Fault Level Calculation

Author: LJ (contactmail@dkarcade.comfor more details)Case: International Stadium Project,


Kochi
1.0 Rating of 110/11KV at Kaloor KSEB SubStation = =12.5MVA2.0 Percentage React
ance of above transformer = 0.095Considering
Future
expansion
of "one more transforemer, PercentageReactance" =R1% 0.04753.0 Base MVA assum
ed for calculation =M = 12.5MVA4.0 Fault Level at 11KV Bus of KSEB assuming 110K
V M*100as an infinate bus =F1 = ------ = 263.16MVAR15.0 Fault Level at 11KV incomin
g side at proposedSubstation at aite = F1 = 263.16MVAF1*10006.0 Max, Short circuit c
urrent at 11KV = ------- = 13812Amperes

3*11
============7.0
Rating of 11KV/433V Transformer = = 1600 KVA8.0 Percentage Reactance of Transfor
emer = R = 6.25%9.0 Percentage Reactance of the Transformer on R*MBase MVA =R
2 = ---- = 48.83%1.6010.0 Total %Reactance up to 433V bus = R3 = R1+R2 = 53.58%
M*10011.0 Fault Level at 433V bus = F3 = -------- = 23.33 MVAR3F3*100012.0 Maximu
m Short circuit Current at 433V = ---------- = 31108.00 Amperes

3*0.433 ===============