Extent of the
installation
covered by this
certificate:
Installation of building services and distribution board DB/1 within Nitrate Removal Building
New
An
addition
An
alteration
DESIGN
N/A
N/A
No. of pages
I/We, being the person(s) responsible for the design of the electrical installation (as indicated by my/our signature(s) below), particulars of which are
described above, having exercised reasonable skill and care when carrying out the design, hereby CERTIFY that the design work for which I/we have been
responsible is, to the best of my/our knowledge and belief, in accordance with BS 7671 amended to
(date)
July 2015
except for the departures, if any, detailed as follows:
Details of departures from BS 7671, as amended (Regulations 120.3,133.5):
None
The extent of liabilty of the signatory/signatories is limited to the work described above as the subject of this certificate.
For the DESIGN of the installation:
Signature
Date
Signature
Date
12/10/2016
Name (CAPITALS)
Name (CAPITALS)
**
Designer 2
CONSTRUCTION
I, being the person responsible for the construction of the electrical installation (as indicated by my signature below), particulars of which
are described above, having exercised reasonable skill and care when carrying out the construction, hereby CERTIFY that the construction work
for which I have been responsible is to the best of my knowledge and belief, in accordance with BS 7671, amended to
(date)
July 2015
except for the departures, if any, detailed as follows:
Details of departures from BS 7671, as amended (Regulations 120.3,133.5):
None
The extent of liabilty of the signatory is limited to the work described above as the subject of this certificate.
For the CONSTRUCTION of the installation:
Signature
Date
12/10/2016
Name (CAPITALS)
LEE GAZUR
Constructor
None
The extent of liabilty of the signatory/signatories is limited to the work described above as the subject of this certificate.
For the INSPECTION AND TESTING of the installation:
Signature
Name (CAPITALS)
Date
12/10/2016
LEE GAZUR
Inspector
Signature
Name (CAPITALS)
Date
12/10/2016
Qualified
Supervisor
GARY ALDER
Date
Signature
Name (CAPITALS)
Where the inspection and testing have been carried out by an Approved Contractor, the inspection and testing results are to be reviewed by the registered Qualified Supervisor.
Where the design, the construction, and the inspection and testing have been the responsibilty of one person, the inspection and testing results are to be reviewed by the
registered Qualified Supervisor.
Reviewed by
Date
Qualified
Supervisor
Page 1 of
16
Original
Issued in accordance with British Standard 7671 - Requirements for Electrical Installations by an Approved Contractor or
Conforming Body enrolled with NICEIC, Warwick House,Houghton Hall Park, Houghton Regis,Dunstable,LU5 5ZX
Client /
Address:
ICN4/0411990
ICN4/0411990
DESIGN (2)
NICEIC Enrolment No
(where appropriate)
Address:
Branch number:
(if applicable)
Postcode:
a.c.
1-phase
(2 wire)
1-phase
(3 wire)
TT
3-phase
(3 wire)
IT
Other
d.c.
400
2-pole
Nominal
frequency, f
50
Prospective fault
current, I
3-pole
3-phase
(4 wire)
Nominal U
Voltage(s):
2-phase
(3 wire)
TN-C
TN-S
TN-C-S
Original
DESIGN (1)
other
3.06
0.07
Number of
sources
230
Hz
Notes:
(1) by enquiry
kA
(2) by enquiry or by
measurement
BS(EN) 88-2
Type
Gg
Rated current 400
Short-circuit
80
capacity
kA
Confirmation of
supply polarity
Means of Earthing
Distributor's
facility:
Installation
earth electrode:
Type:
(eg rod(s),tape etc)
Electrode
resistance, R:
Location:
Method of
measurement:
()
Main Switch/Switch-Fuse/Circuit-Breaker/RCD
Type:
BS(EN)
No of
Poles
Supply
conductors
material
Supply
conductors
csa
60947-3
4
LIM
LIM
mm
Voltage
rating
Rated
current,I
RCD operating
current, I *
RCD operating
time (at I )*
Rated
delay *
400
400
N/A
mA
N/A
ms
N/A
ms
Maximum
Demand (Load)
400
Protective measures
against electric shock:
Amps
Conductor
material
Conductor
csa
Copper
120
Continuity/
connection verified
mm
Conductor
material
Conductor
csa
Copper
120
Continuity/
connection verified
NEXT INSPECTION **
ADS
None
mm
Bonding of extraneous-conductive-parts ()
Water
installation pipes
Oil
installation pipes
Gas
installation pipes
Lightning
protection
Structural
steel
Other
I/We the designer(s), RECOMMEND that this installation is further inspected and tested after an interval of not more than
5 years
** The proposed date for the next inspection should take into consideration the frequency and quality of maintenance that the installation can
reasonably be expected to receive during its intended life, and the period should be agreed between the designer, installer and other relevant parties.
