Data Center Cabling Guide

Planning Your Data Center

Version 2

TA B L E O F C O N T E N T S

PA G E

Introduction

Data Center Horizontal Cabling Topology

Topology Number 1:
Centralized with Cross-connect

Topology Number 2:
Partially Centralized (end-of-row) with Inter-connect

Topology Number 3:
Distributed In-cabinet (top-of-rack) Switching

10

The Storage Area Network (SAN)

11

Data Center Cabling Sample Configurations

12

Cabling Sample Number 1:

14

Centralized Cross-connect in a 672 x 672-port HDA


Cable Routing Guidelines

16

Bill of Materials

18

Cabling Sample Number 2:

19

Partially Centralized Inter-connect in a 672 x 672-port HDA


Cable Routing Guidelines

21

Bill of Materials

23

Cabling Sample Number 3:

24

EDA with 96 Copper Ports from HDA and 48 Fiber Ports From SAN
Cable Routing Guidelines

25

Bill of Materials

27

Cabling Sample Number 4:

28

Cross-connect Cabling for a 720-port SAN


Cable Routing Guidelines

30

Bill of Materials

32

Belden Data Center Product Offering

www.belden.com

1.800.BELDEN.1

33

Introduction

Your Data Center is more than a space that simply houses servers and network equipment
it is a system. The term system is defined as a set of interacting or interdependent entities, real
or abstract, forming an integrated whole. Within the Data Center, the various entities that make
up the system work together to protect and manage both current and future equipment, the data
transmitted, and the thousands of connections between servers and switches and the outlying areas
of the network. All of these entities are interrelated and connected by the structured cabling system,
which designers and end-users are striving to design for better scalability, flexibility, manageability,
availability and lower total cost of ownership. Belden understands that designing the Data Center
structured cabling system is a complex and often confusing task with many options to weigh and
consider, and were here to help. That is why weve developed this guide as a living document,
adding more configurations over time.
General Cabling Considerations

Before designing the backbone and horizontal


cabling in your Data Center, there are several
factors to consider:

Scalability
Calculate the required life expectancy of
the cabling infrastructure by determining
current and future requirements for data
transmission between functional areas of the
Data Center. Ensure ample space to support
current and future number of ports, servers
and switches.

Flexibility and Manageability


Clarify how frequently you will need to
make moves, adds and changes, and if you
anticipate needing to reconfigure functional
areas of the Data Center. Also, determine
cabling distances and limitations from
one functional area to another and ensure
ample pathway space to reroute or add
more cabling.

www.belden.com

Availability
Determine required uptime for the Data
Center and establish level of redundancy
for cabling uplinks, power, and cooling.
Determine overall level of security for
equipment in the Data Center.

Total Cost of Ownership


Determine current and future cost per
square foot of the Data Center based on
all scalability, flexibility, manageability
and availability requirements.
Each of these elements will have a role in
determining the design of each of the
functional areas of a Data Center and the
cabling products selected.

1.800.BELDEN.1

Introduction (continued)

Functional Area

The TIA-942 Telecommunications Infrastructure


Standard for Data Centers addresses cabling
infrastructure in the Data Center and defines
specific functional areas to help determine
the placement of cabling, components and
equipment. Following TIA-942 for functional
area layout is the first step in establishing a
well-designed cabling infrastructure for
your Data Center.

Backbone

ER/TR

MDA/HDA
Support Offices

Entrance Room
The entrance room is the location for access
provider equipment, demarcation points and
interface with other campus locations.

Main Distribution Area (MDA)


The MDA houses the main cross-connect
and the core routers and switches for the
corporate LAN.

Horizontal Distribution Area (HDA)

ZDA

EDA

The HDA houses cross-connects and active


equipment (LAN, SAN, KVM switches) for
connecting to the EDA(s).

Zone Distribution Area (ZDA)


Horizontal

The optional ZDA acts as a consolidation


point within the Horizontal Cabling run
between the HDA and EDA(s).

Equipment Distribution Area (EDA)


The EDA is where cabinets and racks
house end equipment (servers) and where
Horizontal Cabling from the HDA is
terminated at patch panels.

www.belden.com

Backbone Cabling and Horizontal Cabling


Backbone Cabling provides connections
between the entrance room, MDA and HDA.
Horizontal Cabling provides connection
between the HDA and EDA, including the ZDA.

1.800.BELDEN.1

Data Center Horizontal Cabling Topologies

To connect the main core routers and switches


in the MDA to the end equipment located in
the EDA(s), cabling can be designed in various
topologies, each with its own benefits and
disadvantages.

Cabling capacity of pathways

In a centralized switching topology, Backbone


Cabling from the MDA runs to switches in
the HDA(s), which connect to the EDA(s) via
Horizontal Cabling. This topology can also
deploy a ZDA within the Horizontal Cabling.
In a distributed topology, the MDA connects
directly to the EDA(s) via Horizontal Cabling,
eliminating the HDA. To determine which
topology is best for your specific Data Center
situation, there are several factors to consider:

Physical space available for

Number of ports deployed in the EDA(s)

Frequency of moves, adds, and changes

to each functional area


Ample pathway capacity must be available
to converge Horizontal Cabling from EDA(s)
to a single HDA.

Primary Entrance
Facility

Access
Providers

Backbone Cable

Small Data Centers may not require HDA(s),


whereas large number of EDA ports may be
more easily managed in an HDA.

patch panels in the HDA


Physical space must be available to locate
several patch panels in close proximity
to switches.

Support Center

TR
Backbone
Cable

Horizontal Cable

MDA

Level of security and protection required


for core switches and servers
The use of a centralized switching topology
in an HDA can limit access to core switches in
the MDA and servers in the EDA(s).

Making frequent moves, adds, and changes


can be more difficult in a distributed
topology where several switches are
spread out in EDA(s).

Offices, Operations Center,


Support Rooms

Backbone Cable

Backbone Cable

HDA

HDA
Horizontal Cable

Distance limitations to reach each

Horizontal Cable

EDA from the MDA


Multiple HDAs may be required to reach
EDA(s) in larger Data Centers.

ZDA

Horizontal Cable

EDA

EDA

Horizontal Cable or
Zone Area Cord

EDA
Computer Room

www.belden.com

1.800.BELDEN.1

Topology Number 1:
Centralized with Cross-connect

the HDA patch panels. The cabling from each


switch in the HDA terminates on patch panels
that mirror the switch ports. Each switch
patch panel (Equipment Field) is then crossconnected to a second patch panel (Cabling
Field) that mirrors patch panel ports
in each EDA.

In this topology, Backbone Cabling from the


MDA connects to switches in the HDA. All
cabling is centralized in one cross-connect
in the HDA and distributed from the HDA to
multiple EDA(s) or rows. This scenario uses a
three-connector channel where Horizontal
Cabling runs from the EDA patch panels to

Cold aisle

Hot aisle

SW

PP1

PP3

PP2

HDA

SVR

EDA

Cold aisle

3connector channel (patch panels in HDA and EDA)

Hot aisle

SW

PP1

PP4

PP3

PP2
PP2

HDA

ZDA

EDA

SVR
SAN

4connector channel (patch panels in the HDA, ZDA and EDA)


Illustration Legend
Distribution Rack

PP1

PP2

PP3

PP4

Patch Panel Rack


Switch Rack

SW
HDA

ZCA

EDA

4connector channel (patch panels in the HDA, ZCA and EDA)

SVR

Patch Cords
Distribution Cables
Fiber Cables
Pigtails

www.belden.com

1.800.BELDEN.1

Topology Number 1:
Centralized with (end-of-row) Cross-connect (continued)

Benefits of Centralized Cross-connect

Centralized Cross-connect with a ZDA

Enables permanent connections to switches

While not widely deployed, a ZDA can be


used in the Horizontal Cabling from the HDA
to the EDA(s). This scenario uses a four-connector
channel where either one or both patch panels
of the cross-connect are located within a ZDA
(interconnect) or a ZCA (cross-connect). The use
of a ZDA means that functional areas can be
easily reconfigured within the Data Center, and
cross-connects can be located in completely
separate areas for maximum
security and cooling efficiency. On the other
hand, the use of a four-connector channel
and ZDA requires the maximum number of
terminations/connectors and patch panels.

so that sensitive ports are never touched.


Improves flexibility and manageability
with all moves, adds, and changes made at
the patch panels in the cross-connect.
Any switch can be connected to any
equipment location.
Centralized cross-connect can be placed
anywhere in the Data Center to reserve
premium cooling space for active equipment.
Optimizes cabinet utilization by reserving
cabinet space for servers.
Keeps equipment secure if necessary.
The cross-connect can use either modular
patch panels or IDC (Insulation Displacement
Connection) blocks.

Disadvantages of
Centralized Cross-connect

May require longer copper cable runs


to EDA(s) in large Data Centers.
Requires a greater number of terminations
and patch panels.
Requires ample pathway space to converge
cabling from EDA(s) to HDA.
Requires more space to accommodate
patch panels.

www.belden.com

Considerations for cabling in the ZDA


include the following:

How many copper and fiber ports


are required in the ZDA?

The performance of minimally compliant


connectivity if horizontal cabling between
ZDA and HDA is less than
15 meters (49 ft).

1.800.BELDEN.1

Topology Number 2:
Partially Centralized with (end-of-row) Inter-connect

In this topology, the Backbone Cabling


from the MDA is connected to switches in
multiple HDA(s) located within an EDA or row,
essentially locating network equipment closer
to the EDA(s). This scenario uses two-connector
channels where Horizontal Cabling runs from
the EDA patch panels to the HDA patch panels.
To connect a new server to the network, the
EDA patch panel port is connected to the
switch port.

SW

Benefits of Partially
Centralized Switching

Minimizes distances of copper cabling


runs in larger Data Centers.
Reduces number of terminations
and patch panels.
Reduces amount of required pathway space.
Patch panels and switches can be located in
adjacent racks/cabinets.

PP2

PP2

Cold aisle

Hot aisle

Cold aisle

SVR
EDA

HDA

Hot aisle

2connector channel (patch panels in the server cabinet)

SW

PP2
SVR

HDA

SAN

EDA
Illustration Legend

1connector channel (patch panels in the HDA only)

Distribution Rack
Patch Panel Rack

SW
HDA

Switch Rack

EDA

Patch Cords
Distribution Cables
Fiber Cables
Pigtails

Point-to-point (no patch panels involved)

www.belden.com

SVR

1.800.BELDEN.1

Topology Number 2:
Partially Centralized with (end-of-row) Inter-connect (continued)

Disadvantages of Partially
Centralized Switching

Reduces security and efficient use of


premium cooling space by eliminating
ability to locate single HDA anywhere in
the Data Center.
Reduces manageability with moves, adds,
and changes made at patch panels in each
row vs. one central location.
Reduces flexibility because any switch
cannot be easily connected to any
equipment location.
Reduces scalability because unused switch
ports in one row cannot be easily allocated
for another equipment row.

Point-to-Point Connection Scenario

The partially centralized topology can also


include a point-to-point connection scenario
where switches are located in the HDA separate
from the servers in the EDA, but no crossconnect or inter-connect is deployed. This option
is the least expensive cabling option as it requires
only long patch cords that connect directly
from the switch to the server, with no patch
panels required. However, the point-to-point
scenario makes for difficult moves, adds, and
changes, and slack management. This scenario
is also a poor return on investment because
new patch cords lengths are required when
a new server is added, and patch cords are
discarded when servers are decommissioned.

One-connector Channel with


Patch Panels Only in the HDA

Another connection scenario for this topology


includes a one-connector channel where patch
panels are located only in the HDA. Switches
connect to patch panels in the HDA, which
connect directly to equipment in the EDA.
This connection scenario may be used in
smaller applications with few equipment
ports, but where isolating sensitive switch
ports is still desired. One benefit is that the
mounting rail in the server enclosures could be
used 100% for servers since no patch panels
are used in the EDA. However the permanent
cabling deployed in the horizontal limits
the flexibility.

www.belden.com

1.800.BELDEN.1

Topology Number 3:
Distributed In-cabinet (top-of-rack) Switching

In this topology, the Backbone Cabling from


the MDA is connected directly to switches
within each cabinet of the EDA, essentially
eliminating the use of an HDA.

SW
HDA/EDA

Benefits of Distributed Topology

Direct patch from switch to serve

Cold aisle

SVR

Reduces cabling complexity.


Illustration Legend

Lowers cabling costs.

Distribution Rack

Reduces amount of required pathway space.


Ideal for situations where one specific area
of the network must be separately and/or
securely controlled.

Hot aisle

Switch Rack
Patch Cords

Potentially better ROI if planning to use


extremely high bandwidth applications in
the near future (40 Gb/s or 100 Gb/s).

