You are on page 1of 11

<<Contents>> <<Index>>

General
Specifications

R3

Integrated Production Control


System CENTUM CS 3000
System Overview (Vnet/IP Edition)

GS 33P01B10-31E

GENERAL
Vnet/IP is a control network with high reliability and quick response and achieves steady response with little delay even
under heavy load. Using general-purpose network equipment conforming to IEEE802.3 and UDP/IP standards, it realizes
open-based communications. Vnet/IP can connect to a Vnet system with a Vnet router. This GS provides the system
specifications, system configuration equipment, and network specifications for CENTUM CS 3000 Systems with Vnet/IP.

SYSTEM CONFIGURATION
Vnet/IP domain
Boundary router
Open Display
Style Console
HIS

Enclosed
Display Style
Console HIS

Remote
network

PC for builder
HIS Human
Interface Station

L3SW

Bus 2

Bus 1

L2SW

Other
Vnet/IP
domains

L2SW

L2SW
Vnet router

FCS (for FIO)


SNTP Server
GSGW Generic
Subsystem
Gateway Package

APCS Advanced
Process Control
Station

Other
Vnet
domains

ESB bus
Local node
ER bus

(Subsystem)

Remote node

L2SW: Layer 2 switch


L3SW: Layer 3 switch
F01E.EPS

Figure Example of System Configuration

Yokogawa Electric Corporation


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan
Tel.: 81-422-52-5634 Fax.: 81-422-52-9802

GS 33P01B10-31E
Copyright Sep. 2004
2nd Edition Oct.1, 2004

<<Contents>> <<Index>>

SYSTEM COMPONENTS
Human Interface Station (HIS)
An HIS serves as a human interface for operation,
monitoring, and engineering. Software packages installed
in a general-purpose personal computer (an IBM PC/AT
compatible computer, hereinafter referred to as a generalpurpose PC) or in a console HIS, consisting of a generalpurpose PC and Open Display Style Console Assembly,
implement operation and monitoring functions as well as
engineering functions.
Users can install and run operation and monitoring
functions and/or engineering functions in an HIS as
necessary. For connections to the Vnet/IP, a VI701 Control
Bus Interface Card is used. For HIS hardware specifications, see publications GS 33Q06B40-31E and GS
33Q06B50-31E for Human Interface Stations and GS
33Q02C10-31E for Standard Operation and Monitoring
Function.

Field Control Station (FCS)


The FCS performs process control and manages communications with subsystems such as PLCs. Two types of
field control stations for Vnet/IP and FIO are available:
AFV10S:

Field Control Unit (for Vnet/IP, FIO, rackmounted)


AFV10D: Duplexed Field Control Unit (for Vnet/IP,
FIO, rack-mounted)
For FCS hardware specifications, see publication GS
33P06C10-31E.

Advanced Process Control Station (APCS)


An APCS advanced process control station implements
control functions with a general-purpose PC connected to
a Vnet/IP, aimed at improving advanced control and plant
efficiency. For this purpose, install LFS1200 APCS control
functions. Use VI701 Control Bus Interface Card for
connection to Vnet/IP. For more details, see APCS Control
Functions General Specifications (publication GS
33Q03M10-31E).

Generic Subsystem Gateway Package


(GSGW)
With a general-purpose PC connected to a Vnet/IP,
GSGW packages can collect and set data of various types
of subsystems using an OPC DA server. They can easily
collect and set subsystem data without creating dedicated
communications programs.
Install LFS1250 Generic Subsystem Gateway Package.
Use VI701 Control Bus Interface Card for connections to
Vnet/IP. For more details, see publication GS 33Q03P1031E.

Vnet/IP
This is a control bus conforming to the IEEE802.3
standard. Line speed is 1Gbps. A Vnet/IP bus has a dualredundant configuration. On its bus 2, control communications and open-based communications with various
Ethernet standard protocols are provided. At the bus-2
side, data access through an Exaopc OPC interface and
TCP/IP protocol-based communications can be carried
out. For equipment for network connections, including
repeaters, cables, layer 2 switches, layer 3 switches, and
the like, commercially available general-purpose products
are used. For the IP address, IPv4 for Class C private
space addressing is applied. (IPv4 for Class B private
space addressing is also applied.)

Layer 2 Switch
This is a device to connect equipment within the Vnet/IP
domain. The layer 2 switch, unlike a HUB, incorporates
bridge functions to send data to the destination terminal
equipment only; it can, therefore, reduce traffic within its
domain. Commercially available equipment can be used
for a layer 2 switch.

