Professional Documents
Culture Documents
PAGE 1 OF 62
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
1.
Introduction
This document sets out some guidelines for designing firewater systems using the
PIPENET VISION Spray/Sprinkler Module. It considers a firewater system on a process
plant. Typically, such systems contain deluge systems, monitors, hydrants, hosereels and
other items.
Although there is more than one approach for designing firewater systems, one approach
that is often followed by experienced fire engineers is to separate the design of deluge
systems from the design of firewater ringmains. There are essentially two reasons for this
approach.
The objectives of the calculations for the two requirements are somewhat different.
The main objectives are summarised in Sections 1.1 and 1.2 of this document. In
view of these differences, in order to optimise the design, it is a good idea to divide
the system into a deluge system and a firewater ringmain before the calculations
are performed.
Furthermore, it is sometimes the case that one company designs the deluge
systems and a different company designs the firewater ringmain.
In this chapter of the training manual, we consider two real firewater systems and show
how our tips and guidelines of Chapters 1 and 2 may be implemented in practice.
The systems used in this document are real applications for which the PIPENET VISION
Spray/Sprinkler Module has been used. The networks are relatively complex. For this
reason, the reader is encouraged to obtain the data files from Sunrise Systems or an
authorised representative.
1.1
Check the velocities and keep them below the specified limits:
As firewater systems do not operate for 24 hours a day, they do not generally suffer from
erosion problems. However, in order to minimise the frictional losses in the pipes, it is still
important to keep the velocities below a reasonable limit. Normally, high velocities arise
because pipe diameters are too small. For a given flow rate, the frictional loss per unit
length is inversely proportional to the fifth power of the diameter. So, one must not merely
reduce pipe sizes solely for the purpose of cutting costs.
-1-
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
1.2
1.3
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
The following phases of hydraulic design are considered in this document. It is important
to emphasise that it would not be necessary to carry out all of these phases for every
design. In particular, it is quite common for the design engineer to set the pipe sizes
(diameters) and skip that phase. It should also be pointed out that, in this document, we
do not allow for safety margins in the design. For example, where the firewater ringmain
and the deluge system meet, we assume (in this document) that the match between them
is exact. In the real design case, it may be wise to allow a slight excess pressure on the
firewater ringmain side (because, for example, (a) the fire pumps may not perform as
expected or (b) during fabrication it may become necessary to re-route the pipes).
2.
2.1
The network for the deluge system is shown below. Although it does not have to be drawn
in this manner, it is done so for illustration purposes only.
-3-
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
-4-
2.2
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
Library Data
Actual Internal
Diameter (mm)
25
24
32
32
40
38
50
54
65
66
80
82
90
95
100
108
125
not used
150
161
200
211
Wall Drench-4
K-factor
45 (lit/min,barg)
-5-
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
Output
Node
A/2
A/3
A/4
A/5
A/6
A/7
A/8
A/9
A/10
A/11
A/12
A/13
B/2
B/3
B/4
B/5
B/6
B/7
B/8
B/9
B/10
B/11
B/12
B/13
C/2
C/3
C/4
C/5
C/6
C/7
C/8
C/9
C/10
C/11
C/12
C/13
C/7
B/7
A/7
Length
(m)
2.068
2.068
2.068
2.068
2.068
1.034
1.034
2.068
2.068
2.068
2.068
2.068
2.068
2.068
2.068
2.068
2.068
1.034
1.034
2.068
2.068
2.068
2.068
2.068
2.068
2.068
2.068
2.068
2.068
1.034
1.034
2.068
2.068
2.068
2.068
2.068
0.5
3.28
3.28
Elevation
Change (m)
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.5
3.28
3.28
-6-
C-factor
Status
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Pipe
Type
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
SPECIAL
Group
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3
3
3
4
4
4
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
2.3
Nozzle
Status
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
It should be emphasised here that the pipe sizes determined by PIPENET VISION are not
always ideal, as PIPENET VISION does not have the experience and intuition of an
engineer. The pipe sizes determined by PIPENET VISION should be regarded as initial
guesses. In most cases, the design engineer will simply set the pipe sizes based on past
experience.
-7-
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
For pipe sizing, the D Button must be selected on the Calculation Toolbar, as shown
below.