Where the Approved Contractor responsible for the construction of the electrical installation has also been responsible for the design
and the inspection and testing
of that installation, the 'Particulars of the Organisation(s) responsible for the Electrical Installation' may be recorded only in the section entitled 'CONSTRUCTION'
Where a number of sources are available to supply the installation, and where the data given for the primary source may differ from other sources,
a separate sheet must be provided which identifies the relevant information relating to each additional source.
Page 2 of
16
1.0
1.1
1.2
1.3
1.4
1.5
1.6
2.0
2.1
2.2
2.3
3.0
3.1
3.2
3.3
3.4
4.0
4.1
5.0
5.1
6.0
6.1
6.2
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
LOCATION
DISTRIBUTION EQUIPMENT
Adequacy of working space/accessibility
Security of fixing
Insulation of live parts not damaged during erection
Adequacy / security of barriers
Suitability of enclosures for IP and fire ratings
Enclosures not damaged during installation
Presence and effectiveness of obstacles
Presence of main switch(es), linked where required
Operation of main switch(es) (functional check)
Operation of circuit-breakers and RCDs to prove functionality
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Original
ICN4/0411990
CIRCUITS
Identification of conductors
Cables correctly supported throughout their length
Examination of cables for signs of mechanical damage during
installation
Examination of insulation of live parts, not damaged during erection
N/A
N/A
Page 3 of
16
8.5
8.6
8.7
8.8
8.9
9.2
9.3
9.4
N/A
N/A
N/A
N/A
N/A
Emergency switching/stopping
a) Presence of appropriate devices
N/A
N/A
N/A
N/A
Functional switching
N/A
N/A
N/A
N/A
N/A
N/A
9.1
Isolators
a) Presence and location of appropriate devices
b) Capable of being secured in the OFF position
c) Correct operation verified (functional check)
d) The installation, circuit or part thereof that will be isolated is
clearly identified by location and/or durable marking
e) Warning label posted in situations where live parts cannot be
isolated by the operation of a single device
Original
ICN4/0411990
N/A
N/A
N/A
N/A
12.0 OTHER
All boxes must be completed. '' indicates that an inspection was carried out and that the result was satisfactory. 'N/A' indicates that an inspection
was not applicable to the particular installation.
* Where the electrical work to which this certificate relates includes the installation of a fire alarm system and/or an emergency lighting system (or a part
of such systems) , this electrical safety certificate should be accompanied by the particular certificate(s) for the system(s).
