Professional Documents
Culture Documents
1999-Air Distribution For Large Spaces - Inthout PDF
1999-Air Distribution For Large Spaces - Inthout PDF
GUIDE
The following article was published in ASHRAE Journal, April 1999. Copyright 1999 American Society of Heating, Refrigerating and AirConditioning Engineers, Inc. It is presented for educational purposes only. This article may not be copied and/or distributed electronically or in paper
form without permission of ASHRAE.
AIR DISTRIBUTION
FOR LARGE SPACES
By Dan Int-Hout
Member ASHRAE
and
Leon Kloostra
Member ASHRAE
Basic Principles
A downward jet of cold air will travel further than isothermal air.
A downward jet of hot air will not travel as far as isothermal air.
Figure 1 shows this effect. This chart can be used several ways:
1. If the outlet discharge velocity and flow rate are known,
the chart can be used to estimate the downward vertical
projection of a jet to 50 fpm (0.25 m/s) terminal velocity
(T 50), for various temperature differences between the
discharge jet and the ambient or room temperature. For
example, for an isothermal 1,000 cfm (470 L/s) jet with a
1,000 fpm (5 m/s) discharge velocity, the distance to 50
fpm (0.25 m/s) will be about 28 ft (9 m).
2. Because the buoyancy effect is a function only of temperature, the chart can also be used to predict upward jet projection by switching the T values. For a given air quantity and
discharge velocity, the upward projection of a warm air jet at
20F (11C) temperature difference is the same as the downward projection of a cold air jet at a 20F (11C) temperature difference.
3. If isothermal throw is known (from standard grille performance charts), the right side of the chart can be used
to estimate the effect of temperature difference on
50 fpm (0.4 m/s) terminal velocity. Enter the chart at
the isothermal throw and move across to the temperature difference of interest. For example, if a grille has
an (isothermal) catalog rating of 50 ft (16 m) to a
50 fpm (0.25 m/s) terminal velocity, the jet will travel
about 72 ft (23m) if it is 20F (11C) cooler than the
ambient air. It will travel only 20 ft (6.5m) if it is 50F
(11C) degrees warmer than the surrounding air.
4. Figure 1 assumes that the jet aspect ratio (width to depth)
is near 1. Long linear slots may produce slightly shorter
throws than shown in Figure 1. This difference is due to
their increased surface area and subsequent higher entrainment ratios.
ASHRAE
Journal
51
Practical Guide
Horizontal Jets
ASHRAE JOURNAL
52
ASHRAE
Journal
April 1999
Museums &
Renovation
Figure 4: Throw and drop for outlet 1 ft below ceiling. 0 deflection, 0 spread.
reinduced into the primary air. This action reduces dumping and
keeps the cool air near the ceiling, resulting in uniform temperatures throughout the space. On the other hand, cross flow
jet projection continues after the low terminal velocity just like
the airflow from side wall registers at 0 deflection. During cooling, the circular recirculating airflow results in less drop than
with cross flow jets.
Cross flow patterns with longer throw and individual side
jets are similar to side wall jets. Near the end of the throw,
during cooling, cross flow patterns continue in the direction
April 1999
ASHRAE
Journal
53
Practical Guide
away from the diffuser. The drop can
also depend only on the airflow from
each diffuser side. Both patterns are
usually centered in equal spaces in large
open areas.
The wide spreading 45 deflection
from the side wall grilles is similar to
half the circular pattern. The 0 deflection grille is a pattern that all single nonspreading patterns follow. The horizontal projection from diffusers and grilles
has been used extensively in commercial applications. Perimeter heating may
need special treatment over the conventional horizontal air discharge at the
ceiling level.
Linear diffusers have a tendency to fold
back like the circular pattern. This reaction results in less drop than expected
during cooling from the linear diffusers as
the airflow is reduced.
During cooling, the air will often
drop to the floor. A stratification zone
can be formed near the ceiling, which
may result in non-uniform temperatures
below the stratification layer. The size
of the stratification zone will vary, depending on the primary air and the natural heat sources in the space. With a constant heat source, a VAV system that
reduces flow will allow a larger stratification zone to form. This type of distri- Figure 8: Specific airflow characteristics at high and low airflow rates.
bution allows high level stratification
even when air must be introduced from the ceiling. Return forms above the diffuser. The higher pressure in the room to
push the air up in a manner similar to the effect is often called
intakes can be located between supply sources.
Applications of this type of cooling can be used to maintain the coanda effect. (True coanda effect relies on attraction
constant temperatures around machinery by projection to the to a surface.) Some of these diffusers can adjust the air patfloor near the machines with return over the machines. For ex- tern so that air can come down in a variety of vertical patample, a high-speed printing press may be handled this way. terns.
In some applications, it may be advantageous to locate a cirProjection may be obtained at low jet velocities with the machines located in a near equal temperature. Projecting more or cular pattern diffuser upside down on top of an exposed duct. If
less air to the floor level, providing more air to floor if the main near a ceiling, entrainment may be achieved. With no ceiling
heat source is at the floor level, can control heat loss over the nearby, the diffuser will tend to dump without the adverse effects
of dumping.
machines.
