You are on page 1of 6

Profis Anchor 2.6.

www.hilti.com.sg
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Engineer 360
Collin
|

Page:
Project:
Fastening Point:
Date:

1
12/21/2016

Specifier's comments:

1 Input data
Anchor type and size:

HIT-RE 500 + HIT-V (8.8) M20

Seismic/Filling set or any suitable annular gap filling solution


Effective embedment depth:

hef,opti = 259 mm (hef,limit = 400 mm)

Material:

8.8

Approval No.:

ETA 04/0027

Issued I Valid:

6/26/2013 | 5/16/2018

Proof:

Engineering judgement SOFA BOND - based on ETAG BOND testing

Stand-off installation:

eb = 0 mm (no stand-off); t = 42 mm

Baseplate:

Custom; E = 210000.00 N/mm2; fyk = 265.00 N/mm2; gMs = 1.000


lx x ly x t = 526 mm x 526 mm x 42 mm; (Recommended plate thickness: calculated (42 mm))

Profile:

Pipe; (L x W x T) = 324 mm x 324 mm x 13 mm

Base material:

uncracked concrete, C35/45, fc = 45.00 N/mm2; h = 1000 mm, Temp. short/long: 30/30 C

Installation:

hammer drilled hole, Installation condition: Dry

Reinforcement:

No reinforcement or Reinforcement spacing >= 150 mm (any ) or >= 100 mm ( <= 10 mm)
no longitudinal edge reinforcement

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Profis Anchor 2.6.6

www.hilti.com.sg

Page:
Project:
Fastening Point:
Date:

Engineer 360
Collin

Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

12/21/2016

2 Load case/Resulting anchor forces

y
5

Load case: Design loads


Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor
Tension force
Shear force
Shear force x
1
26.965
10.515
10.500
2
0.000
10.515
10.500
3
0.000
10.515
10.500
4
0.000
10.515
10.500
5
26.965
10.515
10.500
6
57.443
10.515
10.500
7
70.162
10.515
10.500
8
57.443
10.515
10.500
max. concrete compressive strain:
0.50 []
max. concrete compressive stress:
15.11 [N/mm2]
resulting tension force in (x/y)=(-139/0):
238.979 [kN]
resulting compression force in (x/y)=(210/0): 242.079 [kN]

Shear force y
0.563
0.563
0.563
0.563
0.563
0.563
0.563
0.563

x
3
Compression

Tension

8
1

3 Tension load (EOTA TR 029, Section 5.2.2)


Load [kN]
70.162

Capacity [kN]
130.667

Combined pullout-concrete cone failure**

238.979

Concrete cone failure**

238.979
N/A

Steel failure*

Splitting failure**
* most unfavourable anchor

Utilisation bN [%]
54

Status
OK

270.084

89

OK

239.062

100

OK

N/A

N/A

N/A

**anchor group (anchors in tension)

3.1 Steel failure


gM,s
1.500

NRk,s [kN]
196.000

NRd,s [kN]
130.667

NSd [kN]
70.162

3.2 Combined pullout-concrete cone failure


Ap,N [mm2]
638124

A0p,N [mm2]
256000

2
t Rk,ucr,25 [N/mm ]
12.00

scr,Np [mm]
506

ccr,Np [mm]
253

yc
1.061

2
t Rk,ucr [N/mm ]
12.73

k
3.200

y g,Np
1.454

y g,Np
1.243

ec1,N [mm]
33

y ec1,Np
0.884

ec2,N [mm]
0

y ec2,Np
1.000

y s,Np
1.000

N0Rk,p [kN]
207.104

NRk,p [kN]
567.177

gM,p
2.100

NRd,p [kN]
270.084

NSd [kN]
238.979

cmin [mm]

y re,Np
1.000

3.3 Concrete cone failure


Ac,N [mm2]
1164737

A0c,N [mm2]
603729

ccr,N [mm]
389

scr,N [mm]
777

ec1,N [mm]
33

y ec1,N
0.921

ec2,N [mm]
0

y ec2,N
1.000

y s,N
1.000

k1
10.100

N0Rk,c [kN]
282.408

gM,c
2.100

NRd,c [kN]
239.062

NSd [kN]
238.979

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

y re,N
1.000

Profis Anchor 2.6.6

www.hilti.com.sg

Page:
Project:
Fastening Point:
Date:

