MANUAL
GAS & ENERGIA
CLIENT:
JOB:
I-MA-4451.28-6250-27D-FRB-002
SHEET
1 OF 73
REA:
PECEM PORT
TITLE:
ENG. RESP.
INS-36789-MA-001
REVISON INDEX
REV
0
A
B
DATE
REV. 0
REV. A
REV. B
01/07/08
06/26/08
07/21/08
AUTOMIND
AUTOMIND
AUTOMIND
EXECUTION
GGC
CMV
CMV
CHECK
AVNO
AVNO
AVNO
APPROVAL
AVNO
AVNO
AVNO
DESIGN
REV. C
REV. D
REV. E
REV. F
REV. G
REV. H
THE INFORMATIONS CONTAINED IN THIS DOCUMENT IS PETROBRAS PROPERY AND MAY NOT BE USED FOR PURPOSES OTHER THAN THOSE SPECIFICALLY INDICATED
HEREIN / FORM STANDARTIZED BY STANDARD PETROBRAS N-381 REV. G
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
NUMBER
I-MA-4451.28-6250-27D-FRB-002
SHEET
FQY - 413
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
2 OF 73
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
NUMBER
I-MA-4451.28-6250-27D-FRB-002
SHEET
REV
3 OF 73
INTRODUCTION .................................................................................................................................................................... 7
REFERENCES ....................................................................................................................................................................... 7
3.2
3.3
3.4
STREAM: #1........................................................................................................................................................................ 7
3.1.1
GENERAL............................................................................................................................................................... 7
3.1.2
INPUTS................................................................................................................................................................... 7
3.1.3
3.1.4
3.1.5
ALARMS ................................................................................................................................................................. 8
STREAM: #2........................................................................................................................................................................ 9
3.2.1
GENERAL............................................................................................................................................................... 9
3.2.2
INPUTS................................................................................................................................................................... 9
3.2.3
3.2.4
3.2.5
ALARMS ................................................................................................................................................................. 10
STREAM: #3........................................................................................................................................................................ 10
3.3.1
GENERAL............................................................................................................................................................... 10
3.3.2
INPUTS................................................................................................................................................................... 10
3.3.3
3.3.4
3.3.5
ALARMS ................................................................................................................................................................. 12
STREAM: #4........................................................................................................................................................................ 12
3.4.1
GENERAL............................................................................................................................................................... 12
3.4.2
INPUTS................................................................................................................................................................... 12
3.4.3
3.4.4
3.4.5
ALARMS ................................................................................................................................................................. 13
4.2
4.3
4.4
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
5.1
5.2
5.3
5.4
5.5
5.6
NUMBER
I-MA-4451.28-6250-27D-FRB-002
SHEET
REV
4 OF 73
GENERAL............................................................................................................................................................... 16
5.1.2
ADVANCED ............................................................................................................................................................ 16
5.1.3
ALARMS ................................................................................................................................................................. 17
GENERAL............................................................................................................................................................... 17
5.2.2
ADVANCED ............................................................................................................................................................ 17
5.2.3
ALARMS ................................................................................................................................................................. 18
GENERAL............................................................................................................................................................... 18
5.3.2
ADVANCED ............................................................................................................................................................ 18
5.3.3
ALARMS ................................................................................................................................................................. 18
GENERAL............................................................................................................................................................... 19
5.4.2
ADVANCED ............................................................................................................................................................ 19
5.4.3
ALARMS ................................................................................................................................................................. 19
GENERAL............................................................................................................................................................... 20
5.5.2
ADVANCED ............................................................................................................................................................ 20
5.5.3
ALARMS ................................................................................................................................................................. 20
GENERAL............................................................................................................................................................... 20
5.6.2
ADVANCED ............................................................................................................................................................ 21
5.6.3
ALARMS ................................................................................................................................................................. 21
GENERAL............................................................................................................................................................... 21
6.1.2
ADVANCED ............................................................................................................................................................ 22
6.1.3
ALARMS ................................................................................................................................................................. 22
8.1
8.2
8.3
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
SHEET
REV
12
13
14
15
FST'S...................................................................................................................................................................................... 28
15.1 FST 1................................................................................................................................................................................... 28
15.2 FST 2................................................................................................................................................................................... 30
15.3 FST 3................................................................................................................................................................................... 33
15.4 FST 4................................................................................................................................................................................... 33
16
HISTORY................................................................................................................................................................................ 34
16.1 STREAM 01......................................................................................................................................................................... 34
16.2 STREAM 02......................................................................................................................................................................... 34
16.3 STREAM 03......................................................................................................................................................................... 34
16.4 STREAM 04......................................................................................................................................................................... 35
17
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
5 OF 73
10
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
NUMBER
I-MA-4451.28-6250-27D-FRB-002
SHEET
REV
6 OF 73
FLAGS.................................................................................................................................................................................... 37
18.1 FLAGS................................................................................................................................................................................. 37
18.1.1 ADVANCED ............................................................................................................................................................ 37
19
20
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
SHEET
REV
7 OF 73
INTRODUCTION
The purpose of this document is to detail the configuration of the Flow Computer FQY-413, of the Metering
System on LNG Flexible Terminal, at Pecm Port CE.
