800
1050
T100P90IB
100
7/1.60
38.4
770
9000
1970
Note:
*O/D measured over sheath excluding bearer wire. Mutual Capacitance max 52 nF/km.
**Tensile applied to the bearer wire.
52
49
COMMUNICATION CABLES
Prysmian
Material
Code
Material
Description
Number
of Pairs
kg/
km
Min
Bending
Diameter
mm
Overall
Diameter
mm
Standard
Pack
Length
mm
Stock
Vs
MTO
490/05023
5414776
CABLE, TEL
LEAD-IN 2/0.40
PEIFLI PE
18.5
80
4.6
500
Stock
490/08123
5432879
CABLE, TEL
LEAD-IN 2/0.40
PEIFLI PEHJC
20
100
4.7
500
Stock
490/05741
5414790
CABLE, TEL
LEAD-IN 2/0.64
PEILI PEIB
38
100
4.4
500
Stock
490/08142
5432886
CABLE, TEL
LEAD-IN 2/0.64MM
CPFLI PEHJC
37
100
6.3
500
Stock
490/05024
5407211
CABLE, TEL
LEAD-IN 5/0.40
PEIFLI PE
29
100
5.2
500
Stock
490/08124
5432916
CABLE, TEL
LEAD-IN 5/0.40
PEIFLI PEHJC
34
100
5.8
500
Stock
Max
Nominal Drum
Hauling
Dimensions
Tension
mm
N
REELEX 415/415/225
50
(MAGENTA)
1xREEL
(338/102/230),
50
CRTN
(340/340/245)
1xREEL
(338/102/230),
1000
CRTN
(340/340/245)
1xREEL
(422/102/306),
120
CRTN
(435/435/320)
REELEX 415/415/225
120
(MAGENTA)
1xREEL
(422/102/306),
120
CRTN
(435/435/320)
CONNECTING WIRE
Jumper Wire
Solid PACW, PVC Insulated, Max Resist 94.5, Capacitance Unbalance max 300/500m @ 800hz.
Number Of
Wires
Overall
Diameter
mm
CJMP2RDWH
Red-White
2 PACW
1.8
1/0.50
CJMP2GRWH
Green-White
2 PACW
1.8
1/0.50
50 WWW.PRYSMIANCABLE.COM.AU
Mass
kg/km
Telstra Version
For Approved
Contractors
Telstra Part No.
38
4.5
003/00250
38
4.5
003/00249
Max.
No./Dia. Wire
Pulling Tension
mm
N
Description
Code
53
Cables Selection
51
Cable Selection
The following are some simplified procedures for cable selection. Refer to the Wiring Rules
AS/NZS 3000 and AS/NZS 3008.1.1 for detailed information. The four main electrical
criteria for cable selection are:
a.
b.
c.
d.
Current rating.
Voltage drop.
Short-circuit capacity.
Earth loop impedance.
56 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
52
1300304
300 304
CABLE SELECTION
Current ratings in this technical manual are based on AS/NZS 3008.1.1 with the following
typical Australian installation conditions. If other installation conditions are necessary,
refer to derating/rating factors in the General Information section or/and AS/NZS 3008.1.1
for appropriate derating/rating factors.
B) Voltage drop:
Wiring Rules in general stipulate a maximum voltage drop of 5% of the nominal voltage
between the point of supply and any point in the installation when the conductors are
carrying maximum demand. Voltage drops in this technical manual are based on:
a.
b.
c.
d.
Vd x 1000
IxL
Vc
Vd
I
L
millivolts/ampere metre
Now select a cable such that Vc is equal to or less than the voltage drop value given in the
relevant table, and check that it will carry the current.
1300
300 304
| WWW.PRYSMIAN.COM.AU 57
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
53
CABLE SELECTION
C) Short-circuit capacity:
During a short-circuit, the conductor temperature will increase due to the heat energy
produced. To satisfy this requirement, short-circuit permissible temperature limit of the
conductor of cable must not be exceeded. This may require the time current curves of the
short-circuit protective device to be checked against the cable damage curves.
D) Maximum earth loop impedance:
The earth loop impedance has to be low enough to allow sufficient current to flow in the
fault loop to cause the protective device to operate and disconnect the supply within
the specified time when a fault of negligible impedance occurs between an active and
a protective earthing conductor. To accurately calculate the earth loop impedance is not
easy and requires information of the HV supply system that may or may not be available.
As the internal impedance of an earth loop may be expressed in terms of circuit length,
a simplified method is listed below to provide a reasonably accurate calculation of the
maximum route length to ensure correct operation of protective devices to provide
protection against indirect contact:
Lmax =
Where:
0.8Uo SphSpe
Ia (Sph + Spe)
Lmax Maximum route length (m).
Uo
Nominal phase voltage (230V).
P
Resistivity at normal working temperature (.mm2/m).
= 22.5 x 10-3 for copper.
= 36 x 10-3 for aluminium.
Ia
Sph
Spe
Notes:
1. This method is only reliable where the conductors that make up the earth-fault-current loop are in close proximity to each other and
are not separated by ferromagnetic materials.
2. This calculation method is considered valid for cable sizes up to 120mm2. For larger sizes, maximum length and fault loop impedance
should be calculated by other methods taking account of cable inductance.
58 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
304
54
1300
300 304
CABLE SELECTION
Maximum Route Lengths, in metres, for different sizes of Conductors and Protective
Devices using Mean Tripping Currents (la)* for a disconnection time of 0.4 sec.
Conductor Size
mm2
Active
Earth
Protective
Device Rating
Amps
Type B
Type C
Type D
Fuses
(see Note 2)
m
170
91
55
204
10
102
55
33
114
1.5
1.5
10
153
82
49
170
1.5
1.5
16
96
51
31
82
2.5
2.5
16
160
85
51
136
2.5
2.5
20
128
68
41
93
2.5
25
126
67
40
90
2.5
32
98
52
31
70
2.5
40
90
48
29
60
10
50
117
62
37
73
16
63
142
76
45
85
16
80
112
59
36
59
25
80
124
66
40
66
25
100
99
53
32
47
35
10
100
159
85
51
75
35
10
125
127
68
41
58
50
16
125
198
106
63
90
50
16
160
155
83
50
71
70
25
160
235
126
75
108
70
25
200
188
100
60
84
Notes:
1. * la for circuit-breakers are mean tripping currents as follows:
Type B = 4 times rated current.
Type C = 7.5 times rated current.
Type D = 12.5 times rated current.
2. Fuses based on AS/NZS 60269.1 also known as BS 88 type fuses.
3. When the nominal phase voltage of the electrical installation is not 230V, the maximum length may be determined by multiplying
by a factor of Uo/230. For a nominal phase voltage of 240V, the factor would be approximately 1.04.
4. The above table is for guidance only. In many cases, other requirements such as loading, short circuit and voltage drop will need to
be considered in the selection of active and earth conductor sizes.
1300
300 304
| WWW.PRYSMIAN.COM.AU 59
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
55
A perfect fit.
Cable solutions your way.
Your satisfaction is our livelihood. So it goes without saying we tailor-make our cable
solutions to fit your needs. To make sure our offer fits the bill we have both research
centres and very skilled experts at your service.
Australian made? Yes, of course.
56 WWW.PRYSMIANCABLE.COM.AU
57
Current Ratings
CURRENT RATINGS 2 SINGLE CORE (CU) 75C
Cable description:
2 Single Core LV, Non Flexible, Copper Conductor, Sheathed and Unsheathed Non-Armoured Cables with V-75, V-90, V-90HT PVC ,
HFI-75-TP or HFI-90-TP LSOH Insulation. Based on AS/NZS 3008.1.1.
Unenclosed
Nominal
Conductor
Area
mm2
Spaced
Enclosed
Thermal Insulation
Partially
Wiring
Spaced
Surrounded
Exposed
Enclosure
from Touching
by Thermal
to Sun
in Air
Surface
Insulation
Completely
Surrounded
by Thermal
Insulation
Buried
Direct
Underground Wiring
Enclosure
Single
Phase
Voltage
Drop
(@ 50Hz
& 75C)
mV/A.m
1.0
16
16
13
13
11
18
18
21
51.6
1.5
21
21
16
10
18
14
23
23
26
33.0
18.0
2.5
30
29
23
13
24
20
12
32
32
36
40
39
31
18
32
25
16
41
41
47
11.2
51
49
40
22
41
33
20
52
52
58
7.49
10
69
67
54
30
54
44
27
69
69
77
4.46
16
92
89
72
39
70
56
36
122
89
99
2.81
25
124
119
97
50
94
75
48
158
116
129
1.78
35
153
145
119
61
112
90
59
190
139
155
1.29
50
187
177
146
72
138
110
225
168
186
0.963
70
238
223
184
89
170
136
277
206
228
0.680
0.507
95
295
276
230
107
212
169
332
252
278
120
344
321
267
122
242
193
378
287
316
0.415
150
395
367
308
137
282
225
424
329
354
0.352
185
459
424
358
154
320
256
480
373
408
0.301
240
549
505
428
177
381
305
556
438
472
0.255
300
636
582
495
198
628
496
546
0.229
400
744
676
577
221
713
575
621
0.209
500
867
780
668
245
805
649
721
0.194
630
1014
897
770
269
904
750
816
0.181
Note:
Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