Cross flow pattern diffusers set for a horizontal pattern
During heating, the warm supply air demonstrates less projection, spreading out, rising toward the ceiling. The floor level cannot cause airflow to go upward because the air pressure
becomes cooler and a stratification layer and zone can form at between the jets is equal to the air pressure in the room. Theresome level above the floor. Heat sources near the floor or supply fore, no low pressure is developed above the diffusers.
On the other hand, a cross flow pattern diffuser generally
air projected all the way to the floor help push the stratification
layer interface closer to the floor. Return intakes located at the produces a better intermediate vertical projection than circular pattern diffusers. With properly designed and installed
floor in stratification zones will help.
Some diffusers (check with the manufacturer) can provide diffusers, the velocities can be spread out almost uniformly
a good horizontal circular pattern when located below the from the center to the outside edges of these jets. The result
ceiling. In these designs, the jet projects upward toward the is a good spread with a drop proportional to the distance
ceiling. This action is caused by a low-pressure region that from the diffuser to the ceiling.
54
ASHRAE
Journal
April 1999
Museums &
Renovation
Spreading horizontal projection at floor level permits considerable stratification at high levels during cooling while maintaining uniform temperatures in the occupied zone. Although high
velocities in the occupied zone may preclude use of this type of
distribution for comfort cooling, application to situations with
high internal loads or where occupant comfort is not of primary
concern could be considered.
Figure 12 matches the actual definition given for displacement ventilation. Defined as a low velocity, low temperature differential air distribution across the floor level, displacement ventilation utilizes natural convection currents within the space to
cause air to rise and form a neutral zone above a stratification
level. The stratification level usually occurs at a level where the
room load and air loading match.
Displacement ventilation has a limited ability to handle high
cooling or heating loads. The range of supply air temperatures
and discharge velocities are limited to avoid discomfort, as the
jet is located in the occupied zone. European office designs often use chilled ceilings or heated floors to overcome this limitation. Chilled ceilings, at least, are seldom an option in large
open spaces, because of the distance from the occupant and temperature limits to avoid condensation.
FIGURE
VERTICAL DEFLECTION
HORIZONTAL DEFLECTION
THROW
DROP
2 to 4 ft (0.6 to 1.3 m)
20 up
27 ft (8.7 m)
3 ft (0.9 m)
no ceiling
20 up
23 ft (7.4 m)
3 ft (0.9 m)
1 ft (0.3 m)
27 ft (8.7 m)
5 ft (1.6 m)
no ceiling
25 ft (8.1 m)
7 ft (2.3 m)
1.5 ft (0.5 m)
20 up
45
20 ft (6.5 m)
3 ft (0.9 m)
2 to 4 ft (0.6 to 1.3 m)
45
15 ft (4.8 m)
3 ft (0.9 m)
ASHRAE
Journal
55
Practical Guide
comments on return grille acoustics.
The influence of the return air device
on air movement is very subtle. A number of CFD analyses show many arrows
pointing toward the return opening from
great distances away. Those researchers
need to get another model. In the real
world, air movement toward return openings is imperceptible except within a few
inches of the opening.
ASHRAE
Journal
April 1999
Museums &
Renovation
rating usually results. The numerical value that results (the average of the 500, 1000 and 2000 frequency bands) is typically so
low that it has no impact on sound quality in the space. The
resulting R rating, gives no discrimination between units.
Therefore, RC is not recommended or practical as a single number rating for an air terminal.
Large spaces are often very reverberant due to hard surfaces,
geometry etc., so an acoustical consultant should be employed.
The manufacturers traditional assumption that the room will
absorb 10 dB, is usually over conservative. Most large spaces
will have more attenuation than that. More importantly, large
spaces seldom experience near field sounds. More often, sound
is in a reverberant field, and calculations can be convoluted.
ARI-885 suggests the use of the Shultz equation to determine room effect. Unfortunately, this equation assumes some
sound absorption resulting from ceiling tile, furniture or some
other absorbing elements. Often, in large spaces, these are not
present. For this reason, the Shultz equation is not a recommended method in large spaces.
Finally, the return air path is often overlooked as a source of
noise in a space. The quantity of air returned is always nearly
the same as that being supplied, but usually through many fewer
air devices and shorter duct runs.
Summary
As with most HVAC designs common sense rules. Air distribution in large spaces can be summed up with a few simple
axioms:
Cold air falls; hot air rises. The effect is about 1%/F
(2%/C) temperature difference for 75 fpm (0.4 m/s)
terminal velocity.
Use stratification to avoid conditioning spaces without
occupants.
Return air is just as noisy as supply air.
You cannot suck out a match. Returns have little direct
influence on air patterns.
Noise is not always bad. Libraries and other spaces can
benefit from constant background noise.
April 1999
ASHRAE
Journal
57