REFERENCES
3.1
STREAM: #1
3.1.1
GENERAL
Item
Description
Valor
Meter Tag
STREAM Identification
FIT-413
Meter Description
STREAM Description
Meter Type
Meter Type
Turbine
Alarming
Enabled
Scan Period
Scan Period
1 Seconds
3.1.2
INPUTS
Item
Description
Value
Uncorrected Volume
PIN A7, EU
Static Pressure
AIN A3, EU
Temperature
Temperature Input
AIN A1, EU
3.1.3
GAS QUALITY
Item
Description
Value
Nitrogen
Input by Operator
CO2
Input by Operator
Methane
Input by Operator
Ethane
Input by Operator
Propane
Input by Operator
n-Butane
Input by Operator
i-Butane
Input by Operator
n-Pentane
Input by Operator
i-Pentane
Input by Operator
Hexane
Input by Operator
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
NUMBER
MANUAL
JOB OR PROJECT
Heptane
Input by Operator
Octane
Input by Operator
Nonane
Input by Operator
Decane
Input by Operator
H2S
Input by Operator
Water
Input by Operator
Helium
Input by Operator
Oxygen
Input by Operator
CO
Input by Operator
Hydrogen
Input by Operator
Dry
Adjust of methane
Enabled
Heating Value
Heating Value
Calculate (MJ/M3)
Spec Gravity
Specific Gravity
Calculate
3.1.4
SHEET
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
ADVANCED FEATURES
Item
Description
Valor
FPV Method
Type Calculation
Detailed
Units
Units
Metric KM3/GJ
Base Temperature
Base Temperature
20 Deg C
Base Pressure
Base Pressure
101.325 kPa
Atmospheric Pressure
Atmospheric Pressure
Elevation
Elevation
0.0 Meters
Latitude
Latitude
0.0 Deg
Gravity Correction
1.0
Pressure Tap
Pressure Tap
Gauge
Meter Factor
Meter Factor
1.0
3.1.5
ALARMS
Item
Description
Value
Low Alarm
1000
High Alarm
7900
RBX Alarming
Disabled
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
8 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
3.2
I-MA-4451.28-6250-27D-FRB-002
SHEET
STREAM: #2
3.2.1
GENERAL
Item
Description
Valor
Meter Tag
STREAM Identification
Not Applicable
Meter Description
STREAM Description
Not Applicable
Meter Type
Meter Type
Not Applicable
Alarming
Disabled
Scan Period
Scan Period
Not Applicable
3.2.2
INPUTS
Item
Description
Value
Uncorrected Volume
Manual
Static Pressure
Manual
Temperature
Temperature Input
Manual
3.2.3
GAS QUALITY
Item
Description
Value
Nitrogen
Not Applicable
CO2
Not Applicable
Methane
Not Applicable
Ethane
Not Applicable
Propane
Not Applicable
n-Butane
Not Applicable
i-Butane
Not Applicable
n-Pentane
Not Applicable
i-Pentane
Not Applicable
Hexane
Not Applicable
Heptane
Not Applicable
Octane
Not Applicable
Nonane
Not Applicable
Decane
Not Applicable
H2S
Not Applicable
Water
Not Applicable
Helium
Not Applicable
Oxygen
Not Applicable
CO
Not Applicable
Hydrogen
Not Applicable
Not Applicable
Adjust of methane
Disabled
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
9 OF 73
NUMBER
MANUAL
JOB OR PROJECT
Heating Value
Heating Value
Not Applicable
Spec Gravity
Specific Gravity
Not Applicable
3.2.4
ADVANCED FEATURES
Item
Description
Valor
FPV Method
Type Calculation
Not Applicable
Units
Units
Not Applicable
Base Temperature
Base Temperature
Not Applicable
Base Pressure
Base Pressure
Not Applicable
Atmospheric Pressure
Atmospheric Pressure
Not Applicable
Elevation
Elevation
Not Applicable
Latitude
Latitude
Not Applicable
Gravity Correction
Not Applicable
Pressure Tap
Pressure Tap
Not Applicable
Meter Factor
Meter Factor
Not Applicable
3.2.5
ALARMS
Item
Description
Value
Low Alarm
Not Applicable
High Alarm
Not Applicable
RBX Alarming
Disabled
3.3
3.3.1
STREAM: #3
GENERAL
Item
Description
Valor
Meter Tag
STREAM Identification
Not Applicable
Meter Description
STREAM Description
Not Applicable
Meter Type
Meter Type
Not Applicable
Alarming
Disabled
Scan Period
Scan Period
Not Applicable
3.3.2
SHEET
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
INPUTS
Item
Description
Value
Uncorrected Volume
Manual
Static Pressure