-8-
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
Note the
creation
of groups
-9-
2.4
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
The results below were obtained after the pipe-sizing phase was performed. The yellow
background indicates that these sizes have not been fixed. In this context, the term fixed
means the following. Once the sizes are fixed they can only be changed manually;
PIPENET VISION will not automatically change them, depending on the specifications.
During the Design Phase, the yellow background to the pipe sizes means that the pipe
sizes can change, depending on the operating conditions.
- 10 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
- 11 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
We note from the above figure that the maximum velocity is well below the specified
maximum of 4 m/sec.
This point can also be seen in a Data Window, in which the pipes are re-ordered on the
basis of velocities, as shown below.
- 12 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
Depending on the design rules, there is scope for increasing the maximum velocity for pipe
sizing. Our next step is to increase this maximum velocity to 6 m/sec.
2.5
- 13 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
- 14 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
We note that the velocities in some of the pipes are more than the maximum of 6 m/sec.
Therefore, we have to increase the pipe sizes for some of these pipes, and this change is
carried out in Section 4 below. Please note the highlighted velocities in the screen shots
below.
As expected, the required inlet pressure is higher. However, the inlet flow rate is also
slightly higher. Please offer an explanation for this.
- 15 -
2.6
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
Clearly, the pipe sizes with a maximum velocity of 6 m/sec are considerably smaller than
those with a maximum velocity of 4 m/sec. We note from the output, however, that the
velocities in Pipes B/6, B/7, C/6, C/7 and V/1 exceed the maximum of 6 m/sec. This
indicates that optimal pipe sizes for the other pipes could be fixed at their current values,
provided the sizes of Pipes B/6, B/7, C/6, C/7 and V/1 are increased (in order to bring the
velocity below 6 m/sec).
The next step, therefore, is to fix the sizes of the diameters, and then increase the sizes of
Pipes B/6, B/7, C/6, C/7 and V/1. Firstly, click on the Analysis (or Calculation) Button.
The diameters will now be fixed at their current values. This ensures that the diameters do
not change automatically between different calculations; for example, because the
specifications have changed. At some point in the Design Phase calculations, the pipe
diameters become fixed, and can only be changed manually.
After fixing the diameters, we can turn our attention to Pipes B/6, B/7, C/6, C/7 and V/1.
The nominal sizes of Pipes B/6, B/7, C/6, and C/7 are to be increased from 40 mm to
50 mm, and that of V/1 is to be increased to 100 mm (as shown in the highlighted rows in
the screenshot below).
- 16 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
Please note that the yellow background to the diameters has been changed to white, and
the diameters have been set manually.
The diameters of Pipes B/6, B/7, C/6 and C/7 are now set to 50 mm, and the diameter of
Pipe V/1 is set to 100 mm. These changes are indicated in the above Data Window. Also,
please note that the group data has now been set to unset, as only one diameter is
allowed in a given group.
- 17 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
- 18 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
- 19 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
2.7
In the above scenario, it is clear that the nozzles at the lower levels are discharging too
much water (which can be seen by looking at the nozzle percentage deviation shown in
the above screen shot). This is to be expected. We can try to reduce some of the pipe
sizes and check the implications.
- 20 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
It can be seen from the Data Window below, in which the nozzles have been re-ordered on
the basis of the nozzle deviation, that there is better balance.
We can also see this improvement in the inlet conditions (in the schematic below), as there
is better balance between the nozzles.
- 21 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
It is, of course, not good news all they way round. There is a price to pay. The velocity in
some of the pipes now exceeds the maximum value. It is a matter of engineering
judgement as to whether or not this system is acceptable.
The pipe velocities, re-ordered in decreasing value, are shown in the following screen
shot. Please note that the velocities below are positive. Since the system is symmetric,
there will be corresponding negative velocities in other pipes. However, these negative
values do not appear in the table below, as only the top ten values are present. Negative
velocities indicate that the flow is in the opposite direction of the pipe; i.e., directed from
the output node of the pipe to the input node.
- 22 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
At this stage, it is the decision of the design engineer as to the extent to which the deluge
is to be optimised and fine-tuned. For the purpose of this document, we shall assume that
the design of the deluge system is frozen at this point.
The equivalent K-factor for the deluge system is recorded in the output file, an extract of
which is shown below.