62 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
304
58
1300
300 304
Spaced
Enclosed
Thermal Insulation
Partially
Wiring
Spaced
Surrounded
Exposed
Enclosure
from Touching
by Thermal
to Sun
in Air
Surface
Insulation
Completely
Surrounded
by Thermal
Insulation
Buried
Direct
Underground Wiring
Enclosure
Single
Phase
Voltage
Drop
(@ 50Hz
& 90C)
mV/A.m
1.0
20
20
16
12
16
13
20
20
24
54.0
1.5
26
25
20
15
21
16
10
26
26
30
34.6
2.5
36
36
28
21
30
24
14
36
36
41
18.9
48
47
37
28
38
30
19
46
46
53
11.8
61
60
47
36
47
38
24
58
58
66
7.86
10
84
82
65
48
65
52
32
78
78
87
4.68
16
112
108
86
64
84
67
43
139
100
112
2.94
25
151
145
117
86
113
90
58
179
131
146
1.87
35
186
177
144
105
135
108
72
215
157
175
1.35
50
228
216
176
127
166
133
255
189
211
1.01
70
291
273
224
160
204
164
313
233
258
0.710
0.528
95
361
338
278
197
255
204
375
285
309
120
422
393
325
229
292
233
427
325
358
0.431
150
486
451
375
262
329
263
480
365
401
0.365
185
565
522
436
303
387
309
543
423
463
0.311
240
678
622
522
359
461
369
630
497
536
0.262
0.233
300
787
718
605
413
711
562
620
400
923
836
708
478
808
653
706
0.211
500
1078
966
821
550
913
739
800
0.196
630
1261
1113
950
629
1026
856
930
0.184
Note:
Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
1300
300 304
| WWW.PRYSMIAN.COM.AU 63
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
59
Spaced
Enclosed
Thermal Insulation
Partially
Wiring
Spaced
Surrounded
Exposed
Enclosure
from Touching
by Thermal
to Sun
in Air
Surface
Insulation
Completely
Surrounded
by Thermal
Insulation
Buried
Direct
Underground Wiring
Enclosure
Single
Phase
Voltage
Drop
(@ 50Hz
& 90C)
mV/A.m
16
87
84
67
50
65
52
33
107
78
87
4.91
25
117
112
91
66
87
70
45
139
102
114
3.08
35
144
137
111
81
105
84
56
167
122
136
2.24
50
177
167
136
99
129
103
198
147
164
1.65
70
226
212
174
124
159
127
243
181
200
1.15
95
280
262
216
153
198
158
291
221
239
0.839
0.672
120
328
305
253
178
226
181
332
252
278
150
377
350
291
204
255
204
372
283
311
0.557
185
439
406
340
236
301
241
423
329
359
0.455
240
527
485
408
280
360
288
492
388
417
0.363
300
612
562
473
323
556
440
482
0.307
400
723
660
559
377
638
516
553
0.261
500
850
772
656
439
729
590
632
0.227
630
1003
904
772
511
833
695
740
0.204
Note:
Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
64 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
60
1300304
300 304
Spaced
Enclosed
Thermal Insulation
Partially
Wiring
Spaced
Surrounded
Exposed
Enclosure
from Touching
by Thermal
to Sun
in Air
Surface
Insulation
Completely
Surrounded
by Thermal
Insulation
Buried
Direct
Underground Wiring
Enclosure
Single
Phase
Voltage
Drop
(@ 50Hz
& 110C)
mV/A.m
1.0
25
24
20
17
20
16
10
21
23
26
57.4
1.5
32
31
25
21
25
20
13
26
29
33
36.8
2.5
45
44
36
30
35
28
18
36
40
46
20.1
59
58
47
39
46
37
23
48
53
59
12.5
75
73
59
50
58
46
30
60
66
74
8.35
10
103
99
81
68
78
62
40
80
88
97
4.97
16
137
131
107
89
104
83
53
154
115
127
3.12
25
183
175
143
119
137
109
72
198
148
163
1.99
35
225
214
176
146
165
132
88
238
177
195
1.43
50
276
261
215
178
205
164
282
214
236
1.07
70
349
328
272
224
255
204
346
262
288
0.751
95
434
406
339
277
321
257
416
321
352
0.555
120
505
471
394
321
369
296
473
366
400
0.453
150
581
540
454
369
430
344
531
420
448
0.382
0.323
185
673
624
527
427
493
394
601
477
517
240
806
743
630
508
594
476
698
561
600
0.271
300
934
857
730
586
789
648
694
0.240
400
1094
998
853
682
898
738
790
0.216
500
1278
1155
990
789
1018
837
921
0.199
630
1498
1334
1146
909
1148
973
1045
0.185
Note:
Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
1300304
300 304
| WWW.PRYSMIAN.COM.AU 65
1300 300
WWW.PRYSMIANCABLE.COM.AU
61
Nominal
Conductor
Area
mm2
Unenclosed
Spaced
Enclosed
Thermal Insulation
Partially
Wiring
Spaced
Surrounded
Exposed
Enclosure
from Touching
by Thermal
to Sun
in Air
Surface
Insulation
Completely Buried
Surrounded Direct
by Thermal
Insulation
Underground
Wiring
Enclosure
Three Phase
Voltage Drop
(@ 50Hz
& 75 C)
mV/A.m
11.0
16
14
13
12
10
16
16
19
44.7
44.7
1.5
20
17
16
10
15
12
20
20
24
28.6
28.6
2.5
29
25
23
13
21
17
12
27
27
33
15.6
15.6
38
33
31
18
28
23
16
36
36
43
9.71
9.71
49
42
40
22
35
28
20
45
45
53
6.49
6.49
10
67
58
54
30
47
37
27
59
59
70
3.86
3.86
16
89
77
72
39
62
50
36
104
78
90
2.43
2.43
25
120
103
97
50
81
64
48
134
100
117
1.54
1.55
35
148
127
119
61
100
80
59
160
122
140
1.12
1.12
50
181
156
146
72
119
95
190
144
168
0.834
0.840
70
230
197
184
89
152
122
233
180
205
0.589
0.597
95
287
246
230
107
183
147
279
217
250
0.439
0.449
120
335
287
267
122
217
173
317
252
283
0.359
0.371
150
385
330
308
137
244
195
356
283
317
0.305
0.319
185
447
383
357
154
284
227
402
325
365
0.261
0.277
Note:
Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
66 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
62
1300304
300 304
Nominal
Conductor
Area
mm2
Unenclosed
Spaced
Enclosed
Thermal Insulation
Partially
Wiring
Spaced
Surrounded
Exposed
Enclosure
from Touching
by Thermal
to Sun
in Air
Surface
Insulation
Completely Buried
Surrounded Direct
by Thermal
Insulation
Underground
Wiring
Enclosure
Three Phase
Voltage Drop
(@ 50Hz
& 90 C)
mV/A.m
1.0
19
16
16
12
15
12
18
18
22
46.8
46.8
1.5
25
21
20
15
18
15
10
22
22
27
30.0
30.0
2.5
35
30
28
21
25
20
14
31
31
38
16.4
16.4
46
40
37
28
33
26
19
40
40
49
10.2
10.2
59
50
47
36
42
34
24
50
50
60
6.81
6.81
10
81
69
65
48
56
45
32
67
67
79
4.05
4.05
16
108
92
86
64
72
58
43
117
86
101
2.55
2.55
25
146
125
117
86
97
77
58
151
113
132
1.62
1.62
35
180
154
144
105
120
96
72
180
137
158
1.17
1.18
50
221
188
176
127
143
114
214
163
190
0.872
0.878
0.623
70
282
240
224
160
183
146
262
203
232
0.615
95
350
298
278
197
220
176
313
244
276
0.457
0.467
120
410
349
325
229
261
209
356
284
320
0.373
0.385
150
472
403
375
262
295
236
400
320
358
0.316
0.330
185
550
468
435
302
335
268
452
363
413
0.269
0.285
0.245
240
660
560
521
358
399
320
523
426
477
0.227
300
766
648
602
410
469
375
589
491
552
0.202
0.222
400
899
756
702
474
534
427
668
557
626
0.183
0.205
500
1051
874
812
544
633
506
752
648
707
0.170
0.193
630
1230
1010
938
621
714
571
843
727
820
0.159
0.182
Note:
Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
1300
300 304
| WWW.PRYSMIAN.COM.AU 67
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
63
Nominal
Conductor
Area
mm2
Unenclosed
Spaced
Enclosed
Thermal Insulation
Partially
Wiring
Spaced
Surrounded
Exposed
Enclosure
from Touching
by Thermal
to Sun
in Air
Surface
Insulation
Completely Buried
Surrounded Direct
by Thermal
Insulation
Underground
Wiring
Enclosure
Three Phase
Voltage Drop
(@ 50Hz
& 90 C)
mV/A.m
16
84
71
67
50
56
45
33
91
66
79
4.25
4.25
25
113
97
91
66
75
60
45
117
87
103
2.67
2.67
35
140
119
111
81
93
75
56
140
106
122
1.94
1.94
50
171
146
136
99
111
89
166
126
147
1.43
1.44
70
219
186
174
124
142
114
203
158
180
0.997
1.00
95
271
232
216
153
171
137
243
190
214
0.727
0.733
120
318
271
253
178
203
162
277
221
248
0.582
0.589
150
366
313
291
203
229
183
310
249
277
0.482
0.491
185
427
365
339
235
261
209
352
283
321
0.394
0.404
0.327
240
513
438
407
280
312
250
409
333
371
0.314
300
596
508
472
322
368
294
463
385
430
0.266
0.281
400
705
599
557
376
424
339
530
442
491
0.226
0.243
500
829
703
652
437
509
407
604
520
559
0.197
0.216
630
978
824
765
507
583
466
688
593
654
0.177
0.198
Note:
Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
68 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
304
64
1300
300 304
Nominal
Conductor
Area
mm2
Unenclosed
Spaced
Enclosed
Thermal Insulation
Partially
Wiring
Spaced
Surrounded
Exposed
Enclosure
from Touching
by Thermal
to Sun
in Air
Surface
Insulation
Completely Buried
Surrounded Direct
by Thermal
Insulation
Underground
Wiring
Enclosure
Three Phase
Voltage Drop
(@ 50Hz
& 110 C)
mV/A.m
10
99
86
81
68
71
57
40
71
77
88
4.30
4.30
16
132
114
107
89
93
74
53
130
99
115
2.70
2.71
25
177
153
143
119
125
100
72
168
130
148
1.72
1.72
35
218
188
176
146
151
121
88
201
155
176
1.24
1.25
50
267
230
215
178
182
146
237
184
212
0.924