Manual
Temperature
Temperature Input
Manual
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
10 OF 73
NUMBER
MANUAL
JOB OR PROJECT
3.3.3
GAS QUALITY
Item
Nitrogen
Description
Value
Not Applicable
CO2
Not Applicable
Methane
Not Applicable
Ethane
Not Applicable
Propane
Not Applicable
n-Butane
Not Applicable
i-Butane
Not Applicable
n-Pentane
Not Applicable
i-Pentane
Not Applicable
Hexane
Not Applicable
Heptane
Not Applicable
Octane
Not Applicable
Nonane
Not Applicable
Decane
Not Applicable
H2S
Not Applicable
Water
Not Applicable
Helium
Not Applicable
Oxygen
Not Applicable
CO
Not Applicable
Hydrogen
Not Applicable
Not Applicable
Adjust of methane
Disabled
Heating Value
Heating Value
Not Applicable
Spec Gravity
Specific Gravity
Not Applicable
3.3.4
SHEET
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
ADVANCED FEATURES
Item
Description
Valor
FPV Method
Type Calculation
Not Applicable
Units
Units
Not Applicable
Base Temperature
Base Temperature
Not Applicable
Base Pressure
Base Pressure
Not Applicable
Atmospheric Pressure
Atmospheric Pressure
Not Applicable
Elevation
Elevation
Not Applicable
Latitude
Latitude
Not Applicable
Gravity Correction
Not Applicable
Pressure Tap
Pressure Tap
Not Applicable
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
11 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
3.3.5
I-MA-4451.28-6250-27D-FRB-002
ALARMS
Item
Description
Value
Low Alarm
Not Applicable
High Alarm
Not Applicable
RBX Alarming
Disabled
3.4
SHEET
STREAM: #4
3.4.1
GENERAL
Item
Description
Valor
Meter Tag
STREAM Identification
Not Applicable
Meter Description
STREAM Description
Not Applicable
Meter Type
Meter Type
Not Applicable
Alarming
Disabled
Scan Period
Scan Period
Not Applicable
3.4.2
INPUTS
Item
Description
Value
Uncorrected Volume
Manual
Static Pressure
Manual
Temperature
Temperature Input
Manual
3.4.3
GAS QUALITY
Item
Description
Value
Nitrogen
Not Applicable
CO2
Not Applicable
Methane
Not Applicable
Ethane
Not Applicable
Propane
Not Applicable
n-Butane
Not Applicable
i-Butane
Not Applicable
n-Pentane
Not Applicable
i-Pentane
Not Applicable
Hexane
Not Applicable
Heptane
Not Applicable
Octane
Not Applicable
Nonane
Not Applicable
Decane
Not Applicable
H2S
Not Applicable
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
12 OF 73
NUMBER
MANUAL
JOB OR PROJECT
I-MA-4451.28-6250-27D-FRB-002
AREA/UNIT:
TITLE
Water
Not Applicable
Helium
Not Applicable
Oxygen
Not Applicable
CO
Not Applicable
Hydrogen
Not Applicable
Not Applicable
Adjust of methane
Disabled
Heating Value
Heating Value
Not Applicable
Spec Gravity
Specific Gravity
Not Applicable
3.4.4
ADVANCED FEATURES
Item
Description
Valor
FPV Method
Type Calculation
Not Applicable
Units
Units
Not Applicable
Base Temperature
Base Temperature
Not Applicable
Base Pressure
Base Pressure
Not Applicable
Atmospheric Pressure
Atmospheric Pressure
Not Applicable
Elevation
Elevation
Not Applicable
Latitude
Latitude
Not Applicable
Gravity Correction
Not Applicable
Pressure Tap
Pressure Tap
Not Applicable
3.4.5
ALARMS
Item
Description
Value
Low Alarm
Not Applicable
High Alarm
Not Applicable
RBX Alarming
Disabled
SHEET
4.1
Description
Value
Tag
MVS Identification
Address
Address RS-485
Not Applicable
Not Applicable
Scanning
Disabled
Units
Unit System
Not Applicable
Sensor Alarms
Disabled
Disabled
Not Applicable
Low Alarm
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
13 OF 73
NUMBER
MANUAL
JOB OR PROJECT
I-MA-4451.28-6250-27D-FRB-002
AREA/UNIT:
TITLE
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Disabled
Pressure Alarm
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Disabled
Temperature Alarm
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Report Pressure As
Upstream or Downstream
Not Applicable
Action on Failure
Action on Failure
Not Applicable
