These MCCBs provide overload and short circuit protection for all
Features
Mechanical Life
Electrical Life
In < 100
8500
1500
7000
1000
4000
1000
2500
500
30
Construction
The insulating case and cover are made of high strength, heat resistant,
flame retardant resin bonded thermo setting material which provides:-
Switching mechanism
Control mechanism
Push to trip
Trip bar
Instantaneous trip release
Instantaneous trip release
31
SKB-1 & 2
Rating (Amps.)
Cat No.
SKB-1
SKB-2
SKB-1
SKB-2
25
ISLAST0025
ISLANT0025
25
ISLASF0025
ISLANF0025
32
ISLAST0032
ISLANT0032
32
ISLASF0032
ISLANF0032
50
ISLAST0050
ISLANT0050
50
ISLASF0050
ISLANF0050
63
ISLAST0063
ISLANT0063
63
ISLASF0063
ISLANF0063
80
ISLAST0080
ISLANT0080
80
ISLASF0080
ISLANF0080
100
ISLAST0100
ISLANT0100
100
ISLASF0100
ISLANF0100
125
ISLAST0125
ISLANT0125
125
ISLASF0125
ISLANF0125
160
ISLAST0160
ISLANT0160
160
ISLASF0160
ISLANF0160
200
ISLAST0200
ISLANT0200
200
ISLASF0200
ISLANF0200
250
ISLANT0250
250
ISLANF0250
32
Standard conformity
Rated operational voltage
Rated Insulation Voltage
Type of release
Utilisation Category
Rated frequency
Ambient temp
Operating altitude
Humidity
Rated impulse voltage
:
:
:
:
:
:
:
:
:
:
IEC 60947-2/IS:13947-2
500V AC
750V AC
Thermomagnetic
A
50/60 Hz
40oC (50oC on request)
2000 meters
0 - 90%
8 KV
Frame
SKB1
SKB2
No. of Poles
1P / 3P / 4PwSN
1P / 3P / 4PwSN
A
25-200*
25-250*
Standard current range / ratings (In)
70-100% of In
Thermal release setting (Adjustable)
70-100% of In
Magnetic release setting for current rating :
25A - 63A
400A
400A
80A - 125A
800A
800A
160A - 250A
1600A
1600A
50A -125A AM Frame
-
160A -250A AM Frame
-
Rated short circuit making capacity (Peak) Icm
KA
32
73.5
Rated ultimate short circuit breaking
(160-200A)
(25-125A)
capacity (Icu), KA
240V
25
50
(at different voltages)
415V
16
35
440V 16
35
500V
12 25
52.5
(25-250A)
40
25
25
18
Ics = % Icu
100% 75%
75%
Weight SP (Single Pole)
Kg
0.7
0.7
TP (Triple Pole)
Kg
1.8
1.8
FPwSN (Four Pole Switched Neutral)
Kg
2.4
2.4
Terminal capacity (Cable)
Sq.mm 70 (upto 100A)/150 (125A-250A)
(Bus bar width)
mm
25 (125A-250A)
Recommended Torque
Nm
10
10
Internal Accessories
Auxiliary Switch (1 C/O or 2C/O)
Shunt Trip
External Accessories
Earth Fault Relay
Rotary Handle
Back Studs
1P - Single Pole
3P - Three Pole
4PwSN - Four Pole with Switched Neutral
33
Shunt trip
Voltage
Cat No.
100-110Vac
ISLLSTD110
220-240Vac
ISLLSTD240
380-415Vac
ISLLSTD415
Cat No.
100-110Vac
ISLUVRD110
220-240Vac
ISLUVRD240
380-415Vac
ISLUVRD440
Cat No.
1-Changeover
ISLLASD1CO
2-Changeover
ISLLASD2CO
Rotary handle
Accessories
Cat No.
Direct Mounting
ISLLRRHD30
Back studs
Accessories
Cat No.
ISLLBSA250
Extended terminals
Cat No.
Accessories
Cat No.
3 Pole
ISLAX0062
Factory fitted
ISLLALA1C0
4 Pole
ISLAX0059
3 Pole
ISLAX0061
4 Pole
ISLAX0050
Accessories
125A
160A - 250A
34
10000
10000
1000
63A
0A
100
10
Time (seconds)
Time (seconds)
0A
25
20
100
16
50A
0A
100A
32A
1000
A
125
80A
25A
10
0.1
0.1
0.01
0.01
0
10
100
100
1000
1000
46
100
Scale-1.5
45.5
35
135
35
25
92
92
154
112
35
112
45.5
8
136
35
35
45
17
3P
70
29
140
Dia. 6.0 (4 Off) Mounting Holes
35
35
105
12.5
91
83
4PwSN
25
25
25
35
SKB-3 & 4
Cat No.