Patch Panel Rack

Distribution Cables

Switches

Fiber Cables

Cold aisle

Pigtails

Disadvantages of Distributed Switching

Requires costly switches to support ports

Hot aisle

in each equipment cabinet.

Higher initial investment in


network equipment.

SAN/CORE

Requires touching sensitive switch ports


during moves, adds, and changes.

Reduces manageability and flexibility


with moves, adds, and changes made
within each cabinet.

Reduces scalability because unused switch

More difficult to conduct maintenance on


switches (i.e., firmware updates) since they
are distributed in many locations.

ports in one EDA are not easily allocated for


use in another.
Note: See SAN details on pg. 11

www.belden.com

1.800.BELDEN.1

10

The Storage Area Network (SAN)

As the amount of data and storage required


continues to increase, Data Center managers
are looking to implement faster backup and
retrieval speeds, better scalability to add more
storage, and overall better flexibility and
manageability. As a result, network storage is
now being moved away from other servers to
a separate network of its own, known as the
SAN. The SAN is strictly dedicated to transmitting large amounts of data between servers
and storage devices such as disk arrays, tape
libraries, and optical jukeboxes. This is most
often accomplished using fiber cross-connect
or inter-connect technology for maximum
data transfer rates.
The use of a centralized SAN cross-connect
offers the following benefits:

Enables permanent connections to switches

Cabling Considerations for the SAN

Pre-terminated Solutions

When allocating space and designing cabling


and connectivity for the SAN, there are many
factors and options to consider.

For easy, quick, and reliable deployment and


reconfigurations in the SAN, pre-terminated
solutions are an ideal choice. These connector
modules feature multiple pre-terminated fiber
connectors on one side that transition to one
plug-and-go MPO connector on the other.
Pre-terminated solutions can provide the
following benefits in a SAN environment:

Ensure plenty of space for scalability


by determining the number of servers
connected to the SAN both now and
in the future.

When deciding between a cross-connect


or inter-connect, determine the frequency
of moves, adds, and changes and level
of security required.

When selecting cabling and connector type,


and termination method, determine amount
of bandwidth required, cabling distance
limitations, return loss budget for the
application, and level of expertise to
connectorize and install fiber.

Faster overall deployment.


No fiber connectorization expertise required.
Fast and easy moves, adds, and changes with
plug-and-go application.

Easy slack management and


protection of fibers.

High density for more space and scalability.

so that sensitive ports are never touched.

Improves flexibility and manageability with


all moves, adds, and changes made at the
fiber patch panels in the cross-connect.

Any switch can be connected to any


equipment location.

SAN cross-connect can be placed anywhere


in the Data Center for improved security
with all switch ports mirrored on fiber
patch panels.

www.belden.com

1.800.BELDEN.1

11

Data Center Cabling Sample Configurations

The following Data Center cabling configurations


represent typical layouts often encountered
in Data Centers, but they are not necessarily
connected together within the same Data
Center. The information presented in these
samples is intended to help the designer of the
cabling infrastructure choose the right Belden
products to optimize Data Center scalability,
flexibility, manageability, availability and lower
total cost of ownership. Belden can work with
customers to design alternative configurations
using the same components to address specific
Data Center needs.
The configurations detailed on the following
pages include:
Partially Centralized Inter-connect in a
672-port HDA.
Centralized Cross-connect in a 672 x 672port HDA.
EDA with 96 Copper Ports from the HDA
and 48 Fiber Ports from SAN.
Cross-connect Cabling for a 384 X 720port SAN.
More configurations will be added over time.

www.belden.com

Cable Installation and


Routing Guidelines

Using back-to-back vertical managers with


high-density fingers in the back provides
intuitive routing by better guiding the cables.
A bundle size of 12 cables is the optimum
vertical manager fill ratio. See calculation
tables on the following page for capacity.

Cables should be inserted in a specific order


for proper management:
When cabling enters the rack from
under-floor cable pathways, bundles of
cables intended for the upper patch
panels should be routed first. These
cables should be placed at the bottom
of the channel and then connected.
Layers of bundles are then laid in an
orderly manner on top of each other
with cables connected to patch panels
routed from the upper part to lower
part of the rack.

Managing patch cords from both sides in


a patch panel (ports 1-12 and 13-24)
facilitates patch cord dressing and allows
better visibility to the port labeling.
Whenever possible, populate patch cords in
the patch panels by progressing from the
outer ports toward the center.
Four Simple Rules for Optimum Patch
Cord Management

Cable slack must never be left hanging loose


in the channel. This can cause bunching of
the cords at the bottom.

Always use Velcro ties to guide patch cords


and manage slack.

Always use the shortest cord available for


the connection.

Create patching zones between Cabling


Distribution and Equipment fields.

When cabling enters the rack from


overhead cable pathways, bundles of
cables intended for the lower patch
panels should be routed first. These
cables should be placed at the bottom
of the channel and then connected.
Layers of bundles are then laid in an
orderly manner on top of each other
with cables connected to the patch
panels routed from the lower part to
the top of the rack.

1.800.BELDEN.1

12

Maximum Number of Cables or Patch Cords in


Vertical and Horizontal Managers

The following tables define the maximum


number of copper cables or patch cords that

can be installed in vertical or horizontal cable


managers based on cable type.

Table A - Maximum number of cables in vertical managers

Vertical Manager Size


6
10
12

CAT6A
360
456
720

Beyond CAT6 (4800)


408
576
816

CAT6 (2400)
480
948
1092

Note: All with bundles of 12 cables.

Table B - Maximum number of patch cords in vertical managers

Vertical Manager Size


6
10
12

CAT6A
168
288
432

CAT6+
264
384
552

Note: With the minimum slack left in the channel.

Table C - Maximum number of patch cords in a horizontal manager

Horizontal Manager Size


1U
2U
3U

CAT6A
40
80
120

CAT6+
60
120
180

Note: All cords are passing through, no slack left in the channel

Table D - Maximum number of pigtails in a vertical manager

Vertical Manager Size


6
10
12

www.belden.com

CAT6A
168
288
432

CAT6+
264
384
552

1.800.BELDEN.1

13

Cabling Sample Number 1:


Centralized Cross-connect in a 672 x 672-port HDA

This example demonstrates how to cable a


672 x 672-port HDA using a centralized crossconnect. The switch patch panels (Equipment
Field) located in the center of each rack both
contain 14 24-port patch panels for a total of 672
ports that mirror switch ports. Those patch panels
are then cross-connected to patch panels (Cabling
Field) located in the top and bottom of the racks,
which mirror patch panel ports in each EDA.
HDA Cabling Considerations:

Number of ports in each EDA.


Distance limitation to reach EDAs.
Capacity of pathways converging to HDA.
Capacity to install patch panels close to switches.
Level of security required in HDA.
Frequency of moves, adds, and changes.

www.belden.com

HDA Cross-connect Installation Tips:

HDA Alternatives:

AngleFlex patch panels allow intuitive

Can be assembled in a high-density cabinet

patch cord management and help keep clean


HDA connection fields.
Locating the Equipment Field in the center
of the rack alleviates congestion on
vertical channels.
Configure AngleFlex patch panels with
left/right cable management per installation
guidelines supplied with product.
Avoid too much patch cord slack for optimum
operation. Refer to the table for patch cord
length recommendations.

(XHD84-Series). See Product Offering.


When using the high-density (XHD84 Series)
cabinet, use the center and side extension
kits (XHD8443CXF and XHG8443SXF) to
increase the capacity of the vertical
channels and properly manage patch cords.
See Product Offering.

1.800.BELDEN.1

14

Cabling Sample Number 1:


Centralized Cross-connect in a 672 x 672-port HDA (continued)

Center Vertical Manager


12" Wide

19" Telecom Rack #1

5
6

5
6

5
6

5
6

5
6
5
6
5
6
5
6
5
6

3
4
3
4
3
4
3
4
3
4

1
2
1
2
1
2
1
2
1

5
6

5
6
5
6
5
6
5
6

2
1

3
4

3
4
3
4
3
4
3
4

1
2
1
2
1
2
1
2

37
37

22
22

22
22

21
21

21
21

20
20

20
20

19
19

19
19

18
18

18
18

18
18

18
18

17
17

17
17

17
17

17
17

16
16

16
16

16
16

16
16

15
15

15
15

14
14

14
14

13
13

13
13

12
12

12
12

11
11

11
11

10
10

10
10

5
6

5
6

5
6

5
6

5
6

5
6

5
6

5
6

5
6

5
6

5
6

5
6

5
6

2
1

5
6

5
6

5
6

5
6
5
6
5
6
5
6
5
6
5
6
5
6
5
6
5
6
5
6
5
6
5
6
5
6
5
6
5
6
5
6
5
6
5
6

3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3

5
6

1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2

2
1

3
4

5
6
5
6
5
6
5
6
5
6
5
6
5
6
5
6
5
6
5
6
5
6
5
6
5
6
5

3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3

10
10

01
01

01
01

01
01

01
01

02
02

03
03

02
02

03
03

02
02

03
03

02
02

04
04

03
03

04
04

04
04

05
05

04
04

05
05

05
05

06
06

05
05

06
06

06
06

09
09
2

07
07

06
06

07
07

07
07

08
08

07
07

08
08

09
09

08
08

09
09

08
08

EDA Cabling Field No. 4


7 x 24 Ports 1U Patch Panels

11
11
6

12
12
6

13
13
6

14
14

2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1

19
19

15
15
6

20
20
6

21
21
6

23
23

24
24

25
25

22
22
6

HDA Cabling Field No. 2


14 x 24 Ports 1U Patch Panels

26
26
2

27
27
2

28
28
2

29
29
2

30
30
6

31
31
6

09
09

10
10

11
11

12
12

13
13

32
32
2

14
14

15
15

20
20

21
21

19
19

22
22

23
23

24
24

23
23

23
23

25
25

24
24

24
24

25
25

25
25

26
26

26
26

27
27

26
26

27
27

28
28

28
28

29
29

29
29

30
30

30
30

31
31

32
32

31
31

33
33

32
32

27
27

36
36
2

33
33

33
33

34
34

33
33

34
34

34
34

35
35

34
34

35
35

28
28

EDA Cabling Field No. 2


7 x 24 Ports 1U Patch Panels

38
38

36
36

29
29

445 mm
(17.5 po)

39
39

35
35

30
30

EDA Cabling Field No. 3


7 x 24 Ports 1U Patch Panels

40
40

36
36

31
31

CMS 3U

41
41

35
35

32
32

HDA Cabling Field No. 1


14 x 24 Ports 1U Patch Panels

36
36

Right Side Vertical Manager


6" Wide

42
42
2

37
37

37
37

37
37

38
38

39
39

38
38

38
38

39
39

39
39

EDA Cabling Field No. 1


7 x 24 Ports 1U Patch Panels

40
40

40
40

41
41

40
40

41
41

42
42

41
41

42
42

42
42

43
43

44
44

43
43

45
45

44
44

43
43

45
45

44
44

43
43

45
45

44
44

45
45

Left Side Vertical Manager


6" Wide

19" Telecom Rack #2

Slack Management Spool

Floor

Front View

www.belden.com

1.800.BELDEN.1

15

Cabling Sample Number 1:


Centralized Cross-connect in a 672 x 672-port HDA (continued)

Front Cable Routing Guidelines for 672 x 672 Cross-connect

EDA 1
EDA 2
EDA 3
EDA 4

Upper Left
Left
Right
Left
Right
Left
Right
Left
Right

4 ft
7 ft
7 ft
8 ft
5 ft
7 ft
8 ft
9 ft

HDA 1
Upper Right Lower Left Lower Right Upper Left

7 ft
4 ft
5 ft
7 ft
7 ft
5 ft
6 ft
8 ft

5 ft
7 ft
9 ft
8 ft
4 ft
7 ft
7 ft
7 ft

7 ft
5 ft
8 ft
6 ft
7 ft
4 ft
5 ft
8 ft

7 ft
5 ft
4 ft
7 ft
8 ft
6 ft
5 ft
7 ft

HDA 2
Upper Right Lower Left Lower Right

8 ft
7 ft
7 ft
4 ft
9 ft
8 ft
7 ft
5 ft

8 ft
6 ft
5 ft
7 ft
7 ft
5 ft
4 ft
7 ft

Left Side

Left Side

Right Side

Upper
Left Side

Upper
Right Side

9 ft
8 ft
7 ft
5 ft
8 ft
7 ft
7 ft
4 ft

Right Side

Upper
Right Side

HDA Ca b lin g
Field 1
Upper
Left Side

Right Side Vertical Manager

To

E DA Ca b lin g
Field 2

Upper
Left Side

C
L
From

E DA Ca b lin g
Field 1

Upper
Right Side

HDA Ca b lin g
Field 2
Upper
Left Side

Upper
Right Side

E DA Ca b lin g
Field 3

E DA Ca b lin g
Field 4

Left Side

Left Side

Right Side

Right Side

Left Side Vertical Manager

Typical Patch Cord Path


From EDA Fields
To HDA Most Distant Fields

C
L

Center Vertical Manager

Typical Patch Cord Path


From EDA Fields
To HDA Closest Fields

C
L

Front View
Patch Cord Management

www.belden.com

1.800.BELDEN.1

16

Cabling Sample Number 1:


