3*11
============7.0
Rating of 11KV/433V Transformer = = 1600 KVA8.0 Percentage Reactance of Transfor
emer = R = 6.25%9.0 Percentage Reactance of the Transformer on R*MBase MVA =R
2 = ---- = 48.83%1.6010.0 Total %Reactance up to 433V bus = R3 = R1+R2 = 53.58%
M*10011.0 Fault Level at 433V bus = F3 = -------- = 23.33 MVAR3F3*100012.0 Maximu
m Short circuit Current at 433V = ---------- = 31108.00 Amperes
3*0.433 ===============