You are on page 1of 10

Air Source Heat Pumps: Insulation, Heat Loss & Design

Principles
Matching Heat Pump to Building
It is essential that the heat pump is sized correctly to suit the building load. Unlike a conventional
boiler the heat pump needs to be sized correctly to match the building heat loss.
Pumps that are over sized will have problems with cycling; the building load will be too small as the
return temperature will be reached a lot quicker. Due to this the compressor will stop/start reducing
the life cycle and increasing running costs.

reduces the heat pump efficiency


reduces compressor life cycle

Under sizing could lead to freezing up due to the refrigeration cycle demand.

inadequate heating provided


will be unable to satisfy the load and will require addition heating
defrost will happen more often

Heat Loss Calculation


Accurate dimensioning is very important for heat pump systems because incorrect sizing may
increase costs and have a negative effect on efficiency. The heat consumption (w/m2) is multiplied
by the living space area to be heated; the result is the total heat consumption including both the
transmission heat consumption as well as the ventilation heat consumption.
Because of the comparative capacity of air source heat pumps it is essential to do an accurate survey
of a building and carry out a correct heat loss calculation.
Heat pump installation should be designed to run 24/7
The following points must be taken into consideration:

Location
Design temperature
Wall, floor and roof insulation levels
Windows and doors
Use an up to date heat loss calculator

Figure 1 Heat Loss from Building - Poorly insulated property with high U
values.

Page 1 of 10

Example of existing Building


Heat Loss for ground floor =15.59kw
Design Temperature -3C

Walls
U values
Room

Windows
1.6

Temperature

4.7
Air change

Doors
2.0
Area

Roof
2.6
W/m

Floors
2.0
Heat loss (kW)

Hallway

18

1.5

13.1

142.2

1.87

WC

21

2.0

2.9

246.2

0.71

Kitchen

22

2.0

19.3

165.5

3.19

Dining room

21

1.0

23.9

98.0

2.34

Utility

18

1.0

10.1

102.2

1.03

Study

21

1.0

10.4

203.2

2.11

Living room

21

1.0

19.2

226.1

4.34
15.59kw

Page 3 of 10

The heated area (in m2) is multiplied with the following specific heating load:

Energy-efficient house 10 W/m2


Low energy house 40 W/m2
New build (good thermal insulation) 50 W/m2
House (standard thermal insulation) 80 W/m2
Older house (without specific thermal insulation) 120 W/m2

Example:
New build with good thermal insulation, area 180 m2:
Calculated output requirement: 9 kW
Maximum off period 3 x 2 hours at minimum outside temperature (see EN 12831, previously DIN
4701).
For a 24 hour period, a daily heating demand of 9 kW 24 h = 216 kWh results. To cover the
maximum daily heating demand, only 18 h/day are available on account of the off periods of 3 x 2
hours. The building inertia means that two hours of the off period are not taken into consideration.
216 kWh/20h = 10.8 kW
Purely from a calculation standpoint, a heat pump with an output of 10.8 kW would be sufficient. In
other words, the heat pump output would need to be increased by 17%, if off periods of 3 x 2 hours
per day were to be applied.

Page 6 of 10

Supplement for DHW heating


For conventional buildings, a maximum DHW demand of approx. 50 litres per person and per day at
a temperature of approx. 45C are assumed. This represents an additional output of approx. 0.25 kW
per person with an eight hour heatup time.
The precise calculation of supplements and the sizing of the heat pump are made in accordance with
DIN 4708 part 2 (see DHW Heating Table).

DHW Heating Table

Low demand
Standard demand**
Or

Apartment billing acc.


to consumption
Apartment (lump-sum
billing)
Detached house
(average demand**)

DHW demand at DHW


temperatures of 45C
(litres/day per person)
15 to 20
30 to 60

Specific available heat


(Wh/day per person)

At a reference
temperature of 45C

Specific available heat

30

Approx. 1,200

Recommended suppl.
For DHW heating
(kW/person*)
Approx. 0.15

45

Approx. 1,800

Approx. 0.225

50

Approx. 2,000

Approx. 0.25

600 to 1,200
1,200 to 2,400

Recommended suppl.
For DHW heating
(kW/person*)
0.08 to 0.15
0.15 to 0.30

* With 8 hour DHW heat-up time.