Centralized Cross-connect in a 672 x 672-port HDA (continued)

Rear Cable Routing Guidelines for 672 x 672 Cross-connect

To EDA Cabinets

168 UTP Pigtails

168 UTP Pigtails

168 UTP Pigtails


336 UTP Pigtails

168 UTP Pigtails


84 UTP Pigtails

ED A C a b l i n g
Field 3
Rear

Left Side Vertical Manager

ED A C a b l i n g
Field 4
Rear

ED A C a b l i n g
Field 1
Rear

84 UTP Pigtails

HDA Cabling
Field 1
Rear

Center Vertical Manager

ED A C a b l i n g
Field 2
Rear

HDA Cabling
Field 2
Rear

84 UTP Pigtails

Right Side Vertical Manager

168 UTP Pigtails

168 UTP Pigtails

To Network Switch

Rear View
Cable Management

www.belden.com

1.800.BELDEN.1

17

Cabling Sample Number 1:


Centralized Cross-connect in a 672 x 672-port HDA (continued)

Belden Bill of Materials for 672 X 672 Cross-connect

Item
Racks, Frames & Cable Management
19" Telecom Rack
Vertical Managers 12"
Vertical Managers 6"
Horizontal Manager with Cover 3U

Description
Aluminum relay rack 19"Wx84"H, #12-24 tapped hole, Black, Knock Down
Combination High/low with front doors, 12"Wx84"H, w 3 Slack Management Spools, Black
Combination High/low with front doors, 6"Wx84"H, Black
19" WX3U, Black

Part Number

Quantities

BHRR194
BHVHL12
BHVHL06
BHH193U

2
1
2
4

Notes

Augmented Category 6 Solution - IBDN System 10GX


Distribution Cable
Augmented Category 6A Cable
Single-ended Patch Cords (Pigtails)
7.6 m (25 ft)
Patch Cords
Cat6A Modular Cord
Cat6A Modular Cord
Cat6A Modular Cord
Cat6A Modular Cord
Cat6A Modular Cord
Cat6A Modular Cord
Patch Panels
HDA Cabling Field
Panels
Keystone Style Modules
EDA Cabling Field
Panels
Keystone Style Modules

10GX12 0061000

672 runs

10GX Pigtail, 4-Pair, 23 AWG Solid, T568B Open, CMR

CA21208025

672

10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 4 ft (1.2 m)


10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 5 ft (1.5 m)
10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 6 ft (1.8 m)
10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 7 ft (2.1 m)
10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 8 ft (2.4 m)
10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 9 ft (2.7 m)

CA21106004
CA21106005
CA21106006
CA21106007
CA21106008
CA21106009

336
168
84
54
20
10

AngleFlex Patch Panel, 1U, 24 ports, Black


10GX KeyConnect Modular Jack, Red

AX103248
AX102285

28
672

AngleFlex Patch Panel, 1U, 24 ports, Black


10GX KeyConnect Modular Jack, Blue

AX103248
AX102268

28
672

10GX12 Nonbonded-Pairs Cable, 4-Pair, 23 AWG UTP, 305 m (1000 ft), Spool, Blue

Length = TBD

Beyond Category 6 Solution - IBDN System 4800LX


Distribution Cable
Enhanced Category 6 Nonbonded-Pairs, Riser
Pig Tails
Cat6 7,6 m (25 ft)
Patch Cords
CAT6+ Modular Cord
CAT6+ Modular Cord
CAT6+ Modular Cord
CAT6+ Modular Cord
CAT6+ Modular Cord
CAT6+ Modular Cord
Patch Panels
HDA Cabling Field
Patch Panels
Keystone Style Modules
EDA Cabling Field
Patch Panels
Keystone Style Modules

4812 D151000

672 runs

GigaFlex CAT6+ Pig Tails, 4 pairs, 23 AWG, T568A/B-open, CMR, Grey, 7.6 m (25 ft)

C601308025

672

CAT6+ Patch Cord, Bonded-Pair, 4-Pair, 24 AWG Solid, T568A/B-T568A/B, CMR, Blue, 4 ft (1.2 m)
CAT6+ Patch Cord, Bonded-Pair, 4-Pair, 24 AWG Solid, T568A/B-T568A/B, CMR, Blue, 5 ft (1.5 m)
CAT6+ Patch Cord, Bonded-Pair, 4-Pair, 24 AWG Solid, T568A/B-T568A/B, CMR, Blue, 6 ft (1.8 m)
CAT6+ Patch Cord, Bonded-Pair, 4-Pair, 24 AWG Solid, T568A/B-T568A/B, CMR, Blue, 7 ft (2.1 m)
CAT6+ Patch Cord, Bonded-Pair, 4-Pair, 24 AWG Solid, T568A/B-T568A/B, CMR, Blue, 8 ft (2.4 m)
CAT6+ Patch Cord, Bonded-Pair, 4-Pair, 24 AWG Solid, T568A/B-T568A/B, CMR, Blue, 9 ft (2.7 m)

C601106004
C601106005
C601106006
C601106007
C601106008
C601106009

336
168
84
54
20
10

AngleFlex Patch Panel, 1U, 24 ports, Black


CAT6+ KeyConnect Modular Jack, Red

AX103248
AX101323

28
672

AngleFlex Patch Panel, 1U, 24 ports, Black


CAT6+ KeyConnect Modular Jack, Blue

AX103248
AX101326

28
672

AX101569

DataTwist 4800 Cable, 4-pair, 23 AWG UTP, 305m (1000 ft) Spool, Blue

Length = TBD

Miscellaneous Accessories
Labeling

www.belden.com

Automated LabelFlex Advanced Software, 1 CD/pack

1.800.BELDEN.1

18

Cabling Sample Number 2:


Partially Centralized Inter-Connect in a 672-port HDA

This example demonstrates how a 672-port


HDA is cabled using a partially centralized
topology with inter-connect. Within this
HDA, two 336-port switches each connect to
fourteen 24-port patch panels via permanent
cabling. From each patch panel, cabling
terminates to patch panels or equipment
in the EDA (not shown).
HDA Cabling Considerations:

Number of ports in each EDA.


Distance limitation to reach EDAs.
Capacity of pathways converging to HDA.
Capacity to install patch panels
close to switches.
Level of security required in HDA.
Frequency of moves, adds, and changes.

www.belden.com

HDA Inter-connect Installation Tips:

HDA Installation Alternatives:

AngleFlex patch panels allow intuitive patch

Can be assembled in a high-density cabinet

cord management and help keep clean HDA


connection fields.
Horizontal managers below and above the
switch increase flexibility for switch access.
Configure AngleFlex patch panels with
left/right cable management per installation
guidelines supplied with product.
Avoid too much patch cord slack for
optimum operation. Refer to the table for
patch cord length recommendations.
Cisco Catalyst switches (shown) should be
cabled from the right to avoid blocking the
cooling fan.
Manage patch cord slack at the patch
panel level to avoid congesting the
entry of the switch.

1.800.BELDEN.1

(XHD84-Series). See Product Offering.

When using the high-density (XHD84 Series)


cabinet, use the center and side extension
kits (XHD8443CXF and XHG8443SXF) to
increase the capacity of the vertical channels
and properly manage patch cords. See
Product Offering.

19

Cabling Sample Number 2:


Partially Centralized Inter-Connect in a 672-port HDA (continued)

Front Cable Routing Guidelines for 672-port HDA

19" Rack

19" Rack

Left Side
Vertical Manager
6" Wide

Right Side
Vertical Manager
6" Wide

Center
Vertical Manager
12" Wide

45
45

45
45

44
44

44
44

44
44

43
43

43
43

43
43

43
43

42
42

42
42

42
42

41
41

41
41

40
40

40
40

39
39

39
39

38
38

38
38

38
38

38
38

37
37

37
37

37
37

37
37

36
36

36
36

36
36

36
36

35
35

35
35

34
34

34
34

33
33

33
33

32
32

32
32

31
31

31
31

30
30

30
30

29
29

29
29

28
28

28
28

27
27

27
27

26
26

26
26

25
25

25
25

24
24

24
24

23
23

23
23

22
22

22
22

21
21

21
21

21
21

20
20

20
20

20
20

19
19

19
19

ac
Sp
ee

11
2

22

24

22

24

1314

23
24

12

44

45

46

47

44

45

46

47

17
17

16
16

16
16

11
2

1314

23
24

12

26

27

26

27

44

45

46

47

15
15

22

24

10/100/1000 BASE-T
ETHERNET

42

44

45

46

47

42

44

45

46

47

27

11

14
14

13
13

13
13

44

45

46

47

22

24

22

24

1314

1
2

5
6

26

48

18
18

48

17
17

SWITCHING MODULE
26

27

35
26

42

44

45

46

47

3738

47

36

SWITCHING MODULE
25

26

27

25

26

27

25

35
26

10/100/1000 BASE-T
ETHERNET

23
24

47

36

25

25

10/100/1000 BASE-T
ETHERNET

23
24

1314

11

22

42

44

45

46

47

42

44

45

46

47

3738

47

36

48

1314

23
24

35
26

3738

47

36

48

SWITCHING MODULE
25

26

27

25

35
26

42

44

45

46

47

3738

47

36

48

14
14
10/100/1000 BASE-T
ETHERNET

48 P OR T
2

11
2

22

24

22

24

1314

23
24

12

SWITCHING MODULE
25

26

27

25

26

27

25

35
26

42

44

45

46

47

42

44

45

46

47

3738

47

36

48

13
13
10/100/1000 BASE-T
ETHERNET

48 P OR T

11
2

1314

23
24

12

SWITCHING MODULE

25

35
26

3738

47

36

48

12
12

16
16

SWITCHING MODULE

25

10/100/1000 BASE-T
ETHERNET

24

12

12
12
48 P OR T
2

23
24

48 P OR T
4

STATUS
42

24

12

STATUS

WS-X6548-GE-TX
48

48 P OR T

48

47

22

3738

15
15

WS-X6548-GE-TX

47

12

11

14
14

SWITCHING MODULE
26

48 P OR T
2

SWITCHING MODULE

3738

1314

STATUS
7

3738

12

48

36

25

11

35

15
15

12
12
4 8 P ORT
2

47

12
12
STATUS

36

35

STATUS
42

3738

35

26

SWITCHING MODULE
25

25

26

25

25

10/100/1000 BASE-T
ETHERNET

48 P OR T
5

STATUS

WS-X6548-GE-TX
48

23
24

12

WS-X6548-GE-TX
48

47

17
17

47

5
5
5

42

6
5
6

4
3
4
3

6
5
6

4
3
4
3

6
5

4
3

6
5
6

4
3
4

42

36

25

10/100/1000 BASE-T
ETHERNET

4 8 P ORT

STATUS

10/100/1000 BASE-T
ETHERNET

4 8 P ORT

STATUS

6
5
6

4
3
4

1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2

26

1314

STATUS
7

6
5
6

4
3
4

1
2
1
2

WS-X6548-GE-TX

47

3738

35

25

11

3738

6
5
6

4
3
4

2
1
2

2
1
2
1
2
1
2
1
2
1
2
1
2
1
2

12

47

13
13

Switch A
Rear view
336 UTP ports

46

20
20

19
19

1
2

WS-X6548-GE-TX
23
24

1314

11

1
2

WS-X6548-GE-TX

45

14
14

WS-X6548-GE-TX

44

48

SWITCHING MODULE
27

21
21

CMS 3U

18
18

SWITCHING MODULE

26

42

36

25

22
22
6

24

22

23
23
6

36

35

24
24
6

27

27

26

3738

35

10/100/1000 BASE-T
ETHERNET

4 8 P ORT

STATUS

26

25

26

15
15

18
18

SWITCHING MODULE
25

26

25

25
25

36

25

10/100/1000 BASE-T
ETHERNET

23
24

10/100/1000 BASE-T
ETHERNET

23
24

24

24

26
26
6

22

22

2
2

1
7

35

27
27

STATUS
7

1314

4 8 P ORT

12

1314
12

11

28
28
6

11

27

5
7

26

6
6

25

26

22

24

10/100/1000 BASE-T
ETHERNET

SWITCHING MODULE
25

26

27

42

44

45

46

47

11
11

11
11

11
11

11
11

10
10

10
10

10
10

10
10

09
09

09
09

09
09

09
09

08
08

08
08

08
08

08
08

07
07

07
07

07
07

07
07

06
06

06
06

06
06

06
06

05
05

05
05

05
05

05
05

04
04

04
04

03
03

03
03

02
02

02
02

01
01

01
01

04
04

03
03

02
02

01
01

CMS 3U

Cabling
Fields
1 to2EDA
Cabinets
Cabling
Fields
to EDA
Cabinets
14 14
x 24x 24
ports
AngleFlex
Patch
Panels
1U 1U
ports
AngleFlex
Patch
Panels
Total
of 336
UTPUTP
Ports
Total
of 336
Ports