RBX Alarming
Exception Alarm
Disabled
Reference Temperature
Reference Temperature
Not Applicable
4.2
SHEET
Description
Value
Tag
MVS Identification
Not Applicable
Address
Address RS-485
Not Applicable
Scanning
Disabled
Units
Unit System
Not Applicable
Sensor Alarms
Disabled
Disabled
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Disabled
Pressure Alarm
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Temperature Alarm
Disabled
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Report Pressure As
Not Applicable
Upstream or Downstream
Not Applicable
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
14 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
I-MA-4451.28-6250-27D-FRB-002
TITLE
Action on Failure
Action on Failure
Not Applicable
RBX Alarming
Exception Alarm
Disabled
Reference Temperature
Reference Temperature
Not Applicable
4.3
Description
Value
Tag
MVS Identification
Not Applicable
Address
Address RS-485
Not Applicable
Scanning
Disabled
Units
Unit System
Not Applicable
Sensor Alarms
Disabled
Disabled
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Pressure Alarm
Not Applicable
Disabled
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Temperature Alarm
Disabled
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Report Pressure As
Action on Failure
Upstream or Downstream
Action on Failure
Not Applicable
Not Applicable
RBX Alarming
Exception Alarm
Disabled
Reference Temperature
Reference Temperature
Not Applicable
4.4
SHEET
Tag
Description
MVS Identification
Value
Not Applicable
Address
Address RS-485
Not Applicable
Scanning
Disabled
Units
Unit System
Not Applicable
Sensor Alarms
Disabled
Disabled
Not Applicable
Low Alarm
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
15 OF 73
NUMBER
MANUAL
JOB OR PROJECT
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Disabled
Pressure Alarm
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Disabled
Temperature Alarm
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Report Pressure As
Upstream or Downstream
Not Applicable
Action on Failure
Action on Failure
Not Applicable
RBX Alarming
Exception Alarm
Disabled
Reference Temperature
Reference Temperature
Not Applicable
SHEET
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
5.1
5.1.1
GENERAL
Item
Description
Value
Scanning
Enabled
Alarming
Enabled
Units
Unit of Engineering
Scan Period
Scan Period
1 Seconds
Low Reading EU
High Reading EU
70
5.1.2
ADVANCED
Item
Description
Value
Filter
Filter
Adjusted A/D 0%
800
4000
Action on Failure
Action on Failure
Fault Value
Value on Failure
Not Applicable
Enabled
Disabled
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
16 OF 73
NUMBER
MANUAL
JOB OR PROJECT
Temp Compensation
5.1.3
Disabled
ALARMS
Item
Description
Value
Low Alarm
Low Alarm
High Alarm
High Alarm
60
LoLo Alarm
LoLo Alarm
HiHi Alarm
HiHi Alarm
75
Rate Alarm
Rate Alarm
70
Alarm Deadband
Alarm Deadband
RBX Alarming
RBX Alarming
Disabled
5.2
SHEET
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
5.2.1
GENERAL
Item
Description
Value
Scanning
Disabled
Alarming
Disabled
Units
Unit of Engineering
Not Applicable
Scan Period
Scan Period
Not Applicable
Low Reading EU
Not Applicable
High Reading EU
Not Applicable
5.2.2
ADVANCED
Item
Filter
Description
Value
Filter
Not Applicable
Adjusted A/D 0%
Not Applicable
Not Applicable
Action on Failure
Action on Failure
Not Applicable
Fault Value
Value on Failure
Not Applicable
Disabled
Disabled
Disabled
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
17 OF 73
NUMBER
MANUAL
JOB OR PROJECT
5.2.3
SHEET
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
ALARMS
Item
Description
Value
Low Alarm
Low Alarm
High Alarm
High Alarm
Not Applicable
LoLo Alarm
Not Applicable
HiHi Alarm
Not Applicable
Rate Alarm
Rate Alarm
Not Applicable