This certificate is based on the model shown in Appendix 6 of BS7671
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright
Certsure LLP (January 2015)
Page 4 of
16
CIRCUIT DETAILS
Type: 88-2
BS(EN)
DB/1 Supply
3C
Circuit
conductors: csa
Live
cpc
(mm)
(mm)
(s)
50
SWA
Max. disconnection
time permitted
by BS 7671
Number of
points served
Reference
method
Circuit number
and line
Type of wiring
(see code below)
Circuit designation
Rating: 100
Nominal 400
voltage:
BS (EN)
88-2
N/A
mA
Maximum
permitted by BS 7671
No of
phases: 3
Associated N/A
RCD (if any): BS(EN)
RCD No N/A
A
of poles:
RCD
Operating
current, I
Distribution
board designation:
Supply to distribution
board is from:
Short-circuit
capacity
Nitrate Building
Rating
Location of
distribution board:
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*
Type
(A)
(kA)
(mA)
Gg
63
80
N/A
()
0.62
Mineralinsulated
cables
Page 5 of
* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
16
Original
ICN4/0411990
Yes
N/A
ms
Insulation
resistance
Multi- ALP005
function
At 5I
N/A
ms
Continuity
Other
I 3.8
Circuit number
and line
RCD
At I
0.13
3C
kA
Operating times
of associated
RCD (if any)
Circuit impedances
()
Ring final circuits only
(measured end to end)
Insulation resistance
All circuits
(At least one column
to be completed)
Line/Line
Polarity
Maximum
measured earth
fault loop
impedance,
r
(Line)
r
(Neutral)
r
(cpc)
R + R
(M)
(M)
(M)
(M)
()
()
N/A
N/A
N/A
0.3
N/A
>299
>299
>299
>299
0.16
Original
RCD operating
times
(if applicable)
Test
button
operation
(ms)
(ms)
()
N/A
N/A
at I
at 5I
* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.
TESTED BY
Signature:
Position:
Approved Electrician
Date of
testing:
12/10/2016
Page 6 of
Name:
(CAPITALS)
LEE GAZUR
ICN4/0411990
16
CIRCUIT DETAILS
Location of
distribution board:
Nitrate Building
Distribution
board designation:
DB1
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*
Supply to distribution
board is from:
No of
phases: 3
Associated N/A
RCD (if any): BS(EN)
RCD No N/A
A
of poles:
Nitrate MCC/3C
Type: 88-2
BS(EN)
N/A
mA
Operating
current, I
(mm)
(mm)
(s)
(A)
(kA)
(mA)
1/L1
Internal lights
13
1.5
1.5
0.4
60898
10
10
N/A
3.49
1/L2
External lights
1.5
1.5
0.4
60898
10
10
N/A
3.49
1/L3
Heater 1
2.5
2.5
0.4
60898
16
10
N/A
1.09
2/L1
Heater 2
2.5
2.5
0.4
60898
16
10
N/A
1.09
2/L2
Heater 3
2.5
2.5
0.4
60898
16
10
N/A
1.09
2/L3
Heater 4
2.5
2.5
0.4
60898
16
10
N/A
1.09
3/L1
110V transformer 1
2.5
2.5
0.4
60898
20
10
N/A
1.75
3/L2
Mess Room DB
10
10
0.4
60898
40
10
N/A
0.87
3/L3
110V transformer 2
2.5
2.5
60898
20
10
N/A
1.75
4/L1
Fire alarm
1.5
1.5
0.4
60898
10
N/A
5.82
4/L2
Security panel
2.5
2.5
0.4
60898
10
10
N/A
3.49
4/L3
Shower
0.4
60898
20
10
N/A
1.75
5TP
Spare
6TP
Spare
7TP
Spare
8TP
Spare
Reference
method
Short-circuit
capacity
RCD
Rating
BS (EN)
Type
Circuit
conductors: csa
Live
cpc
Max. disconnection
time permitted
by BS 7671
Number of
points served
Circuit number
and line
Type of wiring
(see code below)