29
29
6

48

SWITCHING MODULE

25

23
24

24

22

30
30
6

6
4

STATUS

WS-X6548-GE-TX

2
2

16
16

WS-X6548-GE-TX

4 8 P ORT

STATUS

WS-X6548-GE-TX

1314
12

11

5
7

31
31

WS-X6548-GE-TX

47

36

32
32
6

26

3738

35

10/100/1000 BASE-T
ETHERNET

4 8 P ORT
2

WS-X6548-GE-TX

25

12

STATUS

17
17

23
24

1314

11

33
33
6

18
18

CMS 3U

19
19

WS-X6548-GE-TX

22
22

23
23

24
24

34
34
6

25
25

26
26

27
27

28
28

30
30

29
29

39
39

32
32

31
31

Patch Cord Management Spool

40
40

35
35
6

33
33

34
34

Cabling Fields 1 to EDA Cabinets


14 x 24 ports AngleFlex Patch Panels 1U
Total of 336 UTP Ports

35
35

41
41

39
39

42
42

Fr

Fr

ee

40
40

ac
Sp

41
41

45
45

44
44

45
45

Switch B
Rear view
336 UTP ports

04
04

03
03

CMS 3U

02
02

01
01

Front View

www.belden.com

1.800.BELDEN.1

20

Cabling Sample Number 2:


Partially Centralized Inter-Connect in a 672-port HDA (continued)

Shortest
Cord

Longest
Cord

Patch Cord Path


From Right Side of Distribution Field 2
To Switch B

C
L

Patch Cord Path


From Right Side of Distribution Field 1
To Switch A

Switch A
Switch A
Switch A
Switch A
Switch A
Switch A

7 ft (2.1 m)
6 ft (1.8 m)
5 ft (1.5 m)
5 ft (1.5 m)
4 ft (1.2 m)
3 ft (0.9 m)

8 ft (2.4 m)
7 ft (2.1 m)
6 ft (1.8 m)
6 ft (1.8 m)
5 ft (1.5 m)
4 ft (1.2 m)

Switch B
Switch B
Switch B
Switch B
Switch B
Switch B

7 ft (2.1 m)
6 ft (1.8 m)
5 ft (1.5 m)
5 ft (1.5 m)
4 ft (1.2 m)
3 ft (0.9 m)

8 ft (2.4 m)
7 ft (2.1 m)
6 ft (1.8 m)
6 ft (1.8 m)
5 ft (1.5 m)
4 ft (1.2 m)

C
L

Distribution
Field 1 to EDA
336 ports

Center Vertical Manager

Distribution Field #1
Ports
of PP
to PP
01 to 12
01
03
01 to 12
04
09
01 to 12
10
14
13 to 24
01
02
13 to 24
03
08
13 to 24
09
14
Distribution Field #2
Ports
of PP
to PP
01 to 12
01
03
01 to 12
04
09
01 to 12
10
14
13 to 24
01
02
13 to 24
03
08
13 to 24
09
14

To

Left Side Vertical Manager

From

Right Side Vertical Manager

Front Cable Routing Guidelines for 672-port HDA (continued)

Distribution
Field 2 to EDA
336 ports

Middle Horizontal
Management

Patch Cord Path


From Left Side of Distribution Field 2
To Switch B

Patch Cord Path


From Right Side of Distribution Field 1
To Switch A

Sw i t c h A
336
UTP ports

Sw i t c h B
336
UTP ports

Lower Horizontal
Management

Front View
Patch Cord Management

www.belden.com

1.800.BELDEN.1

21

Cabling Sample Number 2:


Partially Centralized Inter-Connect in a 672-port HDA (continued)

Rear Cable Routing Guidelines for 672-port HDA

168 UTP
4 pair cables

168 UTP
4 pair cables

Sw i t c h A

Left Side Vertical Manager

Sw i t c h B

Distribution
Field 1 to
EDA
Rear

Center Vertical Manager

Distribution
Field 2 to
EDA
Rear

Right Side Vertical Manager

To EDA Cabinets

168 UTP
4 pair cables

168 UTP
4 pair cables

To EDA Cabinets

Rear View
Cable Management

www.belden.com

1.800.BELDEN.1

22

Cabling Sample Number 2:


Partially Centralized Inter-Connect in a 672-port HDA (continued)

Belden Bill of Materials for 672-port HDA

Item
Racks, Frames & Cable Managements
4-post Rack
Vertical Managers 12"
Vertical Managers 6"
Retention Bar for 6" Vert. Manager
Horizontal Manager with Cover 3U
Network Cabinet
Vertical Cable Management
Vertical Cable Management

Description
Steel Relay Rack,84" x 19",12-24 tap,36"deep
Combination High/low density with doors, 12"Wx84"H, Black
Combination High/low density with front doors, 6"Wx84"H, Black
Retention gates (6) 6", Black
19" WX3U, Black
Cabinet mounting alternative
Server cabinet 84"Hx30" Wx43"D, Black,
Side Extension Kit for XHD 84" H x 43" D
Center Extension Kit for XHD 84" H x 43" D

Part Number

Quantities

XDR8419-31236
BHVHL12
BHVHL06
BHGR06X
BHH193U

2
1
2
2
4

XHD84432110
XHD8443SXF
XHD8443CXF

2
2
1

CA21100xxxA06

112

AX103248
AX104024

28
672

10GX120061000

672 runs

AX103248
AX102288

28
672

CA21106003
CA21106004
CA21106005
CA21106006
CA21106007
CA21106008

144
144
168
144
72
144

4812 D151000

672 runs

C601106003
C601106004
C601106005
C601106006
C601106007
C601106008

144
144
168
144
72

AX103248
AX101326

28
672

AX101569
AX102515

1
as req'd

Notes

Category 6A Solution - IBDN System 10GX


Pre-terminated Option

Cable Assemblies
Category 6A Cable Assemblies
Patch Panels
Patch Panel
Keystone Style Couplers

10GX Pre-term. Cable Assy, Bonded-Pair, 4-Pair, 23 AWG Solid, T568 A/B-T568 A/B, 6 Cables
AngleFlex Patch Panel, 24 ports, 1U, Black (Empty)
10GX KeyConnect RJ45 Coupler, Black

Use xxx to specify length in feet

Field-terminated Option

Distribution Cable
Category 6A Cable
Patch Panels
Patch Panel
Keystone Style Modules

10GX12 Nonbonded-Pairs Cable, 4-Pair, 23 AWG UTP, 305 m (1000 ft), Spool, Blue
AngleFlex Patch Panel, 24 ports, 1U, Black (Empty)
10GX KeyConnect Modular Jack, Blue

Length = TBD

Patch Cords

Patch Cords
CAT6A Modular Cord
CAT6A Modular Cord
CAT6A Modular Cord
CAT6A Modular Cord
CAT6A Modular Cord
CAT6A Modular Cord

10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 0,9 m (3 ft)
10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 1,2 m (4 ft)
10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 1.5 m (5 ft)
10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 1.8 m (6 ft)
10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 2.1 m (7 ft)
10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 2.4 m (8 ft)

Beyond Category 6 Solution - IBDN System 4800LX


Distribution Cable
Enhanced Category 6 Cable
Patch Cords
CAT6+ Modular Cord
CAT6+ Modular Cord
CAT6+ Modular Cord
CAT6+ Modular Cord
CAT6+ Modular Cord

DataTwist 4800 Cable, 4-pair, 23 AWG UTP, 305m (1000 ft) Spool, Blue
CAT6+, Bonded-Pair Modular Cord, 4 pairs, 24 AWG, T568A/B-T568A/B, Riser, 0,9 m (3 ft)
CAT6+ Bonded-Pair Modular Cord, 4 pairs, 24 AWG, T568A/B-T568A/B, Riser, 1,2 m (4 ft)
CAT6+, Bonded-Pair Modular Cord, 4 pairs, 24 AWG, T568A/B-T568A/B, Riser, 1,5 m (5 ft)
CAT6+, Bonded-Pair Modular Cord, 4 pairs, 24 AWG, T568A/B-T568A/B, Riser, 1,8 m (6 ft)
CAT6+, Bonded-Pair Modula1 Cord, 4 pairs, 24 AWG, T568A/B-T568A/B, Riser, 2,1 m (7 ft)
CAT6+, Bonded-Pair Modula1 Cord, 4 pairs, 24 AWG, T568A/B-T568A/B, Riser, 2,4 m (8 ft)

Patch Panels
Patch Panel
Keystone Style Modules

AngleFlex Patch Panel, 24 ports, 1U, Black (Empty)


CAT6+ KeyConnect Modular Jack, Blue

Labeling
Velcro Ties

Automated LabelFlex Advanced Software, 1 CD/pack


75 ft Roll x 1/2 in. Bulk Velcro

Length = TBD

Miscellaneous Accessories

www.belden.com

1.800.BELDEN.1

23

Cabling Sample Number 3:


EDA with 96 Copper Ports from HDA and 48 Fiber Ports from SAN

This example demonstrates how to cable an


EDA containing 96 copper ports from the HDA
and 48 fiber optic ports from the SAN. From
the HDA, 96 copper cables terminate to two
48-port high-density patch panels, which in
turn connect to UTP ports on the servers. From
the SAN, fiber optic cabling terminates to four
LC adapter modules each equipped with 12 LC
duplex connectors for a total of 48 LC duplex
fiber ports. The adapter modules are housed in
a high-density 1U fiber patch panel.

EDA Installation Tips:

EDA Alternatives:

Using 30-inch wide enclosures provides better

Use MPO-LC 24-fiber Modules (AX103729)

patch cord management to the servers.

Using 1U 48-port patch panels saves 2 RU for


server installation.

Assembling 30-inch wide enclosures provides


a 7-inch wide vertical management channel
between enclosures.

Install the KeyConnect patch panels per the

and Multi-MPO 24-fiber assemblies (NXCUPFX-PHXFEN-PHPFEN-O-0000) for quick


deployment between EDA and HDA or SAN.

If cabling is distributed under raised floor,


installing the patch panels at the bottom of
the cabinet will simplify cable management
within the cabinet.

installation guidelines supplied with product.


EDA Cabling Considerations:

Maximum number of servers allowed


in enclosure based on power/cooling
limitations.

Number of copper ports required


by each server.

Number of fiber ports required


by each server.

Space for cable and patch cord


management, including slack.

Space required for additional


equipment, such as power and
environmental monitoring.

Install the FiberExpress Ultra 1U shelf per the


installation guidelines supplied with product.

Use a 1U horizontal cable manager to route


patch cords to the left after exiting from the
right of the panel.

Route copper and fiber patch cords in two


separate vertical channels. Route fiber patch
cords on the same side as Cabinet Distribution
Units (CDUs). If two CDUs are used in the
enclosure, follow power separation guidelines
per the TIA-942 standard (Table 2 in section
7.3.1) to avoid electro-magnetic interference
on copper cords.

Avoid too much patch cord slack for optimum


operation. Refer to table for patch cord
length recommendations.

