Overview
This document contains known issues for each version of NI-Industrial Communications for IEC 61850.
Issue ID
476205
Issue - Changing of data of VISIBLE STRING and OCTET STRING types doesn't trigger GOOSE message in GOOSE control block.
Workaround - N/A.
358387
Issue - Data of user-defined array types which includes another structure array cannot be written/read correctly.
Workaround - N/A.
475863
Issue - The GOOSE message is dropped by the GOOSE control block without warning if the size of GOOSE message exceeds 1517 bytes (the maximum size as defined in
the spec).
Workaround - N/A.
353254
353451
Issue - Reports are only buffered till time-out period of TCP socket in event of connection loss.
Description - According to IEC 61850 specifications, when there is a loss of connection, all reports should be buffered before the connection is re-established. In this version,
reports can only be buffered until the time-out period of TCP socket.
Workaround - In "Commit.vi", set the input parameter of "Generate Report" to TRUE. It will queue the report to be sent out.
1/1