SKB-3
SKB-4
ISLCNT0160
ISLCHT0160
Rating (Amps.)
Cat No.
SKB-3
SKB-4
160
ISLCNF0160
ISLCHF0160
200
ISLCNT0200
ISLCHT0200
200
ISLCNF0200
ISLCHF0200
250
ISLCNT0250
ISLCHT0250
250
ISLCNF0250
ISLCHF0250
315
ISLCNT0315
ISLCHT0315
315
ISLCNF0315
ISLCHF0315
400
ISLCNT0400
ISLCHT0400
400
ISLCNF0400
ISLCHF0400
500
ISLCNT0500
ISLCHT0500
500
ISLCNF0500
ISLCHF0500
630
ISLCNT0630
ISLCHT0630
630
ISLCNF0630
ISLCHF0630
800
ISLCNT0800
ISLCHT0800
800
ISLCNF0800
ISLCHF0800
36
Standard conformity
Rated operational voltage
Rated Insulation Voltage
Type of release
Utilisation Category
Rated frequency
Ambient temp
Operating altitude
Humidity
Rated impulse voltage
:
:
:
:
:
:
:
:
:
:
IEC 60947-2/IS:13947-2
500V AC
690V AC
Thermomagnetic
A
50/60 Hz
40oC (50oC on request)
2000 meters
0 - 90%
8 KV
Frame
No. of Poles
SKB 3
3P/4PwSN 3P/4PwSN
SKB 4
160-800*
160-800*
70-100% of In
70-100% of In
Adjustable
Adjustable
160 - 315A
5-10 times In
5-10 times In
400 - 800A
4-10 times In
4-10 times In
73.5
105
KA
Rated short circuit making capacity (Peak) Icm
Rated ultimate short circuit breaking
capacity(Icu), KA
(at different voltages)
240V
380V
415V
500V
50
35
35
25
Ics = % Icu
Weight TP (Triple Pole)
Kg
Kg
Sq.mm
70
50
50
35
75%
50%
9.2
9.2
11.6
11.6
(Busbar width)
mm
40
40
Internal Accessories
Auxiliary Switch (1 C/O or 2 C/O)
Shunt Trip
External Accessories
Earth Fault Relay
Rotary Handle
Back Studs
Extended Terminals
Dolly Extension
Phase Barriers
Terminal Shrouds
* Current Ratings - 160A, 200A, 250A, 315A, 400A, 500A, 630A, 800A, 1000A, 1250A, 1600A.
3P - Three Pole
** Terminals at Front
# Terminals at back / rear
37
Shunt trip
Voltage
Cat No.
18-30Vac,
12-36Vdc
ISLLSTC030
100-110Vac
ISLLSTC110
220-240Vac
ISLLSTC240
380-415Vac
ISLLSTC415
Cat No.
100-110Vac
ISLUVRC110
220-240Vac
ISLUVRC240
380-415Vac
ISLUVRC440
Cat No.
1-Changeover
ISLLASC1CO
2-Changeover
ISLLASC2CO
Rotary handle
Accessories
Cat No.
Direct Mounting
ISLLRRHC30
Back studs
Accessories
Cat No.
ISLLBSC###
Extended terminals
Accessories
250A
315A - 500A
630A - 800A
Accessories
Cat No.
3 Pole
ISLCX0019
Factory fitted
ISLLALC1C0
4 Pole
ISLCX0023
3 Pole
ISLCX0020
4 Pole
ISLCX0025
3 Pole
ISLCX0027
4 Pole
ISLCX0028
38
A
315
250A
10000
A
500
1000
1
Time (seconds)
80
0A
100
10
0.1
0.01
0
100
1000
10000
54.5
24.5
100
206
70
70
Scale-1.10
17.5
40
208
70
70
30
208
70
52
Fixing Hole
3P
102
40
375
92
232
257.2
58.9
4PwSN
39
SKB 5, 6 & 7
Cat No.
SKB-6
Rating
(Amps.)