Use blanking panels to block unused


spaces on the front side of the servers
for optimum cooling.

www.belden.com

1.800.BELDEN.1

24

Cabling Sample Number 3:


EDA with 96 Copper Ports from HDA and 48 Fiber Ports from SAN

Right Side
Vertical Manager
Built-in 3" Wide

Left Side
Vertical Manager
Built-in 3" Wide

High Density Cabinet


84"Hx30"Wx43"D

45

45

44

44

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

43

43

Right Side
Vertical Manager
Built-in 3" Wide

High Density Cabinet


84"Hx30"Wx43"D

Fiber Cable from HDA


1x FiberExpress Ultra Patch Panels FXU
4 LC Duplex Adaptor Modules equipped with
12 LC Duplex Connectors
Total of 48 LC Duplex Fiber Ports

SD
45

45

Filler 3U

44

44

43

43

42

42

41

41

40

40

40

40

39

39

39

39

38

38

38

37

37

42
25

26

27

28

29

30

31

P WR
2

38

32

33

34

35

36

37

39

40

41

P WR
1

42

43

44

45

46

PCI-X 1 33

PCI-X 133

PWR
1

Ma n a g e me n tC a rd

PCI-X 133
CONSOLE

Gb LAN A

P WR
2

Gb LAN B

P WR
1

T OC

Gb L A N B

Gb L A NA

TOC

USB

USB

Horizontal CMS 1U

PCI-X 1 33
PCI-X 1 33
PCI-X 1 33

PCI-X 1 33

36

CON S O L E

PCI-X 1 33
S E R IA L A

PCI-X 1 33

T OC
Gb L A N B

USB

35

S E R IA L B

P WR
1

PCI-X 1 33

34

34

PCI-X 1 33
Ma n a g e me n tC a rd

CON S O L E

UTP Cabling from HDA


2x 48 ports Keyconnect 1U Patch Panels

S C S IL V D /S E

Gb L A NA

USB

Gb L A N B

PCI-X 1 33

hp
integrity
rx2620-2

DVD

hp
integrity
rx2620-2

DVD

hp
integrity
rx2620-2

DVD

hp
integrity
rx2620-2

DVD

hp
integrity
rx2620-2

DVD

hp
integrity
rx2620-2

DVD

hp
integrity
rx2620-2

DVD

hp
integrity
rx2620-2

DVD

hp
integrity
rx2620-2

DVD

hp
integrity
rx2620-2

DVD

hp
integrity
rx2620-2

DVD

hp
integrity
rx2620-2

DVD

hp
integrity
rx2620-2

DVD

hp
integrity
rx2620-2

DVD

hp
integrity
rx2620-2

DVD

hp
integrity
rx2620-2

DVD

hp
integrity
rx2620-2

DVD

hp
integrity
rx2620-2

35

34

34

UID

33

33

33
1

S E R IA L B

P WR
1

32

DVD

PCI-X 1 33

T OC

UID

35

PCI-X 1 33
S E R IA L A

33

P WR
2

36

36

PCI-X 1 33
Ma n a g e me n tC a rd

Gb L A NA

37

PCI-X 133

SERIAL B

35

P WR
2

41

S E R IA L B

36

S C S IL V D /S E

42

Filler 2U

48

S E R IA L A

PCI-X 133
SERIAL A
S C S IL V D /S E

47

CON S O L E

Management Card

37

SCSI LVD/SE

38

Filler 1U

41

PWR
2

Left Side
Vertical Manager
Built-in 3" Wide

32

32

32

PCI-X 1 33
Ma n a g e me n tC a rd

CON S O L E

PCI-X 1 33
S E R IA L A

31
S C S IL V D /S E

P WR
2

T OC
Gb L A NA

Gb L A N B

USB

PCI-X 1 33

31

31
1

S E R IA L B

P WR
1

30

UID

31

PCI-X 1 33

30

30

30

PCI-X 1 33
Ma n a g e me n tC a rd

CON S O L E

PCI-X 1 33
S E R IA L A

29
S C S IL V D /S E

P WR
2

T OC
Gb L A NA

Gb L A N B

USB

PCI-X 1 33

29

29
1

S E R IA L B

P WR
1

28

UID

29

PCI-X 1 33

28

28

28

PCI-X 1 33
Ma n a g e me n tC a rd

CON S O L E

PCI-X 1 33
S E R IA L A

27
S C S IL V D /S E

P WR
2

T OC
Gb L A NA

USB

Gb L A N B

UID

27
1

S E R IA L B

P WR
1

PCI-X 1 33

26

27

27

PCI-X 1 33

26

26

26

PCI-X 1 33
Ma n a g e me n tC a rd

CON S O L E

PCI-X 1 33
S E R IA L A

25
S C S IL V D /S E

P WR
2

USB

Gb L A N B

PCI-X 1 33

25

S E R IA L B

P WR
1

24

UID

25

PCI-X 1 33

T OC
Gb L A NA

25

24

24

24

PCI-X 1 33
Ma n a g e me n tC a rd

CON S O L E

PCI-X 1 33
S E R IA L A

23
S C S IL V D /S E

P WR
2

PCI-X 1 33

T OC
Gb L A NA

Gb L A N B

USB

PCI-X 1 33
22

PCI-X 1 33
CON S O L E

PCI-X 1 33
S E R IA L A

21
S C S IL V D /S E

PWR
2

PCI-X 1 33

T OC
Gb L A NA

USB

Gb L A N B

21

S E R IA L B

PWR
1

PCI-X 133

20

PCI-X 133
Management Card

20

CONSOLE

20 Servers 2U Each with


3 UTP Ports
2 LC Fiber Ports

SCSI LVD/SE

PCI-X 133

TOC
Gb LAN A

Gb LAN B

USB

19

19

18

18

18

CON S O L E

PCI-X 1 33

S E R IA L A

17

PCI-X 1 33

T OC
Gb L A NA

UID

19
1

PCI-X 1 33
Ma n a g e me n tC a rd

S C S IL V D /S E

20

20

PCI-X 1 33

18

P WR
2

21

SERIAL B

P WR
1

UID

PCI-X 133

P WR
2

22

22

21

SERIAL A

19

23

23

S E R IA L B

P WR
1

22
Ma n a g e me n tC a rd

UID

23

Gb L A N B

USB

17

17

S E R IA L B

P WR
1

UID

17
1

PCI-X 1 33

16

16

16

16

PCI-X 1 33
Ma n a g e me n tC a rd

CON S O L E

PCI-X 1 33

S E R IA L A

15
S C S IL V D /S E

P WR
2

PCI-X 1 33

T OC
Gb L A NA

USB

Gb L A N B

15

15

S E R IA L B

P WR
1

UID

15
1

PCI-X 1 33

14

14

14

14

PCI-X 1 33
Ma n a g e me n tC a rd

CON S O L E

PCI-X 1 33

S E R IA L A

13
S C S IL V D /S E

P WR
2

PCI-X 1 33

T OC
Gb L A NA

Gb L A N B

USB

13

S E R IA L B

P WR
1

UID

13

13

PCI-X 1 33

12

12

12

12

PCI-X 1 33
Ma n a g e me n tC a rd

CON S O L E

PCI-X 1 33

S E R IA L A

11
S C S IL V D /S E

P WR
2

PCI-X 1 33

T OC
Gb L A NA

Gb L A N B

USB

11

S E R IA L B

P WR
1

UID

11

11

PCI-X 1 33

10

10

10

10

PCI-X 1 33
Ma n a g e me n tC a rd

CON S O L E

PCI-X 1 33

S E R IA L A

09
S C S IL V D /S E

P WR
2

PCI-X 1 33

T OC
Gb L A NA

USB

Gb L A N B

09

09

S E R IA L B

P WR
1

09

PCI-X 1 33

08

UID

08

08

08

PCI-X 1 33
Ma n a g e me n tC a rd

CON S O L E

PCI-X 1 33

S E R IA L A

07
S C S IL V D /S E

P WR
2

PCI-X 1 33

T OC
Gb L A NA

USB

Gb L A N B

P WR
1

07

07

PCI-X 1 33

06

UID

07

S E R IA L B

06

06

06

PCI-X 1 33
Ma n a g e me n tC a rd

CON S O L E

PCI-X 1 33

S E R IA L A

05
S C S IL V D /S E

P WR
2

PCI-X 1 33

T OC
Gb L A NA

Gb L A N B

USB

P WR
1

05

05

PCI-X 1 33

04

UID

05

S E R IA L B

04

04

04

PCI-X 1 33
Ma n a g e me n tC a rd

CON S O L E

PCI-X 1 33

S E R IA L A

03
S C S IL V D /S E

P WR
2

PCI-X 1 33

T OC
Gb L A NA

USB

Gb L A N B

P WR
1

03

03

PCI-X 1 33

02

UID

03

S E R IA L B

02

02

02

PCI-X 1 33
Ma n a g e me n tC a rd

CON S O L E

PCI-X 1 33

S E R IA L A

01
S C S IL V D /S E

PCI-X 1 33

T OC
Gb L A NA

Gb L A N B

USB

UID

01

01

01

S E R IA L B

UID

Rear View

UID

Front View
hp
integrity
rx2620-2

www.belden.com

1.800.BELDEN.1

25

Cabling Sample Number 3:


EDA with 96 Copper Ports from HDA and 48 Fiber Ports from SAN (continued)

Front and Rear Cable Routing Guidelines for 96-copper Port, 48-fiber Port EDA

To HDA
Cabinet

Fiber Cabling

96 UTP Cables
4 x 24 Fiber Cables

Fiber Cabling

Maximum of 24 Fiber Patch Cords


- Servers on U 1 to 22 can be reached with a 3 m (10') Patch Cord
- Servers on U 23 to 40 can be reached with a 2 m (7') Patch Cord

CMS 1U

Rear View
Patch Cord Management

www.belden.com

Right Side Vertical Manager for Fiber Only

Front

2 0

96 UTP Cables

Maximum of 24 Fiber Patch Cords


- Servers on U 1 to 28 can be reached with a 2 m (7') Patch Cord
- Servers on U 29 to 40 can be reached with a 1 m (3') Patch Cord

Left Side Vertical Manager for UTP Only

Maximum of 60 UTP Patch Cords


- Servers on U 1 to 12 can be reached with a 7' (2.1 m) Patch Cord
- Servers on U 13 to 24 can be reached with a 6' (1.8 m) Patch Cord
- Servers on U 13 to 24 can be reached with a 5' (1.5 m) Patch Cord
- Servers on U 37 to 40 can be reached with a 4' (1.2 m) Patch Cord

S E R V E R S

UTP Cabling
Left Side Vertical Manager for UTP Only

S E R V E R S

Rear Each with 2 LC fiber port & 3 UTP ports

2 0

Right Side Vertical Manager for Fiber Only

UTP Cabling

Front View
Cable Management

1.800.BELDEN.1

26

Cabling Sample Number 3:


EDA with 96 Copper Ports from HDA and 48 Fiber Ports from SAN (continued)

Belden Bill of Materials for 96-copper Port, 48-fiber Port EDA

Item
Racks, Frames & Cable Management
Server Cabinet
Horizontal Manager
Filler Panel
Filler Panel
Filler Panel

Description
Server cabinet 84"Hx30"Wx43"D, Black
Horizontal mgr/cover 19"x1U Black
1U 19" Solid Filler Panel, Black
2U 19" Solid Filler Panel, Black
3U 19" Solid Filler Panel, Black

Part Number

Quantity

XHD84432112
BHH191U
B9910-0100
B9911-0200
B9912-0200

1
1
1
1
1

Notes

Augmented Category 6 Solution - IBDN System 10GX


Distribution Cable
Category A Cable
Patch Cords
CAT6a Modular Cord
CAT6a Modular Cord
CAT6a Modular Cord
CAT6a Modular Cord
Patch Panels
Patch Panel
Modular Jacks

10GX12 Cable, 4 Nonbonded-Pairs, 23 AWG UTP, Riser, Blue

10GX120061000

96 runs

10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 1,2 m (4 ft)
10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 1.5 m (5 ft)
10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 1.8 m (6 ft)
10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 2.1 m (7 ft)

AX360014
AX360370
AX360371
AX360015

6
18
18
18

KeyConnect Modular Patch Panel, 48 ports, 1U, Black (Empty)


10GX KeyConnect Modular Jack, Blue

AX103121
AX102288

2
96

4812 D151000

96 runs

CA21106003
CA21106004
CA21106005
CA21106006
CA21106007
CA21106008

144
144
168
144
72
144

AX103121
AX101326

2
96

NXC-UPFX-PHXFGNPHPFGN-O-0000

4 cables

Fiber Optic Patch Cord, Duplex Zip, 2.0mm, 2f, FX2K, Riser, 1,0 m
Fiber Optic Patch Cord, Duplex Zip, 2.0mm, 2f, FX2K, Riser, 2,0 m
Fiber Optic Patch Cord, Duplex Zip, 2.0mm, 2f, FX2K, Riser, 3,0 m

AX200992
AX200664
AX200665

6
24
10

FiberExpress Ultra FXU, 1U, Black


FiberExpress Ultra MPO Pre-terminated Module, LC-Duplex, 24f, FX2000

AX103143
AX103729

1
4

Length = TBD

Beyond Category 6 Solution - IBDN System 4800LX


Distribution cable
Enhanced Category 6 Cable
Patch Cords
CAT6A Modular Cord
CAT6A Modular Cord
CAT6A Modular Cord
CAT6A Modular Cord
CAT6A Modular Cord
CAT6A Modular Cord
Patch Panels
Patch Panel
Modular Jacks

DataTwist 4800 Cable, 4-pair, 23 AWG UTP, 305m (1000 ft) Spool, Blue
10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 0,9 m (3 ft)
10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 1,2 m (4 ft)
10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 1.5 m (5 ft)
10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 1.8 m (6 ft)
10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 2.1 m (7 ft)
10GX, Modular Cord, 4 pairs, 23 AWG, T568A/B-T568A/B, CMR, Blue, 2.4 m (8 ft)
KeyConnect Modular Patch Panel, 48 ports, 1U, Black (Empty)
CAT6+ KeyConnect Modular Jack, Blue