0.929
70
339
291
272
224
234
187
291
230
259
0.650
0.657
95
422
363
339
277
285
228
348
277
315
0.481
0.491
120
492
422
394
321
337
269
396
322
357
0.392
0.403
150
565
486
453
368
382
306
445
362
400
0.331
0.344
185
656
564
526
426
449
359
503
415
461
0.280
0.296
240
786
674
629
507
548
439
583
492
533
0.235
0.252
300
912
780
727
584
626
501
657
556
617
0.208
0.227
400
1069
910
847
678
718
575
746
631
700
0.187
0.208
500
1248
1053
981
782
865
692
843
736
815
0.172
0.195
630
1462
1217
1132
898
983
787
947
827
920
0.160
0.184
Note:
Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
1300
300 304
| WWW.PRYSMIAN.COM.AU 69
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
65
Nominal
Conductor
Area
mm2
Unenclosed
Spaced
Touching
Enclosed
Exposed
to Sun
Wiring
Enclosure
in Air
Unenclosed
Thermal Insulation
Completely Buried
Partially
Surrounded Surrounded Direct
by Thermal by Thermal
Insulation Insulation
Underground
Wiring
Enclosure
Single Phase
Voltage Drop
(@ 50Hz
& 75 C)
mV/A.m
1.0
15
14
11
13
11
17
17
51.6
1.5
19
18
14
16
14
21
21
33.0
2.5
27
26
20
23
20
13
30
30
18.0
37
34
27
30
27
17
39
39
11.2
46
44
34
39
35
22
50
50
7.49
10
64
60
46
52
48
30
66
66
4.46
16
85
80
60
68
64
40
114
86
2.81
25
113
107
79
90
85
53
147
112
1.78
35
139
131
97
112
105
65
178
136
1.28
50
170
159
116
133
127
211
162
0.957
70
215
201
145
170
161
259
202
0.673
95
265
248
175
204
198
311
243
0.498
0.405
120
307
288
202
241
230
355
282
150
351
328
227
271
263
398
317
0.342
185
403
377
258
313
302
449
363
0.290
240
477
446
300
364
357
520
421
0.242
300
547
511
339
424
409
586
483
0.215
400
631
589
384
482
471
663
548
0.194
500
716
668
429
561
534
741
628
0.180
Note:
Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
70 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
304
66
1300
300 304
Nominal
Conductor
Area
mm2
Unenclosed
Spaced
Touching
Enclosed
Exposed
to Sun
Wiring
Enclosure
in Air
Unenclosed
Thermal Insulation
Completely Buried
Partially
Surrounded Surrounded Direct
by Thermal by Thermal
Insulation Insulation
Underground
Wiring
Enclosure
Single Phase
Voltage Drop
(@ 50Hz
& 90 C)
mV/A.m
1.0
18
17
15
16
14
19
19
54.0
1.5
24
22
19
20
18
11
24
24
34.6
2.5
34
31
27
28
25
16
34
34
18.9
45
42
36
37
33
21
45
45
11.8
57
53
46
46
42
27
56
56
7.85
10
78
73
63
63
58
36
75
75
4.68
16
104
97
83
82
78
49
132
98
2.94
25
140
131
111
110
105
66
170
128
1.86
35
173
162
136
132
129
81
205
154
1.35
50
211
197
165
162
158
244
185
1.00
70
268
250
208
200
200
300
228
0.703
95
331
309
255
250
247
360
279
0.520
120
385
359
295
285
287
410
318
0.423
150
441
411
336
332
328
460
365
0.354
185
509
473
385
377
379
520
413
0.299
240
604
562
454
448
449
603
485
0.249
300
694
645
518
523
516
680
558
0.219
400
804
745
594
596
596
771
633
0.197
500
915
848
671
695
678
862
728
0.182
Note:
Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
1300
300
304 | WWW.PRYSMIAN.COM.AU
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
71
67
Nominal
Conductor
Area
mm2
Spaced
Unenclosed
Enclosed
Touching
Exposed
to Sun
Wiring
Metallic
Enclosure
in Air
Thermal Insulation
Completely Buried
Partially
Surrounded Surrounded Direct
by Thermal by Thermal
Insulation Insulation
Underground
Wiring
Enclosure
Single Phase
Voltage Drop
(@ 50Hz
& 110 C)
mV/A.m
1.0
23
22
20
19
15
11
22
22
57.4
1.5
29
28
25
24
19
14
28
28
36.8
2.5
41
39
36
33
27
19
39
39
20.1
55
51
47
45
36
26
51
51
12.5
69
65
59
56
45
33
64
64
8.34
10
95
89
81
76
60
45
85
85
4.95
16
126
118
107
102
81
59
145
111
3.12
25
168
158
142
133
107
79
188
144
1.97
35
206
194
174
166
133
97
226
175
1.43
50
251
236
211
200
160
268
208
1.06
70
317
298
265
256
205
330
260
0.745
95
392
367
326
312
250
396
313
0.548
120
455
426
377
368
294
452
363
0.445
150
519
486
429
417
333
507
409
0.372
185
598
559
491
486
389
573
468
0.313
240
708
662
580
588
470
665
554
0.259
300
815
760
664
670
536
751
626
0.226
400
941
878
763
768
615
853
711
0.202
500
1074
1000
866
905
724
957
819
0.185
Note:
Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
72 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
304
68
1300
300 304
Nominal
Conductor
Area
mm2
Unenclosed
Spaced
Touching
Enclosed
Exposed
to Sun
Wiring
Enclosure
in Air
Unenclosed
Thermal Insulation
Completely Buried
Partially
Surrounded Surrounded Direct
by Thermal by Thermal
Insulation Insulation
Underground
Wiring
Enclosure
Three Phase
Voltage Drop
(@ 50Hz
& 75 C)
mV/A.m
1.0
13
12
11
14
14
44.7
1.5
16
15
12
14
12
18
18
28.6
2.5
23
22
17
20
17
11
25
25
15.6
31
29
23
25
23
15
33
33
9.71
40
37
29
33
30
19
42
42
6.49
10
54
51
39
44
41
25
55
55
3.86
16
72
68
51
58
54
34
96
73
2.43
25
97
91
67
76
73
46
125
94
1.54
35
120
112
82
94
90
56
150
114
1.11
50
146
137
99
112
109
178
136
0.829
70
185
172
123
142
138
219
170
0.583
95
228
213
150
177
170
263
208
0.431
120
265
247
172
202
198
300
237
0.351
150
303
282
194
228
226
336
266
0.296
185
348
324
220
263
259
379
304
0.251
240
412
383
256
316
307
438
359
0.210
300
472
438
288
493
404
0.186
400
544
504
326
557
468
0.168
500
616
571
363
620
522
0.156
Note:
Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
1300
300 WWW.PRYSMIANCABLE.COM.AU
304 | WWW.PRYSMIAN.COM.AU
1300 300
304
73
69
Nominal
Conductor
Area
mm2
Unenclosed
Enclosed
Exposed
to Sun
Wiring
Enclosure
in Air
Unenclosed
Thermal Insulation
Completely Buried
Partially
Surrounded Surrounded Direct
by Thermal by Thermal
Insulation Insulation
Underground
Wiring
Enclosure
Three Phase
Voltage Drop
(@ 50Hz
& 90 C)
mV/A.m
Spaced
Touching
1.0
16
14
13
13
12
16
16
46.8
1.5
20
19
16
16
15
20
20
30.0
2.5
28
26
23
24
21
13
29
29
16.4
38
35
30
30
28
18
37
37
10.2
48
45
39
38
36
22
46
46
6.80
10
66
62
53
53
49
31
63
63
4.05
16
88
83
70
68
66
41
110
81
2.55
25
119
111
94
91
89
56
143
107
1.61
35
147
137
115
114
110
69
172
130
1.17
50
180
168
140
136
134
204
155
0.868
70
229
213
177
173
170
251
193
0.609
95
283
263
217
209
210
302
233
0.450
120
330
306
251
246
245
344
270
0.366
150
377
350
285
277
280
385
304
0.307
185
436
404
327
322
323
435
348
0.259
240
517
479
385
386
383
504
411
0.216
300
594
549
439
567
463
0.190
400
685
632
502
640
524
0.171
500
779
718
566
714
601
0.158
Note:
Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
74 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
304
70
1300
300 304
Nominal
Conductor
Area
mm2
Spaced
Unenclosed
Enclosed
Touching
Wiring
Metallic
Enclosure
in Air
Exposed
to Sun
Thermal Insulation
Completely Buried
Partially
Surrounded Surrounded Direct
by Thermal by Thermal
Insulation Insulation
Underground
Wiring
Enclosure
Three Phase
Voltage Drop
(@ 50Hz
& 110 C)
mV/A.m
1.0
20
18
17
16
13
17
19
49.7
1.5
25
24
22
20
16
12
21
24
31.9
2.5
35
33
30
29
23
17
30
33
17.4
47
44
40
38
30
22
39
43
10.8
59
56
50
47
38
28
49
53
7.22
10
81
76
69
64
51
38
65
71
4.29
2.70
16
107
101
91
86
68
50
122
93
25
144
135
121
116
93
67
158
122
1.71
35
177
166
148
140
112
83
190
146
1.24
50
216
202
180
174
139
226
177
0.920
70
272
255
227
217
173
277
217
0.645
95
337
314
278
270
216
333
267
0.475
120
391
364
322
311
249
379
304
0.385
150
447
416
367
360
288
426
346
0.322
185
515
479
421
411
329
481
391
0.271
240
611
567
496
498
398
558
463
0.224
0.196
300
701
650
567
629
522
400
810
751
651
713
608
0.175
500
921
852
737
797
680
0.160
Note:
Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
1300304
300 304
| WWW.PRYSMIAN.COM.AU 75
1300 300
WWW.PRYSMIANCABLE.COM.AU
71
Single Core
2 m/s wind
3 and 4 Core
Twisted Cable
2 m/s wind
Single Phase
Three Phase
79
59
56
7.75
6.71
10
109
80
76
4.63
4.01
2.55
16
145
107
100
2.94
25
191
142
133
1.93
1.67
35
232
171
160
1.45
1.26
50
276
205
192
1.14
0.988
70
347
257
242
0.886
0.767
Note:
Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
94.9
82.2
0.75
7.5
63.3
54.8
1.0
10
47.5
41.1
1.5
16
32.3
28.0
2.5
20
19.4
16.8
4.0
25
12.0
10.4
Nominal
Conductor Area
mm2
Note:
1. Where a flexible cord is wound on a drum, multiply current-carrying capacity by the appropriate factor, as follows:
Number of layers:
1
2
3
4
Derating factor:
