Installation Guide

351405.033

PRSB 15kW, 48VDC

Information in this document is subject to change without notice and does not represent a
commitment on the part of Eltek Energy AS.
No part of this document may be reproduced or transmitted in any form or by any means
electronic or mechanical, including photocopying and recording for any purpose without
the explicit written permission of ELTEK Energy.

Copyright : Eltek Energy AS, Norway 2004


NS-EN ISO 9001:1994 Certificate no: 900005Q
NS-EN ISO 14001:1996 Certificate no: 900005E.
This product holds a CE mark and satisfies all requirements covering relevant standards and
directives.

EMC

LVD

EN61000-6-2 Industrial Environment


EN61000-6-3 Residential, Commercial and Light Industry
ETS 300386 v1.3.1 Telecommunication Equipment

LVD73/23/EEC Low Voltage Directive


EN60950 Safety of Technology Equipment

Certificate no: 900005Q

Head Office:

Certificate no: 900005E

Eltek Energy AS
P.O. Box 2340 Strms
N-3003 Drammen
NORWAY
Phone:
(+47) 32 20 32 00
Fax:
(+47) 32 20 32 10
E-Mail
eltek@eltekenergy.com
Internet: http://www.eltekenergy.com

Art. No. 351405.033

Issue 3, 2004 November

Published 2004-11-18
Mfm

Flatpack PRSB 15kW, 48VDC


(Outdoor Site Power Cabinet, Fan Cooled) has part no. CF1032.001

Installation Guide Flatpack PRSB 15kW, 48VDC, Outdoor Cab., Fan Cooled Art. No. 351405.033, v32004-11

Table of Contents
1 DESCRIPTION OF FLATPACK PRSB 15KW, 48VDC

OVERVIEW GENERAL ARRANGEMENT

INPUT AND DISTRIBUTION ARRANGEMENT

AC INPUT TERMINALS

DC DISTRIBUTION AND LVBD DEVICE

MONITORING, CONTROL AND SIGNAL INTERFACE

SYSTEM MONITORING

2 INSTALLATION PROCEDURES

SAFETY PRECAUTIONS

UNPACKING AND MECHANICAL INSTALLATION

ELECTRICAL INSTALLATION

RECTIFIER INSTALLATION MAINS SUPPLY EFFECT BALANCING

11

RECTIFIER INSTALLATION HANDLES AND LOCKING MECHANISM

11

COMMISSIONING

11

3 ALARM RELAY OUTPUTS AND SIGNAL CONNECTIONS

12

CONNECTIONS FOR INTERNAL SYSTEM WIRING

13

CONNECTIONS GMT FUSES

14

4 SPECIFICATIONS FLATPACK PRSB 15KW, 48VDC, FAN COOLED

15

SPECIFICATION

15

FAN OPERATION

15

5 APPENDIX: SCHEMATICS, DRAWINGS, FIGURES, ETC.

16

GENERAL ARRANGEMENT DRAWING

16

SYSTEM SCHEMATIC PRSB 15KW, 48VDC, OUTDOOR CABINET, FAN COOLED

17

ON SITE DOOR REMOVAL OUTDOOR CABINET, FAN COOLED

18

DRILLING TEMPLATE

18

Installation Guide Flatpack PRSB 15kW, 48VDC, Outdoor Cab., Fan Cooled Art. No. 351405.033, v32004-11

Description of Flatpack PRSB 15kW, 48VDC

This Installation Guide contains information about how to install the Flatpack PRSB 15kW,
48VDC system1 , for the outdoor site power cabinet, fan cooled. Please, refer to the systems
Documentation Set (art. 351405.003) for an overview of related user documentation.

Overview General Arrangement


The Flatpack PRSB 15kW, 48VDC is a DC power supply system based on the Flatpack 1500
48V rectifier. The system contains AC termination blocks, DC distribution, Flatpack Power
Rack, Flatpack 1500 rectifier modules and the Flatpack Monitoring and Control Unit (MCU).
The system is designed for cable entry from top and the cabinet size is 770x820x2000mm,
(30.3 x 32.3 x 78.7) (WxDxH).