Length = TBD

Fiber - FX 2000 Series - Pre-terminated Solution


Horizontal Cabling From HDA to EDA
MPO Pre-terminated Cable
Patch Cords
LC Duplex Patch Cord
LC Duplex Patch Cord
LC Duplex Patch Cord
Patch Panels
Fiber Patch Panel
Fiber Adaptor Module

MPO Cable, 24 fibers, MPO-MPO, type-C, FX2000, Plenum

Length = TBD

For EDA cabinet only


For EDA cabinet only

Fiber - FX 2000 Series - Field-terminated Solution


Horizontal Cabling From HDA to EDA
50/125m, Laser Optimized Fiber Cable

FX 2000, Distribution, 24 fibers, Plenum,

B9C602

4 cables

Field Installable Connectors


Optimax Field Installable Connector

LC 50m Multimode, Field Installable Connector

AX101982

192

Fiber Optic Patch Cord, Duplex Zip, 2.0mm, 2f, FX2K, Riser, 1.0 m
Fiber Optic Patch Cord, Duplex Zip, 2.0mm, 2f, FX2K, Riser, 2.0 m
Fiber Optic Patch Cord, Duplex Zip, 2.0mm, 2f, FX2K, Riser, 3.0 m

AX200992
AX200664
AX200665

6
24
10

FiberExpress Ultra FXU, 1U, Black


FXU Frame, LC Duplex, 24 fibers

AX103143
AX103465

1
4

Patch Cords
LC Duplex Patch Cord
LC Duplex Patch Cord
LC Duplex Patch Cord
Patch Panels
Fiber Patch Panel
Fiber Adaptor Module

Length = TBD
96 connectors go in the HDA

For EDA cabinet only


For EDA cabinet only

Miscellaneous Accessories
Labeling
Velcro Ties
Cable Slack Management

Automated LabelFlex Advanced Software, 1 CD/pack


75 ft Roll x 1/2 in. Bulk Velcro
12 in. Fiber Optic Cable Manager

AX101569
AX102515
AX102516

1
as req'd
as req'd

Use with Pre-terminated Cables

Cable Slack Management

24 in. Fiber Optic Cable Manager

AX102517

as req'd

Use with Pre-terminated Cables

www.belden.com

1.800.BELDEN.1

27

Cabling Sample Number 4:


Cross-connect Cabling for a 720-port SAN

This example shows how to cable a 720-port


SAN using a centralized topology with a crossconnect. A SAN switch containing 384 LC
duplex fiber ports connects to 384 LC duplex
fiber ports housed in three, 4U fiber patch
panels via permanent cabling. The 4U fiber
patch panels cross-connect to another 720
ports housed in five, 4U patch panels in the
bottom half of the cabinet. From there, fiber
optic cabling terminates to fiber patch panels
in the EDA. Setting up the SAN as a crossconnect increases security with all switch ports
mirrored on fiber patch panels. This set-up
offers the possibility to expand the SAN to
720 ports in the future.
SAN Cabling Considerations:

Number of servers connected to SAN,

now and future.


Frequency of moves, adds, and changes.
Distance limitations.
Level of security.
Bandwidth required for transmitting data.
Fiber connectorization expertise.
Loss budget for fiber applications.

www.belden.com

SAN Installation Tips:

SAN Alternatives:

The FiberExpress Ultra 4U shelf terminates

Use MPO-LC 24-fiber Modules (AX103729)

144 LC duplex ports and is perfect for


managing a high concentration of
fiber connections.
Using 24-fiber LC cable assemblies between
the switch and the back of the Equipment
Field patch panels enables quick deployment
of new equipment cards.
Ganging high-density cabinet (XHD84 Series)
together creates a 7-inch wide vertical
management channel in the center.
Install the FiberExpress Ultra 4U shelf
per the installation guidelines supplied
with the product.
Avoid too much patch cord slack for
optimum operation. Refer to the table for
patch cord length recommendations.
Use blanking panels to block unused spaces
for optimum cooling.

1.800.BELDEN.1

and Multi-MPO 24-fiber assemblies (NXCUPFX-PHXFEN-PHPFEN-O-0000) for quick


deployment between EDA and HDA or SAN.
(See Product Offering.)

28

Cabling Sample Number 4:


Cross-connect Cabling for a 720-port SAN

Center Vertical Manager


Built-in 6" Wide

High Density Cabinet


84"Hx30"Wx43"D

High Density Cabinet


84"Hx30"Wx43"D

45

45

45

44

44

44

43

43

43

42

42

42

42

41

41

41

41

45

44

43

Filler 3U

Filler 4U

40

40

40

39

39

39

38

38

38

38

37

37

37

37

Filler 4U

CMS 2U

Right Side Vertical Manager


Built-in 3" Wide

45

44

44

43

43

42

42

41

41

40

40

39

39

38

38

38

37

37

37

36

36

36

35

35

35

34

34

34

34

33

33

33

33

32

32

32

32

31

31

31

30

30

30

29

29

29

28

28

28

27

27

27

26

26

26

25

25

25

24

24

24

43

42

Filler 4U

41

Left Side Vertical Manager


Built-in 3" Wide

High Density Cabinet


84"Hx30"Wx43"D

45

45

44

39

40

Center Vertical Manager


Built-in 6" Wide

High Density Cabinet


84"Hx30"Wx43"D

40

39

Filler 4U

45

44

Filler 4U

42

41

40

Filler 4U

39

36

36

36

35

35

35

34

34

34

34

33

33

33

33

32

32

32

31

31

31

30

30

30

29

29

29

28

28

28

27

27

27

27

26

26

26

26

25

25

25

25

24

24

24

23

23

23

23

22

22

22

22

23

23

23

21

21

21

22

22

22

20

20

20

21

21

21

19

19

19

19

20

20

20

18

18

18

18

19

19

19

19

17

17

17

17

18

18

18

18

16

16

16

16

17

17

17

17

15

15

15

15

16

16

16

16

14

14

14

15

15

15

13

13

13

14

14

14

12

12

12

13

13

13

32

Filler 4U

31

30

29

28

24

Filler 4U

Filler 4U

21

20

14

Filler 4U

Filler 4U
1

10

pwr4

pwr3

SAN Equipment Field


3 x FiberExpress Ultra Patch Panels 4U
Rear

SAN Equipment Field


3 x FiberExpress Ultra Patch Panels 4U
Max of 432 LC Duplex Fiber Ports
384 LC Duplex Ports Installed

CMS 3U

Cabling Field to EDA Cabinets


5 x FiberExpress Ultra Patch Panels 4U
Rear

Cabling Field to EDA Cabinets


5 x FiberExpress Ultra Patch Panels 4U
Total of 720 LC Duplex Fiber Ports

Manager Trough
Double Sided

38

35

36

Left Side Vertical Manager


Built-in 3" Wide

43

37

36

Filler 4U

35

Filler 4U

Manager Trough
Double Sided

31

30

29

28

Filler 4U

27

26

25

24

Filler 4U

23

22

21

20

Filler 4U

CMS 3U

15

pwr2

13

12

pwr1

14

13
1

SAN Switch
Front

11

11

11

11

12

12

12

10

10

10

10

11

11

11

09

09

09

09

10

10

10

08

08

08

08

09

09

09

07

07

07

07

08

08

08

06

06

06

06

07

07

07

05

05

05

05

06

06

06

04

04

04

04

05

05

05

03

03

03

03

04

04

04

02

02

02

02

03

03

03

01

01

01

01

02

02

02

10

12
Power Supply
11

SAN Switch
Rear view
384 LC duplex fiber ports

10

09

Power Supply

01

Front View

www.belden.com

07

06

Power Supply

01

01

05

04

03

Power Supply

02

POWER SUPPLY 2 & 4

POWER SUPPLY 1 & 3

Filler 2U

08

01

Rear View

1.800.BELDEN.1

29

Cabling Sample Number 4:


Cross-connect Cabling for a 720-port SAN (continued)

Front Cable Routing Guidelines for 720-port SAN Cross-connect

Note 1

To SAN Switch
On Rear Side

60 Cables

From
EDA Cabling Field

To EDA Cabinets

32 Cables

PP
Note 2

To
SAN Cabling FIeld

With

Ports

Patch Panels with

** Left Side Access

01 to 36

Right Side Access **

37 to 72

** Left Side Access

73 to 108

Right Side Access **

109 to 144

** Left Side Access

01 to 36

Right Side Access **

37 to 72

** Left Side Access

73 to 108

Right Side Access **

109 to 144

** Left Side Access

01 to 36

Right Side Access **

37 to 72

** Left Side Access

73 to 108

Right Side Access **

109 to 144

** Left Side Access

01 to 36

Right Side Access **

37 to 72

** Left Side Access

73 to 108

Right Side Access **

109 to 144

Right Side Access **


** Left Side Access
Right Side Access **
** Left Side Access
Right Side Access **
** Left Side Access
Right Side Access **
** Left Side Access
Right Side Access **
** Left Side Access
Right Side Access **
** Left Side Access
Right Side Access **
** Left Side Access
Right Side Access **
** Left Side Access
Right Side Access **
** Left Side Access
Right Side Access **
** Left Side Access
Right Side Access **
** Left Side Access
Right Side Access **
** Left Side Access
Right Side Access **
** Left Side Access
Right Side Access **
** Left Side Access
Right Side Access **
** Left Side Access
Right Side Access **
** Left Side Access

Left Side Vertical Manager

SAN
Equipment
Field
384 LC
Duplex Ports
30 Cables

30 Cables

Center Vertical Manager

Right Side Vertical Manager

01

02

S A N
S w i t c h

03

Cabling Field
to EDA
Up to 720 LC
Duplex Ports

Notes
1 32 Cables of 24 fibers with
12 LC Duplex/12 LC Duplex,
7 m going to the rear side
2 Cables to EDA Cabinets
Distribution cables, 24 Fibers,
50/125m Laser Optimized,
Various lengths

Front View
Cable Management

www.belden.com

1.800.BELDEN.1

04

Shortest
Cord

Longest
Cord

1 m (3 ft)
1 m (3 ft)
1 m (3 ft)
1 m (3 ft)
1 m (3 ft)
1 m (3 ft)
1 m (3 ft)
1 m (3ft)
1 m (3 ft)
1 m (3 ft)
1 m (3 ft)
2 m (6 ft)
1 m (3 ft)
1 m (3 ft)
1 m (3 ft)
2 m (6 ft)
2 m (6 ft)
1 m (3 ft)
1 m (3 ft)
2 m (6 ft)
2 m (6 ft)
1 m (3 ft)
1 m (3 ft)
2 m (6 ft)
2 m (6 ft)
1 m (3 ft)
1 m (3 ft)
2 m (6 ft)
2 m (6 ft)
1 m (3 ft)
2 m (6 ft)
2 m (6 ft)

3 m (10 ft)
2 m (6 ft)
2 m (6 ft)
3 m (10 ft)
3 m (10 ft)
3 m (10 ft)
2 m (6 ft)
3 m (10 ft)
3 m (10 ft)
3 m (10 ft)
3 m (10 ft)
3 m (10 ft)
3 m (10 ft)
3 m (10 ft)
3 m (10 ft)
3 m (10 ft)
3 m (10 ft)
3 m (10 ft)
3 m (10 ft)
4 m (12 ft)
3 m (10 ft)
3 m (10 ft)
3 m (10 ft)
4 m (12 ft)
3 m (10 ft)
3 m (10 ft)
3 m (10 ft)
4 m (12 ft)
3 m (10 ft)
3 m (10 ft)
3 m (10 ft)
4 m (12 ft)

30

Cabling Sample Number 4:


Cross-connect Cabling for a 720-port SAN (continued)

Rear Cable Routing Guidelines for 720-port SAN Cross-connect

SA N
Equipment
Field
Up to 384 LC
Duplex Ports

16 Cables

16 Cables
Note 2D

Note 2C

C
L

CMS
Note 2B

S A N
S w i t c h

Cabling Field
to EDA
Up to 720 LC
Duplex Ports

Center Vertical Manager

Note 2A

CMS

384 LC DUPLEX FIBER PORTS

Left Side Vertical Manager

C
L

Right Side Vertical Manager

Note 1

Notes
1 32 Cables of 24 Fibers with
12 LC Duplex/12 LC Duplex,
7 m going to the rear side

2 Fiber Patch Cord Path


A - Left Side to Right Side
B - Left Side to Left Side
C - Right Side to Left Side
D - Right Side to Right Side

Rear View
Patch Cord & Pre-terminated
Cable Assemblies Management

www.belden.com

1.800.BELDEN.1

31

Cabling Sample Number 4:


Cross-connect Cabling for a 720-port SAN (continued)