0.76
0.58
0.47
0.40
2. Not applicable for tinsel conductor.
3. Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
76 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
72
1300304
300 304
Nominal
Conductor
Area
mm2
Unenclosed
Spaced
Enclosed
Thermal Insulation
Partially
Wiring
Spaced
Surrounded
Exposed
Enclosure
from Touching
by Thermal
to Sun
in Air
Surface
Insulation
Completely Buried
Surrounded Direct
by Thermal
Insulation
Underground
Wiring
Enclosure
Three Phase
Voltage Drop
(@ 50Hz & 90C)
mV/A.m
10
80
69
64
48
55
45
32
67
66
79
4.22
4.22
16
106
91
85
63
73
58
43
117
85
101
2.68
2.68
25
142
121
114
83
94
77
58
151
109
132
1.73
1.74
35
177
151
141
103
118
96
72
180
134
158
1.24
1.24
50
223
191
178
128
144
114
214
163
190
0.869
0.875
70
283
241
225
161
183
146
262
203
232
0.622
0.630
95
341
290
271
192
214
176
313
237
276
0.483
0.492
120
406
346
322
226
256
209
356
279
320
0.388
0.399
150
470
400
372
260
291
236
400
316
358
0.325
0.338
185
540
459
427
296
334
268
452
357
413
0.280
0.295
240
651
553
514
352
391
320
523
416
477
0.233
0.251
300
752
637
591
402
458
375
589
479
552
0.207
0.227
400
909
764
709
477
533
427
668
554
626
0.183
0.204
500
1062
884
821
546
630
506
752
642
707
0.169
0.192
630
1256
1030
956
630
719
571
843
729
820
0.157
0.181
Note:
Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
1300
300 304
| WWW.PRYSMIAN.COM.AU 77
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
73
Nominal
Conductor
Area
mm2
Unenclosed
Spaced
Enclosed
Thermal Insulation
Partially
Wiring
Spaced
Surrounded
Exposed
Enclosure
from Touching
by Thermal
to Sun
in Air
Surface
Insulation
Completely Buried
Surrounded Direct
by Thermal
Insulation
Underground
Wiring
Enclosure
Three Phase
Voltage Drop
(@ 50Hz &
110C)
mV/A.m
10
99
85
80
67
70
57
40
77
76
88
4.48
4.48
16
130
112
105
88
91
74
53
130
97
115
2.84
2.85
25
173
149
139
116
121
100
72
168
125
148
1.84
1.84
35
214
184
172
143
148
121
88
201
151
176
1.31
1.31
50
270
233
217
179
190
146
237
188
212
0.921
0.926
70
340
292
273
224
234
187
291
229
259
0.658
0.665
95
410
353
329
269
277
228
348
268
315
0.509
0.518
120
487
418
390
317
331
269
396
316
357
0.408
0.419
150
562
482
450
365
378
306
445
357
400
0.340
0.353
185
644
553
516
417
438
359
503
404
461
0.293
0.307
240
775
665
620
499
538
439
583
481
533
0.242
0.259
300
895
766
714
572
612
501
657
542
617
0.213
0.232
400
1079
918
855
682
757
575
746
648
700
0.187
0.208
500
1260
1064
990
786
864
692
843
729
815
0.172
0.194
630
1493
1240
1154
913
993
787
947
828
920
0.159
0.182
Note:
Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
78 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
74
1300304
300 304
Nominal
Conductor Area
mm2
2 Single
Core
3 Single
Core
1 Phase
Voltage
Drop
(@ 50Hz
& 75C)
mV/A.m
Exposed to Sun
2 Core
3 and 4
Core
2 Single
Core
3 Single
Core
2 Core
3 and 4
Core
3 Phase
Voltage Drop
(@ 50Hz & 75C)
mV/A.m
3 Phase
Voltage
Drop
(@ 50Hz
& 75C)
mV/A.m
2,3 and
4 Core
Single Core
1.5
17
17
18
16
10
10
14
12
32.3
28.0
28.0
28.0
2.5
22
22
25
21
13
13
19
16
19.4
16.8
16.8
16.8
30
30
33
28
17
17
26
22
12.0
10.4
10.4
10.4
38
38
42
36
21
21
32
28
8.03
6.95
6.96
6.95
10
54
54
59
51
29
29
45
38
4.65
4.03
4.03
4.03
16
71
71
78
67
38
38
59
50
2.96
2.56
2.56
2.55
25
94
94
104
89
49
49
77
65
1.91
1.65
1.66
1.65
35
117
117
128
110
59
59
94
80
1.36
1.18
1.18
1.18
50
147
147
161
138
73
73
117
100
0.960
0.831
0.837
0.827
70
185
185
202
173
89
89
145
123
0.688
0.596
0.603
0.591
95
223
223
241
207
104
104
170
145
0.535
0.463
0.473
0.457
120
265
264
285
244
120
120
199
169
0.431
0.373
0.385
0.367
150
306
305
326
280
135
135
225
192
0.361
0.313
0.327
0.306
185
351
350
370
318
150
149
252
215
0.314
0.272
0.287
0.264
240
422
420
439
378
173
172
294
251
0.262
0.227
0.245
0.219
Note:
Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
1300
300 304
| WWW.PRYSMIAN.COM.AU 79
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
75
Nominal
Conductor Area
mm2
2 Single
Core
3 Single
Core
2 Core
1 Phase
Voltage
Drop
(@ 50Hz
& 90C)
mV/A.m
Exposed to Sun
3 and 4
Core
2 Single
Core
3 Single
Core
2 Core
3 and 4
Core
3 Phase
Voltage Drop
(@ 50Hz & 90C)
mV/A.m
3 Phase
Voltage
Drop
(@ 50Hz
& 90C)
mV/A.m
Multicore
Single Core
1.5
20
20
23
19
16
16
20
17
33.9
29.4
29.4
2.5
27
27
30
26
21
21
26
22
20.3
17.6
17.6
29.4
17.6
36
36
40
34
27
27
35
29
12.6
10.9
10.9
10.9
46
46
51
43
34
34
44
37
8.42
7.29
7.29
7.29
10
64
64
72
61
48
48
62
52
4.87
4.22
4.22
4.22
2.68
16
85
85
96
81
63
63
82
69
3.09
2.68
2.68
25
114
114
128
108
83
83
108
92
2.00
1.73
1.74
1.73
35
141
141
158
135
103
103
134
113
1.43
1.24
1.24
1.23
50
178
178
199
170
128
128
167
142
1.00
0.869
0.875
0.866
70
225
225
251
214
161
161
209
177
0.718
0.622
0.630
0.618
95
271
271
300
256
192
192
248
211
0.558
0.483
0.492
0.477
120
322
322
355
303
226
226
292
248
0.448
0.388
0.399
0.383
150
373
372
408
348
260
260
333
283
0.375
0.325
0.338
0.318
185
428
427
464
396
296
296
377
320
0.323
0.280
0.295
0.273
240
515
514
554
472
353
352
446
379
0.269
0.233
0.251
0.225
300
594
591
633
539
404
402
507
430
0.239
0.207
0.227
0.198
400
715
709
751
638
480
477
597
504
0.211
0.183
0.204
0.174
500
830
821
862
730
552
546
679
573
0.195
0.169
0.192
0.16
630
969
956
639
630
0.181
0.157
0.181
Note:
Refer to Cable Selection in General Information for more information and data based on AS/NZS 3008.1.1.
80 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
76
1300304
300 304
100
Number of
Circuits
Distance (S), m
S
0.30
0.45
0.15
0.60
0.83
0.88
Derating factors
0.73
0.79
0.68
0.64
0.15
0.61
0.59
0.83
0.57
0.73
0.56
0.68
0.55
0.64
0.54
0.61
0.53
0.59
0.57
0.56
0.55
0.54
0.53
0.91
0.93
0.84
0.87
0.74
0.81
0.85
Distance
(S),
m
Distance (S), m
0.73
0.79
0.83
0.30 0.45
0.450.60
0.30
0.71
0.78
0.82
0.88
0.91
0.69
0.76
0.82
0.88
0.91
0.93
0.79 0.76
0.840.81
0.68
0.79
0.74 0.84
0.81 0.87
0.67
0.75
0.81
0.74
0.81
0.85
0.73 0.75
0.79 0.80
0.67
0.73
0.79
0.83
0.66
0.71 0.74
0.78 0.80
0.71
0.78
0.82
0.66
0.74
0.80
0.69
0.76
0.69
0.76
0.82
0.68
0.76
0.68
0.76
0.81
0.67 0.75
0.75 0.81
0.67
0.67 0.75
0.75 0.80
0.67
0.66 0.74
0.74 0.80
0.66
0.66
0.66 0.74
0.74 0.80
Derating factors
0.15
0.83
0.73
0.68
0.64
0.61
0.59
0.57
0.56
0.55
0.54
0.53
0.60
0.93
0.87
0.85
0.83
0.82
0.82
0.81
0.81
0.80
0.80
0.80
0.15
2 2
3 3
4 4
Number of
5 5
cables in group
6 6
7
2 7
8
3 8
9
4 9
10
5
11 10
6
12 11
7 12
8
9
10
11
12
0.87
0.78
0.74
0.70
0.15
0.68
0.66
0.87
0.64
0.78
0.63
0.74
0.62
0.70
0.61
0.68
0.60
0.66
0.64
0.63
0.62
0.61
0.60
0.81 0.81
0.70 0.70
0.63 0.63
0.59 0.59
Touching
0.55 0.55
0.52
0.81 0.52
0.50
0.70 0.50
0.48
0.63 0.48
0.47
0.59
0.45 0.47
0.55
0.44 0.45
0.52 0.44
0.50
0.48
0.47
0.45
0.44
Derating factors
Derating factors
Distance (S), m
Distance (S), m
0.30
0.45
0.15
0.87 S
0.30
0.91
0.91
0.93
0.78
0.84
0.84
0.88
Derating factors
0.81
0.86
0.74
0.81
Distance (S), m
0.78
0.84
0.70
0.78
0.30
0.45
0.77
0.83
0.68
0.77
0.75
0.82
0.66
0.75
0.91
0.93
0.75
0.81
0.64
0.75
0.84
0.88
0.74
0.81
0.63
0.74
0.81
0.86
0.73
0.80
0.78
0.84
0.62
0.73
0.73
0.80
0.77
0.83
0.61
0.73
0.72
0.80
0.75
0.82
0.60
0.72
0.75
0.81
0.74
0.81
0.73
0.80
0.73
0.80
0.72
0.80
0.45
0.93
0.88
0.86
0.84
0.83
0.82
0.81
0.81
0.80
0.80
0.80
0.60
0.95
0.90
0.89
0.87
0.60
0.87
0.86
0.95
0.86
0.90
0.85
0.89
0.85
0.87
0.85
0.87
0.84
0.86
0.86
0.85
0.85
0.85
0.84
0.60
0.95
0.90
0.89
0.87
0.87
0.86
0.86
0.85
0.85
0.85
0.84
1300
300 304
| WWW.PRYSMIAN.COM.AU 81
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
77
MULTICOREMULT
101304
SALES 1300 300SALES
304 1300 300
Number
of Of
Number
Touching
cablesCables
in group
In Group
Touching
SINGLE CORE
SINGLE CORE DERATING FACTORS
DERATING FACTORS
2
3
Number
Number
4 of Of
Circuits
5Circuits
6
7 2
2
8 3
3 4
9
4
10 5
5
11 6
6
12 7
7
8 8
9 9
10 10
11 11
12 12
Touching
Trefoil
Laid flat
S
0.78
0.81
0.66
0.70
0.61
0.64
Touching
Touching
0.56
0.60
Trefoil
Laid flat
Trefoil
Laid flat
0.53
0.57
0.78
0.50
0.54 0.81
0.78
0.81
0.490.66
0.53 0.70
0.660.61
0.70 0.64
0.47
0.51
0.610.56
0.64
0.46
0.50 0.60
0.56
0.60
0.440.53
0.49 0.57
0.53
0.57
0.430.50
0.48 0.54
0.50
0.54
0.49
0.49
0.53 0.53
0.470.47
0.51 0.51
0.460.46
0.50 0.50
0.440.44
0.49 0.49
0.430.43
0.48 0.48
DERATING FACTORS
DERATING FACTORS
Derating factors for groups of circuits of cables buried direct in the ground Derating factors
Single Core cables.
Derating factors
Derating
for groups
factors
of circuits
for groups
of cables
of circuits
buried
of direct
cablesinburied
the direct in the
Derating factors
Derating
for groups
factors
of circuits
for groups
of cables
of circuits
buried
of direct
cablesinburied
the dire
ground Single
ground
Core cables.
Single Core cables.
ground Multicore
ground
cables.
Multicore cables.
100
Derating factors for groups of circuits of cables installed in underground wiring enclosures
S
- Single Core cables enclosed separately.