FLOW AT INLETS
-------------Inlet Node
Pressure
Flowrate
Equivalent K-factor
(bar G
)
(lit/min )
(lit/min , bar G
)
-----------------------------------------------------------V/1
3.635
2519.
1321.2
Note: A * after a value indicates that this is a specification
We note that the value of the equivalent K-factor is 1321.2 (lit/min, bar). This value can be
readily used if this deluge system is to be modelled as a nozzle. As we saw in Chapter 3
of the Spray/Sprinkler Training Manual (entitled Fire Protection Systems Design Firewater Ringmain Systems), this value is typical for deluge systems that are to be
modelled by equivalent nozzles where clack shut deluge valves are used.
- 23 -
3.
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
3.1
By this stage, all of the deluge systems have been designed, and all of the monitors,
hydrants and hosereels have been chosen. Their equivalent nozzles and, hence, their
equivalent K-factors have all been determined. It is entirely possible that these designs
and selections are preliminary, and so could be modified. However, in order to perform
design calculations for firewater ringmain systems, we should at least know the results
from preliminary designs and selections. If they are not known, typical values or estimated
values must be assumed.
One of the earliest tasks in the hydraulic design of the firewater ringmain system is to
determine the pipe sizes. Clearly, the difficulty in this step is due to the fact that the
firewater ringmain system has to work under a wide variety of conditions. For example,
the system should be able to deal with a number of potential fire scenarios and pump
scenarios (in other words pumps working in different combinations).
Experienced fire engineers know through their own experience as to which diameters to
use. Their experience is often a better guide to the optimal design, and so it is typical for
all the pipe sizes to be set by the fire engineer. Typically, the diameters are input by the
user, rather than being calculated using PIPENET VISION.
However, for the sake of completeness of the design procedure, the pipe sizing procedure
is described here.
- 24 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
- 25 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
Working
Working
- 26 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
- 27 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
- 28 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
Node Equip/3 is defined as an output node, and does not have a nozzle attached.
- 29 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
Node Equip/3
- 30 -
3.2
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
We can compare the diameters calculated by PIPENET VISION for all the above cases,
and then decide which diameters are the best to use. The fixed diameters are shown in
the table in Appendix 4, at the end of this chapter.
The requirements for the worst-case scenario and, hence, the nozzle data and status are
as shown below.
In the first instance, no orifice plates are inserted, as we wish to establish whether the pipe
sizes determined in this section produce a well-balanced flow in the system.
The calculated results for the above users are shown below. It is clear that there is
significant imbalance in the supply to the users. In the next section, we shall see how to
correct this imbalance using orifice plates.
- 31 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
The inlet flow-rate and pressure requirements are shown on the screenshot of the input
node results:
It is clear that the inlet conditions can be made less demanding by balancing the flow
through the deluge systems (which can be easily achieved by placing orifice plates in the
inlets to the deluge systems).
3.3
The sizes for orifice plates can be determined using the following steps.
At the inlet of the worst nozzle from the previous calculation, define the required
pressure as well.
Perform a calculation.
This calculation will result in the pressures at the outlet nodes. These pressures are
the available pressures. Subtract the required pressures from the available
pressures, to yield the required pressure drops in the orifice plates.
Input the orifice plates, and assign the required pressure drops. Now, perform a
calculation to obtain the orifice plate diameters. These diameters can now be fixed,
the outlets can be removed, and the nozzles can be placed back again.
Before working through the above steps, we first need to specify the flow rates and
pressures required for the systems that are working.
- 32 -
Nozzle
Label
FH/56
TANK/13
FH/86
FH/85
TANK/10
FH/84
FM/13
Input
Node
279
168
309
308
169
307
170
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
Required Flow
Rate (m3/hr)
36
421.2
36
36
1278
36
144
K-factor
20.78
317.6
20.78
20.78
404.14
20.78
54.43
Required
Pressure (bar)
3.00
1.76
3.00
3.00
10.00
3.00
7.00
The dialog boxes for defining the outlet conditions are as follows.
The dialog boxes for the output nodes created by removing the nozzles are all assigned
the specifications that are shown above.
- 33 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
At the critical outlet node, both the pressure and the flow rate are given.
All the calculation specifications that have been input are shown in the screen shot below.