Belden Bill of Materials for 720-port SAN Cross Connect

Item
Racks, Frames & Cable Management
High Density Cabinet
Pass-Through
Pass-Through
Slack Management Spool
3U Filler Plate
4U Filler Plate
Horizontal Manager with Cover 2U
Horizontal Manager with Cover 3U

Description
High Density Cabinet 84"Hx30"Wx43"D, Black,
Manager Through Single 43"D
Manager Through Double 43"D
Slack Management spool kit, Black
3U 19" Solid Filler Panel, Black
4U 19" Solid Filler Panel, Black
19" WX2U, Black
19" WX3U, Black

Part Number

Quantities

XHD84432111
XHDMFR143
XHDMFR243
BHSK020
B9910-0300
B9910-0400
BHH192U
BHH193U

2
1
1
1
1
16
1
2

NXC-MRFX-LCPFBNLCPFBN-O-0000

32 cables

AX103267
AX103465

5
60

NXC-MRFX-LCPFBNLDPFEN-O-0007

32 Cables

AX103267
AX103465

3
32

B9C602

32 cables

AX103267
AX103465
AX101982

5
60
1440

NXC-MRFX-LCPFBNLDPFEN-O-0007

32 Cables

AX103267
AX103465

3
32

AX200992
AX200664
AX200665

120
234
30

AX101569
AX102515
AX102516
AX102517

1
as req'd
as req'd
as req'd

Notes

Fiber Cabling - FX 2000 Series - Pre-terminated Solution


Fiber Cabling to EDA
Multi-duplex Pre-terminated Cable
Patch Panels
Fiber Patch Panel
Fiber Adaptor Module

Pre-terminated Distribution Cable, 24 fibers, FX2000, Riser, 12 LC Duplex, 1m 900m fan-out,


pull-eye at one end
FiberExpress Ultra FXU, 4U, Black
FXU Frame, LC Duplex. 24 fibers

Length = TBD

From SAN Switch to Equipment Field


Multi-duplex Pre-terminated Cable
Patch Panels
Fiber Patch Panel
Fiber Adaptor Module

Pre-terminated Distribution Cable, 24 fibers, FX2000, Riser, 12 LC Duplex, 1m 900m fan-out


inside end, 1m 2mm fan-out outside end, pull-eye at one end
FiberExpress Ultra FXU, 4U, Black
FXU Frame, LC Duplex. 24 fibers

Fiber Cabling - FX 2000 Series - Field-terminated Solution


Fiber Cabling to EDA
Fiber Cable, 50/125m, Laser Optimised, OFNR
Patch Panels
Fiber Patch Panel
Fiber Adaptor Module
Field Installable LC Connectors

FX 2000, Distribution, Riser 24 fibers


FiberExpress Ultra FXU, 4U, Black
FXU Frame, LC Duplex. 24 fibers
Optimax, LC, Multimode 50m, for 900m Tight buffer fiber

Length = TBD

From SAN Switch to Equipment Field


Multi-duplex Pre-terminated Cable

Pre-terminated Distribution Cable, 24 fibers, FX2000, Riser, 12 LC Duplex, 1m 900m fan-out


inside end, 1m 2mm fan-out outside end, pull-eye at one end

Patch Panels
Fiber Patch Panel
Fiber Adaptor Module

FiberExpress Ultra FXU, 4U, Black


FXU Frame, LC Duplex. 24 fibers

Patch Cords
LC Duplex Patch Cord
LC Duplex Patch Cord
LC Duplex Patch Cord

Fiber Optic Patch Cord, Duplex Zip, 2.0mm, 2f, FX2K, Riser, 1.0 m
Fiber Optic Patch Cord, Duplex Zip, 2.0mm, 2f, FX2K, Riser, 2.0 m
Fiber Optic Patch Cord, Duplex Zip, 2.0mm, 2f, FX2K, Riser, 3.0 m

Labeling
Velcro Ties
Cable Slack Management
Cable Slack Management

Automated LabelFlex Advanced Software, 1 CD/pack


75 ft Roll x 1/2 in. Bulk Velcro
12 in. Fiber Optic Cable Manager
24 in. Fiber Optic Cable Manager

www.belden.com

1.800.BELDEN.1

Fiber Patch Cord

Miscellaneous Accessories
Use with Pre-terminated Cables
Use with Pre-terminated Cables

32

Data Center Product Offering:


Cable Management

High Density Racking System


DESCRIPTION

ORDERING NUMBER (CPC)

Racks
Aluminum relay rack, 19" mounting x 84"H, #12-24 tap, Black

BHRR194

Steel relay rack, 19" mounting x 84 H, #10-32 tap, Black

XDR8419-310

Steel relay rack, 19" mounting x 84 H, #12-24 tap, Black

XDR8419-312

Four-post Steel Relay Rack, 19" Mounting x84"H, #12-24 tap, 36"deep

XDR8419-31236

Double-sided High density with doors, 6"Wx84"H, Black


Double-sided High density with doors, 10"Wx84"H, Black
Double-sided High density with doors, 12"Wx84"H, Black
High/Low density combination with front doors, 6"Wx84"H, Black
High/Low density combination with front doors, 10"Wx84"H, Black
High/Low density combination with front doors, 12"Wx84"H, Black
Vertical Manager Backcover, 6"W, Black
Vertical Manager Backcover, 10"W, Black
Vertical Manager Backcover, 12"W, Black

BHVHH06
BHVHH10
BHVHH12
BHVHL06
BHVHL10
BHVHL12
BHBC06X
BHBC10X
BHBC12X

Horizontal Manager with Cover 19"Wx1U, Black


Horizontal Manager with Cover 19"Wx2U, Black
Horizontal Manager with Cover 19"Wx3U, Black

BHH191U
BHH192U
BHH193U

Top transition channel, 19"Wx6"D, Black


Lower transition channel, 19"Wx6"D, Black
Lower transition channel double, 19"Wx6"D, Black
Transition tray (rack to rack)

BHTT196
BHTL196
BHTD196
BHTR196

Slack management spool kit, Black


Divider bar, 10"W, Black
Divider bar, 12"W, Black

BHSK020
BHDB10X
BHDB12H

Vertical Managers

Horizontal Managers

Transition Channels

Accessories

See Belden New Product Bulletin 247 for more details

www.belden.com

1.800.BELDEN.1

33

Data Center Product Offering:


Cable Management (continued)

Enclosures
DESCRIPTION

ORDERING NUMBER (CPC)

30-inch Enclosures

www.belden.com

High Density Cabinet 84"Hx30"Wx43"D, Black, four rail kit, 12-24 tap, screws,
perforated door, corrugated panel front and back, no side panels

XHD84432110

Side Panel Set, 84x30x43"deep frame (2 sides)


High Density Cabinet 84"H x30"Wx43"D, Black, four rail kit, 12-24 tap, screws,
perforated door, corrugated panel front and back, side panel kit, two sides
Door, perforated split, 84"H x 30"W frame, perforated door set with
flat panel key locking swing handle, retractable hinge pins.
Vertical Manager Backplane kit (use w/ganged 30"W) backplane kit, span gap
between posts of ganged 30"W cabinets. Includes (8) half assemblies
Vertical Manager Backplane kit (use w/single 30"W cabinet) backplane kit,
attach to post of single 30"W cabinet -or- to a 30"W cabinet ganged
to 24"W cabinet, includes (4) assemblies
Vertical Manager Backplane kit (use w/extension) backplane kit,
span gap between posts of ganged cabinets when using center extension.
Includes (8) half assemblies
Slack Cable Spool Kit (set of two) set of two spools w/hdwr
Side horizontal manager 43" deep (single wide) front-to-rear horizontal manager single wide,
span gap from front post to rear post of 43" deep cabinet
Side horizontal manager 43" deep (double wide) front-to-rear horizontal manager double wide,
span gap from front post to rear post of 43" deep cabinet
Ladder Tray Mounting Kit top mount ladder tray bracket
Power Strip Mounting bracket vertical power strip mounting bracket, full height,
10-32 clinch nuts AND keyhole slot for APC & Geist 66" strips

XHD844302SP
XHD84432112

1.800.BELDEN.1

XHD8430PDS
XHDVMBP
XHDVMBPS

XHDVMBP-13

XHDMS02
XHDMFR143
XHDMFR243
XHD8430LM
XHD84PM

34

Data Center Product Offering:


Cable Management (continued)

Enclosures
DESCRIPTION

ORDERING NUMBER (CPC)

24-inch Enclosures
High Density Cabinet 84"H x 24"W x 43"D, Black, four rail kit, 12-24 tap, screws,
perforated door, corrugated panel front and back, no side panels
Side Panel Set, 84"H x 24"W x43"D deep frame (2-sides)
High Density Cabinet 84"H x 24"W x 43"D, Black, four rail kit, 12-24 tap, screws,
perforated door, corrugated panel front and back, side panel kit, two sides
Door, perforated, 84"H x 24"W frame, perforated door set w/flat panel key locking
swing handle, retractable hinge.
Door, 940 cfm exhaust fan, 84"H x 24"W frame, solid door with four 7" diameter
exhaust fans, 940 cfm total, key locking swing handle, retractable hinge pins.
Ladder tray mounting kit top mount ladder tray bracket
Rear Vertical Fill Panel (use without rear fingers) rear vertical filler panel to span gap
between rear frame post and rear door when not using rear mounted fingers

XHDS84432110
XHDS844302SP
XHDS84432112
XHDS8424PDS
XHDS8424FD
XHDS8424LM
XHDS84RVF

Cable Management
Extension Kits
Extension Frame Center, 6"W x 43"D deep frame open bay extension 6"wide,
between 43" deep cabinets, includes front and rear covers
Extension Frame Side, 6"W x 43"D deep frame open bay extension 6"wide, end of row,
43" deep cabinets, includes front and rear covers, includes side panel kit

XHD8443CXF
XHD8443SXF

Accessories
1U 19" Solid Filler Panel, Black
2U 19" Solid Filler Panel, Black

9910-0100
9911-0200

3U 19" Solid Filler Panel, Black

9912-0300

See Belden New Product Bulletin 268 for more details

www.belden.com

1.800.BELDEN.1

35

Data Center Product Offering:


Copper Cabling

Copper Products
DESCRIPTION

ORDERING NUMBER (CPC)

10GX Cable Assemblies


10GX Pre-term. Cable Assy, Bonded-Pair, 4-Pair, 23 AWG Solid,
T568 A/B-T568 A/B, 6 Cables Use xxx to specify length in feet
See NPB 293 for more details

Black
Gray
CA21100xxxA06

White
Yellow
CA21109xxxA06

Green

Blue
CA21106xxxA06

10GX Modular Couplers


10GX KeyConnect RJ45 Coupler, Black
See NPB 293 for more details

Black
AX104024

Gray

White

Yellow

Green

Blue

10GX Modules, KeyConnect


10GX KEYSTONE MOD. T568A/B CAT6A, Black
Other colors available

Black
AX102283

Gray
AX102284

White
AX102285

Yellow
AX102286

Green
AX102287

Blue
AX102288

Gray

White

Yellow

Green

Blue

CA21108002
CA21108003
CA21108004
CA21108005
CA21108006
CA21108007
CA21108008
CA21108009
CA21108010
CA21108012
CA21108015
CA21108025

CA21109002
CA21109003
CA21109004
CA21109005
CA21109006
CA21109007
CA21109008
CA21109009
CA21109010
CA21109012
CA21109015
CA21109025

CA21104002
CA21104003
CA21104004
CA21104005
CA21104006
CA21104007
CA21104008
CA21104009
CA21104010
CA21104012
CA21104015
CA21104025

CA21105002
CA21105003
CA21105004
CA21105005
CA21105006
CA21105007
CA21105008
CA21105009
CA21105010
CA21105012
CA21105015
CA21105025

CA21106002
CA21106003
CA21106004
CA21106005
CA21106006
CA21106007
CA21106008
CA21106009
CA21106010
CA21106012
CA21106015
CA21106025

Gray

White

Yellow

Green

Blue

10GX Patch Cords


Black
10GX Modular Cord, Bonded-Pair, 4-Pair, 23 AWG Solid, T568A/B - T568A/B, CMR
2 ft (0.6 m)
CA21100002
3 ft (0.9 m)
CA21100003
4 ft (1.2 m)
CA21100004
5 ft (1.5 m)
CA21100005
6 ft (1.8 m)
CA21100006
7 ft (2.1 m)
CA21100007
8 ft (2.4 m)
CA21100008
9 ft (2.7 m)
CA21100009
10 ft (3.0 m)
CA21100010
12 ft (3.6 m)
CA21100012
15 ft (4.6 m)
CA21100015
25 ft (7.6 m)
CA21100025
Other lengths and colors available
10GX Pigtails
10GX Pigtail, 4-Pair, 23 AWG Solid, T568A Open, CMR
15 ft (4.6 m)
25 ft (7.6 m)
35 ft (10.6 m)
50 ft (15.0 m)
Other lengths and colors available