Derating factors
Number of
Circuits
2
Number of
3Number Of
Circuits
4 Circuits
5
2
6
2
3
7
3 4
8
4
5
9
5
10 6
6
11 7
7
12 8
8
9 9
10 10
11 11
12 12
Touching
S
0.87
0.78
Touching
0.74 Touching
0.70
0.69 0.87
0.87 0.78
0.67
0.78 0.74
0.66
0.74
0.65 0.70
0.70
0.64 0.69
0.69
0.63
0.67 0.67
0.63
0.66 0.66
0.65 0.65
0.64 0.64
0.63 0.63
0.63 0.63
Distance (S), m
0.45
0.60
Derating factors
0.91 Derating factors
0.93
0.84
0.87
Distance
(S), m
Distance (S), m
0.81
0.85
0.45
0.60
0.45
0.79
0.83
0.91
0.78
0.82
0.91
0.93
0.84
0.76
0.82
0.84
0.87
0.81
0.76
0.81
0.81
0.85
0.79
0.75
0.81
0.79
0.83
0.75
0.80
0.78
0.78
0.82
0.74
0.80
0.76
0.76
0.82
0.74
0.80
0.76
0.76
0.81
0.75
0.75
0.81
0.75
0.80
0.75
0.74
0.80
0.74
0.74
0.80
0.74
0.60
0.93
0.87
0.85
0.83
0.82
0.82
0.81
0.81
0.80
0.80
0.80
Derating factors for groups of circuits of cables installed in underground wiring enclosures
- Multicore cables enclosed separately or more than one Single Core cable per wiring
enclosure.
2 2
3 3
Number of
4 4
Circuits
5 5
6 6
2
7 7
3
8
4 8
9
5 9
10
6
11 10
7 11
12
8
12
9
10
11
12
Touching
Touching
S
Derating factor
Derating factors
Distance (S), m
Distance (S), m
0.30
0.45
0.60
S0.45
0.30
0.90 0.90
0.83 0.83
Touching
0.79 0.79
0.75 0.75
0.73 0.73
0.90
0.71 0.71
0.83
0.70
0.79 0.70
0.68
0.75 0.68
0.67
0.73
0.66 0.67
0.71 0.66
0.66
0.70
0.66
0.68
0.67
0.66
0.66
0.95
0.93 0.93
0.95
Derating factor
0.91
0.88 0.88
0.91
Distance (S), m
0.85 0.85
0.89
0.89
0.30
0.45
0.83 0.83
0.88
0.88
0.82 0.82
0.87
0.87
0.93
0.95
0.81 0.81
0.86
0.86
0.88
0.91
0.80
0.85
0.85
0.85 0.80
0.89
0.79
0.85
0.83 0.79
0.88
0.85
0.79
0.85
0.82
0.87
0.85
0.78 0.79
0.84
0.81 0.78
0.86
0.84
0.78
0.84
0.80
0.85
0.78
0.84
0.79
0.85
0.79
0.85
0.78
0.84
0.78
0.84
82 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
78
1300304
300 304
0.96
0.93
0.92
0.60
0.91
0.90
0.96
0.89
0.93
0.89
0.92
0.89
0.91
0.89
0.90
0.88
0.89
0.88
0.89
0.89
0.89
0.88
0.88
0.60
0.96
0.93
0.92
0.91
0.90
0.89
0.89
0.89
0.89
0.88
0.88
DERATING
DERATING
FACTORSFACTORS
MULTICORE
MULTICORE
ENCLOSED
ENC
Number
of Of
Number
Circuits
Circuits
Derating factors
Derating
for factors
groups of
forcircuits
groupsof
ofcables
circuitsinstalled
of cables
in installed i
underground
underground
wiring enclosures
wiring enclosures
Multicorecables
Multicore
enclosed
cables enclose
separately or
separately
more than
or one
moreSingle
than Core
one Single
cable per
Corewiring
cableenclosure.
per wiring e
DERATING
DERATING
FACTORSFACTORS
SINGLE CORE
SINGLE
ENCLOSED
CORE ENCLOSED
102
Derating factors
Derating
for factors
groups of
forcircuits
groupsof
ofcables
circuitsinstalled
of cables installed
in underground
in underground
wiring enclosures
wiring enclosures
Single Core
Single
cablesCore
enclosed
cables enclosed
separately. separately.
102
Rating Factor
Air Ambient Temperature (see Note 1), C
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
100
110
1.16
1.13
1.10
1.07
1.04
1.0
0.96
0.93
0.89
0.85
0.80
0.76
0.71
0.65
0.60
0.53
0.38
90
1.26
1.20
1.15
1.10
1.05
1.0
0.94
0.88
0.81
0.73
0.65
0.57
0.47
0.34
0.19
80
1.31
1.25
1.19
1.12
1.06
1.0
0.92
0.84
0.76
0.66
0.56
0.45
0.27
75
1.35
1.28
1.21
1.14
1.07
1.0
0.91
0.82
0.72
0.60
0.49
0.37
Note:
1. For heated concrete slabs, the ambient temperature shall be taken as the operating temperature of the slab.
Conductor
Temp
C
10
15
20
25
30
35
40
110
1.08
1.06
1.03
1.0
0.97
0.94
0.91
90
1.11
1.07
1.03
1.0
0.97
0.93
0.89
80
1.13
1.09
1.04
1.0
0.96
0.91
0.85
75
1.14
1.10
1.05
1.0
0.95
0.89
0.83
Rating factors for variations in depth of laying for cables buried direct in the ground
- Single Core or Multicore.
Rating Factor
Depth Of laying
(see note 2)
m
Up to 50
Above 50 up to 300
0.5
1.00
1.00
1.00
0.6
0.99
0.98
0.97
0.94
0.8
0.97
0.96
1.0
0.95
0.94
0.92
1.25
0.94
0.92
0.90
0.89
1.5
0.93
0.91
1.75
0.92
0.89
0.87
2.0
0.91
0.88
0.86
2.5
0.90
0.87
0.85
3.0 or more
0.89
0.86
0.83
Note:
1. The ambient temperature at the surface is to be taken at 40C and not 25C as at a depth of 0.5m. For depth less than 0.5m,
see Table 2(3) of AS/NZS 3008.1.1.
2. Measured to centre of enclosure of trefoil group of cables.
1300
300 304
| WWW.PRYSMIAN.COM.AU 83
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
79
Depth Of Laying
(see note 2)
m
Single Core*
0.5
1.00
1.00
0.6
0.98
0.99
0.8
0.95
0.97
1.0
0.93
0.96
1.25
0.90
0.95
1.5
0.89
0.94
1.75
0.88
0.94
2.0
0.87
0.93
2.5
0.86
0.93
3.0 or more
0.85
0.92
Multicore
*These rating factors apply to single-core cables enclosed separately, or grouped in a single wiring enclosure.
Note:
1. The ambient temperature at the surface is to be taken at 40C and not 25C as at a depth of 0.5m. For depth less than 0.5m, see
Table 2(4) of AS/NZS 3008.1.1.
2. Measured to centre of enclosure of trefoil group of enclosures.
Rating factors for cables buried direct in ground and for cables installed in underground
wiring enclosures where the thermal resistivity of the soil varies from 1.2C.m/W.
Rating Factor
Two Single-Core
Cables In A Wiring
Enclosure*
Three Single-Core
Cables In A Wiring
Enclosure*
1.03
1.06
1.08
1.02
1.04
1.06
1.02
1.03
1.04
Multicore Cable
Buried Direct
Two Or Three
Single-Core Cable
Buried Direct
Multicore Cable In A
Wiring Enclosure
0.8
1.09
1.16
0.9
1.07
1.11
1.0
1.04
1.07
Thermal Resistivity
Of Soil
C.m/W
1.2
1.00
1.00
1.00
1.00
1.00
1.5
0.92
0.90
0.95
0.94
0.92
2.0
0.81
0.80
0.88
0.86
0.83
2.5
0.74
0.72
0.83
0.80
0.77
3.0
0.69
0.66
0.78
0.75
0.71
*These rating factors apply to single-core cables enclosed separately, or grouped in a single wiring enclosure.
84 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
80
1300304
300 304
Cables in Conduits
81
x space factor
where the space factor recognises the reduction of space available from the circular
geometry of the cables and enclosures:
For one cable in enclosure:
0.5
For two cables in enclosure:
0.33
For three or more cables in enclosure: 0.4
It is recommended that the installer refer to tables C9-C11 of AS/NZS 3000 for further
guidance.
86 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
82
1300304
300 304
General Information
83
when
Desired
Data
kVAisisknown
known
kVA
when
Desired
Data
kVA
isisknown
known
kWis
known
kW
Single-Phase
Single-Phase
kVA . 1000kVA 1000
Single-Phase
Eo
Eo
kVA
1000kW 1000
kW ..1000
Single-Phase
EoE.opf Eo pf
Three-Phase
kVA . 1000
Three-Phase
.E
3
.
.
kVA
1000
kW 1000
Three-Phase
. E. .Epf
3
3
Three-Phase
kVA 1000
3 E
kW . 1000
3 E pf
3 PHASE
3 PHASE
3FORMULAE
PHASE
FORMULAE
FORMULAE
Desired Data
Desired Data
NDUITS
ITS
3 PHASE FORMULAE
0.5
0.33
0.4
eduction
cognises
s the reduction
of
the
space
reduction
ofavailable
spaceofavailable
space
from the
available
from
circular
thefrom
circular
the circular
nd
sures:
enclosures:
e:
0.5
0.5
re:
0.33 0.33
sure:
n enclosure:
0.4
0.4
SALES
13003000
300 304
rler
eto
installer
refer
tables
torefer
C9-C11
tables
toC9-C11
tables
of AS/NZS
C9-C11
of AS/NZS
3000
of AS/NZS
3000
SALES 1300 300 304
8
SALES 1300 300 304
SALES SALES
1300 300
SALES
1300
304
300
1300
304
300 304
General Information
kVA
kVA
1000
1000
hp 746Data
hp . 746
kW
kW
hp ..1000
hp .. 1000
746
746
Desired
Single-Phase
Desired
Data
Three-Phase
Single-Phas
.
%Eff
.3
oE.opf. E
E. .Epf. pf 3 E %Eff pf
Eo .E%Eff
3
pfo %Eff pf
E3
. E.. . 3
. Eo
.
.
.
.
o
EData
EData
3
kVA
when
kW
kW
when
when
kVADesired
kVASingle-Phase
kVA . 1000
1000
1000
hp 1000
hp 1000
746
746
Desired
Single-Phase
Three-Phase
kVA
1000
. E3
. %Eff
. E Eo
o . pf. kVA
E . pf. pf EkVA
kW
is known
known
o
3
is known
is1000
known
Eo .E1000
3
%Eff
pf 1000
hp is
. pf
. E..oE.opf
3
.E. .E
3 kW. 1000
. 1000
. .746
. 1000
. kVA
kVA
kVA
kW
o pf
Ewhen
3 pf
Ewhen
when
kVA
when
hpDesired
hpSingle-Phase
746 when
Data
kW
kW. .1000
1000
1000
Desired
Data
Three-Phase
Single-Phase
1000.