Alarm Deadband
Alarm Deadband
Not Applicable
RBX Alarming
RBX Alarming
Disabled
5.3
Not Applicable
5.3.1
GENERAL
Item
Description
Value
Scanning
Enabled
Alarming
Enabled
Units
Unit of Engineering
kPa
Scan Period
Scan Period
1 Seconds
Low Reading EU
High Reading EU
9317
5.3.2
ADVANCED
Item
Filter
Description
Value
Filter
Adjusted A/D 0%
800
4000
Action on Failure
Action on Failure
Fault Value
Value on Failure
Not Applicable
5.3.3
Enabled
Disabled
Disabled
ALARMS
Item
Description
Value
Low Alarm
Low Alarm
High Alarm
High Alarm
9300
LoLo Alarm
HiHi Alarm
9317
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
18 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
Rate Alarm
Rate Alarm
9317
Alarm Deadband
Alarm Deadband
RBX Alarming
RBX Alarming
Disabled
5.4
SHEET
5.4.1
GENERAL
Item
Description
Value
Scanning
Enabled
Alarming
Enabled
Units
Unit of Engineering
Volts
Scan Period
Scan Period
5 Secs
Low Reading EU
0.0
High Reading EU
38.0
5.4.2
ADVANCED
Item
Description
Value
Filter
Filter
Adjusted A/D 0%
4000
5.4.3
Disabled
Disabled
Disabled
ALARMS
Item
Description
Value
Low Alarm
Low Alarm
10.0
High Alarm
High Alarm
30.0
LoLo Alarm
LoLo Alarm
8.0
HiHi Alarm
HiHi Alarm
32.0
Rate Alarm
Rate Alarm
5.0
Alarm Deadband
Alarm Deadband
2.0
RBX Alarming
RBX Alarming
Disabled
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
19 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
5.5
I-MA-4451.28-6250-27D-FRB-002
5.5.1
GENERAL
Item
Description
Value
Scanning
Enabled
Alarming
Enabled
Units
Unit of Engineering
Volts
Scan Period
Scan Period
5 Secs
Low Reading EU
0.0
High Reading EU
38.0
5.5.2
ADVANCED
Item
Description
Value
Filter
Filter
Adjusted A/D 0%
800
4000
5.5.3
Disabled
Disabled
Disabled
ALARMS
Item
Description
Value
Low Alarm
Low Alarm
10.00
High Alarm
High Alarm
30.00
LoLo Alarm
LoLo Alarm
8.00
HiHi Alarm
HiHi Alarm
32.00
Rate Alarm
Rate Alarm
5.00
Alarm Deadband
Alarm Deadband
2.00
RBX Alarming
RBX Alarming
Disabled
5.6
SHEET
5.6.1
GENERAL
Item
Description
Value
Scanning
Enabled
Alarming
Enabled
Units
Unit of Engineering
Scan Period
Scan Period
5 Secs
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
20 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
Low Reading EU
-272.77
High Reading EU
140.55
5.6.2
SHEET
ADVANCED
Item
Description
Value
Filter
Filter
Adjusted A/D 0%
4000
5.6.3
Disabled
Disabled
Disabled
ALARMS
Item
Description
Value
Low Alarm
Low Alarm
10.0
High Alarm
High Alarm
50.0
LoLo Alarm
LoLo Alarm
-272.77
HiHi Alarm
HiHi Alarm
140.55
Rate Alarm
Rate Alarm
400.00
Alarm Deadband
Alarm Deadband
20.00
RBX Alarming
RBX Alarming
Disabled
Obs: Others Analog Inputs must be Configured With Scan and Alarms DISABLED.
6.1
6.1.1
GENERAL
Item
Description
Value
Scanning
Enabled
Alarming
Disabled
Units
Unit of Engineering
Counts
Scan Period
Scan Period
1.0 secs
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
21 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
6.1.2
I-MA-4451.28-6250-27D-FRB-002
SHEET
ADVANCED
Item
Description
Value
EU Options
Value Options
Conversion
Type of Conversion
Pulses/EU
Conversion/K-Factor
Factor of conversion
10937
Rate Period
Rate Period
EU/day
EU Units
Unit of Engineering
MCF/M3
6.1.3
ALARMS
Item
Description
Value
Low Alarm
Not Applicable
High Alarm
Not Applicable
LoLo Alarm
Not Applicable
HiHi Alarm
Not Applicable
Rate Alarm
Not Applicable
Alarm Deadband
Alarm Deadband
Not Applicable
RBX Alarming
Disabled
7.1
Description
Value
ASCII = 0, RTU = 1
Host Enabled = 1
Host Enabled
Init Memory = 1
Init Memory
Port Switch En = 1
DCD = 0, DI = 1, STP = 2
9600
9600
100
300
HI Integer Scale
HI Integer Scale
4095
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
22 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
8.1
SHEET
Description
TYPE
40101
40102
17
128
70
Var. Instant.