Black

CAT6+ Modules, KeyConnect

Black

Gray

White

Yellow

Green

Blue

CAT6+ KEYCONNECT MODULE, T568A/B CODED

AX101321

AX101322

AX101323

AX101324

AX101325

AX101326

www.belden.com

CA21208015
CA21208025
CA21208035
CA21208050

1.800.BELDEN.1

36

Data Center Product Offering:


Copper Cabling (continued)

Copper Products (continued)


DESCRIPTION

ORDERING NUMBER (CPC)

CAT6+ Patch Cords

Black

Gray

White

Yellow

Green

Blue

CAT6+PatchCord, Bonded-Pair, 4-Pair, 24AWG Solid, T568A/B-T568A/B, CMR


2 ft (0.6 m)

C601100002

C601108002

C601109002

C601104002

C601105002

C601106002

3 ft (0.9 m)

C601100003

C601108003

C601109003

C601104003

C601105003

C601106003

4 ft (1.2 m)

C601100004

C601108004

C601109004

C601104004

C601105004

C601106004

5 ft (1.5 m)

C601100005

C601108005

C601109005

C601104005

C601105005

C601106005

6 ft (1.8 m)

C601100006

C601108006

C601109006

C601104006

C601105006

C601106006

7 ft (2.1m)

C601100007

C601108007

C601109007

C601104007

C601105007

C601106007

8 ft (2.4 m)

C601100008

C601108008

C601109008

C601104008

C601105008

C601106008

9 ft (2.7 m)

C601100009

C601108009

C601109009

C601104009

C601105009

C601106009

10 ft (3.0 m)

C601100010

C601108010

C601109010

C601104010

C601105010

C601106010

15 ft (4.6 m)

C601100015

C601108015

C601109015

C601104015

C601105015

C601106015

25 ft (7.6 m)

C601100025

C601108025

C601109025

C601104025

C601105025

C601106025

CAT6+ Pigtails
CAT6+ Pigtail, 4-Pair, 23 AWG Solid, T568A Open, CMR
15 ft (4.6 m)

C601208015

25 ft (7.6 m)

C601208025

35 ft (10.6 m)

C601208035

50 ft (15.0 m)

C601208050

See Belden New Product Bulletin 279 for more details


KeyConnect Patch Panels
KeyConnect Patch Panel, 1U, 48-port, Black

AX103121

KeyConnect Patch Panel, 1U, 24-port, Black

AX103114

KeyConnect Patch Panel, 2U,48-port, Black

AX103115

KeyConnect Patch Panel, 2U, 72-port, Black

AX103116

AngleFlex Patch Panel, 1U, 24-port, Black

AX103248

AngleFlex Patch Panel, 2U, 48-port, Black

AX103249

KeyConnect blank module

AX102263

See Belden New Product Bulletins 276 and 277 for more details

www.belden.com

1.800.BELDEN.1

37

Data Center Product Offering:


Copper Cabling (continued)

Copper Products (continued)


DESCRIPTION

ORDERING NUMBER (CPC)

10GX Cables
10GX Cable, Category 6A Bonded-Pairs, plenum, Blue

10GX33 D151000

10GX Cable, Category 6A Bonded-Pairs, plenum, White

10GX33 0091000

10GX Cable, Category 6A Bonded-Pairs, riser, Blue

10GX32 0061000

10GX Cable, Category 6A Bonded-Pairs, riser, White

10GX32 0091000

10GX Cable, CMP 4-pair, Nonbonded 10GX13, Category 6 Nonbonded, plenum, Blue

10GX13 D151000

10GX Cable, CMP 4-pair, Nonbonded 10GX13, Category 6 Nonbonded, plenum, White

10GX13 0091000

10GX Cable, CMR 4-pair, Nonbonded 10GX12, Category 6 Nonbonded, riser, Blue

10GX12 0061000

10GX Cable, CMR 4-pair, Nonbonded 10GX12, Category 6 Nonbonded, riser, White

10GX12 0091000

CAT6+ Cables
DataTwist 4800, Category 6 Bonded-Pairs, plenum, Blue

7852A D151000

DataTwist 4800, Category 6 Bonded-Pairs, plenum, White

7852A 0091000

DataTwist 4800, Category 6 Bonded-Pairs, riser, Blue

7851A 0061000

DataTwist 4800, Category 6 Bonded-Pairs, riser, White

7851A 0091000

DataTwist 48000, Category 6 Nonbonded, plenum, Blue

4813 D151000

DataTwist 48000, Category 6 Nonbonded, plenum, White

4813 0091000

DataTwist 48000, Category 6 Nonbonded, riser, Blue

4812 0061000

DataTwist 48000, Category 6 Nonbonded, riser, White

4812 0091000

Accessories
Patch Cord Tool

AX102775

Velcro Cable Ties, 25 per Roll, Black, 8 in.

AX100783

Velcro Cable Ties, 25 per Roll, Black, 12 in.

AX100784

Wrap-around Labels, Gray, 48 Labels/Sheet (25 sheets per pack)

AX101555

Connecting Tool

AX100749

Termination Station

AX101852

Release Tool

AX101185

Cable Preparation Tool

www.belden.com

1797B

1.800.BELDEN.1

38

Data Center Product Offering:


Fiber Optic Cabling

Fiber Products
DESCRIPTION

ORDERING NUMBER (CPC)

Optimax Connectors
Optimax Field Installable Connector, LC, Multimode 50m, for 900m tight buffered fiber

AX101982

Optimax Field Installable Connector, LC, Single-mode, for 900m tight buffered fiber

AX101983

Optimax LC Accessory Kit for jacketed fiber, contains 2mm and 3mm boots and crimp sleeves

AX101984

Tools
Optimax Installation Tool Kit LC/SC/ST, Incl. Install. tools, cleaver, manuals, crimping tool, microscope, etc

AX100947

Optimax Installation Tool Kit LC upgrade Incl. LC Install. tools, LC manual and new carrying case foam

AX102061

FiberExpress Ultra Management System


Shelves
1U

AX103143

4U

AX103267

Frames and Modules


FXU FRAME, LC-DUPLEX, 12f, OM3

AX103463

FXU FRAME, LC-DUPLEX, 24f, OM3

AX103465

FXU MPO-PRETERM, LC-DUPLEX, 12f, OM3

AX103713

FXU MPO-PRETERM, LC-DUPLEX, 24f, OM3

AX103729

FXU FRAME, LC-DUPLEX, 12f, SINGLE-MODE

AX103502

FXU FRAME, LC-DUPLEX, 24f, SINGLE-MODE

AX103519

FXU MPO-PRETERM, LC-DUPLEX, 12f, SINGLE-MODE

AX103821

FXU MPO-PRETERM, LC-DUPLEX, 24f, SINGLE-MODE

AX103837

See NPB 287 for more details.

www.belden.com

1.800.BELDEN.1

39

Data Center Product Offering:


Fiber Optic Cabling (continued)

Fiber Products (continued)


DESCRIPTION

ORDERING NUMBER (CPC)

Fiber Patch Cords


Fiber Optic Patch Cord, Duplex Zip 2.0mm LCD/PC-LCD/PC, 2f, FX2K, 1 m, Riser

AX200992

Fiber Optic Patch Cord, Duplex Zip 2.0mm LCD/PC-LCD/PC, 2f, FX2K, 2 m, Riser

AX200664

Fiber Optic Patch Cord, Duplex Zip 2.0mm LCD/PC-LCD/PC, 2f, FX2K, 3 m, Riser

AX200665

Fiber Optic Patch Cord, Duplex Zip 2.0mm LCD/PC-LCD/PC, 2f, FX2K, 5 m, Riser

AX200666

Fiber Optic Patch Cord, Duplex Zip 2.0mm LCD/UPC-LCD/UPC, 2f, SM, 1 m, Riser

AX200506

Fiber Optic Patch Cord, Duplex Zip 2.0mm LCD/UPC-LCD/UPC, 2f, SM, 2 m, Riser

AX200507

Fiber Optic Patch Cord, Duplex Zip 2.0mm LCD/UPC-LCD/UPC, 2f, SM, 3 m, Riser

AX200508

Fiber Optic Patch Cord, Duplex Zip 2.0mm LCD/UPC-LCD/UPC, 2f, SM, 5 m, Riser

AX200509

Multi-duplex Cable Assemblies


Distribution Cable, 12f, LC-LC, FX2000, OFNR, 10 m

NXC-MRFL-LCPFBN-LCPFBN-O-0010

Distribution Cable, 12f, LC-LC, FX2000, OFNP, 10 m

NXC-MPFL-LCPFBN-LCPFBN-O-0010

Distribution Cable, 24f, LC-LC, FX2000, OFNR, 10 m

NXC-MRFX-LCPFBN-LCPFBN-O-0010

Distribution Cable, 24f, LC-LC, FX2000, OFNP, 10 m

NXC-MPFX-LCPFBN-LCPFBN-O-0010

Distribution Cable, 12f, LC-LC, SM, OFNR, 10 m

NXC-MRSL-LCUFBN-LCUFBN-O-0010

Distribution Cable, 12f, LC-LC, SM, OFNP, 10 m

NXC-MPSL-LCUFBN-LCUFBN-O-0010

Distribution Cable, 24f, LC-LC, SM, OFNR, 10 m

NXC-MRSX-LCUFBN-LCUFBN-O-0010

Distribution Cable, 24f, LC-LC, SM, OFNP, 10 m

NXC-MPSX-LCUFBN-LCUFBN-O-0010

www.belden.com

1.800.BELDEN.1

40

Data Center Product Offering:


Fiber Optic Cabling (continued)

Fiber Products (continued)


DESCRIPTION

ORDERING NUMBER (CPC)

MPO Cable Assemblies


MPO Cable, 12f, MPO-MPO, type-C, FX2000, OFNR, 10 m

NXC-URFL-PHXFGN-PHPFGN-O-0010

MPO Cable, 12f, MPO-MPO, type-C, FX2000, OFNP, 10 m

NXC-UPFL-PHXFGN-PHPFGN-O-0010

MPO Cable, 24f, MPO-MPO, type-C, FX2000, OFNR, 10 m

NXC-URFX-PHXFGN-PHPFGN-O-0010

MPO Cable, 24f, MPO-MPO, type-C, FX2000, OFNP, 10 m

NXC-UPFX-PHXFGN-PHPFGN-O-0010

MPO Cable, 12f, MPO-MPO, type-C, SM, OFNR, 10 m

NXC-URSL-PHXFGN-PHPFGN-O-0010

MPO Cable, 12f, MPO-MPO, type-C, SM, OFNP, 10 m

NXC-UPSL-PHXFGN-PHPFGN-O-0010

MPO Cable, 24f, MPO-MPO, type-C, SM, OFNR, 10 m

NXC-URSX-PHXFGN-PHPFGN-O-0010

MPO Cable, 24f, MPO-MPO, type-C, SM, OFNP, 10 m

NXC-UPSX-PHXFGN-PHPFGN-O-0010

Fiber Cables
Distribution 12f, FX2000, OFNR

B9C042

Distribution 12f, FX2000, OFNP

B9C048

Distribution 24f, FX2000, OFNR

B9C602

Distribution 24f, FX2000, OFNP

B9C612

Distribution 12f, SM, OFNR

B9W042

Distribution 12f, SM, OFNP

B9W048

Distribution 24f, SM, OFNR

B9W602

Distribution 24f, SM, OFNP

B9W612

Accessories
75 ft Roll x 1/2 in. Bulk Velcro

AX102515

12 in. Fiber Optic Cable Manager

AX102516

24 in. Fiber Optic Cable Manager

AX102517

www.belden.com

1.800.BELDEN.1

41

www.belden.com

GLOBAL LOCATIONS

Customer Service:
800-BELDEN-1 (800-235-3361)
See www.belden.com for a
complete listing of Belden locations.

UNITED STATES

LATIN AMERICA and the


CARIBBEAN ISLANDS

CANADA

Division HeadquartersAmericas

Regional Office

National Business Center

2200 U.S. Highway 27 South


Richmond, IN 47374

6100 Hollywood Boulevard


Suite 110
Hollywood, Florida 33024
Phone: 954-987-5044
Fax: 954-987-8022
salesla@belden.com

2280 Alfred-Nobel
Suite 200
Saint-Laurent, QC
Canada H4S 2A4

Phone: 765-983-5200

Inside Sales: 800-235-3361


Fax: 765-983-5294
info@belden.com
web: www.belden.com

Phone: 514-822-2345

Fax: 514-822-7979

Copyright 2009,V2 Belden Inc. Printed in U. S. A.

You might also like