Circuit designation
Rating: 63
Nominal 400
voltage:
Maximum
permitted by BS 7671
()
Mineralinsulated
cables
Page 7 of
* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
16
Original
ICN4/0411990
Yes
RCD
At I
N/A
ms
Insulation
resistance
Multi- ALP005
function
At 5I
N/A
ms
Continuity
Other
0.25
I 1.73
Circuit number
and line
kA
Operating times
of associated
RCD (if any)
Circuit impedances
()
Ring final circuits only
(measured end to end)
Insulation resistance
All circuits
(At least one column
to be completed)
Line/Line
Polarity
Maximum
measured earth
fault loop
impedance,
Original
RCD operating
times
(if applicable)
Test
button
operation
(ms)
(ms)
()
N/A
N/A
at I
at 5I
r
(Line)
r
(Neutral)
r
(cpc)
R + R
(M)
(M)
(M)
(M)
()
()
1/L1
N/A
N/A
N/A
0.58
N/A
N/A
>299
>299
>299
0.83
1/L2
N/A
N/A
N/A
2.48
N/A
N/A
>299
>299
>299
0.48
N/A
N/A
1/L3
N/A
N/A
N/A
1.86
N/A
N/A
>299
>299
>299
0.62
N/A
N/A
2/L1
N/A
N/A
N/A
0.36
N/A
N/A
>299
>299
>299
0.73
N/A
N/A
2/L2
N/A
N/A
N/A
0.32
N/A
N/A
>299
>299
>299
0.42
N/A
N/A
2/L3
N/A
N/A
N/A
0.20
N/A
N/A
>299
>299
>299
0.43
N/A
N/A
3/L1
N/A
N/A
N/A
0.14
N/A
N/A
>299
>299
>299
0.66
N/A
N/A
3/L2
N/A
N/A
N/A
0.16
N/A
N/A
>299
>299
>299
0.38
N/A
N/A
3/L3
N/A
N/A
N/A
0.22
N/A
N/A
>299
>299
>299
0.57
N/A
N/A
4/L1
N/A
N/A
N/A
0.17
N/A
N/A
>299
>299
>299
0.60
N/A
N/A
4/L2
N/A
N/A
N/A
0.35
N/A
N/A
>299
>299
>299
0.48
N/A
N/A
4/L3
5TP
6TP
7TP
8TP
* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.
TESTED BY
Signature:
Position:
Approved Electrician
Date of
testing:
12/10/2016
Page 8 of
Name:
(CAPITALS)
LEE GAZUR
ICN4/0411990
16
CIRCUIT DETAILS
Type:
BS(EN)
13TP
Circuit
conductors: csa
Live
cpc
(mm)
(mm)
(s)
50
SWA
BS (EN)
88
Max. disconnection
time permitted
by BS 7671
Reference
method
Circuit number
and line
Type of wiring
(see code below)
Circuit designation
Number of
points served
Rating:
Nominal
voltage:
mA
Maximum
permitted by BS 7671
No of
phases:
Associated
RCD (if any): BS(EN)
RCD No
A
of poles:
RCD
Operating
current, I
Distribution
board designation:
Supply to distribution
board is from:
Short-circuit
capacity
Rating
Location of
distribution board:
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*
Type
(A)
(kA)
(mA)
100
80
N/A
()
0.34
Mineralinsulated
cables
Page 9 of
* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
16
Original
ICN4/0411990
kA
Operating times
of associated
RCD (if any)
Circuit number
and line
RCD
At I
ms
Insulation
resistance
Multi- ALP005
function
At 5I
ms
Continuity
Other
13TP
N/A
Circuit impedances
()
Ring final circuits only
(measured end to end)
Original
Insulation resistance
All circuits
(At least one column
to be completed)
Line/Line
Polarity
Maximum
measured earth
fault loop
impedance,
r
(Line)
r
(Neutral)
r
(cpc)
R + R
(M)
(M)
(M)
(M)
()
()
N/A
N/A
N/A
0.07
N/A
>200
>200
>200
>200
0.14
RCD operating
times
(if applicable)
Test
button
operation
(ms)
(ms)
()
N/A
N/A
at I
at 5I
* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.