** A higher performance supplement must be selected, if the actual heat demand exceeds the stated
values.

Page 7 of 10

Insulation
Insulation, insulation, INSULATION! Solar panels, turf roofs, windmills, heat pumps they are all wonderful, very fancy and visible. What really makes the difference is loads
of insulation - not visible, not sexy, but vital. This is especially true in Britain where the
sunshine is, to say the least, limited.

So, how much insulation?


Heat will always find the easiest way out so insulation needs to be as equally distributed
as possible. There is no point in having a metre of insulation in the loft when all the heat
is going out through leaky single glazed windows
In any existing property there are always practical limits to the thickness of insulation;
the size of the cavity; the availability of head space in the loft; the space between the
floor joists. You will have a lot more freedom with any new construction. In this case
there is a beautiful logic to insulation-it costs very little extra to double or even triple the
insulation required by current building regulations: the cost of the extra thickness and
scarcely more labour. This additional insulation is one of the best investments you can
make in your home.

Insulation
There are three ratings used for estimating heat loss: the k rating, the R rating, and the u value. Any
manufacturer of building products and external fixtures such as doors and windows should know the
R or u of their products. If you are looking for the lowest heat loss, all you need to know is:

R value - the higher the better


u value - the lower the better

Armed with this information, you can make direct comparisons between different products and
materials. For example, normal off the shelf double glazing with aluminum frames has a u-value of
3.5. The high performance double glazing we used has a u-value of 1.6, half the level of heat loss.
The difference in thermal performance between seemingly similar products can be dramatic, which
is why its so important to keep an eye on the R and u values. Normal 75mm concrete blocks have an
R of 0.07. Solar concrete blocks have an R of 1.36. A wall built of normal concrete blocks will
therefore lose nearly 20 times as much heat as a wall built of solar blocks.

Insulation Materials
The standard materials for insulation are glass and mineral fibre, and expanded foam sheet. Their
insulation performance is excellent, they are highly water resistant, and are reasonably fire
retardant.

Page 8 of 10

Insulation Priorities for Renovation


In an average house the main sources of heat loss are:
Draughts
25%
Roof
15%
Windows
20%
Walls
30%
Floors
10%
These figures are averages and will vary greatly from house to house - a terraced house has half the
area of external walls of a detached house and so roofs and windows are a greater priority. In a
house with an unheated basement, floors will be less important, in a flat the windows may be the
most important.
So the priorities for insulation will depend on the individual house and what has already been done
to it- every time some improvement is made to the house, the remaining sources of heat loss will
become relatively more important. Generally speaking the order of priorities for insulating an
existing property is:
1. Draughts - a major source of heat loss that is very cheap to reduce substantially.
2. Roof - it is very easy and cheap to insulate an unoccupied loft space (and vital for a
converted loft space). A well insulated roof makes a large difference to the comfort of
sleeping in upstairs rooms.
3. Windows - secondary internal glazing or good quality double glazing. Replacing single
glazing makes a very significant difference to the internal comfort on cold nights. If you are
not replacing the windows, a thorough draughtproofing will produce immediate gains.
4. Walls - certainly worth insulating if you have a cavity.
5. Floors - a low priority but likely to become a major source of heat loss in an otherwise well
insulated house, especially in floors suspended over a ventilated void.

Page 9 of 10

TYPICAL HEAT TRANSFERENCES OF DIFFERENT MATERIALS


k
typical thickness (mm)
Brickwork
0.84
100
Concrete Blocks
1.12
100
Solar concrete blocks
0.11
100
Clinker blocks
0.36
100
Plasterboard
0.16
12.5
Plywood
0.14
18
Chipboard
0.11
18
Timber
0.14
100
Unventilated cavity
Plaster/render
0.5
2.5
Celotex PIR insulation
0.019
50
Fibre glass/mineral wool
0.035
50
Thermal board
0.02
3
Brick & concrete block Cavity wall
Tiled roof with no felt
Tiled roof with felt
Single glazed window
Double glazed window
Solid timber door

R
0.12
0.09
0.9
0.21
0.06
0.07
0.8
0.71
0.18
0.03
2.63
1.43
0.15

0.6
0.53
1.9
4.5-5.5
2.5-3.5
3

There are three ratings for heat transmittance: the k-value, the R value and the u-value.
The K value gives the comparative conductivity of materials of one metre thickness. R
value gives the resistance of a specified thickness of material. The u-value gives the heat
loss of one square metre of a specified thickness of combined materials. In each case the
value given is for a difference on temperature between the two surfaces of one degree
centigrade.

Page 10 of 10

You might also like