1000
kW
. E1000
. %Eff . pfEookVA
. pf isisknown
. E . pf
kVA
is
known
1000
1000
E. o .1000
3
%Eff
pf
hp is known
3
EEoo. pf
kW
is
known
known
. pf
. E .. .3
. pf kW
. %Eff
Eo .. E%Eff
.
.
33
E. E
.
.pf. 1000
hp
.oEopfwhen
.kVA
. 1000
.hp
. 1000
. 746
. 746
kW
kW
1000
when
E when
3
%Eff pf
kVA
kVAkW
1000
1000
kW
%Eff
when pf
hp . 746
when
hp
746 Eo when
746
kVA
1000
1000
hp
1000
1000
. kW
.Epf
. pf . p
. %Eff
. is
. E. E. %Eff
3
o
pfis
isis746
known
746
kVAkW
ishp
known
EoEo.o%Eff
is
EEoEokVA
3
pfknown
known
hpknown
known
NOTE:
.
.
.
.
.
. Eo .. E%Eff
3
pf
E
%Eff
pf
. pf .
o . pf
. E . 3
.
. . Eo
hp formulae commonly used for determining
o
..kW
E746
3
.746
. 1000
The above table lists
various parameters of an electrical
system
kW
when
kW .hp
Ewhen
kW .hp
1000
1000
when
hp
746
746 when
746
kVA
kVA
1000
1000
1000
1000
. %Eff
. known
. E .1000
.pf
. %Eff
.
where:
E
o
3
pf
%Eff
pf . pf
hp
is
known
E
o
pf
pf
kW
is
known
kW
is
E
o
hp
is
known
NOTE:
. Eo . %Eff . pf
. E . 3
. %Eff . .pf .
.
.
.
Note:
system
EEoo. pf
. EE .
. EEoo pf
Single table
phaselists
voltage,
in volts.
Eg 230V
Eo = above
. .pf
hp
33
The
formulae
commonly
used for determining
various
kW parameters of an electrical
kW
when
hp . 746
when
hp. 746
hp
746
746
746
kVA
x Eo) kVA
1000
1000
1000
= Three
phase
line
voltage,
in volts. Eg
400V
(E
= 3
1000
1000
1000
.
.
.
.
.
.
where:
TheE
above
table
lists
formulae
commonly
used
for
determining
various
parameters
of
an
electrical
system:
.E .%Eff
Eo %Eff
3
Eo %Eff
pf . . pf
hp is known
hppf
is known
NOTE:
. %Eff
..E.oE.o%Eff
33
E..oEo%Eff
. .EE. .
pf .
. pf . pf
.. pf
IE=o =Current
in
Single table
phase
voltage,
in volts.
Eg phase
230V
. Epf
o = lists
Single
voltage,
in volts. Eg
230V. parameters of an electrical
Where:
Eamperes.
hp
hp
o
E
3
o
Esystem
The above
formulae
commonly
used
for determining
various
kW
kW
746
746 1000
746
kVA
kVA
%Eff
= Percent
efficiency
in decimals.
1000
1000
o
)
E
=
Three
phase
line
voltage,
in
volts.
Eg
400V
(E
=
3
x
E
E=
Three phase line voltage, in volts. Eg 400V (E = 3 x Eo).
1000
1000 1000
where:
NOTE:
NOTE:
. pf
. . 3
.. .Eo . .%Eff
.
.
= Power in
factor
in decimals.
.. EEoo .. %Eff
Ipf
. %Eff
3
pf
. EE .
pfEo pfpf p
I =amperes.
Current
in amperes.
Single phase
voltage, in volts.
Eg 230V
E=o =Current
The above table
lists formulae commonly used
Thefor
above
determining
table
lists
various
formulae
parameters
commonly
ofused
an746
electrical
for determinin
kW hp
kWhp
kVA
==Kilovolt-ampere.
746
746system
%Eff
Percent
efficiency
in
decimals.
x Eo)
1000
1000
1000
E = Three phase
volts. Egefficiency
400V (E
=
3
%Effline
= voltage, inPercent
in
decimals.
where:
where:
hp
= Power
Horsepower
(output).
NOTE:
NOTE:
. pf . pf
pf
factor
in decimals.
. .%Eff
. Eo . %Eff . pf
Eo . %Eff
. E . 3
I = =Current
in
pfamperes.
=(input).
Power factor in decimals.
= Single
phase
in volts.
Eg 230V
=
Single
phase
voltage,
in volts.
Eg of
230V
Eo above
Eofor
hplistsvoltage,
hplists
kW ==Kilowatts
The
table
formulae
commonly
used
determining
various
parameters
an
electrical
The
above
table
formulae
commonly
used
for determining
kVA
746
746
746system
%Eff =Kilovolt-ampere.
Percent
efficiency
in decimals.
kVA
=
Kilovolt-ampere.
x Eo)
E = Three phase line voltage, in volts. Eg 400V
E = (E
Three
= phase
3 x Eo)line voltage, in volts. Eg 400V (E = 3
Power
Output = Power
Input x %Eff.
where:
where:
hp
Horsepower
NOTE:
pf== Power
factor (output).
in decimals. HorsepowerNOTE:
(output).
I = Current in amperes.
I = Current in amperes.
3
= Kilowatts
1.732hp =(input).
o = Single phase voltage, in volts. Eg 230V Eo = Single phase voltage, in volts. Eg 230V
E
kW
=
The above table lists formulae commonly used
Thefor
above
determining
table lists
various
formulae
parameters
commonly
of an
used
electrical
for determining
system va
kVA = Kilovolt-ampere.
kW =
Kilowatts (input).
= Percent
efficiency
= Percent
efficiency
phase
x Eo)
E %Eff
= Three
phase line
voltage,inindecimals.
volts. Eg 400V
=
3
x Eo)line
E%Eff
=(E
Three
voltage,inindecimals.
volts. Eg 400V (E = 3
Power
Output = Power
Input x %Eff.
where:
where:
hp = Horsepower
(output).
GENERAL
pfCurrent
= Power
factor
in decimals.
pfCurrent
= Powerinfactor
in decimals.
I= =Single
in
amperes.
= 1.732Power Output = Power InputExo %Eff.
I
=
amperes.
3
INFORMATION
phase voltage, in volts. Eg 230V Eo = Single phase voltage, in volts. Eg 230V
kW = Kilowatts (input).
kVA
=
Kilovolt-ampere.
kVA
=
Kilovolt-ampere.
3 =
1.732.
Percent
in volts.
decimals.
Percent
efficiency
phase
x Eo)
E =%Eff
Three=phase
lineefficiency
voltage, in
Eg 400V
E =%Eff
(E
Three
= =3
x Eo) line
voltage, in
in decimals.
volts. Eg 400V (E = 3
Power Output = Power Input x %Eff.
= Horsepower
hp
= Horsepower
GENERAL
pfhp
= Power
factor in(output).
decimals.
= Power
factor in(output).
decimals.
= 1.732
I = Current
in amperes.
I = pf
Current
in amperes.
3
INFORMATION
kW
=
Kilowatts
(input).
kW
=
Kilowatts
(input).
kVA
= Kilovolt-ampere.
kVA= =Percent
Kilovolt-ampere.
%Eff
= Percent
efficiency in decimals.
%Eff
efficiency in decimals.
Power
Output =(output).
Power Input x %Eff.
Power
Output =(output).
Power Input x %Eff.
= Horsepower
= Horsepower
GENERAL
pf =hp
Power
factor in decimals.
pf hp
= Power
factor in decimals.
3
=
1.732
3
=
1.732 (input).
INFORMATION
kW
=
Kilowatts
(input).
kW
=
Kilowatts
kVA = Kilovolt-ampere.
kVA = Kilovolt-ampere.
Output(output).
= Power Input x %Eff.
Output(output).
= Power Input x %Eff.
hp Power
= Horsepower
hpPower
= Horsepower
GENERAL
GENERAL
= 1.732
= 1.732
INFORMATION
INFORMATION
kW
= 3Kilowatts
(input).
kW=3Kilowatts
(input).
Power Output = Power Input x %Eff.
Power Output = Power Input x %Eff.
GENERAL
GENERAL
= 1.732
= 1.732
3
3
INFORMATION
INFORMATION
when
kVA
is
known
isknown
known
kW
is
known
hphpis
109
109
88 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
304
84
1300
300 304
109
SALES 1300 300 304
109
SALES 1300 300 304
SALES 1300 300 304
109
109
SALES 1300 300 304
109
SALES 1300 300 304
SALES 1300 300 304
SALES SALES
1300 300
SALES
1300
304
300
1300
304
300 109
304 109
GENERAL
INFORMATION
GENERAL
INFORMATION
GENERAL INFORMATION
110
220
230
240
250
2.07
0.37
0.5
4.71
2.35
2.25
2.16
0.56
0.75
7.06
3.53
3.38
3.24
3.11
0.75
9.42
4.71
4.50
4.32
4.14
1.1
1.5
14.1
7.06
6.76
6.48
6.22
1.5
18.8
9.42
9.01
8.63
8.29
10.4
1.9
2.5
23.5
11.8
11.3
10.8
2.2
28.3
14.1
13.5
13.0
12.4
3.0
37.7
18.8
18.0
17.3
16.6
3.7
47.1
23.5
22.5
21.6
20.7
4.5
56.5
28.3
27.0
25.9
24.9
29.0
5.2
65.9
33.0
31.5
30.2
5.6
7.5
70.6
35.3
33.8
32.4
31.1
6.0
75.4
37.7
36.0
34.5
33.2
6.7
84.8
42.4
40.5
38.9
37.3
7.5
10
94.2
47.1
45.0
43.2
41.4
9.3
12.5
118
58.9
56.3
54.0
51.8
11.2
15
141
70.6
67.6
64.8
62.2
14.9
20
188
94.2
90.1
86.3
82.9
18.7
25
235
118
113
108
104
22.4
30
283
141
135
130
124
440
500
380
400
415
Current Rating* (A)
0.37
0.5
0.79
0.75
0.72
0.68
0.60
0.56
0.75
1.18
1.12
1.08
1.02
0.90
0.75
1.57
1.50
1.44
1.36
1.20
1.1
1.5
2.36
2.24
2.16
2.04
1.79
1.5
3.15
2.99
2.88
2.72
2.39
1.9
2.5
3.94
3.74
3.60
3.40
2.99
2.2
4.72
4.49
4.32
4.08
3.59
3.0
6.30
5.98
5.77
5.44
4.79
3.7
7.87
7.48
7.21
6.80
5.98
4.5
9.44
8.97
8.65
8.16
7.18
5.2
11.0
10.5
10.1
9.52
8.37
8.97
5.6
7.5
11.8
11.2
10.8
10.2
6.0
12.6
12.0
11.5
10.9
9.57
6.7
14.2
13.5
13.0
12.2
10.8
7.5
10
15.7
15.0
14.4
13.6
12.0
9.3
12.5
19.7
18.7
18.0
17.0
15.0
11.2
15
23.6
22.4
21.6
20.4
17.9
14.9
20
31.5
29.9
28.8
27.2
23.9
18.7
25
39.4
37.4
36.0
34.0
29.9
22.4
30
47.2
44.9
43.2
40.8
35.9
*Approximate full load currents for standard AC induction motors based on power factor and efficiency of 0.8 and 0.9 respectively.