Layer 3 Switch
This switch is used to connect Vnet/IP domains. The layer
3 switch relays a communications frame to another domain
with IP address route control, or routing functions. Select
layer 3 switch hardware capable of relaying communications frames at high speeds. Commercially available
equipment can be used for a layer 3 switch.

Boundary Router
This is a router to connect a Vnet/IP to a remote network.
Connected to the bus-2 side only.

Vnet Router
A Vnet router is a device to connect a Vnet/IP domain and
a Vnet domain for relaying control communications. This
router realizes operation and monitoring of a control
station in one domain from another domain by connecting
the Vnet/IP and Vnet domains. The following product is
available:
AVR10D: Duplexed Vnet Router (for redundant use of
communications and power supply modules)
For the hardware specifications, see publication GS
33P06H10-31E.

SNTP Server
When synchronizing the time of the Vnet/IP station with
UTC (Coordinated Universal Time), the SNTP server is
connected.

Peripherals
Since an HIS supports Microsoft Windows 2000, Windows
XP, Windows 2000 Server or Windows Server 2003,
windows-compatible peripherals, such as printers, can be
used. Consult Yokogawa for more details on peripherals
that can be used with an HIS.

All Rights Reserved. Copyright 2004, Yokogawa Electric Corporation

GS 33P01B10-31E

Oct.1,2004-00

<<Contents>> <<Index>>

SYSTEM SPECIFICATIONS

On the bus-2 side, up to 124 general-use Ethernet devices


(including intelligent network devices) other than listed
above can be connected.

HIS Operation/Monitoring Capacity (Tags)


Number of tags: Up to 100,000 (when using LHS4000,
up to 1,000,000 per system)
Number of tags that can be entered in one HIS: Up to
100,000

Expanded System
A layer 3 switch allows a hierarchical construction with
other Vnet/IP domains. In addition, a Vnet router allows
connection to a system using other Vnets or VL nets.
Existing systems (via an HF-bus or RL-bus) cannot be
directly connected to a Vnet/IP network. These systems
can be connected via a BCV on a Vnet. A hierarchical
connection using a layer 3 switch and a Vnet router allows
a system expansion that exceeds the maximum system
indicated in the previous section. In other words, hierarchical connections of other control systems allow hierarchical
system expansion at the core of CENTUM CS 3000.

Minimum System
A minimum system consists of one HIS and one FCS.

Maximum System
In a CENTUM CS 3000 system, a system within an area
that does not communicate via devices such as routers,
layer 3 switches, or the like is called a domain. Up to 64
Vnet/IP-enabled devices per domain can be connected.
Our Vnet/IP-enabled devices include equipment with
VI701 (control bus interface cards) incorporated in a
general-purpose PC, FCS for Vnet/IP and Vnet routers.
The following lists our specific Vnet/IP-enabled devices:
HIS:
FCS:
APCS:
GSGW:
Exaopc:
PRM:
AVR10D:

Total number of interconnected domains: Up to 16


(Vnet/IP domains + Vnet domains)
Hierarchical connections by Vnet router: Three-level
control bus hierarchy, i.e., three control bus
levels, linked by two bus converters
Number of tag names: Max. of 100,000 (up to 1,000,000
per system when using LHS4000)
Connecting devices: Vnet routers and bus converters
Note that the levels of Vnet/IP domains on an access
router and the levels of Vnet routers are not counted when
hierarchical connections are restricted.

Human Interface Station


Field Control Station
Advanced Process Control Station
Generic Subsystem Gateway Package
OPC Interface Package
Field Communications Server for Plant
Resource Manager
Vnet Router

HIS

HIS

Vnet/IP domain
Layer 3 switch

Vnet router
Vnet domain
BCV-V
Vnet domain

BCV-V
FCS

BCV-V
HF-bus domain

Vnet domain
FCS

EFCS

FCS

Bus converter
(0 level)
One control-bus
level

BCV-V: Bus converter


(Vnet to Vnet)
BCV-H: Bus converter
(HF-bus to Vnet)

One bus-converter level


and one control-bus level
that are connected via
a Vnet router

Two bus-converter levels and


three control-bus levels (max.)
connected via a Vnet router
F02E.EPS

Figure Expanded System Configuration

Vnet/IP domains and Vnet domains can be managed in the same project. In addition, these two domains can be integrated
with a multiple project connection package.