TESTED BY
Signature:
Position:
Approved Electrician
Date of
testing:
01/11/2016
Page 10 of
Name:
(CAPITALS)
LEE GAZUR
ICN4/0411990
16
CIRCUIT DETAILS
Location of
distribution board:
Nitrate Building
Distribution
board designation:
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*
Supply to distribution
board is from:
No of
phases: 3
Associated N/A
RCD (if any): BS(EN)
RCD No N/A
A
of poles:
Type: 88-2
BS(EN)
N/A
mA
Operating
current, I
(mm)
(mm)
(s)
(A)
(kA)
(mA)
2A
10
10
BS88
50
80
N/A
1.04
2B
10
10
BS88
50
80
N/A
1.04
3C
DB1
50
50
88
80
80
N/A
0.57
3D
DB2
50
50
88
80
80
N/A
0.57
4A
2.5
2.5
0.4
88
80
N/A
8.52
4B
2.5
2.5
0.4
88
80
N/A
8.52
4C
2.5
2.5
0.4
88
80
N/A
8.52
4D
2.5
2.5
0.4
88
80
N/A
8.52
4F
2.5
2.5
0.4
88
10
80
N/A
5.11
3B
2.5
2.5
0.4
88
32
80
N/A
1.04
Page 11 of
16
Reference
method
Short-circuit
capacity
RCD
Rating
BS (EN)
Type
Circuit
conductors: csa
Live
cpc
Max. disconnection
time permitted
by BS 7671
Number of
points served
Circuit number
and line
Type of wiring
(see code below)
Circuit designation
Rating: 100
Nominal 400
voltage:
Maximum
permitted by BS 7671
()
Mineralinsulated
cables
* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Original
ICN4/0411990
Yes
0.14
I 3.27
kA
Operating times
of associated
RCD (if any)
RCD
At I
N/A
ms
Insulation
resistance
Multi- ALP005
function
At 5I
N/A
ms
Continuity
Other
Circuit number
and line
N/A
Circuit impedances
()
Ring final circuits only
(measured end to end)
Original
Insulation resistance
All circuits
(At least one column
to be completed)
Line/Line
Polarity
Maximum
measured earth
fault loop
impedance,
RCD operating
times
(if applicable)
Test
button
operation
(ms)
(ms)
()
N/A
N/A
at I
at 5I
r
(Line)
r
(Neutral)
r
(cpc)
R + R
(M)
(M)
(M)
(M)
()
()
2A
N/A
N/A
N/A
0.25
N/A
>999
N/A
>999
N/A
0.39
2B
N/A
N/A
N/A
0.25
N/A
>999
N/A
>999
N/A
0.39
N/A
N/A
3C
N/A
N/A
N/A
0.11
N/A
>999
>999
>999
>999
0.25
N/A
N/A
3D
N/A
N/A
N/A
0.12
N/A
>999
>999
>999
>999
0.26
N/A
N/A
4A
N/A
N/A
N/A
0.47
N/A
>999
N/A
>999
N/A
0.61
N/A
N/A
4B
N/A
N/A
N/A
0.41
N/A
>999
N/A
>999
N/A
0.54
N/A
N/A
4C
N/A
N/A
N/A
0.40
N/A
>999
N/A
>999
N/A
0.53
N/A
N/A
4D
N/A
N/A
N/A
0.40
N/A
>999
N/A
>999
N/A
0.53
N/A
N/A
4F
N/A
N/A
N/A
0.40
N/A
>999
N/A
>999
N/A
0.53
N/A
N/A
3B
N/A
N/A
N/A
0.29
N/A
>999
>999
>999
>999
0.42
N/A
N/A
* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.