Heater MCB (AC).

DC Load Distribution:
MCBs, Mains, Alarm and
Signal Terminals

LTE Distribution, MCBs


Optional kit.

Battery strings. The top


three shelves are optional
kits

Air filter
Figure 1
Flatpack
Power Rack System
General Arrangement

PRSB = Power Rack System with Batteries

Installation Guide Flatpack PRSB 15kW, 48VDC, Outdoor Cab., Fan Cooled Art. No. 351405.033, v32004-11

Input and Distribution Arrangement


Cabinet main Protective Earth (PE). Connected
to powercore PE. Positioned in the ceiling
ve DC Load Terminals (BTS MCBs) 2
On top of each load breaker, 25 mm (70 mm2)
ve Battery Terminals
Bus bar, 35 mm2

+ve DC Load Terminals


Common positive bus bar, 70 mm2
+ve Battery Terminals
Common positive bus bar, 70 mm2
DC Earth (TE) terminal, M6
AC Earth (PE) terminal, M6
AC Mains Terminals
Terminals for GMT 15A Load
Fuses, 1.5 mm2
CON 5,2Alarm Terminals
1.5 mm (Front access)

Flatpack 1500 rectifier


modules

MCU Ctrl. Unit, and


CON 4, Monitoring Terminals
(Back MCU)

Figure 2 Location of components in


the Power core. Contains
Distribution and Power Racks

Installation Guide Flatpack PRSB 15kW, 48VDC, Outdoor Cab., Fan Cooled Art. No. 351405.033, v32004-11

AC Input Terminals
The AC terminal block is factory configured for mains supply type: 400VAC, 3 phase and N.
L1-bar
N-bar

L2-bar
L3-bar
N (neutral)
(Terminal for
incoming wire)

L1
(Terminal for
incoming wire)

L2
(Terminal for
incoming wire)
L3
(Terminal for
incoming wire)

Labels on internal wires


(Wires may be reconnected to
match the sites type of AC
mains supply)
Figure 3

AC input terminals, L1, L2, L3 & N, with internal terminal connection bars

AC Input Feed Sizing

An external breaker is
required on all sights. This
should be turned OFF
under all installation.

(Recommended AC Breaker Rating and Min. Wire Size)


18kW
VAC Input

400VAC +N, 3 ph
230VAC, 3 ph

40A C
4x6 mm2 Cu max. 30m
63A C
3x10 mm2 Cu max. 45m

You may reconfigure the AC terminal block for connection of 230VAC, 3 phase supply. To do
so, rewire the internal (blue) wires as described in the table below, and connect the AC
mains supply cable to terminals L1, L2 and L3.
AC Terminal Block
400VAC, 3ph+N

AC Terminal Block
230VAC, 3ph

Internal Wire Connections


Internal Wire
Wire Color
Connected to
(Labeled)
Terminal Bar

Internal Wire Connections


Internal Wire
Wire Color
Connected to
(Labeled)
Terminal Bar

L1,1
N1(L2)
L2,1
N1(L3)
L3,1
N1(L1)
L1,2
N2(L2)
L2,2
N2(L3)

Black
Blue
Black
Blue
Black
Blue
Black
Blue
Black
Blue

L1-bar
N-bar
L2-bar
N-bar
L3-bar
N-bar
L1-bar
N-bar
L2-bar
N-bar
Factory configuration

L1,1
N1(L2)
L2,1
N1(L3)
L3,1
N1(L1)
L1,2
N2(L2)
L2,2
N2(L3)

Black
Blue
Black
Blue
Black
Blue
Black
Blue
Black
Blue

L1-bar
L2-bar
L2-bar
L3-bar
L3-bar
L1-bar
L1-bar
L2-bar
L2-bar
L3-bar
Customized configuration

Installation Guide Flatpack PRSB 15kW, 48VDC, Outdoor Cab., Fan Cooled Art. No. 351405.033, v32004-11

To connect your system to


1 phase from a 230 VACsystem or a 400 VAC + Nsystem connect the input
cables as illustrated in the
table to the right. With
one phase the maximum
amount of rectifiers is 4.
These have to be placed in
position 1,4,7 and 9 in
Figure 4, page 11. The
other positions will not be
usable.

