Professional Documents
Culture Documents
Houston, TX 77056-5310
Mailing Address:
P.O. Box 1642
Houston, TX 77251-1642
713.627.5400 main
Algonquin Gas Transmission, LLC, 150 FERC 61,163 (2015) (March 3 Order).
The remaining 97,000 Dth/d of AIM Project capacity will be available when the remaining AIM Project facilities
are placed into service following authorization from the Director of OEP.
3
Algonquin is not requesting an extension for the West Roxbury Meter Station at this time, since this meter station
did not go into service until December 5, 2016.
current solution to reduce noise during operation of this facility.4 Station layouts from the survey
report have been removed from the public version and are marked CONTAINS CRITICAL
ENERGY INFRASTRUCTURE INFORMATIONDO NOT RELEASE and should be
treated as confidential pursuant to Order No. 630, et seq. and is for use by the Commission Staff
only and not to be released to the public.5 Questions pertaining to confidential information may
be submitted to:
Steven E. Hellman
Associate General Counsel
Algonquin Gas Transmission, LLC
P.O. Box 1642
Houston, Texas 77251-1642
Telephone: (713) 627-5215
Facsimile: (713) 386-4405
Email: sehellman@spectraenergy.com
Should you have any questions, please contact me at 713.627.5113.
Sincerely,
Chris Harvey
Chris Harvey
Director, Rates and Certificates
cc:
Algonquin is evaluating additional noise mitigation measures to reduce the noise associated with the Clapboard
Ridge Road Mainline Regulator.
5
Critical Energy Infrastructure Information, Order No. 630, FERC Stats & Regs Regulations Preambles 31,140
(2003), 68 Fed. Reg. 9857 (Mar. 3, 2003), order on rehg, Order No. 630-A, 104 FERC 61,106 (2003), 68 Fed.
Reg. 46456 (Aug. 6, 2003).
HOOVER
& KEITH
INC.
ACOUSTICS &
NOISE CONTROL
ENGINEERING
Subject:
Submitted to:
1.0
INTRODUCTION
In this report, Hoover & Keith Inc. (H&K) summarizes preliminary sound tests conducted on
Nov. 7, 2016 at the Clapboard Ridge Road Mainline Regulator (MLR or Clapboard Ridge Rd
MLR) associated with the Algonquin Incremental Market Project (AIM Project or Project)
after installation and initial in-service of the MLR. The primary purpose of these preliminary
sound tests was to investigate and document the source and character of the noise generated by
the MLR that has caused noise complaints since the MLR has been in-service, and potentially,
evaluate additional noise mitigation measures that could be employed.
2.0
-Page 1-
The West Side 20-Inch Regulator and East Side 16-Inch Regulator includes three (3) regulator
runs, each with a worker/primary pressurecontrol valve (PCV) and a secondary/back-up
PCV, noting that the worker PCV is the valve that typically regulates the gas pressure. The
regulators and some associated upstream and downstream piping for both Regulators are
enclosed inside an acoustically insulated metal building although inlet/outlet headers and other
associated piping are located outside the regulator buildings for both Regulators. The worker
PCVs are Flowserve ball valves that employ a Type Z2 noise attenuator trim/ball. Currently, the
PCVs do not regulate gas pressure to the downstream 30-inch ML (i.e., 20-inch Regulator PCVs
are basically open) since upstream gas pressures have not reached the respective MAOPs. At
times, the pressure in the 30-inch ML has been greater than 674 psig, which resulted in
operation/throttling of the 16-Inch Regulator PCVs.
3.0
4.0
-Page 2-
5.0
Condition(s)
Measd A-Wt.
Reference
Sound Level
Table
Condition A
54 dBA
Table 1
Condition A
82 dBA
Table 1
Condition B
74 dBA
Table 2
Condition C
53 dBA
Table 3
Table A: Summary of Measured Sound Levels on 11/7/16 at the Reported Sound Measurement Positions
during Different Operating Conditions of the West Side 20-Inch Regulator.
Condition A: Flow through Run #1 & #3 (20-In. Reg.) & regulators open; flow through 2 runs for 16-In. Reg.
Condition B: Flow through Run #1 only (20-In. Reg.) & regulator open; flow through 2 runs for 16-In. Reg.
Condition C: Flow through all 3 Runs (20-In. Reg.) & regulators open; flow through 2 runs for 16-In. Reg.
In summary, during the operating condition with flow through Run #1 & Run #3 for the 20-Inch
Regulator (i.e., Condition A), there is a strong 516 Hz tonal noise that radiates from the
upstream and downstream aboveground piping/headers. The source of this 516 Hz tone is
currently unknown although this tonal noise is possibly related to a type of piping resonance
resulting from the piping configuration and/or possibly associated with the Z2 trim of the
Flowserve PCV during higher gas velocities, even though these valves were basically 100% open
during our sound tests. It should be noted that during the operating condition with gas flow only
through Run #1 for the 20-Inch Regulator (i.e., Condition B), there is a different tonal noise
generated (i.e., 813 Hz tonal noise plus harmonics) that is radiated from the piping/headers.