TESTED BY
Signature:
Position:
Approved Electrician
Date of
testing:
01/11/2016
Page 12 of
Name:
(CAPITALS)
LEE GAZUR
ICN4/0411990
16
CIRCUIT DETAILS
Type: 88-2
BS(EN)
TP6
Circuit
conductors: csa
Live
cpc
(mm)
(mm)
(s)
16
SWA
Max. disconnection
time permitted
by BS 7671
Number of
points served
Reference
method
Circuit number
and line
Type of wiring
(see code below)
Circuit designation
Rating: 63
Nominal 400
voltage:
BS (EN)
60898
N/A
mA
Maximum
permitted by BS 7671
DB2
No of
phases: 3
Associated N/A
RCD (if any): BS(EN)
RCD No N/A
A
of poles:
Nitrate MCC 3D
RCD
Operating
current, I
Distribution
board designation:
Supply to distribution
board is from:
Short-circuit
capacity
Nitrate Building
Rating
Location of
distribution board:
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*
Type
(A)
(kA)
(mA)
32
10
N/A
1.10
Page 13 of
16
()
Mineralinsulated
cables
* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Original
ICN4/0411990
Yes
0.26
I 1.81
kA
Operating times
of associated
RCD (if any)
Circuit number
and line
RCD
At I
N/A
ms
Insulation
resistance
Multi- ALP005
function
At 5I
N/A
ms
Continuity
Other
TP6
N/A
Circuit impedances
()
Ring final circuits only
(measured end to end)
Original
Insulation resistance
All circuits
(At least one column
to be completed)
Line/Line
Polarity
Maximum
measured earth
fault loop
impedance,
r
(Line)
r
(Neutral)
r
(cpc)
R + R
(M)
(M)
(M)
(M)
()
()
N/A
N/A
N/A
0.83
N/A
>200
>200
>200
>200
1.09
RCD operating
times
(if applicable)
Test
button
operation
(ms)
(ms)
()
N/A
N/A
at I
at 5I
* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.
TESTED BY
Signature:
Position:
Approved Electrician
Date of
testing:
01/11/2016
Page 14 of
Name:
(CAPITALS)
LEE GAZUR
ICN4/0411990
16
CIRCUIT DETAILS
Type: 88
BS(EN)
Circuit
conductors: csa
Live
cpc
(mm)
(mm)
(s)
Nominal 400
voltage:
N/A
mA
(A)
(kA)
(mA)
()
Max. disconnection
time permitted
by BS 7671
Number of
points served
Reference
method
Circuit number
and line
Type of wiring
(see code below)
Circuit designation
Rating: 32
No of
phases: 3
Associated N/A
RCD (if any): BS(EN)
RCD No N/A
A
of poles:
Maximum
permitted by BS 7671
Nitrate MCC-3B
Operating
current, I
Distribution
board designation:
Supply to distribution
board is from:
Short-circuit
capacity
Nitrate Building
Rating
Location of
distribution board:
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*
BS (EN)
Type
RCD
1L1}
1L2}
2.5
2.5
0.4
MCB/OL
0.4
N/A
N/A
2.5
2.5
0.4
MCB/OL
N/A
N/A
1L3}
2L1}
2L2}
2L3}
Mineralinsulated
cables
Page 15 of
* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
16
Original
ICN4/0411990
Yes
0.42
I 0.952
kA
Operating times
of associated
RCD (if any)
RCD
At I
N/A
ms
Insulation
resistance
Multifunction
At 5I
N/A
ms
Continuity
Other
Circuit number
and line
N/A
Circuit impedances
()
Ring final circuits only
(measured end to end)
Original
Insulation resistance
All circuits
(At least one column
to be completed)
Line/Line
Polarity
Maximum
measured earth
fault loop
impedance,
RCD operating
times
(if applicable)
Test
button
operation
(ms)
(ms)
()
0.59
N/A
N/A
0.57
N/A
N/A
r
(Line)
r
(Neutral)
r
(cpc)
R + R
(M)
(M)
(M)
(M)
()
()
N/A
N/A
N/A
0.17
N/A
>999
N/A
>999
N/A
N/A
N/A
N/A
0.15
N/A
>999
N/A
>999
N/A
at I
at 5I
1L1}
1L2}
1L3}
2L1}
2L2}
2L3}
* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.
TESTED BY
Signature:
Position:
Approved Electrician
Date of
testing:
01/11/2016
Page 16 of
Name:
(CAPITALS)
LEE GAZUR
ICN4/0411990
16