Please note that Node 209 is the inlet and, at this stage, we are not interested in making a
specification at this node.
- 34 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
We can now draw up a table that shows the required pressures against the actual
available pressures. The difference between these pressures is the amount by which the
pressures need to be dropped in the orifice plates.
Input
Node
279
168
309
308
169
307
170
Required
Pressure (bar)
3.00
1.76
3.00
3.00
10.00
3.00
7.00
Available
Pressure (bar)
10.054
10.028
10.059
10.048
9.997
10.059
10.022
Pressure
Difference (bar)
7.054
8.268
7.059
7.048
0
7.059
3.022
The orifice plates are now input, and the pressure losses are assigned to them. Please
ensure that the Crane Option is chosen for orifice plates.
The calculated orifice diameters are shown in the screen shot below.
- 35 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
The calculated flow rate and pressure results at the output nodes are shown below. It can
be seen from the table that the pressures and flow rates at the output nodes are exactly as
required. The relevant nodes are highlighted.
3.4
This system is to be driven by two 50% duty pumps. The inlet node, therefore, must be
separated into two nodes as required. In practice, this is essential because the pumps
- 36 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
may be located in different places, or they could be at different elevations. So it may not
be possible to combine them into a single node.
In principle, several pump combinations can meet the required duty. In order to ensure
that the pumps must be of equal size, we need to define the flow rate through one of the
pumps to be 50% of the total required flow rate.
By adding up the required flow rates through all the outputs, we can calculate that the flow
rate though the two pumps should be a total of 2552.4 m3/hr. So, each pump must deliver
1276.2 m3/hr, which must be given as the flow rate for one of the input nodes, for both the
design specification and the calculation specification. The other input node must be left
completely free, and simply be defined as an input node.
The specifications for Input Nodes 209 and 183 are defined below.
- 37 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
The calculated results for the two input nodes can be easily determined by sorting the
Data Window for the nodes. It can be seen that each pump must deliver 1276.2 m3/hr at
10.514 barg.
- 38 -
Appendix 1:
Label Input
Node
1
1
2
1
3
4
4
5
5
6
6
7
7
8
12
7
13
2
15
10
16
11
17
12
18
13
19
10
20
14
21
15
22
16
23
135
26
19
27
20
28
21
29
22
31
23
32
24
33
205
34
25
35
26
36
27
37
28
38
29
39
30
40
31
41
32
42
33
43
34
44
35
45
36
47
31
48
33
49
35
50
30
51
32
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
Pipe Data
Output
Node
86
91
97
105
112
119
133
140
3
64
57
54
44
210
213
215
11
17
28
9
17
144
80
90
24
20
25
26
27
19
31
32
33
34
35
36
37
38
39
40
41
42
Length
(m)
20.67
29.72
17.97
7
9.14
9.1
25
19
17
8.44
16.22
11.25
24.2
44.73
46.8
13.41
16.48
9.84
15
24
14
26.2
5.12
36.51
20.67
49.2
27.7
29.9
29.9
20.4
8.8
17.4
12.3
11.73
9.33
10.7
27.5
22.7
22.7
22.7
1
1
Elevation
(m)
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
- 39 -
34
44
45
46
47
48
49
50
51
52
53
54
55
51
57
58
59
60
61
62
54
64
65
66
67
68
69
70
71
72
73
72
75
76
77
78
79
80
82
83
85
86
24
87
89
90
43
46
9
47
48
45
55
49
50
51
62
53
13
56
58
59
60
61
331
52
63
65
66
222
68
69
16
10
70
71
72
74
76
77
78
2
82
75
83
84
79
85
87
88
3
89
1
28.32
6.5
27.52
28.18
29.42
29.8
28.34
16.8
16.45
30.34
10.1
28.45
1
28
28
28
28
28
30
15.3
25
23
20.72
22
25
7
21.57
55
29.53
25.48
34.7
8.03
50.11
46.23
8.7
7.2
41
22.7
22
20.43
60
23.49
50
35.1
50
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
- 40 -
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
92
93
95
96
97
98
98
95
101
101
103
104
105
106
107
108
109
110
111
112
114
108
116
117
118
120
118
117
124
125
126
127
128
127
128
123
125
134
136
137
138
139
9
140
141
142
93
4
96
5
98
94
99
100
103
102
104
6
106
107
101
109
110
111
7
113
108
115
328
120
327
8
121
122
127
128
125
123
124
129
130
131
132
21
135
136
137
138
139
141
142
22
50
30.83
26.31
25.03
30
29.96
1
1
30
1
30
29.26
28
28
28
28.93
30
30
26.6
30
28.84
1
11.23
27
13.45
20.2
1
1
16.5
28.28
21
13
12.74
4.77
4.77
25.2
1
15.5
25
25
25
30
18.5
19
20.7
12
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
- 41 -
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
141
144
145
146
147
148
149
145
148
146
149
155
156
157
158
159
160
161
162
163
164
156
157
158
161
162