AC Input Connection
1-phase
External Wire Connections

AC configuration in
Terminal Block
400 VAC + N

Input
(230 VAC, 3ph or
400 VAC, 3ph +
N)

400VAC +
N
230VAC

L1
N
L1
L2

L1-terminal
N-terminal
L1-terminal
N-terminal

230 VAC

L1-terminal
L2-terminal
L1-terminal
L2-terminal

1 phase configurations

DC Distribution and LVBD device


The system is configured for negative distribution. The common positive bus bar is located
inside the distribution section; see, page 5. The system is equipped with a Low Voltage
Battery Disconnect (LVBD) device.

Monitoring, Control and Signal Interface


The Flatpack PRSB 15kW, 48VDC is available with basic functionality for monitoring and
control of the system, and is equipped with:

Relay outputs, 6 pcs


Digital inputs, 4 pcs
Symmetry input signals, 2 pcs
(battery string midpoint measurements)
Digital input for external symmetry circuitry

One of the interface boards (104649) is located behind the MCU (with rear access to the
terminals), while the other board (104648) is mounted on top of the MCU (with front access
to the terminals).
Ses Figure 7 Customer connections interface, page 12.

System Monitoring
The Flatpack MCU Monitoring & Control Unit monitors and controls the entire rectifier
system including distribution and batteries, as well as other equipment on site. The unit also
incorporates a communication port for connecting computers via the RS232C interface.
The Flatpack system can be operated and configured locally via the keypad on the MCU
unit, by selecting commands from set-up menus in a hierarchical menu system.
Please refer to the Flatpack MCU Operation Guide for detailed information about system
monitoring.
Remote system monitoring and configuration may also be performed using WinPower Silver
a Windows-based program that runs on a connected PC.
The following configuration tasks require the use of a PC:

Installation settings
System calibration
Battery configuration
Alarm setup
Alarm log retrieval
Site information
Site specific configuration

Installation Guide Flatpack PRSB 15kW, 48VDC, Outdoor Cab., Fan Cooled Art. No. 351405.033, v32004-11

Installation Procedures

This section describes how to install the Flatpack PRSB 15kW, 48VDC. Step-by-step
procedures will guide you through the installation.
For full description of the Flatpack Rectifier and the Flatpack MCU monitoring and control
unit, please refer to the Operation Guides for the respective modules.

Safety Precautions

The equipment described in this manual must only be


installed by authorized personnel, and only operated by
persons who have attended a suitable Eltek Energy
training course.

The equipment represents an energy hazard and failure


to observe this could cause terminal injury and invalidate
our warranty.

There are hazardous voltages inside the rectifier system.


As the rectifier units incorporate large charged
capacitors, it is dangerous to work inside the system
even if the mains supply is disconnected.

Products into which our components are incorporated


have to comply with a number of requirements.
Installation is to be in accordance with the
recommendations herein.

Please read the manual carefully before using the


equipment.

Unpacking and Mechanical Installation


Installation Step

Comments

1 TAKE THE FLATPACK POWER


SYSTEM OUT OF THE PACKAGING

Inspect the unit for any physical or transit


damage, and tighten the screws that connect
conductors. Report any transit damage to Eltek
Energy immediately

2 DRILL HOLES

IN THE GROUND

ACCORDING TO DRILLING
TEMPLATE

3 POSITION THE CABINET

IN THE

REQUIRED LOCATION

4 BOLT THE CABINET


GROUND/PLINTH

TO THE

OK

The Drilling Template with instructions is located


in section 5, page 18.
The floor construction must be capable of
supporting the equipment.
Bolts are not included in the cabinet. If a plinth
is used, refer to Installation Guide, Kit for
Plinth, Doc. No. 351416.033.