During the operating conditions with gas flow through all 3 runs for the 20-Inch Regulator (i.e.,
Condition C), there is no noticeable tonal noise and only minimum noise radiated from the piping
and headers. The measured sound level difference at Meas. Pos. 2 between Condition A and
Condition C is almost 30 dB. Therefore, as a current solution to reduce noise complaints from
nearby residences, gas flows through all 3 runs for the 20-Inch Regulator.
Because the sound level at the closest NSA(s) were not measured during these recent sound
tests, it is beneficial to estimate (extrapolate) the sound attributable to the MLR at the closest NSA
when comparing the MLR sound level to the FERC sound requirement, and the MLR sound
-Page 3-
contribution was estimated from sound measurement data at Meas. Pos. 1. Table 4 (p. 9) shows
the spreadsheet calculation of the estimated sound level at the closest NSA (i.e., residence
located 220 feet north of the MLR site acoustic center), and a discussion of the method utilized to
calculate the sound contribution of the MLR at this NSA is included in Table 4. It is assumed that
the noise generated by the MLR at other surrounding NSAs will be equal to or lower than the
predicted MLR noise level this closest NSA.
The following Table B summarizes the estimated A-wt. sound level at the closest NSA during
typical operation of the MLR [i.e., gas flow through 2 runs (Run #1 & Run #3) of the West Side 20Inch Regulator] and the resulting Ldn, as calculated from the estimated A-wt. sound level.
Closest NSA and
Type of NSA
Distance and
Direction of NSA from
the MLR Site Center
46.8 dBA
53.2 dBA
Table B: Estimated Sound Level of MLR at the Closest NSA based on Sound Tests at Meas. Pos. 1 (Gas
Flow through 2 Runs of the West Side 20-Inch Regulator & PCVs Open).
In summary, the results indicate that the sound level generated by the Clapboard Ridge Road
MLR during the current operating condition that generates the audible tonal noise at nearby
residences is probably below the sound level requirement (Ldn of 55 dBA) but since the character
of the noise generated by the MLR during specific operating conditions is distinctive and different
than the typical ambient environment, the MLR noise is noticeable and can be disturbing to some
of the surrounding residences.
Currently, additional noise mitigation measures are being evaluated to reduce the noise
associated with the Clapboard Ridge Road MLR. In addition, it is anticipated that another sound
survey will be conducted, probably in January or February (2017), after further acoustical
evaluation and additional noise mitigation measures are employed and during a time frame when
the MLR regulators are actually required to regulate the gas pressure to the 30-inch ML and/or 26inch ML.
-Page 4-
Measurement Set
Meas. Pos.
Description/Location
100 ft. north of the West Side
A-Wt.
63
125
250
500
1000
2000
4000
8000
Level
55
54
52
44
56
44
39
32
28
54
58
59
60
52
85
51
47
39
33
82
63
66
57
50
70
50
46
37
35
67
60
52
52
50
91
59
58
51
41
88
61
57
53
48
71
57
55
47
40
69
60
60
59
55
85
61
53
44
46
82
56
55
56
49
58
62
58
50
40
64
Regulator Bldg.
31.5
header.
Table 1: Algonquin Clapboard Ridge Rd MLR at VS19: Summary of Meas'd Sound Levels [i.e., A-Wt. Sound Levels and
Unweighted O.B. SPLs] as Measured on Nov. 7, 2016 for the Following Operating Conditions:
> West Side 20-Inch Regulator Skid: Flow through Run #1 and Run #3 (PCV for Run #2 having operational issues).
> East Side 16-Inch Regulator Skid: Flow through Run #4 and Run #5 (typical operation of this regulator).
> W. Side 20-Inch Reg. Skid: Inlet Pressure: 623 psig; Outlet Pressure: 620 psig.
> Very little pressure drop (PD) since 20-Inch PCVs open approx. 100% open (PD of 3 psi).
> E. Side 16-Inch Reg. Skid: Inlet Pressure: 621 psig; Outlet Pressure: 620 psig.
> Very little pressure drop since 16-Inch PCVs open approx. 100% open (PD of 1 psi).
> Actual gas flow through each regulator skid unknown: 0.7 Bcfd to 1.4 Bcfd between both regulator skids.
Measurement Set
Meas. Pos.
Description/Location
N. fenceline, 20 ft. north of
A-Wt.
31.5
63
125
250
500
1000
2000
4000
8000
Level
65
57
56
51
57
74
61
51
42
74
72
64
58
58
72
84
84
71
59
88
Table 2: Algonquin Clapboard Ridge Rd MLR at VS19: Summary of Meas'd Sound Levels [i.e., A-Wt. Sound Levels and
Unweighted O.B. SPLs] as Measured on Nov. 7, 2016 for the Following Operating Conditions (i.e., All Flow
through Run #1 of the West Regulator Skid):
> West Side 20-Inch Regulator Skid: All flow through Run #1.