SKB-5
SKB-6
SKB-7
25
ISLGNS0025
25
ISLGST0025
ISLGNT0025
ISLGHT0025
32
ISLGNS0032
32
ISLGST0032
ISLGNT0032
ISLGHT0032
50
ISLGNS0050
50
ISLGST0050
ISLGNT0050
ISLGHT0050
63
ISLGNS0063
63
ISLGST0063
ISLGNT0063
ISLGHT0063
80
ISLGNS0080
80
ISLGST0080
ISLGNT0080
ISLGHT0080
100
ISLGNS0100
100
ISLGST0100
ISLGNT0100
ISLGHT0100
125
ISLGNS0125
125
ISLGST0125
ISLGNT0125
Rating (Amps.)
Cat No.
SKB-5
SKB-6
SKB-7
ISLGSF0025
ISLGNF0025
ISLGHF0025
32
ISLGSF0032
ISLGNF0032
ISLGHF0032
50
ISLGSF0050
ISLGNF0050
ISLGHF0050
63
ISLGSF0063
ISLGNF0063
ISLGHF0063
80
ISLGSF0080
ISLGNF0080
ISLGHF0080
100
ISLGSF0100
ISLGNF0100
ISLGHF0100
125
40
Standard conformity
Rated operational voltage
Rated Insulation Voltage
Type of release
Utilisation Category
Rated frequency
Ambient temp
Operating altitude
Humidity
Rated impulse voltage
:
:
:
:
:
:
:
:
:
:
IEC 60947-2/IS:13947-2
500V AC
750V AC
Thermomagnetic
A
50/60 Hz
40oC (50oC on request)
2000 meters
0 - 90%
8 KV
Frame
No. of Poles
1P / 3P / 4PwSN
1P / 3P / 4PwSN
3P / 4PwSN
16-160*
16-160*
16-160*
Fixed
Fixed
Fixed
16A - 32A
350
350
350
40A - 50A
500
500
500
63A - 80A
800
800
800
100A - 160A
1000
1000
1000
KA
17
32
52.5
capacity (Icu), KA
240V
16
25
40
415V
10
16
25
440V
10
14
16
500V
7.5
10
Ics = % Icu
Weight
SP
12
100%
75%
50%
Kg
0.35
0.35
0.35
TP
Kg
0.93
0.93
0.93
Kg
1.2
1.2
1.2
70
70
70
4PwSN
Sq.mm
mm
10
10
10
Nm
2.5
2.5
2.5
Recommended Torque
Internal Accessories
Dolly Extension
Phase Barriers
Terminal Shrouds
1P - Single Pole
3P - Three Pole
Available in 3P & 4P
41
Shunt trip
Voltage
Cat No.
18-30Vac,
12-36Vdc
ISLLSTG030
100-110Vac
ISLLSTG110
220-240Vac
ISLLSTG240
Cat No.
100-110Vac
ISLUVRG110
220-240Vac
ISLUVRG240
380-415Vac
ISLUVRG440
Cat No.
1-Changeover
ISLLASG1CO
2-Changeover
ISLLASG2CO
Rotary handle
Accessories
Cat No.
Direct Mounting
ISLGD000
Direct Mounting
ISLGRN30
Extended terminals
Accessories
16A - 160A
Accessories
Cat No.
3 Pole
ISLGX0012
Factory fitted
ISLLALA1C0
4 Pole
ISLGX0046
42
50A
25A
32A
10000
80
63A
1000
Time (seconds)
12
5A
10
0A
100
10
0.1
0.01
0
10
100
1000
11.4
70.5
74
78.6
44
120
12
11.2
33.5
20
77.5
26.25
83.5
96
43
26.25
38
15
Fixing hole
94
26.25
38
12.5
26.26
18
83.5
78.50
18
18
26
3P
104.50
94.00
120.00
102.00
26.25
26.25
26.25
83.50
77.50
71
ON
OFF
26.25
97.00
44
SKB-8 & 9
SKB-8
SKB-9
25
ISLFNT0025
ISLFHT0025
32
ISLFNT0032
50
ISLFNT0050
63
Rating (Amps.)
Cat No.