Installation Guide Flatpack PRSB 15kW, 48VDC, Outdoor Cab., Fan Cooled Art. No. 351405.033, v32004-11

Electrical Installation
For location of components, see
Figure 2 - page 5, Figure 3 - page 6, and Figure 9.- page 16.

Installation Step

1. EARTH CONNECTIONS

Comments

OK

The AC Earth (PE) and DC Earth (TE) terminals are


mechanically connected to
the cabinet chassis.
The Common Positive Bus bar
is internally cabled to DC
Earth (TE); thus the positive
output of the rectifiers is
connected to ground (TE),
and the negative output
represents the 48Vdc supply
voltage.
If required, you can remove the internal cable that connects
the positive bus bar to local PE.
Switch OFF the AC input power (external MCBs), before
connecting the cable.
Open the clamps that fasten the cable entry rubber gland.
Shape the cable entry rubber gland with a knife to fit the
mains cables, and draw the cables into the top of the
cabinet. It is recommended to do the same with the load
cables at this time. Fasten the cables with strips to the
brackets inside the cabinet. Do not make the cable slot too
wide! Use silicon to make the input hole watertight.

2. AC CONNECTIONS

Connect the AC cables, max. 35sq mm(AWG 2), to the


terminal block in the top of the cabinet as the labels
indicate. Replace the cable entry clamps. Do not power up
the system until the whole installation is complete.
Connect the external AC ground wire to the cabinets main
Protective Earth (PE) terminal. See

Figure 2.- page 5.

Installation Guide Flatpack PRSB 15kW, 48VDC, Outdoor Cab., Fan Cooled Art. No. 351405.033, v32004-11

3. LOAD CONNECTIONS
Alarm
connection

100A

150A

Cable gland

4. GMT FUSE
CONNECTION

5. BATTERY CONNECTIONS

6. POWER UP

Turn OFF the Load/BTS MCBs.


Turn OFF the PRS battery MCBs on the left side of the
cabinet.
Loosen the screws and pull the black cable gland back to
draw the load cables down to the powercore.
The kit includes two copper bridges. One for 100 A (two
pins) and one for 150 A. If the load current is larger than
50 A use the two pin copper bridge. Then the 3rd hole in the
breaker cannot be used. If the load current is larger than
100 A, use the three pin copper bridge. Insert the chosen
copper bridge on to the top of the MCB.
Connect the orange alarm wire to the copper bridges with a
screw if the bridges are used.
Connect the positive cable(s), max 70 mm sq (AWG 2/0), to
the common positive bus bar on the top of the powercore. 2
Connect the negative (-48V) cables, max 25 mm sq each
(AWG 3), to the top of the MCBs or the copper bridges.
Connect the negative (-48V) cables to the MCBs.
Connect the adequate cables, 1,5 mm sq (AWG 15), to the GMT
fuse card according to the table in section 3 page 14
The positive and negative (-48V) battery cables are connected
from factory to the common positive bus bar and to the
battery MCBs. (Excluding additional battery string kits) The
battery temperature sense cable is also pre-wired to CON4,
and temporally fixed to the cabinets wall.
Connect the loose end of the battery cables to the battery
terminals; blue cable to the negative terminal and black
cable to the positive terminal.
Connect all battery intercell links
Place the temperature sensor, located at the end of the
battery temperature sense cable, on top of the topmost
battery string.
Please follow chapters Pre-Start Check and Start-Up
Procedure in manual Commissioning Guide Flatpack 1500 DC
Rectifier Plant, Doc. No. 360006.163.

The bus bar is prepared for connection of cables with lugs or ferrules. M8 bolts are fitted
at delivery.