40103
40104
10
70
Instantaneous Temperature
Var. Instant.
40105
40106
10
70
Var. Instant.
40107
40108
10
70
Energy Flowrate
Var. Instant.
40109
40110
70
Relative Density
Var. Instant.
40111
40112
10
16
70
Compressibility Factor
Var. Instant.
40113
40114
17
129
11
70
Var. Instant.
40115
40116
42
70
Var. Instant.
40117
40118
42
70
Var. Instant.
10
40119
40120
17
129
12
70
Var. Instant.
8.2
Description
TYPE
40121
40122
42
11
70
Var. Instant.
40123
40124
42
12
70
Var. Instant.
40125
40126
28
70
Parameters
40127
40128
29
70
Parameters
40129
40130
30
70
Parameters
40131
40132
32
70
Parameters
40133
40134
31
70
Parameters
40135
40136
34
70
Parameters
40137
40138
33
70
Parameters
10
40139
40140
35
70
Parameters
8.3
40141
40142
40143
40144
40145
40150
7
8
9
Description
TYPE
23
70
Parameters
24
70
Parameters
17
131
39
Parameters
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
23 OF 73
TITLE
REV
I-MA-4451.28-6250-27D-FRB-002
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
SHEET
9.1
Description
Value
ASCII = 0, RTU = 1
Host Enabled = 1
Host Enabled
Init Memory = 1
Init Memory
Port Switch En = 1
DCD = 0, DI = 1, STP = 2
9600
9600
100
300
HI Integer Scale
HI Integer Scale
4095
10
Description
TYPE
30216
30217
17
128
66
Var. Instant.
30218
30219
10
66
Instantaneous Temperature
Var. Instant.
30220
30221
17
66
Var. Instant.
30222
30223
10
66
Reserve
Reserve
30224
30231
17
128
66
30232
30233
66
Relative Density
Var. Instant.
30234
30235
10
16
66
Compressibility Factor
Var. Instant.
30236
30251
128
28
66
Gas Composition
Parameters
30252
30255
128
23
66
Gas Composition
Parameters
10
30256
30257
66
Heating Value
Var. Instant.
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
24 OF 73
TITLE
10
REV
I-MA-4451.28-6250-27D-FRB-002
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
REV
I-MA-4451.28-6250-27D-FRB-002
SHEET
25 OF 73
TITLE
Description
TYPE
30258
30260
12
128
33
Parameters
30261
30263
12
128
33
Parameters
30500
30501
17
129
66
Var. Instant.
30502
30503
17
129
66
Var. Instant.
30504
30505
17
129
10
66
Var. Instant.
30600
30603
17
129
66
Var. Instant.
30604
30605
42
66
Var. Instant.
30606
30607
42
12
66
Var. Instant.
30608
30609
17
128
15
66
Var. Instant.
10
30800
30803
17
128
11
66
Var. Instant.
Description
TYPE
30113
30113
14
33
30114
30114
130
16
33
Alarms
30115
30115
128
16
33
Alarms
30116
30116
132
16
33
Alarms
30117
30117
135
16
33
Alarms
10
Alarms
Description
TYPE
30301
30326
128
23
66
Parameters
30327
30332
12
128
34
Parameters
10
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
SHEET
12
Device Parameter
Text
Device Parameter
FI-413
FLW 1, CURFLO
FQI-413-LM
ERN 1, FLOPRV
TI-413
FLW 1, CURTMP
10
PI-413
FLW 1, CURFP
11
FIn-413
FLW 1, CURDP
12
-5
FQI-413
ERN 1, FLOACC
13
FQI-413-TD
ERN 1, FLOTDY
14
FQI-413-LD
ERN 1, FLOYDY
15
FQI-413-M
ERN 1, FLOMTH
16
13
13.1 GENERAL
Item
Description
Value
Station Name
Floboss Identification