1300
300 304
| WWW.PRYSMIAN.COM.AU 89
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
85
GENERAL INFORMATION
90C
105C
75C
Copper
105C
Aluminium
90C
90C
Copper
Aluminium
0.095
1.0
0.111
0.100
0.088
0.074
0.066
0.058
0.143
1.5
0.167
0.150
0.131
0.110
0.099
0.087
0.215
0.142
2.5
0.278
0.250
0.219
0.184
0.165
0.145
0.358
0.236
4.0
0.444
0.400
0.350
0.294
0.264
0.232
0.572
0.378
6.0
0.666
0.599
0.526
0.442
0.396
0.347
0.858
0.567
10
1.11
0.999
0.876
0.736
0.660
0.579
1.43
0.945
16
1.78
1.60
1.40
1.18
1.06
0.926
2.29
1.51
25
2.78
2.50
2.19
1.84
1.65
1.45
3.58
2.36
35
3.89
3.50
3.07
2.58
2.31
2.03
5.01
3.31
50
5.55
5.00
4.38
3.68
3.30
2.90
7.15
4.73
70
7.77
6.99
6.13
5.15
4.62
4.05
10.0
6.62
95
10.5
9.49
8.32
6.99
6.27
5.50
13.6
8.98
120
13.3
12.0
10.5
8.83
7.92
6.95
17.2
11.3
150
16.7
15.0
13.1
11.0
9.90
8.69
21.5
14.2
185
20.5
18.5
16.2
13.6
12.2
10.7
26.5
17.5
240
26.6
24.0
21.0
17.7
15.8
13.9
34.3
22.7
300
33.3
30.0
26.3
22.1
19.8
17.4
42.9
28.4
400
39.5
34.2
28.3
26.1
22.6
18.7
57.2
37.8
500
49.4
42.8
35.4
32.6
28.3
23.4
71.5
47.3
630
62.2
53.9
44.6
41.1
35.7
29.5
90.1
59.5
Note:
1. *Short-circuit capacities are based on maximum permissible temperature limits of: 160C for PVC insulation with conductor up to and
including 300mm2. 140C for PVC insulation with conductor greater than 300mm2. 250C for XLPE insulation. Short-circuit capacities
have to be derated if short-circuit temperature limits of other components of the circuit, eg., joints, are less than those stated.
2. The short-circuit capacity for durations up to and including 5 seconds may be calculated with the following formula:
lk =
Ii
tk
where
90 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
86
1300304
300 304
GENERAL INFORMATION
FLEXIBLE CONDUCTORS
Conductor, DC Resistance to AS/NZS 1125 and Nominal Diameter.
Plain Copper
Nominal Conductor Area
mm2
Conductor Nominal
Diameter
mm
0.5
0.75
Tinned Copper
Max. dc Resistance
at 20C
/km
Max. dc Resistance
at 20C
/km
Conductor Nominal
Diameter
mm
0.89
39.0
0.89
40.1
1.09
26.0
1.09
26.7
1.0
1.26
19.5
1.26
20.0
1.5
1.54
13.3
1.51
13.7
2.5
1.98
7.98
1.95
8.21
4.0
2.51
4.95
2.48
5.09
Conductor Nominal
Diameter
mm
Aluminium
Plain
Tinned
Max. dc Resistance
at 20C
/km
Max. dc Resistance
at 20C
/km
Conductor Nominal
Diameter
mm
Max. dc Resistance
at 20C
/km
*1.0
1.13
18.1
18.2
1.0
1.20
21.2
21.6
1.5
1.50
13.6
13.8
*2.5
1.78
7.41
7.56
2.5
2.0
7.41
7.56
4.0
2.5
4.61
4.70
6.0
3.1
3.08
3.11
10
4.0
1.83
1.84
16
5.1
1.15
1.16
5.1
1.91
25
6.4
0.727
0.734
6.4
1.20
35
7.6
0.524
0.529
7.5
0.868
50
8.9
0.387
0.391
8.8
0.641
70
10.6
0.268
0.270
10.6
0.443
0.320
95
12.5
0.193
0.195
12.5
120
14.1
0.153
0.154
14.1
0.253
150
15.7
0.124
0.126
15.6
0.206
0.164
185
17.5
0.0991
0.100
17.5
240
20.1
0.0754
0.0762
20.1
0.125
300
22.6
0.0601
0.0607
22.4
0.100
400
25.5
0.0470
0.0475
25.5
0.0778
500
28.8
0.0366
0.0369
28.8
0.0605
630
33.0
0.0283
0.0286
32.7
0.0469
Notes:
* Single Wire Conductor. Single core only.
1300
300
304 | WWW.PRYSMIAN.COM.AU
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
91
87
GENERAL INFORMATION
COMPACTED CONDUCTORS
Conductor, DC Resistance to AS/NZS 1125 and Nominal Diameter.
Plain Copper
Nominal Conductor Area
mm2
Conductor Nominal
Diameter
mm
16
25
Aluminium
Max. dc Resistance
at 20C
/km
Max. dc Resistance
at 20C
/km
Conductor Nominal
Diameter
mm
4.8
1.15
4.8
1.91
6.1
0.727
6.1
1.20
0.868
35
7.1
0.524
7.1
50
8.2
0.387
8.2
0.641
70
9.8
0.268
9.8
0.443
0.320
95
11.5
0.193
11.5
120
12.9
0.153
12.9
0.253
150
14.3
0.124
14.3
0.206
0.164
185
16.1
0.0991
15.9
240
18.3
0.0754
18.3
0.125
300
20.8
0.0601
20.8
0.100
400
23.5
0.0470
23.5
0.0778
500
26.6
0.0366
26.6
0.0605
630
30.2
0.0283
30.2
0.0469
Notes:
Single core only.
92 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300300
304
88
1300
300 304
GENERAL INFORMATION
WIRE GAUGES
Wire Gauges and Standard Metric Wires.
B&S (AWG)
Approx. Diameter
mm
Calculated Area
mm2
0.122
0.0117
36
.127
.0127
39
.132
.0137
35
.142
.0159
38
.152
.0182
34
.160
.0201
37
.173
.0234
33
.180
.0255
38
.193
.0293
SWG
Metric
40
-
0.20
.200
.0314
32
.203
.0325
35
.213
.0358
31
.226
.0401
34
.234
.0429
0.25
.250
.0491
33
30
.254
.0507
32
.274
.0591
29
.287
.0645
31
.295
.0682
0.30
.300
.0707
.305
.0730
30
.315
.0779
28
.320
.0806
29
.345
.0937
27
.361
.102
28
.376
.111
0.40
.400
.126
28
.404
.128
27
.417
.136
26
.455
.163
26
.457
.164
0.50
.500
.196
25
.508
.203
.205
24
.511
24
.559
.245
23
.574
.259
23
.610
.292
22
.643
.324
0.67
.670
.353
22
.711
.397
21
.724
.412
.737
.426
0.80
.800
.503
1300
300 304
| WWW.PRYSMIAN.COM.AU 93
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
89
GENERAL INFORMATION
WIRE GAUGES
Wire Gauges and Standard Metric Wires.
Metric
B&S (AWG)
Approx. Diameter
mm
Calculated Area
mm2
21
20
0.813
0.519
.85
.850
.568
19
.912
.652
20
.914
.657
1.0
.785
19
1.02
.81
18
1.02
.826
1.04
1.04
.849
1.12
.981
1.13
1.13
1.00
1.04
SWG
17
1.15
18
1.22
1.17
16
1.29
1.31
1.32
1.37
1.35
1.35
1.43
1.50
1.38
1.38
17
1.42
1.59
15
1.45
1.65
1.53
1.53
1.84
16
1.63
2.08
14
1.63
2.08
1.70
1.70
2.27
1.78
1.78
2.49
15
13
1.83
2.63
2.00
3.14
14
2.03
2.03
3.24
12
2.05
3.31
2.11
3.50
2.14
2.14
3.60
2.25
2.25
3.98
11
2.30
4.17
13
2.34
4.29
2.36
4.38
2.52
2.52
4.99
10
2.59
5.26
2.62
5.38
12
2.64
5.48
2.70
5.73
2.85
2.85
6.38
6.63
2.91
3.00
7.07
3.20
3.20
8.04
10
3.25
8.30
94 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
90
1300304
300 304
GENERAL INFORMATION
CSA
mm2
MCM
Size
CSA
mm2
MCM
Size
CSA
mm2
456
6.63
250
127
900
8.37
300
152
950
481
10.6
350
177
1000
507
13.3
400
203
1100
557
16.8
450
228
1200
608
21.2
500
253
1300
659
26.7
550
279
1400
709
33.6
600
304
1500
760
42.4
650
329
1600
811
53.5
700
355
1700
861
2/0
67
750
380
1800
912
3/0
85
800
405
1900
963
4/0
107
850
431
2000
1010
American conductor sizes are based on American Wire Gauge (AWG) for small sizes and circular mils (CM) for larger sizes.Mil is an
engineering term for one thousandth of an inch and the circular mil is the area of a circle one thousandth of an inch in diameter. The
term MCM is used for one thousand circular mils.
1300304
300 304
| WWW.PRYSMIAN.COM.AU 95
1300 300
WWW.PRYSMIANCABLE.COM.AU
91
GENERAL INFORMATION
IMPERIAL CONDUCTORS
A Comparison of Metric and Imperial Conductors for Fixed Cables.
Metric
Nominal Conductor Area
mm2
Imperial
Stranding
No./mm
Stranding
No./mm
Calculated Area*
mm2
0.5
1/0.80
0.503
0.001
1/.036
0.657
1.0
7/0.40
0.862
0.0015
1/.044
0.981
1.0
1/1.13
1.00
0.002
3/.029
1.28
1.5
7/0.50
1.37
1.5
1/1.38
1.50
0.003
3/.036
1.97
0.0032
1/.064
2.08
2.5
7/0.67
2.47
2.5
1/1.78
2.49
0.0045
7/.029
2.98
4
7/0.85
3.97
0.007
7/.036
4.60
6
7/1.04
5.95
0.01
7/.044
6.81
0.0145
7/.052
9.59
10
7/1.35
10.0
0.0225
7/.064
14.5
16
7/1.70
15.9
0.03
19/.044
18.6
0.04
19/.052
26.0
25
19/1.35
27.2
35
19/1.53
34.9
0.06
19/.064
39.4
50
19/1.78
47.3
0.075
19/.072
49.9
0.1
19/.083
66.3
70
19/2.14
68.3
0.12
37/.064
76.8
95
19/2.45
89.6
0.15
37/.072
97.2
120
37/2.03
120
0.2
37/.083
129
150
37.2.25
147
0.25
37/.093
162
185
37/2.52
185
0.3
37/.103
199
240
61/2.25
243
0.4
61/.093
267
300
61/2.52
304
0.5
61/.103
328
400
61/2.85
389
0.6
91/.093
399
0.75
91/.103
489
500
61/3.20
491
0.85
127/.093
557
630
91/3.00
643
1.0
127/.103
683
1.25
127/.112
807
800
127/2.85
810
1000
127/3.20
1020
1.5
127/.128
1050
* The area has been calculated as follows:
For single wires - based on nominal wire diameter. For stranded conductors - based on nominal wire diameter and number of wires.