10 Installation Guide Flatpack PRSB 15kW, 48VDC, Outdoor Cab., Fan Cooled

Art. No. 351405.033, v32004-11

Rectifier Installation Mains Supply Balancing Effect


The Flatpack PRSB system may be expanded to a maximum of 10 Flatpack 1500 rectifiers.
In order to load the AC supply net evenly similar current load from the 3 phases of the
mains supply it is advisable to mount the required number of rectifiers in the following
order:
MCU

Rectifiers

1st Pos
(on L1)

4th Pos
(on L1)

2nd Pos
(on L2)

5th Pos
(on L2)

3rd Pos
(on L3)

6th Pos
(on L3)
9th Pos
(on L1)

7th Pos
(on L1)

10th Pos
(on L2)

8th Pos
(on L2)
Figure 4

Rectifier mounting order to load the mains supply evenly.

When possible, mount an equal number of rectifiers on each phase, L1, L2 and L3.

Rectifier Installation Handles and Locking Mechanism


The Flatpack 1500 rectifier module is equipped with handles that serve two purposes:

Locking the module into position


Open both handles, insert and plug the module into power
shelf. Then lock it into position by rotating the handles upwards
and pushing them firmly home; failure to do so will prevent the
module from making proper contact.
Figure 5

Module with released handles

Pulling the module out


Unlock and release the handles by inserting
a small screwdriver into the upper holes,
thus releasing the spring mechanisms. Do
not use excessive force. The handles will
release and pop out. When both handles are
released, use them to pull the module out.
Do not hold or carry the rectifier by its
handles.
Figure 6

Upper hole to
release the spring
mechanism

Handle in locked position

Releasing the modules handles

Commissioning
For information regarding system commissioning, please read manual Commissioning
Guide Flatpack 1500 DC Rectifier Plant, art. No. 360006.163.

Installation Guide Flatpack PRSB 15kW, 48VDC, Outdoor Cab., Fan Cooled Art. No. 351405.033, v32004-11

11

Alarm Relay Outputs and Signal Connections

The digital inputs are configured as fail-safe, i.e. if the input is


enabled, it will trigger an alarm if the input is open. If several
external devices are going to the same digital input, they
must be connected in series.
The alarm relays are also operated in fail-safe, i.e. the relays
are energized when there is no alarm. The description below
describes the pin out in normal state, i.e. the NO output is
open in normal operation and shorts to the COM output in the
alarm-state.

Input 1
AGND

CON4

External device
alarm state

Alarm relay specification


Nominal switching capacity

2A/30V DC

Maximum switching power

60W (resistive load)

Maximum switching voltage

220V DC

Maximum switching current

2A DC

Interface Customer Connection Pin Out

Interface Card 104648


Located on top of the
MCU Ctrl. Unit

Interface Card 104649


Located back the MCU
Ctrl. Unit
(plug for MCU)

Pin 11
Pin 20

Pin 12
Pin 1

CON2
CON5
CON3

CON4
Pin 1

Pin 1

Pin 10

Pin 20

Terminal

Description

Terminal

Description

CON 2
CON 3

Internal system connections


Internal communication

CON 4
CON 5

Customer connections (digital inputs, symmetry, etc.)


Customer connections (alarm relay outputs)

Figure 7

Customer connections interface and internal terminals. (Max. 1,5 mm , AWG 15)

12 Installation Guide Flatpack PRSB 15kW, 48VDC, Outdoor Cab., Fan Cooled

Art. No. 351405.033, v32004-11

CON 5 Pin Assignment


for basic PCB version, art. No. 104648

Pin
1
2
3
4
5
6
7
8
9

Signal
NC
NO
Com
NC
NO
Com
NC
NO
Com

Function
Relay 6:
Common Alarm

Pin
10
11
12
13
14
15
16
17
18
19
20

Relay 5:
Module Alarm
Relay 4:
Load / Battery Fuse Alarm

Signal
NC
NO
Com
NC
NO
Com
NC
NO
Com

Function
Relay 3:
Low Battery Alarm
Relay 2:
Heat Management
Alarm
Relay 1:
High temp.
(Fan regulation)
(not used)
(not used)
Factory Settings