163
171
172
173
174
175
176
177
178
179
180
181
174
176
177
181
179
180
190
191
143
145
146
147
148
149
150
151
152
153
154
156
157
218
159
160
161
162
163
164
12
165
166
167
168
169
170
172
173
174
175
176
177
178
179
180
181
182
184
185
186
187
188
189
195
190
1
20.67
15.85
9.5
12.12
18
18
6
6
1
1
22.95
5.74
10.45
18.9
30
6.2
5.74
21.15
23.9
18.4
19.95
4.45
1
19.95
4.45
1
15.25
11.86
17.9
6.4
28
21.74
7.65
7.07
22.93
11.7
12.2
18.64
1
18.64
18.64
14.7
1
29.71
30
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
- 42 -
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
192
193
194
195
196
197
190
195
191
193
196
204
207
206
209
210
211
212
213
214
215
216
218
219
19
222
81
83
222
205
204
78
77
76
80
81
82
85
86
91
92
93
97
94
96
105
191
192
193
196
197
198
199
200
201
202
203
23
205
204
206
219
212
14
214
15
216
217
158
220
221
67
23
81
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
15.2
18.88
11.13
21.6
8.3
23.96
1
1
1
11.9
11.9
20.43
30.69
22.41
6.82
14.3
53.53
7.98
56.73
37.1
53.45
48.5
22
18.1
26.9
9.3
39.9
17.32
15.3
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
- 43 -
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
106
107
103
104
112
113
114
109
110
111
119
116
120
133
134
135
136
137
138
139
36
37
29
28
27
26
25
20
45
48
47
46
44
55
49
50
52
62
53
61
60
59
58
57
69
68
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
- 44 -
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
67
66
65
64
70
71
73
89
90
87
88
198
197
192
194
182
178
175
173
171
164
160
159
218
155
150
147
144
142
140
124
126
210
211
212
213
214
215
216
217
327
328
328
327
331
331
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
116
117
329
330
12
332
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
16.55
18.77
5.2
5.2
24.1
1.5
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
- 45 -
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
219
209
4
88
207
3
182
94
198
113
21
37
217
119
133
18
17
22
150
6
91
211
207
194
1
206
73
11
95
10
114
126
18
16
118
134
29
30
123
13
155
92
34.12
6.82
31.95
13.6
6.92
28.6
18.2
27.66
18.1
30
28.2
11.6
44.66
15.7
30
29.3
28
25.2
18
23.7
50
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
- 46 -
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
4.57E-02
0
0
0
0
0
0
0
0
0
0
0
0
11.89
0
0
0
0
0
0
0
0
Appendix 2:
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
Fittings on Pipes
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
4
4
4
4
4
4
4
4
3
4
4
4
4
5
4
4
4
4
4
4
4
4
4
4
4
3
4
4
4
3
4
4
4
4
4
4
4
4
4
4
5
4
4
4
4
4
4
4
4
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
16.29
54.31
54.31
54.31
54.31
5.408
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
16.29
54.31
54.31
54.31
16.29
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
5.408
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
1 x
1 x
5
4
5.408
54.31
1 x
54.31
1 x
54.31
- 47 -
1 x
5.408
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
4
4
4
4
5
4
4
4
5
4
4
5
4
4
4
4
4
4
4
4
5
4
4
4
4
3
4
4
5
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
54.31
54.31
54.31
54.31
5.408
54.31
54.31
54.31
5.408
54.31
54.31
5.408
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
5.408
54.31
54.31
54.31
54.31
16.29
54.31
54.31
5.408
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
1 x
54.31
1 x
5.408
1 x
5.408
- 48 -
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
4
4
4
4
3
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
5
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
5
4
4
54.31
54.31
54.31
54.31
16.29
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
5.408
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
5.408
54.31
54.31
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
1 x
54.31
1 x
5.408
- 49 -
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
4
4
4
4
4
4
4
4
4
5
5
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
5
5
4
4
4
4
4
4
4
4
4
4
5
4
4
5
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
5.408
5.408
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
5.408
5.408
54.31
54.31
54.31
54.31
54.31
54.31
54.31
54.31
10.67
54.31
5.408
54.31
54.31
5.408
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
1 x
5.408
1 x
5.408
1 x
5.408
1
1
1
1
1
1
x
x
x
x
x
x
5
5
5
5
5
5
5.408
5.408
5.408
5.408
5.408
5.408
1 x
1 x
5
5
1.219
5.408
1 x
1 x
5
5
5.408
5.408
- 50 -
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
45 Deg Elbow,
90 Deg Standard Elbow,
90 Deg Long Radius Elbow,
Tee or Cross (Flow Turned Thro 90 Deg),
Gate Valve,
Swing Check Valve,
Non-Return Valve,
Ball Valve,
Butterfly Valve.