> East Side 16-Inch Regulator Skid: Flow through Run #4 and Run #5 (typical operation of this regulator).
> W. Side 20-Inch Reg. Skid: Inlet Pressure: 670 psig; Outlet Pressure: 663 psig.
> Some pressure drop (PD of 7 psi), noting 20-Inch PCV for Run #1 open approx. 100% open.
> No changes to the operating conditions for the E. Side 16-Inch Regulator Skid.
Measurement Set
Meas. Pos.
Description/Location
N. fenceline, 20 ft. north of
A-Wt.
31.5
63
125
250
500
1000
2000
4000
8000
Level
59
54
54
49
49
49
45
37
33
53
Table 3: Algonquin Clapboard Ridge Rd MLR at VS19: Summary of Meas'd Sound Levels [i.e., A-Wt. Sound Levels and
Unweighted O.B. SPLs] as Measured on Nov. 7, 2016 for the Following Operating Conditions [i.e., Flow
through all 3 Runs (Run #1, #2 & #3) of the West Regulator Skid]:
> West Side 20-Inch Regulator Skid: Flow through all 3 runs (i.e., Run #1, Run #2 & Run #3); PCVs at 100% open.
> W. Side 20-Inch Reg. Skid: Inlet Pressure: 682 psig; Outlet Pressure: 679 psig; very little PD across PCVs.
-Page 8-
Conditions/Factors associated
31.5
63
125
250
500
1000
2000
4000
8000
Level
55
54
52
44
56
44
39
32
28
54
-7
-7
-7
-7
-7
-7
-7
-7
-7
0
0
0
0
0
0
0
0
0
0
0
0
0
-1
0
-1
0
-2
48
47
45
37
49
37
31
24
19
A-Wt.
Resulting/Calculated
Ldn (dBA): Note (5)
46.8
53.2
Table 4: Algonquin Clapboard Ridge Rd MLR: Est'd Sound Contribution of MLR during Current Operating Conditions at
the Closest NSA (i.e., Residence 220 Ft. North of MLR) via Measured Sound Data at Meas. Pos. 1 (i.e., 100 Ft. from
the MLR "Acoustic Site Center"), noting that Sound Tests were not Measured at this Closest NSA during Survey.
Discussion of Method to Calculate MLR Sound Contribution provided Below.
Discussion of Method to Calculate (via Extrapolation) the Sound Contribution due to the MLR:
Note (1): Sound data meas'd at Pos. 1 (220 feet) during operation of the MLR considered an accurate representation
of noise due only to the MLR during current operation (i.e., noise of MLR was dominant noise source).
Note (2): Attenuation due to hemispherical sound propation from 100 feet to the closest NSA (220 ft.). Sound
propagates outwards in all directions from a point source, and the sound energy of a noise source decreases
with increasing distance from the source. In the case of hemispherical sound propagation, the source is located
on a flat continuous plane/surface (e.g., ground), and the sound radiates hemispherically from the source.
Decrease in SPL (hemispherical propagation) from a noise source = 20*log(R2/R1) dB, where R2 is the
distance of receiver from the noise source and "R1" is distance of reference sound level from the source.
For example, hemispherical sound radiation from 100 ft. to 220 ft. = 20*log (220/100) = 6.8 dB.
Note (3): Attenuation due to air absorption: Air absorbs sound energy and the amount of sound absorption ("attenuation") is
dependent on temperature and relative humidity (R.H.) of the air and the frequency of sound. For calculation of air
absorption sound attenuation, "standard day" temperature & R.H. are utilized (e.g., 70% R.H. & 60 deg. F.). In
addition, since the land contour and/or site buildings influenced the MLR noise propagation to nearby receptors,
attenuation due to land contour and shielding was included, if appropriate.
Note (4): Total sound contribution of the MLR calculated be adding measured unweighted O.B. SPLs of the MLR at 100 feet
to the respective O.B. attenuation due to air absorption and hemispherical propagation, to obtain the unweighted
O.B. SPLs at the respective NSAs. Then, overall A-wt. sound level of the MLR at the nearby NSAs was calculated by
logarithmically summing the estimated unweighted O.B. SPLs of the MLR, corrected for A-weighting.
Note (5): The resulting Ldn is calculated by adding 6.4 dB to the calculated A-wt. sound level (i.e., Leq).
file: ProjWord\Algonquin\AIM Project Post Sound Surveys\Meter Stations & MLRs\Clapboard Ridge Rd MLR\H&K Report Summary of Preliminary Tests (11-7-15) at Clapbd Ridge Rd MLV.doc
-Page 9-