All Rights Reserved. Copyright 2004, Yokogawa Electric Corporation

GS 33P01B10-31E

Oct.1,2004-00

<<Contents>> <<Index>>

Installing of Server PCs


CENTUM CS 3000 realizes many functions using file
sharing function of Windows. The number of PCs to share
files simultaneously is restricted on the Windows Workstation OS. Therefore, when there are 9 or more stations
(HIS, ENG, Exaopc) in one project, the server PC may be
required.
Please count the total station number in one project using
the equations shown below in order to judge whether
server PC is required or not. If the number is eight or
smaller, a server PC is not required. If the number is larger
than 8, consult our sales rep for further examination.
In case of PCs storing master Engineering database
file
When not using Engineering Tool for Foundation Fieldbus
(SSS5700)
Total station number = HIS + ((ENG - 1) x 2) + Exaopc

In case of PCs storing Audit trail data


When using LHS5170 Access Administrator Package, one
PC which is dedicated to the audit trail data must be
prepared. When there are 9 or more stations (ENG,
Recipe Management PC) in one project, the server PC
may be required for storing Audit trail data.
Please count the total station number in one project using
the equations shown below in order to judge whether
server PC is required or not. If the number is eight or
smaller, a server PC is not required. If the number is larger
than 8, consult our sales rep for further examination.
Total station number = ENG + Recipe Management
ENG:

Number of PCs in which Standard Builder


Function (LHS5100 or LHM5100) is
installed.
Recipe Management: Number of PCs in which CS
Batch 3000 Recipe Management package
(LHS5161) is installed

When using Engineering Tool for Foundation Fieldbus


(SSS5700)
Total station number = HIS + ((ENG - 1) x 2) + Exaopc + 2
HIS :

Number of PCs in which Standard Operation


and Monitoring Function (LHS1100 or
LHM1101) is installed
ENG:
Number of PCs in which Standard Builder
Function (LHS5100 or LHM5100) is
installed.
Exaopc:
Number of PCs with Exaopc Interface
Package (NTPF100)
When using Multiple Project Connection Package
(LHS4450), please see the specifications for Multiple
Project Connection Package (GS 33Q02S10-31E).
When using Expanded Test Function (LHS5425), server
PC is always required for storing master Engineering
database.

All Rights Reserved. Copyright 2004, Yokogawa Electric Corporation

GS 33P01B10-31E

Oct.1,2004-00

<<Contents>> <<Index>>

Vnet/IP NETWORK SPECIFICATIONS


The Vnet/IP is a real-time process control network used to connect system components. The Vnet/IP supports two types of
communications: control-bus communications and open communications. The Vnet/IP is always dual-redundant. Usually,
control bus communications are carried out via bus 1. Open communications are carried out via bus 2. If a control communications error occurs at the bus-1 side, control bus communications will be carried out via bus 2. The Vnet/IP uses generalpurpose communications devices for network connection.
HIS ENG
APCS GSGW
Exaopc
1000BASE-T
Max. 100 m

Up to seven levels of
layer 2 switch
Layer 3
switch

Bus 1

Vnet router

Layer 2 switch

Vnet
domain

Vnet/IP
domain

Bus 2
Layer 2 switch
Vnet/IP domain
BCV-H

HF-bus
domain

Wide-area connection
enabled by dedicated-line
connection

Vnet/IP
domain

Layer 3
switch

FFCS-L
F03E.EPS

Figure Network Configuration

Connection within a Domain


In a system used with the Vnet/IP, sections separated by communications devices, such as routers, layer 3 switches, etc.,
are called domains. One domain allows the connection of up to 64 of our Vnet/IP-based devices including the FCS, HIS, etc.
In addition, a maximum of 124 devices, which includes switches, routers, etc., can be connected in configuring a network
with Ethernet devices other than our Vnet/IP-based devices.
Devices in a domain are connected in a star or tree-like fashion at the core of a layer 2 switch. A dual-redundant Vnet/IP bus
is an independent subnet for each line; therefore, a layer 2 switch should be installed in each line. Up to seven levels of layer
2 switch connections can be connected in a domain.