- 51 -
Appendix 3:
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
Input
Node
200
199
201
99
100
184
186
187
189
185
102
167
170
56
115
154
153
143
121
122
131
132
41
42
43
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
Nozzle
Type
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
K-factor
(lit/min, bar)
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
54.4269
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
Required Flow
Rate (lit/min)
144
144
144
144
144
144
144
144
144
144
144
144
144
144
144
144
144
144
144
144
144
144
144
144
144
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
- 52 -
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
- 53 -
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
8
8
9
6
6
7
7
5
5
4
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
20.7846
154
154
52.61
82.8
82.8
55.2
55.2
145.72
145.72
404.14
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
435.6
291
148.8
136.8
248.4
165.6
165.6
460.8
151
1278
- 54 -
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
1.00E+01
4
3
3
3
10
404.14
317.62
317.62
317.62
178.73
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
1278
1004.4
421
1004.4
531.3
Fire monitor,
Fire hydrant,
Nozzle for 301,
Nozzle for 304,
Nozzle for 303,
Nozzle for 302-001-002,
Nozzle for 302-003-004,
Nozzle for 305-001-002,
Nozzle for 305-003,
User Defined.
- 55 -
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+00
1.00E+01
1.00E+01
1.00E+01
1.00E+01
2.00E+01
Appendix 4:
Pipe Diameters
Calculations
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
Fixed
After
PIPENET
VISION
The following table contains the diameters for each case and the final fixed diameters.
Pipe
Label
1
2
3
4
5
6
7
8
9
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
Area 301 Area 302 Area 303 Area 304 Area 305-1 Condensate
Unit
400
400
200
600
200
300
400
400
250
600
250
300
400
400
250
600
250
300
400
400
250
600
250
300
200
200
250
200
250
100
125
125
250
125
400
65
125
125
250
125
400
65
400
400
200
600
20
300
200
200
100
350
200
400
400
400
80
200
200
150
150
150
100
600
250
300
400
400
250
200
250
80
400
400
200
600
250
300
400
400
250
600
400
300
400
400
200
600
200
300
200
200
250
600
200
300
125
125
250
200
200
100
250
250
250
125
300
65
250
250
150
300
400
200
250
250
150
300
400
200
400
400
150
300
400
200
125
125
250
600
400
300
125
125
250
125
80
65
125
125
250
125
200
65
125
125
250
125
200
65
125
125
250
125
250
65
125
125
250
125
400
65
150
150
250
125
400
65
15
15
350
200
400
80
400
400
250
15
400
15
400
400
200
600
400
300
400
400
200
600
400
300
125
125
250
600
400
300
125
125
250
125
400
65
125
125
250
125
400
65
125
125
250
125
400
65
125
125
250
125
400
65
125
125
250
125
400
65
125
125
250
125
200
65
125
125
250
125
250
65
125
125
250
125
15
65
125
125
250
125
15
65
125
125
250
125
150
65
125
125
250
125
150
65
- 56 -
Fire
Station
300
300
300
300
65
32
32
300
300
100
300
50
300
300
300
300
65
32
200
200
200
300
32
32
32
32
32
32
50
15
300
300
300
32
32
32
32
32
32
32
32
32
32
32
Final Fixed
Diameter
600
600
600
600
400
400
400
600
400
450
600
350
600
600
600
600
400
400
250
250
250
600
400
400
400
400
400
400
350
300
600
600
600
400
400
400
400
400
400
400
400
400
400
400
125
15
15
15
15
15
15
125
125
125
125
125
200
200
200
200
200
200
200
15
400
400
400
400
400