SKB-8
SKB-9
25
ISLFNF0025
ISLFHF0025
ISLFHT0032
32
ISLFNF0032
ISLFHF0032
ISLFHT0050
50
ISLFNF0050
ISLFHF0050
ISLFNT0063
ISLFHT0063
63
ISLFNF0063
ISLFHF0063
80
ISLFNT0080
ISLFHT0080
80
ISLFNF0080
ISLFHF0080
100
ISLFNT0100
ISLFHT0100
100
ISLFNF0100
ISLFHF0100
125
ISLFNT0125
ISLFHT0125
125
ISLFNF0125
ISLFHF0125
160
ISLFNT0160
ISLFHT0160
200
ISLFNF0200
ISLFHF0200
200
ISLFNT0200
ISLFHT0200
250
ISLFNF0250
ISLFHF0250
250
ISLFNT0250
ISLFHT0250
45
Standard conformity
Rated operational voltage
Rated Insulation Voltage
Type of release
Utilisation Category
Rated frequency
Ambient temp
Operating altitude
Humidity
Rated impulse voltage
:
:
:
:
:
:
:
:
:
:
IEC 60947-2/IS:13947-2
500V AC
750V AC
Thermomagnetic
A
50/60 Hz
40oC (50oC on request)
2000 meters
0 - 90%
8 KV
Frame
SKB 8
SKB 9
No. of Poles
3P / 4PwSN
3P / 4PwSN
25-250*
25-250*
Fixed
Fixed
Fixed
Fixed
25A - 32A
500A
500A
40A - 80A
800A
800A
100A - 125A
1250A
1250A
160A - 250A
1600A
1600A
73.5
105
240V
50
70
380V
35
50
415V
35
50
500V
25
35
Ics = % Icu
Weight TP (Triple Pole) / FPwSN
Kg
100%
2.9 / 3.8
100%
2.9 / 3.8
Terminal Type
M8
M8
Sq.mm
mm
185
18
185
18
Shunt Trip
Rotary Handle
Back Studs
Extended Terminals (above 63A)
Dolly Extension
Phase Barriers
Terminal Shrouds (only in 3P MCCB)
Dolly pad locking Device
+
-
+
+
+
Internal Accessories
External Accessories
Current Ratings - 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A, 160A, 200A, 250A
3P - Three Pole
Factory Fitted
46
Shunt trip
Voltage
Cat No.
18-30Vac,
12-36Vdc
ISLLSTF030
100-110Vac
ISLLSTF110
220-240Vac
ISLLSTF240
380-415Vac
ISLLSTF415
Cat No.
100-110Vac
ISLUVRF110
220-240Vac
ISLUVRF240
380-415Vac
ISLUVRF440
Cat No.
1-Changeover
ISLLASF1CO
2-Changeover
ISLLASF2CO
Rotary handle
Accessories
Cat No.
Direct Mounting
ISLLRRHF30
Extended terminals
Cat No.
Accessories
Cat No.
3 Pole
ISLFX0048
Factory fitted
ISLLALF1C0
4 Pole
ISLFX0045
3 Pole
ISLFX0049
4 Pole
ISLFX0046
Accessories
160A
200A - 250A
47
1000
Time (seconds)
100
10
250A
200A
80A/125A/160A
63A/100A
0.1
32A/50A
25A
0.01
0.005
0
10
100
30 TERMINAL HIGHT
SUITABLE FOR M8 SCREWS
55
35
35
FIXING CTRS.
35
78.6
94
100
114
135
104.5
T hree P ole
48
SKB 10 & 11
Cat No.
Three pole
Rating (Amps.)
Cat No.
Three pole
250
ISLLSEBT0250
ISLLSEBF0250
250
ISLLSECT0250
ISLLSECF0250
315
ISLLSEBT0315
ISLLSEBF0315
315
ISLLSECT0315
ISLLSECF0315
400
ISLLSEBT0400
ISLLSEBF0400
400
ISLLSECT0400
ISLLSECF0400
500
ISLLSEBT0500
ISLLSEBF0500
500
ISLLSECT0500
ISLLSECF0500
630
ISLLSEBT0630
ISLLSEBF0630
630
ISLLSECT0630
ISLLSECF0630
250
ISLLNFBT0250
ISLLNEBF0250
250
ISLLNFCT0250
ISLLNECF0250
315
ISLLNFBT0315
ISLLNEBF0315
315
ISLLNFCT0315
ISLLNECF0315
400
ISLLNFBT0400
ISLLNEBF0400
400
ISLLNFCT0400
ISLLNECF0400
500
ISLLNFBT0500
ISLLNEBF0500
500
ISLLNFCT0500
ISLLNECF0500
630
ISLLNFBT0630
ISLLNEBF0630
630
ISLLNFCT0630
ISLLNECF0630
49
Standard conformity
Rated operational voltage
Rated Insulation Voltage
Type of release
Utilisation Category
Rated frequency
Ambient temp
Operating altitude
Humidity
Rated impulse voltage
:
:
:
:
:
:
:
:
:
:
IEC 60947-2/IS:13947-2
415V AC
750V AC
Thermomagnetic
A
50/60 Hz
40oC (50oC on request)
2000 meters
0 - 90%
8 KV
Frame
SKB 10
No. of Poles
3P/4P
A
250, 315, 400, 500
Standard Current Ratings (In)
Thermal release setting (Adjustable)
80-100% In
SKB 11
3P/4P
250, 315, 400, 500
80-100% In
4000A
6300A
Trip Unit
Adjustable Thermal & fixed magnetic setting
Adjustable Thermal & adjustable magnetic setting
Rated S.C. Making Capacity at 415V (Icm)
Rated Ultimate S.C breaking capacity (Icu) at
Rated Service S.C Breaking Capacity at 415V
=
=
=
=
kA
240V
kA
415V kA
Ics = % Icu
4000A
6300A
75.6
50
36
65
50
100
75
Weight
Kg
6/7
Terminal capacity (Max.)