Inter-domain Connection
General-use layer 3 switches allow connections between Vnet/IP domains. Up to 16 domains can be connected.
Up to 15 level (16-hierarchical) connections of Vnet/IP domains can be connected.
Two types of Vnet/IP domain connections are possible: bidirectional and hierarchical connections. In bidirectional connections, HIS's in both domains can perform operation and monitoring of the other domain.
Bidirectional Connection
Both HIS's can perform operation and monitoring of the other domain. Stations in both domains can receive and send FCS
and HIS messages.
Hierarchical Connection
Hierarchical domain relations are established. The HIS of a high-order domain can operate and monitor a low-order domain.
FCS and HIS messages generated in a low-order domain can be accepted by a station in a high-order domain. A Vnet
conversion router allows connection to a system connected to a Vnet. Connection to an existing system connected with a
BCV via a Vnet is also possible.

All Rights Reserved. Copyright 2004, Yokogawa Electric Corporation

GS 33P01B10-31E Sep.13,2004-00

<<Contents>> <<Index>>

Communications Specifications

Network Device Specifications

Control bus communications


Communication Method: Read/write communication,
message communication, and link transmission
Link Transmission Period: 100 msec

Layer 2 switch
Connection Port: 1000BASE-T, full duplex
Connection between switches: 1000BASE-T,
1000BASE-LX with speed, 1 Gbps (1.5
Mpps@64 byte) or faster, full duplex
Auto-Negotiation: Essential

Open communications
Open communications are executed via the bus-2 side.
Connected with commercially available Ethernet
communications devices.
The bandwidth that can be used for open communications via the bus-2 side is up to 300 Mbps.
Transmission Path Specifications
Network Topology: Star formation
Transmission Path Redundancy: Available (control bus
communications only)
Transmission Cable: Unshielded twisted pair (UTP) at
enhanced category 5 or greater.
Connection
Between station
and layer 2
switch
Between layer 2
switches

Cable
Standard
100BASE-TX
(IEEE802.3u)

Speed

Maximum
Distance

100 Mbps 100 m


(*1)

1000BASE-LX
(IEEE802.3z)

1 Gbps

1 Gbps
Between layer 2 1000BASE-T
switch and router (IEEE802.3ab)
1000BASE-LX
(IEEE802.3z)

1 Gbps

Management function
SNMP

Class C private address is used for communications for


control and open communications.
Communications for control
Bus-1 side 192.168.(Domain No.).1 to 129, 254
Bus-2 side 192.168.(Domain No.).1 to 129, 254
Open Communications
Bus-2 Side 192.168.(128 + Domain No.).130 to 253

100 m
5 km
100 m
5 km
T01E.EPS

*1:

Multicast Protocol:
IGMP:
Essential
DVMRP or PIM-DM: Essential

Address Used for Vnet/IP

1 Gbps
1000BASE-T
(IEEE802.3ab)
1 Gbps
1000BASE-T
(IEEE802.3ab)

Layer 3 switch
Connection Port: 1000BASE-T, full duplex
Connection between switches: 1000BASE-T,
1000BASE-LX with speed, 1 Gbps (1.5
Mpps@64 byte) or faster, full duplex
Unicast dynamic routing protocol: RIPv2 (RIPv compatible mode essential)

For Vnet Router and Open communication network.

Communications between Devices


Maximum distance between arbitrary stations: 40 km
Only a couple of media converter between devices can
be connected.

The following addresses are used for multicast communications.


For stations within domains
Bus-1 side 239.192.24.0
Bus-2 side 239.192.24.1
For all domains
Bus-1 side 239.192.24.4
Bus-2 side 239.192.24.5
Class B address is used for the TCP/IP protocol
communications on Vnet/IP.
Make sure that there are no overlaps in IP addresses.

All Rights Reserved. Copyright 2004, Yokogawa Electric Corporation

GS 33P01B10-31E

Oct.1,2004-00

<<Contents>> <<Index>>

I/O COMMUNICATIONS BUS

ER Bus

ESB Bus

Application
An ER bus is a remote I/O communications bus to connect
an FCU or local node unit to a remote node.

Application
An ESB bus is an I/O communications bus that connects
the processing unit of an FCS to a local node.
Communication Specifications
Connectable Devices: Node units (ANB10S and
ANB10D)
Number of Connectable Devices: The number of local
node units that can be connected to an ESB
bus varies according to the database
selected.