200
250
400
400
400
400
400
400
400
400
400
400
15
400
400
400
400
400
400
400
400
400
15
400
400
400
400
125
15
15
15
15
15
15
125
125
125
125
125
200
200
200
200
200
200
200
15
400
400
400
400
400
200
250
400
400
400
400
400
400
400
400
400
400
15
400
400
400
400
400
400
400
400
400
15
400
400
400
400
250
250
15
15
15
15
15
15
250
250
250
250
250
250
250
250
250
250
250
250
15
250
250
250
250
250
250
15
200
200
200
200
200
200
250
250
250
250
15
200
200
200
200
200
200
200
200
200
15
200
200
200
125
125
15
15
15
15
15
15
125
125
125
125
125
200
200
200
200
200
200
200
15
600
600
600
600
600
200
250
600
600
600
600
600
600
600
600
600
600
15
600
600
600
600
600
600
600
600
600
15
600
600
600
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
400
400
400
400
400
250
250
250
250
250
250
250
15
250
250
250
250
250
250
15
250
250
250
250
250
250
250
250
250
250
15
200
200
200
200
200
200
200
15
200
200
200
200
200
200
250
250
250
250
250
250
15
- 57 -
65
65
15
15
15
15
15
15
65
65
65
65
65
100
100
100
100
100
100
100
15
300
300
300
300
300
100
15
300
300
300
300
300
300
300
300
300
300
15
300
300
300
300
300
300
300
300
300
15
300
300
300
32
32
15
15
15
15
15
15
32
32
32
32
32
65
65
65
65
65
65
65
15
300
300
300
300
300
65
15
300
300
300
300
300
300
300
300
300
300
15
300
300
300
300
300
300
300
300
300
15
300
300
300
400
400
250
250
150
150
150
150
400
400
400
400
400
400
400
400
400
400
400
400
150
600
600
600
600
600
400
300
600
600
600
600
600
600
600
600
600
600
100
600
600
600
600
600
600
600
100
600
600
600
600
600
400
400
350
400
400
400
400
400
400
400
15
15
400
15
400
400
400
400
400
200
200
200
200
200
200
200
15
125
125
125
125
125
15
15
15
15
15
15
15
15
15
15
15
15
125
125
125
125
125
125
125
150
400
400
350
400
400
400
400
400
400
400
15
15
400
15
400
400
400
400
400
200
200
200
200
200
200
200
15
125
125
125
125
125
15
15
15
15
15
15
15
15
15
15
15
15
125
125
125
125
125
125
125
150
200
200
200
250
250
250
250
250
250
250
250
15
15
250
15
250
250
250
250
250
250
250
250
250
250
250
250
15
250
250
250
250
250
15
15
250
250
250
250
250
250
15
15
15
15
250
250
250
250
250
250
250
600
600
600
600
600
600
600
600
600
600
15
15
600
15
600
600
600
600
600
200
200
200
200
200
200
200
15
125
125
125
125
125
15
15
15
15
15
15
15
15
15
15
15
15
125
125
125
125
125
125
125
200
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
15
250
15
250
250
250
250
250
250
250
250
250
250
250
15
400
400
400
400
15
15
200
200
200
200
200
15
15
15
15
400
400
400
400
400
400
200
200
200
15
80
80
80
80
80
80
15
15
15
15
20
20
- 58 -
300
300
300
300
300
300
300
300
300
300
300
15
15
300
15
300
300
300
300
300
100
100
100
100
100
100
100
15
65
65
65
65
65
15
15
15
15
15
15
15
15
15
15
15
15
65
65
65
65
65
65
65
300
300
300
300
300
300
300
300
300
300
300
15
15
300
15
300
300
300
300
300
65
65
65
65
65
65
65
15
32
32
32
32
32
15
15
15
15
15
15
15
15
15
15
15
15
32
32
32
32
32
32
32
600
600
600
600
600
600
600
600
150
150
600
150
600
600
600
600
600
400
400
400
400
400
400
400
150
400
400
400
400
400
150
150
300
300
300
300
300
300
200
200
600
150
400
400
400
400
400
400
400
350
350
350
150
150
15
150
150
150
150
150
150
150
15
15
15
15
400
400
400
400
400
400
400
400
400
400
15
15
15
15
15
15
450
450
450
450
450
450
450
450
450
450
450
450
15
15
150
15
15
400
150
200
200
200