Sq. mm
1x240 (250A-400A)
2x185 (500A)
Bus bar width
mm
30
Overall dimension (W X H X D)
140x254x109
Internal Accessories #
Auxillary Switch
1C/O or 2C/O
=
Shunt Trip (bulit-in auxillary contact)
=
Under Voltage release
=
Alarm Switch
=
External Accessories
Rotary Handle - Extended
=
Extended Terminals
=
Dolly Extension
=
Phase Barriers
=
Dolly pad locking device
=
Earth Fault Relay
=
Available
# Only 2 accessories at a time can be fitted in the MCCB
50
105
6/7
1x240 (250A-400A)
2x185 (500A)
30
140x254x109
=
=
=
=
=
=
=
=
=
=
Alarm switch
Voltage
Cat No.
Rating
Configuration
240Vac
ISLLB000
1A
1NO + NC
Voltage
Cat No.
110Vac
ISLLS110
110Vac
ISLLU110
240Vac
ISLLS240
240Vac
ISLLU240
415Vac
ISLLS415
415Vac
ISLLU440
Voltage
Note: The breaker trips if the supply voltage dips below 70%- 35% of the
rated voltage.
The breaker cannot be switched ON unless there is a supply to the UVR.
(NVNC feature).
Suplied with external mounting Electronic Power pack to operate on AC
supplies.
Auxiliary switch
Voltage
Cat No.
Current rating
(AC12)
Configuration
250Vac
ISLLA1CO
4A
1NO + 1NC
250Vac
ISLLA2CO
4A
2(1NO + 1NC)
Rotary handle
Accessories
Cat No.
ISLLRN30
Voltage
Dolly extension
Dolly pad locking device
ISSLX0013
ISSLX0014
Phase barriers
ISSLLX0004
51
Cat No.
ISCPSMLLX009
ISLLP000
Mounting
58.75
58.75
43.75
43.75
186
43.75
52
354
254
102.5
75.7
35
15
40 18.75
53
Frame
4 th Digit
MCCBs
SKB 10
ISLLSEBT0250
Example
SKB 10
Product ID
3 rd Digit
Code logic
Ics = % of Icu
Frame
Product ID
Icu
6 th Digit
Icu Designation
36kA
E
50kA
F
50%
75%
N
H
100%
Designation Ics as %
of Icu
5 th Digit
3
2
10
11
500A
630A
0500
0630
400A
315A
0315
0400
250A
0250
(A)
9-12 th Digit
Breaker current Rating
8 th Digit
No. of poles
T
Three Pole
12
7 th Digit
No. of poles
Type of Release
SKB-0
Rating (Amps.)
SKB-0
Rating (Amps.)
SKB-0
1000
ISLDNT1000
1000
ISLDNF1000
1250
ISLDNT1250
1250
ISLDNF1250
1600
ISLDNT1600
1600
54
Standard conformity
Rated operational voltage
Rated Insulation Voltage
Type of release
Utilisation Category
Rated frequency
Ambient temp
Operating altitude
Humidity
Rated impulse voltage
:
:
:
:
:
:
:
:
:
:
IEC 60947-2/IS:13947-2
500V AC
690V AC
Thermomagnetic
A
50/60 Hz
40oC (50oC on request)
2000 meters
0 - 90%
8 KV
Frame
No. of Poles
3P/4PwSN
SKB 0
1000-1600*
70-100% of In
800 - 1600A
Adjustable
4000-10,000A
105
capacity(Icu), KA
(at different voltages)
240V
380V
70
50
415V
50
500V
Ics = % Icu
Weight TP (Triple Pole)
Kg
Kg
(Busbar width)
Sq.mm
mm
35
75%
17#/19**
22/25
-
Internal Accessories
Auxiliary Switch (1 C/O or 2 C/O)
Shunt Trip
Rotary Handle
Back Studs
Extended Terminals
Dolly Extension
Phase Barriers
External Accessories
Terminal Shrouds
* Current Ratings - 160A, 200A, 250A, 315A, 400A, 500A, 630A, 800A, 1000A, 1250A, 1600A.