CON 4 Pin Assignment


for basic PCB version, art. No. 104649

Pin
1
2
3
4
5
6

Signal
+
AGND
+
AGND
+
AGND

Function
Digital Input 1
(Heat management)
Digital Input 2
(programmable)
Digital Input 3
(programmable)

7
8

+
AGND

Digital Input 4
(programmable)

9
10

+
AGND

Battery Symmetry 2
(digital input)

Pin
11
12
13
14
15
16
17
18
19
20

Signal
+

screen

Function
Battery Symmetry 1
(analogue input)
Battery Symmetry 3
(analogue input)
+21V Auxiliary Supply
(for modem or ext.equipment)
(not used)
Battery Temperature Sense
Analogue ground (system ref.)

Connections for Internal system wiring


CON3 is used for rectifier and power shelf communication. CON2 is used for internal system
wiring, which has been wired at the factory. These connectors are not involved in the
system installation and commissioning process. The table below shows the pin assignment
for CON2.
CON 2 Pin Assignment
for basic PCB version, art. No. 104649

Pin
1
2
3
4
5
6
7
8

Signal
+

VDC+
VDC

Function
Shunt 2:
Battery current measurement
Shunt 1:
Battery current measurement
Auxiliary Supply
(for Flatpack MCU)
Voltage Sense
(system signal reference)

Pin
9

Signal
+

10

11

12

Function
Battery Fuse State
(digital input)
Load Fuse State
(digital input)
LVBD control
(Battery Disconnect contactor)
LVLD control
(Load Disconnect contactor)

Installation Guide Flatpack PRSB 15kW, 48VDC, Outdoor Cab., Fan Cooled Art. No. 351405.033, v32004-11

13

Connections for GMT fuses

Pin 16

Pin 1

GMT fuses
Max. 15 A each

Figure 8

GMT fuse card (Max. cable size 1,5 mm sq)

The table below shows the pin assignment for the GMT load fuse card.
Pin Assignment for GMT Fuse
Pin
1
2

Signal
+

Function
GMT fuse 1 (F4)

Pin
9
10

Signal
+

Function
GMT fuse 5 (F8)

3
4

GMT fuse 2 (F5)

11
12

GMT fuse 6 (F9)

5
6

GMT fuse 3 (F6)

13
14

GMT fuse 7 (F10)

7
8

GMT fuse 4 (F7)

15
16

GMT fuse 8 (F11)

14 Installation Guide Flatpack PRSB 15kW, 48VDC, Outdoor Cab., Fan Cooled

Art. No. 351405.033, v32004-11

Specifications Flatpack PRSB 15kW, 48VDC, Fan Cooled

Site Power Outdoor cabinet


SPECIFICATION
Max. number of rectifiers
AC INPUT
Voltage

1 phase 230
rectifiers)
3 phase 208
3 phase 230
3 phase 400

10
VAC (max 4
VAC ( )
VAC ( )
VAC+N ( Y )

Frequency

45 to 66Hz

Maximum
Current

See Flatpack 1500 48VDC


datasheet (241114.100.DS3)

Protection

Soft start
Surge protection (varistors)
Disconnect above 312 VAC

MONITORING
Monitoring Unit
Local operation
Remote
operation
Alarm relays

Flatpack MCU
Menu driven software via
keypads and LCD or PC
(WinPower)
WinPower via modem or Web
NMS via SNMP-agent
6 relays are standard

Visual indications Green LED System ON


Red LED Active alarm(s)
LCD system status
Digital inputs
5 (for monitoring of external
equipment)
Current
Battery current
measurements
Rectifier current
Alarms
Load fuse alarm
Battery fuse alarm
LVD operated
Low output voltage alarms
(2 individual alarm levels)
High output voltage alarms
(2 individual alarm levels)
Battery capacity
Temperature alarm
Symmetry alarm

DC OUTPUT
Voltage

48 VDC

Current

Up to 15 KW 300 Amps

CONNECTIONS
Battery
connections
Load MCB
connections

Battery cable, M8 bolts


Negative distribution, Load
cable, M8 bolts. Common
positive bus bar, M8 bolts
Front access screw terminals