FQY-413
Address
Floboss Address
Group
Floboss Group
Contract Hour
Contract Hour
00:00
14
SOFT POINT
NUMBER
TAG
#1
CONV
#2
MDIAS
#3
ACCUM
Accumulated Average
#4
DATA/HORA
#5
ALARMES
26 OF 73
TITLE
11
REV
I-MA-4451.28-6250-27D-FRB-002
DESCRIPTION
Units Conversion
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
NUMBER
MANUAL
JOB OR PROJECT
SHEET
AREA/UNIT:
REV
I-MA-4451.28-6250-27D-FRB-002
27 OF 73
TITLE
DESCRIPTION
COD. FLOBOSS
DESCRIPTION
11
12
13
14
15
16
17
18
2
3
19
10
20
Energy Accumulated
DESCRIPTION
Hour Temperature
12
Hour Inst.Flow
13
14
15
Day Temperature
16
Day Inst.Flow
17
18
COD. FLOBOSS
11
19
10
20
DESCRIPTION
-
DESCRIPTION
COD. FLOBOSS
DESCRIPTION
Count Pressure
11
Accumulated Pressure
12
Count Temperature
13
Accumulated Temperature
14
Count Flow
15
Accumulated Flow
16
17
18
19
10
20
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
NUMBER
MANUAL
JOB OR PROJECT
SHEET
AREA/UNIT:
REV
I-MA-4451.28-6250-27D-FRB-002
28 OF 73
TITLE
DESCRIPTION
COD. FLOBOSS
DESCRIPTION
Current Day
11
Current Month
12
Current Year
13
Current Hour
14
Current Minute
15
Current Second
16
17
18
19
10
20
DESCRIPTION
COD. FLOBOSS
DESCRIPTION
Flow Alarms
11
Temperature Alarms
12
Pressure Alarms
13
14
15
16
17
18
19
10
20
15
FST'S
15.1 FST 1
Units Conversion
Label
CMD
WT
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
Argument 1
Argument 2
Comment
1
FLW 1, CURFP
0.010197
SFP 1, DATA1
FLW 1, CURFLO
1000
SFP 1, DATA2
FLW 1, TDYFLO
1000
SFP 1, DATA3
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
END
ERN 1, FLOMTH
NUMBER
I-MA-4451.28-6250-27D-FRB-002
SHEET
1000
SFP 1, DATA4
ERN 1, ENGMTH
0.0036
SFP 1, DATA5
ERN 1, FLOACC
1000
SFP 1, DATA6
AGA 1, GASHV
1000
SFP 1, DATA7
ERN 1, FLOYDY
1000
SFP 1, DATA8
ERN 1, ENGYDY
0.0036
SFP 1, DATA9
ERN 1, FLOPRV
1000
SFP 1, DATA10
ERN 1, ENGPRV
0.0036
SFP 1, DATA11
VAL
ERN 1, ENGACC
SAV
SFP 1, DATA20
VAL
CLK 1, DAY
SAV
SFP 4, DATA1
VAL
CLK 1, MONTH
SAV
SFP 4, DATA2
VAL
CLK 1, YEAR
SAV
SFP 4, DATA3
VAL
CLK 1, HOUR
SAV
SFP 4, DATA4
VAL
CLK 1, MINUTE
SAV
SFP 4, DATA5
VAL
CLK 1, SECOND
SAV
SFP 4, DATA6
VAL
AGA 1, ALARM
SAV
SFP 5, DATA1
VAL
SAV
SFP 5, DATA2
VAL
SAV
SFP 5, DATA3
Energy Accumulated
END
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
29 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
REV
I-MA-4451.28-6250-27D-FRB-002
SHEET
30 OF 73
15.2 FST 2
Load Alarms Table and Save Flash Memory Once a Day
Label
CMD
10
VAL
>=
VAL
+
P1
64
Argument 2
Comment
10 Seconds Temporization
P1
Fault Pressure
SFP 3, DATA1
1
SAV
SFP 3, DATA1
VAL
SFP 3, DATA2
SFP 1, DATA1
SAV
SFP 3, DATA2
VAL
>=
64
VAL
SFP 3, DATA3
P2
Fault Temperature
SAV
SFP 3, DATA3
VAL
SFP 3, DATA4
+
P2
Argument 1
WT
FLW 1, CURTMP
Temperature oC
SAV
SFP 3, DATA4
VAL
SFP 3, DATA5
SAV
SFP 3, DATA5
VAL
SFP 3, DATA6
SFP 1, DATA2
Flow (m/dia)
SAV
SFP 3, DATA6
VAL
SFP 3, DATA7
SAV
SFP 3, DATA7
VAL
SFP 3, DATA8
AGA 1, SPGR
Relative Density