3P - Three Pole
** Terminals at Front
# Terminals at back / rear
55
Accessories - SKB-0
Shunt trip
Voltage
Cat No.
100-110Vac
ISLLSTD110
220-240Vac
ISLLSTD240
380-415Vac
ISLLSTD415
Cat No.
100-110Vac
ISLUVRD110
220-240Vac
ISLUVRD240
380-415Vac
ISLUVRD440
Cat No.
1-Changeover
ISLLASD1CO
2-Changeover
ISLLASD2CO
Rotary handle
Accessories
Cat No.
Direct Mounting
ISLLRRHD30
56
57
S. No.
Rating
1.
800A
70
45
6x2
2.
1000A
70
45
15
3.
1250A
82
60
15
4.
1600A
87
65
18
100
1000
0A
800A
10000
16
50
12
Time (seconds)
0A
100
10
0.1
0.01
1000
10000
58
The earth fault detection system for use with STANDARD MCCBs
comprises of a core balance transformer (CT) coupled to an advanced
RCD relay. The relay may be used to trip a circuit breaker via a shunt
trip or an under voltage release in the event of an Earth Fault.
The relay and one of the four available CTs is all that is required for a
complete earth fault sensing system suitable for the control of a circuit
breaker in a circuit upto 800A fitted with either a shunt trip or an under
voltage release. The simple arrangement and a small number of interconnection necessary ensure that EFR is easily selected and installed.
The relay is suitable for 220-240V AC supply with the flexibility of
choosing the sensitivity between 300mA to 2A and time delay should
be selected by the DIP switches provided on the facia of the relay.
Features
No nuisance tripping
DIN rail mounting
Adjustable time delay
Choice of sensitivity from 300mA upto 2A
Trip indication LED(Red)
ON indication LED(Green)
Test push button
Reset push button
59
Technical data
Supply Voltage
Changeover contact
5A-15A 240V AC
Sensitivity
The earth fault relay is supplied with the CT based on the current
rating. To operate the EFR a shunt trip or an under voltage release is
necessary which has to be ordered separately.
Coil Voltage
Cat No.
25-100
ISEF1100
125-200
ISEF2200
250-400
ISEF3400
500-800
ISEF4800
Size
Internal Dimension
Shape
25-100A
60mm
Circular
125-200A
95mm
Circular
250-400A
145mm
Circular
500-800A
300 x 80 mm
Rectangular
1000-1600A
On Request
Rectangular
60
Enclosures made of special grade CRCA steel are available for housing SKB-1 to SKB-9 Frame MCCBs upto 800A. They are manufactured with
latest technology using CNC Punch and Brake presses to attain highest degree of perfection. The enclosures are painted with latest techniques
in powder coating using epoxy polyester and polyester resin based powder paints to ensure smooth, scratch resistant surface coatings. They
are suitable for wall mounting & adequate knockouts are provided for cable entry.
Description
Cat. No.