96 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
92
1300304
300 304
GENERAL INFORMATION
EARTH SIZE
Minimum Copper Earthing Conductor Size.
Nominal Size Of ACTIVE Conductor
1.0
1.0*
1.5
1.5*
2.5
2.5
4.0
2.5
6.0
2.5
10
16
25
35
10
50
16
10
70
25
10
95
25
16
120
35
25
150
50
25
185
70
35
240
95
50
300
120
70
400
120
95
500
120
95
630
120
120
>630
*These earthing conductors may be used only where incorporated in a multicore cable or flexible cord, other than a lift travelling cable,
in accordance with Clause 5.3.3.4(b) & (c) AS/NZS 3000:2007, Wiring Rules.
A larger earthing conductor may be required to Safety Clause 5.3.3.1.1 of AS/NZS 3000:2007.
1300
300 304
| WWW.PRYSMIAN.COM.AU 97
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
93
GENERAL INFORMATION
During installation
Fixed or Location
Where
6D
4D
6D
4D
9D
6D
12D
8D
12D
8D
5. Armoured Cables
18D
12D
D=
D*=
18D
12D
25D
15D
30D*
20D*
98 WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300 300
304
94
1300
300 304
GENERAL INFORMATION
P=
D=
Tension in kN.
Cable diameter in mm.
Notes:
1. When considering the use of a stocking grip the tension should not exceed the values given for a pulling eye on the conductor(s).
2. 1 kN = 102kgf.
3. Subject to a maximum of 25kN.
1300
300 304
| WWW.PRYSMIAN.COM.AU 99
1300 300
304
WWW.PRYSMIANCABLE.COM.AU
95
GENERAL INFORMATION
Single Core
kN
2 Core
kN
3 Core
kN
4 Core
kN
*More Than
4 Cores
kN
0.5
0.75
1.0
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
0.015
0.0225
0.03
0.045
0.075
0.12
0.18
0.3
0.48
0.75
1.05
1.5
2.1
2.85
3.6
4.5
5.55
7.2
9.0
0.030
0.045
0.06
0.09
0.15
0.24
0.36
0.6
0.96
1.5
2.1
3.0
4.2
5.7
7.2
9.0
11.1
14.4
18.0
0.045
0.0675
0.09
0.135
0.225
0.36
0.54
0.90
1.44
2.25
3.15
4.5
6.3
8.55
10.8
13.5
16.65
21.6
-
0.06
0.09
0.12
0.18
0.3
0.48
0.72
1.2
1.92
3.0
4.2
6.0
8.4
11.4
14.4
18.0
22.2
-
0.015 x N
0.0225 x N
0.03 x N
0.045 x N
0.075 x N
0.12 x N
0.18 x N
0.3 x N
0.48 x N
0.75 x N
1.05 x N
1.5 x N
2.1 x N
2.85 x N
3.6 x N
4.5 x N
-
Safe Working Force of Metric Flexible Cables and Cords (Repeated Flexing).
Safe Working Force for cables subjected to repeated reeling or bending whilst under tension - Safety factor 8 to 1.
Nominal
Conductor Area
mm2
Single Core
kN
2 Core
kN
3 Core
kN
4 Core
kN
*More Than
4 Cores
kN
0.5
0.75
1.0
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
0.0075
0.01125
0.015
0.0225
0.0375
0.06
0.09
0.15
0.24
0.375
0.525
0.75
1.05
1.425
1.8
2.25
2.775
3.6
4.5
6.0
7.5
0.015
0.0225
0.03
0.045
0.075
0.12
0.18
0.3
0.48
1.75
1.05
1.5
2.1
2.85
3.6
-
0.0225
0.03375
0.045
0.0675
0.1125
0.18
0.27
0.45
0.72
1.125
1.575
2.25
3.15
4.275
5.4
-
0.03
0.045
0.06
0.09
0.15
0.24
0.36
0.6
0.96
1.5
2.1
3.0
-
0.0075 x N
0.01125 x N
0.015 x N
0.0225 x N
0.0375 x N
0.06 x N
0.09x x N
0.15 x N
0.24 x N
0.375 x N
0.525 x N
0.75 x N
-
100WWW.PRYSMIANCABLE.COM.AU
WWW.PRYSMIAN.COM.AU | 1300
300 304
96
1300
300 304
GENERAL INFORMATION
Weather Resistance
Oil Resistance
Water Resistance
Resistance to Chemicals
Resistance to Solvents
Abrasion Resistance
Insulation Resistance
Electric Strength
MATERIAL
90
VG
PVC* - V-90
PVC* - V-90 HT
105*
XLPE X-90
90
VG
VG
VG
Polyethylene LD
70
VG
VG
VG
Polyethylene HD
90
VG
VG
VG
VG
R-EP-90
90
VG
VG
VG
VG
R-CSP-90, R-CPE-90
90
R-HF-90, R-HF-110
90/110
VG
VG
VG
VG
HD-85-PCP
85
HD-90-CSP
90
HF-110-R
90/110
VG
VG
VG
VG
VG
VG
Nylon
300 304
| WWW.PRYSMIAN.COM.AU 101
1300 1300
300 304
WWW.PRYSMIANCABLE.COM.AU
97
You probably already know that were world leading in quality cables. But did you know
that we also provide you services from start to finish and beyond. In our offer youll
find everything from cables cut to length to the best technical support on the market.
Doing business with us pays off.
Australian made? Yes, of course.
98 WWW.PRYSMIANCABLE.COM.AU
GENERAL INFORMATION
GLOSSARY OF TERMS
Al:
Aluminium conductor.
Ambient temperature for current-carrying capacity:
The temperature of the medium in the immediate neighbourhood of the installed cable a) including any increase in temperature due to materials or equipment to which the
cables are connected, or are to be connected; but
b) excluding any increase in temperature which may be due to the heat arising from the
cables at that point.
AS/NZS 2053:
Australian/New Zealand Standard - Conduits and fittings for electrical installations.
AS/NZS 3000:
Wiring Rules.
AS/NZS 3008.1.1:
Australian/New Zealand Standard - Electrical installations - Selection of cables
Part 1.1: Cables for alternating voltages up to and including 0.6/1kV - Typical Australian
installation conditions.
AS/NZS 3191:
Australian/New Zealand Standard - Approval and test specification - Electric flexible cords.
AS/NZS 5000:
Australian/New Zealand Standard - Electric Cables - Polymeric insulated.
Part 1: For working voltages up to and including 0.6/1kV.
Part 2: For working voltages up to and including 450/750V.
Part 3: Multicore control cables for working voltages up to and including 450/750V.
Bending radius, installed:
Refers to minimum bending radius to which the cable can be subjected to in its final
position or location.
Bending radius, installing:
Refers to minimum bending radius to which the cable can be subjected to during the
installation process.
BW:
Building wire, usually refers to single core, insulated and unsheathed cable.
Compacted conductor:
A stranded conductor in which, to reduce overall dimensions, wires have been laid up
and pressed together. All conductors in this technical manual are non compacted unless
specified.
300 304
| WWW.PRYSMIAN.COM.AU 103
1300 1300
300 304
WWW.PRYSMIANCABLE.COM.AU
99
GENERAL INFORMATION
Conductor:
That portion of a cable which has the specific function of carrying current.
Consumer terminals:
Refer to Point of Supply.
CCS:
Copper Covered Steel.
Cu:
Copper conductor, usually refers to plain annealed copper.
HDCu:
Hard drawn copper conductor, for aerial application due to its higher tensile strength.
LSOH:
Low Smoke Zero Halogen.
LV:
Low voltage - a.c. = 50V and 1000V; d.c. = >120V and 1500V.
Overcurrent:
A current exceeding the rated value.
PACW:
Plain annealed copper wire.
PE:
Polyethylene (See Thermoplastic material).
Point of Supply:
The junction of the electricity distributors conductors with the consumers mains.
(Formerly known as consumers terminals).
PVC:
Polyvinyl Chloride (See Thermoplastic material), the following grades are commonly used:
Insulation Grade
Sheathing Grade
V-90*, V-90HT*
3V-90, 5V-90
75C
*The use of the higher temperature insulation compounds does not permit a higher current-carrying capacity. AS/NZ 3008.1.1
recommends 75C for current-carrying capacity calculation.
**Where it is possible to guard against plastic flow, and where reduced insulation resistance can be tolerated, V-90HT can be operated
at a temperature up to 105C for an average of 500 hours per annum during the cable service life.
SDI:
Single core double insulated cable.
Short-circuit current:
A fault current resulting from a fault of negligible impedance between live conductors
having a difference in potential under normal operating conditions.
104 WWW.PRYSMIAN.COM.AU
WWW.PRYSMIAN.COM.AU | 1300
1300300
300304
304
100
GENERAL INFORMATION
Solid conductor:
A conductor consisting of a single wire.
TACW:
Tinned annealed copper wire.
TCu:
Tinned copper conductor.
Thermoplastic material:
A material that can be readily softened and resoftened by repeated heating,
eg., PVC and PE.
Thermosetting material:
A material which cures by chemical reaction when heated and, when cured, cannot be
resoftened by heating, eg., XLPE.
Tinsel conductor:
A conductor comprising fine flattened copper wires assembled in combination with
textile material to achieve a high degree of flexibility.
TPS:
Thermoplastic sheath. (See Thermoplastic material).
XLPE:
Cross linked polyethylene. For LV application, usually refers to X-90 grade.
(See Thermosetting material).
Whilst every care has been taken in the preparation of this publication, Prysmian takes no
responsibility for any errors and or omissions. This booklet is intended as a guide only and reference
must be made by any person using this booklet to the appropriate Australian/NZ Standard and or to
local electricity supply authority rulings.
Quality
ISO 9001
The company reserves the right to make changes in product without notice.
The Prysmian Guide to Cable has been completely revised and makes reference to the most recent
information available. Information herein refers to common low voltage power and communication
cables used by industry. For information not covered in this publication eg. High Voltage XLPE and
EPR, Fibre Optics and other specialised Power and Communication cables please contact your nearest
Prysmian Sales Office on 1300 300 304.
Printed in Australia.
Copyright Prysmian Cables & Systems (ABN 36 096 594 080) 2012.
All rights reserved. Subject to change without notice.
105