Engineer 360
Collin

Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

12/21/2016

4 Shear load (EOTA TR 029, Section 5.2.3)


Load [kN]
10.515

Steel failure (without lever arm)*


Steel failure (with lever arm)*
Pryout failure**

Utilisation bV [%]
14

Status
OK
N/A

N/A

N/A

N/A

84.120

863.113

10

OK

N/A

N/A

N/A

N/A

Concrete edge failure in direction **


* most unfavourable anchor

Capacity [kN]
78.400

**anchor group (relevant anchors)

4.1 Steel failure (without lever arm)


VRk,s [kN]
98.000

gM,s
1.250

VRd,s [kN]
78.400

VSd [kN]
10.515

4.2 Pryout failure (concrete cone relevant)


Ac,N [mm2]
1383865

A0c,N [mm2]
603729

ccr,N [mm]
389

scr,N [mm]
777

k-factor
2.000

ec1,V [mm]
0

y ec1,N
1.000

ec2,V [mm]
0

y ec2,N
1.000

y s,N
1.000

N0Rk,c [kN]
282.408

gM,c,p
1.500

VRd,cp [kN]
863.113

VSd [kN]
84.120

y re,N
1.000

5 Combined tension and shear loads (EOTA TR 029, Section 5.2.4)


Steel failure
bN
1.000

bV
0.134

Utilisation bN,V [%]


95

a
1.000

Status
OK

(bN + bV) / 1.2 1

6 Displacements (highest loaded anchor)


Short term loading:
NSk

51.972 [kN]

dN

0.287 [mm]

VSk

7.789 [kN]

dV

0.312 [mm]

dNV

0.424 [mm]

Long term loading:


NSk

51.972 [kN]

dN

0.575 [mm]

VSk

7.789 [kN]

dV

0.467 [mm]

dNV

0.741 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the baseplate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Profis Anchor 2.6.6

www.hilti.com.sg
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Engineer 360
Collin
|

Page:
Project:
Fastening Point:
Date:

4
12/21/2016

7 Warnings
Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!

Input data and results must be checked for agreement with the
existing conditions and for plausibility!
Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
Characteristic bond resistances depend on short- and long-term temperatures.
Please contact Hilti to check feasibility of HIT-V rod supply.
The design method SOFA assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by filling
the gap with mortar of sufficient compressive strength (e.g. by using the HILTI Seismic/Filling set) or by other suitable means
The compliance with current standards (e.g. EC3) is the responsibility of the user
An SLS-check is not performed for SOFA and has to be provided by the user!

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Profis Anchor 2.6.6

www.hilti.com.sg

Page:
Project:
Fastening Point:
Date:

Engineer 360
Collin

Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

12/21/2016

8 Installation data
Anchor type and size: HIT-RE 500 + HIT-V (8.8) M20
Baseplate, steel: Custom; E = 210000.00 N/mm2; fyk = 265.00 N/mm2
Profile: Pipe; 324 x 324 x 13 mm
Installation torque: 0.150 kNm
Hole diameter in the fixture: df = 22 mm
Hole diameter in the base material: 24 mm
Plate thickness (input): 42 mm
Hole depth in the base material: 259 mm
Recommended plate thickness: calculated (42 mm)
Minimum thickness of the base material: 307 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to instructions for use is required

8.1 Recommended accessories


Drilling
Suitable Rotary Hammer
Properly sized drill bit

Cleaning
Compressed air with required
accessories to blow from the bottom of
the hole
Proper diameter wire brush
y

263

43

263

Setting
Dispenser including cassette and mixer
Seismic/Filling set
Torque wrench

65

263

155

263

155

2
65

43

43

65

155

155

65

43

Coordinates Anchor [mm]


Anchor
1
2
3
4

x
0
155
220
155

y
-220
-155
0
155

c-x
-

c+x
-

c-y
-

c+y
-

Anchor
5
6
7
8

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

x
0
-155
-220
-155

y
220
155
0
-155

c-x
-

c+x
-

c-y
-

c+y
-

Profis Anchor 2.6.6

www.hilti.com.sg
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Engineer 360
Collin
|

Page:
Project:
Fastening Point:
Date:

6
12/21/2016

9 Remarks; Your Cooperation Duties


Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

You might also like