SKB-5/6/7 Frame SP
ISEGSP
SKB-5/6/7 Frame TP
ISEGTP
SKB-5/6/7 Frame FP
ISEGFP
SKB-1/2 Frame SP
ISEASP
SKB-1/2 Frame TP
ISEATP
SKB-1/2 Frame FP
ISEAFP
SKB-8/9 Frame TP
ISEFTP
SKB-8/9 Frame FP
ISEFFP
ISECTP
ISECFP
ISECTP
ISECFP
AxB
SKB-5/6/7 Frame
Description
190
81
300
310
160x360
SKB-1/2 Frame
260
108
560
570
160x480
SKB-8/9 Frame
260
122
560
570
160x480
SKB-3/4 Frame
440
122
960
975
280x802
540
122
960
975
380x802
upto 400 A
SKB-3/4 Frame
upto 800 A
61
Ambient temperature compensation chart (SKB 1/2, SKB 3/4, SKB 5/6)
Ambient temperature compensation chart (SKB 1/2, SKB 3/4, SKB 5/6)
Product
SKB 1/2
SKB 3/4
SKB 0
Rating
KA @
(A)
415V
25
32
100
125
160
200
250
315
400
25
1200
1400
1800
2400
3200
4500
5500
8000
25
1200
1400
1800
2400
3200
4500
5500
8000
40
25
350
1400
1800
2400
3200
4500
5500
8000
50
25
300
1400
1800
2400
3200
4500
5500
8000
63
25
250
1400
1800
2400
3200
4500
5500
300
450
2400
3200
4500
400
650
3200
4500
550
3200
650
80
25
100
25
125
25
160
25
500
630
800
12000
14000
23000
12000
14000
23000
12000
14000
23000
12000
14000
23000
8000
12000
14000
23000
5500
8000
12000
14000
23000
5500
8000
12000
14000
23000
4500
5500
8000
12000
14000
23000
1300
5500
8000
12000
14000
23000
1200
1300
8000
12000
14000
23000
1000
8000
12000
14000
23000
2000
12000
14000
23000
2500
14000
23000
3500
23000
200
25
250
50
315
50
400
50
500
50
630
50
5500
800
50
6000
The above table gives fault currents in amperes till which level the downstream breakers shall act prior to the upstream fuse.
62
Discrimination data standard MCCB upstream device instantaneous trip set at high
Product
SKB 1/2
SKB 3/4
SKB 0
Rating
SKB 3/4
SKB 1/2
kA@
25
23 40
50
63
80
315
400
SKB 0
500
630
800
600
800
(A)
415V
63
25
800 800 800 1600 1600 2500 3000 4000 5000 6300 8000 7400 8300 9200 9200 9200
80
25
1600 1600 2500 3000 4000 5000 6300 8000 7400 8300 9200 9200 9200
100
25
1600 1600 2500 3000 4000 5000 6300 8000 7400 8300 9200 9200 9200
125
25
1600 1600 2500 3000 4000 5000 6300 8000 7400 8300 9200 9200 9200
160
25
2500 3000 4000 5000 6300 8000 7400 8300 9200 9200 9200
200
25
2500 3000 4000 5000 6300 8000 7400 8300 9200 9200 9200
315
50
400
50
500
50
630
50
800
50
1000
50
1250
50
9200 9200
1600
50
9200
The above table gives fault current in amperes till which level the downstream breakers shall act prior to the upstream breaker
Transformer Protection
Ie =
kVA 1000
Primary side
3 Ue
Amps
Ib =
Secondary side
Ie
Z%
10 3 Kiloamperes
63
25
25
25
25
25
25
25
40
40
40
40
40
40
63
100
100
100
100
100
100
100
160
160
160
160
160
160
250
250
250
250
250
200
315
315
250
400
400
315
500
500
400
630
630
500
800
800
630
1000
750
1200
kVA
3 Ue
Where,
kVA = Rating of the DG Set
Ue = Rated Voltage
Ie = Rated Current
The MCCB rating selected is greater than or equal to the rated current
value
DG Set
Rating
(kVA)
MCCB
Rating
(Amps)
10
16
16
25
25
40
63
100
10
160
16
250
20
315
25
400
31
500
40
630
63
1000
750
1200
Typical installation
1000 kVA
transformer
10 meters
8sc 300 mm2
B
70 meters 4c 120 mm2
20 meters 2c 16 mm2
D
64
Feeder/cable protection
PSC at A
Aapproximately 27kA
PSC at B
resistance A to B (a)
0.30mW
PSC at D
+resistance A to B
0.30mW
+resistance B to C
10.70mW
+resistance C to D
46.00mW (b)
57.00mW = 3kA
SCkA =
PSC at C
+resistance A to B
0.30mW
+resistance B to C1
10.70mW
11.00mW = 12kA
40
2000 kVA
1500 kVA
30
1250 kVA
1000 kVA
800 kVA
20
500 kVA
10
315 kVA
200 kVA
100 kVA
0.1
= 25kA
1.0
10
Total Circuit Resistance ( ohm)
65
100
Nominal