Alarm
connections

DISTRIBUTION OPTIONS
No. of DC
Load breakers
No. of Battery
fuses
No. of Aux.
fuses
Programmable
LVD

Up to 3 x (3pole 63Amps)
Up to 3 x 125 Amps MCBs mount
next to each battery shelves
8 x 10 Amps GMT type
Standard: 1 LVBD (max. 400 Amps)

OTHER SPECIFICATIONS
Isolation
Operating temp
Storage temp
Dimensions
Weight

3.0 KVAC input and output


1.5 KVAC input earth
1.0 KVDC output earth
-40 to +50C (-40 to +122F)
-40 to +85C (-40 to +185F)
770 x 820 x 2000mm (WxDxH)
(30.3 x 32.3 x 78.7)
Approx. 170kg excl. rectifiers and
batteries
Max. 250kg load per battery shelf

APPLICABLE STANDARDS
Electrical safety
EMC

Environment

EN 60950
UL 60950
ETSI EN 300 386 V.1.3.1
(telecommunication network)
EN 61000-6-3
(emission, light industry)
EN 61000-6-2
(immunity, industry)
ETSI EN 300 019-2
ETSI EN 300 132-2

Fan operation
The fan runs as soon as the temperature in the cabinet passes 25oC and the fan MCB is
switched on. The fan speed adjuster is pre installed and factory set to the right speed,
which is a bit slower than full speed. It shall not be set again.

Installation Guide Flatpack PRSB 15kW, 48VDC, Outdoor Cab., Fan Cooled Art. No. 351405.033, v32004-11

15

Appendix: Schematics, Drawings, Figures, etc.


General Arrangement drawing

See also
Figure 2, page 5, for more detailed information about DC distribution.

Main Protective Earth (PE)

Heater MCB (AC)


DC Distribution, Alarm,
AC Terminals, etc.
Rectifiers

LTE Fuses
MCBs

Battery MCB
FB4

Battery MCB
FB3
Battery MCB
FB2
Battery MCB
FB1

Figure 9

General Arrangement drawing, PRSB 15kW, 48VDC Outdoor Cabinet, Fan Cooled

16 Installation Guide Flatpack PRSB 15kW, 48VDC, Outdoor Cab., Fan Cooled

Art. No. 351405.033, v32004-11

System Schematic PRSB 15kW, 48VDC, Outdoor Cabinet, Fan Cooled

Figure 10 Schematic
drawing, PRSB 15kW, 48VDC
system

Installation Guide Flatpack PRSB 15kW, 48VDC, Outdoor Cab., Fan Cooled Art. No. 351405.033, v32004-11

17

On Site Door Removal Outdoor Cabinet, Fan Cooled

Step Description
1

Disconnect the earth


connection cable on
the bottom of the
door

Lift the door off the


hinges.

When the door is to


be mounted back
on, lift the door
back on to its hinges

Reconnect the earth


connection

Ok

Air filter

Earth
connection

Drilling Template
Figure 11 Top
view of the
cabinets bottom
plate.
700x700 mm
external
dimensions

Holes for mounting


the cabinet to the
ground without a
plinth.

Holes for the


plinth. Factory
drilled

Holes for the


plinth. Factory
drilled

The cabinet
overhangs by 35
mm outside the
plinth on the rear,
on the left hand
and on the right
hand side

18 Installation Guide Flatpack PRSB 15kW, 48VDC, Outdoor Cab., Fan Cooled

Art. No. 351405.033, v32004-11

Installation Guide Flatpack PRSB 15kW, 48VDC, Outdoor Cab., Fan Cooled Art. No. 351405.033, v32004-11

19

Main Office:

Eltek Energy AS
P.O. Box 2340 Strms
N-3003 DRAMMEN
Norway
Phone:
Fax:

47 32 20 32 00
47 32 20 32 10

E-Mail:

eltek@eltek.no

Internet:

www.eltekenergy.com

Art. No. 351405.033


Issue 3, 2004 November
Published 2004-11-18