NI-Industrial Communications for IEC 61850 Known Issues

Publish Date: Aug 27, 2014

Overview
This document contains known issues for each version of NI-Industrial Communications for IEC 61850.

Issue ID

NI-Industrial Communications for IEC 61850 14.0 Known Issues

476205

Issue - Changing of data of VISIBLE STRING and OCTET STRING types doesn't trigger GOOSE message in GOOSE control block.
Workaround - N/A.

358387

Issue - Data of user-defined array types which includes another structure array cannot be written/read correctly.
Workaround - N/A.

475863

Issue - The GOOSE message is dropped by the GOOSE control block without warning if the size of GOOSE message exceeds 1517 bytes (the maximum size as defined in
the spec).
Workaround - N/A.

353254

Issue - APC is not supported in control model.


Description - Controllable analogue set point (APC) is not supported in the control model. If a client tries to operate APC, it will get the error message of "invalid object value".
Workaround - N/A.

353451

Issue - Reports are only buffered till time-out period of TCP socket in event of connection loss.
Description - According to IEC 61850 specifications, when there is a loss of connection, all reports should be buffered before the connection is re-established. In this version,
reports can only be buffered until the time-out period of TCP socket.
Workaround - In "Commit.vi", set the input parameter of "Generate Report" to TRUE. It will queue the report to be sent out.