Cross-sectional
Area (mm2)
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
Cable length
5m
90.50
60.50
37.10
23.10
15.40
9.1 5
5.75
3.6 4
2.6 2
1.94
1.34
0.9 6
0.7 7
0.6 2
0.4 9
0.3 4
0.3 0
0.2 3
0.1 8
0.14
10m
181.00
121.00
37.10
46.1 0
30.8 0
18.3 0
11.50
7.27
5.24
3.8 7
2.6 8
1.93
1.53
1.24
1.00
0.75
0.63
0.4 7
0.37
0.28
15m
20m
182.00
74.1 0 111.00
69.2 0 92.2 0
46.2 0 61.6 0
27.50 36.6 0
17.30 23.00
10.9 0 14.5 0
7.86 10.4 8
7.74
5.81
5.3 6
4.0 2
3.8 6
2.1 0
3.0 6
2.3 0
2.4 8
1.86
1.49
1.98
1.51
1.13
1.20
0.9 0
0.9 4
0.7 0
0.7 3
0.55
0.4 2
0.5 7
30m
40m
50m
60m
70m
80m
90m
100m
148.00
138.00
92.40
54.9 0
34.5 0
21.8 0
15.7 0
11.6 0
8.04
5.7 9
4.5 9
3.7 2
2.9 7
2.26
1.8 0
1.41
1.10
0.8 5
123.00
73.2 0
46.00
29.1 0
21.00
15.5 0
10.7 0
7.72
6.12
4.96
3.96
3.0 2
2.8 0
1.88
1.46
1.13
91.50
57.20
36.40
26.2 0
19.40
13.40
9.6 5
7.65
6.2 0
4.96
3.7 7
3.00
2.35
1.83
1.42
110.00
69.00
43.6 0
31.40
23.2 0
16.1 0
11.6 0
9.18
7.44
5.96
4.5 2
3.61
2.8 5
2.2 0
1.78
80.5 0
50.9 0
36.70
27.10
18.8 0
13.6 0
10.70
8.6 8
6.9 4
5.28
4.21
3.29
2.56
2.15
103.5 0
58.2 0
41.9 0
31.00
21.40
15.40
12.2 0
9.9 2
7.93
6.0 3
4.81
3.76
2.9 3
2.51
65.40
47.20
34.8 0
24.10
17.40
13.8 0
11.20
8.9 2
6.79
5.41
4.2 3
3.29
2.8 8
72.7 0
52.40
38.7 0
26.8 0
19.3 0
15.3 0
12.40
9.9 1
7.54
6.0 1
4.7 0
3.6 6
3.2 5
Motor
Rating
KW
HP
Apprx.
Full Load
Current (A)
at 415V
Star/Delta MCCB
Rating/Type
SKB-3/4
SKB-1
SKB-0
SKB-3/4
10
7.5
14
25
25
12.5
17
25
25
15
11
21
25
25
20
15
28
32
32
25
19
35
40
40
30
22
41
50
50
40
30
52
80
63
50
37
69
100
80
60
45
80
100
75
55
97
125
100
75
125
160
125
90
156
250
150
112
190
315
250
175
130
225
315
315
200
149
255
315
315
220
160
275
400
400
250
186
320
400
500
600
300
224
375
500
500
600
350
261
449
630
630
600
400
298
505
630
630
600
66
Motor Control
Star-Delta Starting
DOL Starting
Care is to be taken to avoid nuisance tripping during starting of Squirrel
Cage Motors since the inrush current will be in the order of 600 to
800% of the full load current of the motor. The overload setting is
chosen such that it does not trip during starting.
1200
1000
900
400
50 100 150 200 250 300 350 400 450 500 550 600
Capacitor rating (KvAr)
Ir > 1.5 Ic
Where :
I r
=
I c
=
Iinst =
Ip =
500
100
The maximum time duration during which the maximum current flows
is about 0.5 ms. Selection of a MCCB for capacitor circuit duty must
therefore consider the effects of higher short circuit and inrush currents.
This will affect the choice of instantaneous trip current rating. In practice,
an MCCB which satisfies the following equations should be chosen.
Iinst >
600
200
700
300
800
Ip
2
The short circuit release is actuated by the peak value of the AC sine
wave. Since no such peak exists in DC, DC tripping will be slower.
Hence to achieve the same short circuit pick up level in DC, the short
circuit release will be calibrated specially.
DC Control
In AC the breaking of the short circuit current usually occurs within the
first current zero, by the current limiting effect. No such current zero
exists in DC. Arc breaking and ultimate quenching of arc depends on
the rapid dissipation of the inductive Energy Li2
This energy dissipation is dependent on L/R or time constant of the
circuit. The L/R values should be limited to 10-15 milli seconds to
achieve satisfactory performance. This is achieved usually by splitting
the DC arc voltage over 2 or 3 poles by connecting them in series,
depending upon on the DC voltage.