Database

Total Number of
Maximum
Local and
Number
Remote
of Local Nodes
Nodes (*1)

Control Function for


Standard Field Control
Unit

Control Function for


Standard Field Control
Unit plus Application
Capacity Expansion
Package

14

Database

Total Number of
Maximum
Local and
Number of
Remote
Remote Nodes
Nodes (*1)

Control Function for


Standard Field Control
Unit

Control Function for


Standard Field Control
Unit plus Application
Capacity Expansion
Package

14

14

T03E.EPS
T02E.EPS

*1:
*2:

Communication Specifications
Connectable Devices: Remote node units (ANR10S,
ANR10D)
Number of ER buses: Max. 4 per FCU
Number of Connectable Devices: The number of remote
node units that can be connected to an ER
bus varies according to the model and
database selected.

The total should not exceed this number.


If local node units are connected to an AFV10S or
AFV10D FCU, ESB Bus Coupler Modules (EC401)
should be installed in slots 7 and 8.

Transmission Path Specifications


Network Topology: Bus formation
Transmission Path Redundancy: Available
Transmission Speed: 128 Mbps
Transmission Cable: Dedicated cable (YCB301)
Transmission Distance: 10 m max.

*1:
*2:

The total should not exceed this number.


Up to eight remote nodes per ER bus can be
connected.

Transmission Path Specifications


Network Topology: Bus formation
Transmission Path Redundancy: Available
Transmission Speed: 10 Mbps
Transmission Cable: Coaxial cable (YCB141, YCB311).
Use YCB147 ER-bus Adapter and YCB149
ER Bus Converter Unit for connecting
YCB141 and YCB311 cables.
Transmission Distance:
Max. 185 m (for YCB141)
Extendable to 2 km when using Ethernet
repeaters (total transmission distance up to
2370 m).
Can use two (a set of) Ethernet repeaters
per ER bus.
When mixing YCB141 and YCB311:
Length of YCB141 + (185/500) x Length of
YCB311  185
Number of bus adapter units: Max. 4 per
segment (*3)
Extendable to 2 km when using generalpurpose Ethernet repeaters.
*3:

All Rights Reserved. Copyright 2004, Yokogawa Electric Corporation

If an ER bus is connected with a repeater, one


segment indicates the area between repeaters.

GS 33P01B10-31E Sep.13,2004-00

<<Contents>> <<Index>>

SOFTWARE
Operation and Monitoring Software
LHS1100
LHS1120

Standard Operation and Monitoring Function


Console HIS Support Package for Enclosed
Display Style
LHS1130 Console HIS Support Package for Open
Display Style
LHS1150 Server for Remote Operation and Monitoring
Function
LHS2411 Exaopc OPC Interface Package (for HIS)
LHS2412 CENTUM Data Access Library
LHS4000 Million Tag Handling Package
LHS4100 Configured Information Reference Package
LHS4150 Recorder Output Package
LHS4190 Line Printer Support Package
LHS4200 Consolidated Historical Message Viewer
(Meeting FDA)
LHS4410 Control Drawing Status Display Package
LHS4420 Logic Chart Status Display Package
LHS4450 Multi Project Connection Package
LHS4510 Expert Trend Viewer Package
LHS4600 Multiple-monitor Package
LHS4700 Advanced Alarm Filter Package
LHS6510 Long-term Data Archive Package
LHS6530 Report Package
LHS6600 CS Batch 3000 Process Management
Package
LHS6710 FCS Data Setting/Acquisition Package
(PICOT)
LHS7110 Web Monitoring Package
For details on the above functions, see the respective
GS's.
The operating system for an HIS is Windows 2000
Professional or Windows XP Professional. If it is necessary to run other third-party software on the HIS, contact
our sales representative to confirm that it is supported.

Engineering Software
LHS5100
LHS5110
LHS5150
LHS5160
LHS5161

Standard Builder Function


Access Control Package
Graphic Builder
CS Batch 3000 Builder
CS Batch 3000 Recipe Management
Package
LHS5170 Access Administrator Package (FDA: 21
CFR Part 11 compliant)
LHS5420 Test Function
LHS5425 Expanded Test Functions
LHS5426 FCS Simulator Package
LHS5427 HIS Simulator Package
LHS5450 Multiple Project Connection Builder
LHS5490 Self-documentation Package
SSS4510 Long-term Trend Historian
SSS4520 Event Viewer
SSS5700 Engineering Tool for Foundation Fieldbus
SSS6700 Device Management Tool for Foundation
Fieldbus
SSS7700 Plant Resource Management Server
SSS7710 Plant Resource Management Client
SSS7720 Field Communications Server
For details on the above functions, see the respective
GS's.