150
150
15
150
150
150
150
150
150
150
15
15
15
15
400
400
400
400
400
400
400
400
400
400
15
15
15
15
15
15
450
450
450
450
450
450
450
450
450
450
450
450
15
15
150
15
15
400
150
200
200
200
250
250
250
15
350
350
350
350
350
350
250
150
150
150
100
100
100
100
100
100
100
100
100
100
15
15
15
15
15
15
80
80
80
80
80
80
80
80
80
80
80
80
15
15
15
15
15
15
15
100
100
100
200
200
15
200
200
200
200
200
200
200
15
15
15
15
600
600
600
600
600
600
600
600
600
600
15
15
15
250
450
150
200
200
200
200
200
200
200
200
200
200
200
200
15
15
15
15
15
15
15
350
350
350
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
20
20
20
20
20
20
20
20
15
15
15
15
15
15
80
80
80
80
80
80
80
80
80
80
80
15
15
15
15
15
15
15
125
125
125
125
125
125
125
125
15
15
15
15
15
250
250
250
250
200
200
200
- 59 -
80
80
80
15
80
80
80
80
80
80
80
15
15
15
15
300
300
300
300
300
300
300
300
300
300
15
15
15
15
15
15
150
150
150
150
150
150
150
150
150
150
150
150
15
15
15
15
15
15
15
400
400
50
50
50
15
50
50
50
50
50
50
50
15
15
15
15
300
300
300
300
300
300
300
300
300
300
15
15
15
15
15
15
100
100
100
100
100
100
100
100
100
100
100
100
15
15
15
15
15
15
15
300
300
150
350
350
350
350
350
350
350
250
250
150
150
600
600
600
600
600
600
600
600
600
600
400
450
150
400
450
150
450
450
450
450
450
450
450
450
450
450
450
450
400
150
150
150
150
400
150
400
400
400
400
400
200
200
200
200
200
200
15
15
15
15
15
400
400
400
90
400
400
250
250
250
250
250
250
250
200
400
400
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
200
200
200
200
200
200
15
15
15
15
15
400
400
400
90
400
400
250
250
250
250
250
250
250
200
400
400
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
100
100
100
100
100
100
15
15
15
15
15
250
250
250
65
250
250
150
150
150
150
150
150
150
200
100
200
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
350
350
350
350
350
350
15
15
15
15
15
600
600
600
50
600
600
300
300
300
300
300
300
300
200
600
600
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
200
200
200
200
20
15
15
250
200
200
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
- 60 -
400
400
400
400
400
400
15
15
15
400
15
300
300
300
80
300
300
200
200
200
200
200
200
200
200
300
300
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
300
300
300
300
300
300
250
15
15
15
400
15
300
300
300
80
300
300
200
200
200
200
200
200
200
200
300
300
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
400
400
400
400
150
150
150
400
400
600
600
600
600
600
600
250
250
250
250
250
250
250
250
600
100
200
600
600
600
400
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
- 61 -
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
400
15
125
125
250
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
400
15
125
125
250
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
250
15
250
250
150
15
15
15
15
15
15
15
15
15
80
80
80
80
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
600
15
125
125
300
15
15
SPRAY: CHAPTER 4
REVISION 2.1, SEP 2010
15
15
15
15
15
15
15
15
15
15
400
400
15
15
250
15
200
250
125
200
65
250
80
250
250
80
125
250
80
200
400
200
400
400
400
200
- 62 -
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
300
15
65
65
200
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
300
15
32
32
200
15
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
400
400
15
15
600
80
250