VP-THI-QG29-118 Control Philosophy (QG2) Rev.C3 PDF
VP-THI-QG29-118 Control Philosophy (QG2) Rev.C3 PDF
REVISION: C3
Page 1/16
C3
29th Feb.
2016
C2
SJK
SAFI
CJL
FOR APPROVAL
16 Oct.
2015
SJK
SAFI
CJL
FOR APPROVAL
C1
25th Sep.
2015
SJK
SAFI
CJL
FOR APPROVAL
Revision
Date
Originated
Checked
Approved
Description
th
Actions :
1) Activate ready to start lamp on LCP
2) Activate ready to start lamp on DCS
Note :
1) Compressor can be started only at local job site by pushing compressor start button
when ready to start lamp is ON
Actions :
1) Trip compressor motor
Note :
(1)Push reset button for alarm reset and recover Ready to start condition if all trip
conditions (causes) disappeared
(2) If there is still any trip condition, common trip lamp remain ON even if reset button is
pushed.
(3) This alarm & trip to be overridden before start-up even of alarm&trip condition is
generated.
(4) To check lamp in chiller PLC manually, use lamp test button.
Actions 1 :
1) Decrease open degree of control valve(CV-01)
Actions 2 :
1) Increase open degree of control valve(29FV-87I402A)
Note :
1) Control valve position to return to zero position (0%) immediately when compressor is
stopped
2) Superheat can be calculated by following formula
TY=Ta Ts
Where,
TY : superheat (K or )
Ta : actual temperature read from 29TY-87I408A ()
Ts : saturation temperature () corresponding pressure (actual pressure read from PI05)
Actions 2 :
1) Energize INCREASE solenoid (29XY-87I401A/ 29XY-87I403A)
2) De-energize DECREASE solenoid (29XY-87I402A/ 29XY-87I404A)
Actions 3 :
Actions 4 :
1)
2)
Actions 5 :
1)
2)
Actions 6 :
1) Energize INCREASE solenoid(29XY-87I401A/ 29XY-87I403A)
2) De-energize DECREASE solenoid(29XY-87I402A/ 29XY-87I404A)
Note :
1) Set value of chilled water temperature and Suction pressure high/low gap can only be
changed in THI PLC.
2) If either DECREASE solenoid or INCREASE solenoid is energized at capacity control switch
in AUTO , solenoid ON delay time (1 sec.) & OFF delay time (4 sec.) to be implemented
in THI PLC logic
Causes 1 (All causes in AND logic) : Auto oil pump start control
1)
2)
3)
Actions 1 :
1)
2)
3)
Causes 2 (All causes in AND logic) : Manual oil pump start control
1)
2)
3)
Actions 2 :
1)
2)
3)
Causes 3 (All causes in AND logic) : Manual oil pump stop control
1)
2)
3)
Oil pump run feedback(29XL-87I404A) from MCC not activated within 15sec.
Actions 2 :
1)
2)
3)
P-101 WATER PUMP CONTROL (I-06 INTERLOCK), all below to be implemented and controlled
directly in client PLC
2)
Actions 1 :
1)
2)
Actions 2 :
1)
2)
Actions :
1)