Documentation Software
LHS5459 Electronic Instruction Manual
For details, see publication GS 33Q04N30-31E.

Operation Support Software (for HIS)


NTPS100 Exaplog Event Analysis Package
NTPS200 Exapilot Operation Efficiency Improvement
Package
For details on the above functions, see publication GS
36J06A10-01E, NTPS100 Exaplog Event Analysis
Package and publication GS 36J06B20-01E, NTPS200
Exapilot Operation Efficiency Improvement Package.

Standard FCS Software


LFS1500

Control Function for Standard Field Control


Unit (for Vnet/IP)
LFS1530 Application Capacity Expansion Package
(for AFV10)
For details, see publication GS 33P03B10-31E.

Optional FCS Software


LFS3132 Valve Pattern Monitor Package
LFS8620 Off-site Block Package
For details on these functions, see the respective GS's.

All Rights Reserved. Copyright 2004, Yokogawa Electric Corporation

GS 33P01B10-31E Sep.13,2004-00

<<Contents>> <<Index>>

Subsystem Communication Software


For each subsystem, optional communications software is
available.
LFS2420

FA-M3 Communication Package (for


ALR111, ALR121)
LFS2420 YS Communication Package (for ALR121)
LFS2421 YS Communication Package with Direct
Connection (for ALR121)
LFS2430 MELSEC Communication Package (for
ALE111)
LFS2431 FA-M3 Communication Package (for
ALE111)
LFS2432 DARWIN/DAQSTATION Communication
Package (for ALE111)
LFS2433 PLC-5/SLC500 Communication Package
(for ALE111)
LFS2453 Modbus Communication Package (for
ALE111)
LFS2456 SLC500 Communication Package (for
ALR111, ALR121)
LFS2457 PLC-5 Communication Package (for
ALR111, ALR121)
LFS2542 PROFIBUS Communication Package (for
ALP111)
LFS2610 Foundation Fieldbus Communication
Package (for ALF111)
LFS2710 HART Communication Package (for AAIhhhH)
LFS9153 Modbus Communication Package (for
ALR111, ALR121)
LFS9162 MELSEC-A Communication Package (for
ALR111, ALR121)
For details, see the respective GS's.

All Rights Reserved. Copyright 2004, Yokogawa Electric Corporation

INSTALLATION AND ENVIRONMENTAL CONDITIONS


The installation and environmental conditions for
Yokogawa's devices, except for general-purpose PCs,
General-Purpose Network Device, console HIS's, node
units for FIO and I/O modules, are shown below. For a
general-purpose PC and General-Purpose Network
Device, see their specifications. For an enclosed display
style console HIS, an open display style console HIS, a
node unit for FIO, or an I/O module, see the general
specifications for each device (publications GS 33Q06B4031E, GS 33Q06B50-31E or GS 33Q06Q01-31E).
Ambient Temperature:
5 to 40 C (YAX101)
5 to 35 C (YAX801, YAX211)
0 to 50 C (FCS)
Ambient Humidity:
20 to 80%RH
10 to 90%RH (FCS)
Non-condensation
Temperature Change Rate:
 10 C per hour
Power Requirements:
100 to 120 V AC  10%, 50 or 60 Hz 
3 Hz
220 to 240 V AC, 50 or 60 Hz  3 Hz
24 V DC  10%
Withstanding Voltage:
1,500 V AC for 1 minute (for 100-V or 220-V
AC model)
500 V AC for 1 minute (for 24-V DC model)
Insulation Resistance:
20 M at 500 V DC
10 M at 500 V DC (YAX101, YAX801,
YAX211)
Grounding:
Independent ground of up to 100 
Noise:
Electric Field: Up to 3 V/m (26 MHz to 1 GHz)
Magnetic Field: Up to 30 A/m (AC), 400 A/m (DC)
Static:
Up to 4 kV (direct discharge)
Continuous Vibration:
Displacement amplitude: Up to 0.25 mm (1
to 14 Hz)
Acceleration: Up to 2 m/s2 (14 to 100 Hz)

GS 33P01B10-31E Sep.13,2004-00

10

<<Contents>> <<Index>>

CENTUM CS 3000 Entry Class


The CENTUM CS 3000 Entry Class is available for small-scale systems.

Components and Software


The CENTUM CS 3000 Entry Class uses specific Entry Class packages such as built-in HIS packages. There is no restriction on FCS models.

Operation and Monitoring Software

The following software packages are provided for the Entry Class. Except for the packages listed below, current CS 3000
system operation and monitoring software packages can be used. But, the LHS4000 Million Tag Handling Package cannot
be used in an HIS with the built-in LHM1101 Standard Operation and Monitoring Function.
Operation and Monitoring Software
Entry Class Model

Product

Remarks

LHM1101

Standard Operation and Monitoring Function

Number of operation and monitoring tags :


up to 8000

LHM1150

Server for Remote Operation and Monitoring


Function

LHM4410

Control Drawing Status Display Package

LHM4420

Logic Chart Status Display Package

LHM6600

CS Batch 3000 Process Management


Package

LHM6710

FCS Data Setting/Acquisition Package


(PICOT)

Maximum number of active recipes:


Type A: 4
Type B: 10
Type C: 999

T04E.EPS

Engineering Software
Entry Class Model

Product

Remarks

LHM5100

Standard Builder Function

LHM5150

Test Function

LHM5490

Self-documentation Package

T05E.EPS

All Rights Reserved. Copyright 2004, Yokogawa Electric Corporation

GS 33P01B10-31E Sep.13,2004-00

11

<<Contents>> <<Index>>

REGULATORY COMPLIANCE

TRADEMARKS

The standards to which CENTUM CS 3000 hardware


devices conform are listed below. See the applicable
general specifications to ensure each device's compliance.

CENTUM, Vnet/IP, DARWIN, DAQSTATION and


Exaopc are registered trademarks of Yokogawa Electric
Corporation.
Exaplog and Exapilot are trademarks of Yokogawa
Electric Corporation.
Windows is a registered trademark of Microsoft Corporation in the United States and/or other countries.
Ethernet is a registered trademark of XEROX Corporation.
Modbus is a registered trademark of Schneider Electric
and/or such related companies.
PLC, PLC-5 and SLC500 are trademarks or registered
trademarks of Rockwell Automation, Inc.
MELSEC and MELSEC-A are registered trademarks of
Mitsubishi Electric Corporation.
SYSMAC is a registered trademark of Omron Corporation.
FOUNDATION of FOUNDATION fieldbus is a registered
trademark of Fieldbus Foundation.
Other product and company names appearing in this
document are trademarks or registered trademarks of
their respective holders.

Safety Standards (*1)


[CSA]
CSA C22.2 No. 1010.1 for 100 to 120 V AC and 24 V
DC power supply
[CE Mark] Low Voltage Directive
EN 61010-1 for 220-240 V AC and 24 V DC power
supply (*6)
EMC Conformity Standards (*1)
[CE Mark] EMC Directive
EN 55011 Group 1 Class A for 220-240 V AC and 24 V
DC power supply
EN 61000-6-2 for 220-240 V AC and 24 V DC power
supply (*2)
EN 61000-3-2 for 220-240 V AC power supply (*3)
EN 61000-3-3 for 220-240 V AC power supply (*4)
[C-Tick Mark]
AS/NZS 2064 for 220-240 V AC and 24 V DC power
supply
Standards for Hazardous Location Equipment
[Non-incendive] (*5)
Class I, Division 2, Groups A, B, C and D Temperature
code T4
CSA Standard C22.2 No. 157-92
CSA Standard C22.2 No. 213-M1987
ISA Standard ISA-S12.12 1994
For 100-120 V AC and 24 V DC power supply
[Type n]
EN 50021 1998
[Intrinsic Safety]
EN 50014 1997 +A1 +A2
EN 50020 1994
EN 50021 1999
*1:

*2:
*3:

*4:
*5:

*6:

To conform to safety standards and EMC conformity


standards, install 19-inch rack-mounted devices in a
keyed metallic cabinet.
A lightning arrestor or the like is required to meet
this surge immunity standard.
An external device such as a power unit with
harmonic current neutralizer and an active
harmonics conditioner must be connected to meet
this harmonic current emission standard.
The specified limits of voltage drops across wiring
must be satisfied to meet this standard.
To meet the standard for hazardous location
equipment, 19-inch rack-mounted devices must be
approved by CSA in Canada, or must be installed in
a keyed metallic cabinet approved by non-incendive
regulator in your area.
The analog input side of this equipment is measurement category 1.

For details, see CENTUM CS 3000 Installation Guidance


(TI 33Q01J10-01E).

All Rights Reserved. Copyright 2004, Yokogawa Electric Corporation


Subject to change without notice.

GS 33P01B10-31E

Oct.1,2004-00