SAV
SFP 3, DATA8
VAL
CLK 1, MINUTE
!=
VAL
==
VAL
SAV
FST 2, R1
VAL
SFP 3, DATA1
==
VAL
SFP 3, DATA2
SFP 3, DATA1
SAV
SFP 2, DATA1
VAL
SFP 3, DATA9
P41
FST 2, R1
Verify Minutes = 0
Verify Condition Control Flag
P42
P8
Hour Pressure Average
Count. Today Pressurte Average
SAV
SFP 3, DATA9
VAL
SFP 3, DATA10
SFP 2, DATA1
SAV
SFP 3, DATA10
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
GO
P9
P8
VAL
-1
SAV
SFP 2, DATA1
P9
VAL
SFP 3, DATA3
==
SFP 3, DATA4
SFP 3, DATA3
SAV
SFP 2, DATA2
VAL
SFP 3, DATA11
P10
P11
SFP 3, DATA11
VAL
SFP 3, DATA12
SFP 2, DATA2
SAV
SFP 3, DATA12
GO
P11
VAL
-1
SAV
SFP 2, DATA2
VAL
SFP 3, DATA5
P13
SFP 3, DATA6
SFP 3, DATA5
SAV
SFP 2, DATA3
VAL
SFP 3, DATA13
SFP 3, DATA13
VAL
SFP 3, DATA14
SFP 2, DATA3
SAV
SFP 3, DATA14
GO
P13
VAL
-1
SAV
SFP 2, DATA3
VAL
SFP 3, DATA7
P15
SFP 3, DATA8
SFP 3, DATA7
SAV
SFP 2, DATA4
VAL
SFP 3, DATA15
SFP 3, DATA15
VAL
SFP 3, DATA16
SFP 2, DATA4
SAV
SFP 3, DATA16
GO
P15
VAL
-1
SAV
SFP 2, DATA4
VAL
SFP 1, DATA6
P10
Hour Today Temperature
Count. Today Temperature Average
P12
Hour Flow Average
Count. Today Flow Average
P14
SAV
SAV
VAL
SAV
==
P14
VAL
SHEET
SAV
==
P12
VAL
I-MA-4451.28-6250-27D-FRB-002
FST 2, R2
SFP 2, DATA9
1000
SAV
SFP 2, DATA10
VAL
SFP 1, DATA6
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
31 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
SAV
FST 2, R2
VAL
SFP 1, DATA20
SFP 2, DATA11
VAL
SFP 1, DATA20
SAV
FST 2, R3
VAL
CLK 1, HOUR
!=
==
0
0
SFP 3, DATA10
SFP 3, DATA9
SAV
SFP 2, DATA5
GO
P25
P24
VAL
-1
SAV
SFP 2, DATA5
P25
VAL
SFP 3, DATA11
0
VAL
SFP 3, DATA12
SFP 3, DATA11
SAV
SFP 2, DATA6
GO
P27
P26
VAL
-1
SAV
SFP 2, DATA6
P27
VAL
SFP 3, DATA13
==
VAL
SFP 3, DATA14
SFP 3, DATA13
SAV
SFP 2, DATA7
GO
P29
P28
VAL
-1
SAV
SFP 2, DATA7
P29
VAL
SFP 3, DATA15
==
VAL
SFP 3, DATA16
SFP 3, DATA15
SAV
SFP 2, DATA8
GO
P31
P30
VAL
-1
SAV
SFP 2, DATA8
P31
VAL
SAV
SFP 3, DATA9
SAV
SFP 3, DATA10
SAV
SFP 3, DATA11
SAV
SFP 3, DATA12
SAV
SFP 3, DATA13
SAV
SFP 3, DATA14
SAV
SFP 3, DATA15
P40
P40
SAV
SFP 3, DATA16
VAL
SAV
SFP 3, DATA1
Verify Hour = 0
P24
Today Pressure Average
P26
Today Temperature Average
P28
Today Flow Average
P30
Today Density Average
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
32 OF 73
SFP 3, DATA9
VAL
==
SHEET
FST 2, R3
SAV
VAL
REV
I-MA-4451.28-6250-27D-FRB-002
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
P41
P42
SAV
SFP 3, DATA2
SAV
SFP 3, DATA3
SAV
SFP 3, DATA4
SAV
SFP 3, DATA5
SAV
SFP 3, DATA6
SAV
SFP 3, DATA7
SAV
SFP 3, DATA8
GO
P42
VAL
SAV
FST 2, R1
I-MA-4451.28-6250-27D-FRB-002
SHEET
REV
33 OF 73
END
15.3 FST 3
It updates the gas composition values for the Z calculation
Label
CMD
Argument 1
Argument 2
END
WT
300
VAL
SAV
FLW 1, RECALCZS
Comment
300 Seconds Temporization
Update Z Calculation for Gas Composition
END
15.4 FST 4
It updates the gas composition values for the Z calculation
Label
CMD
Argument 1
Argument 2
CKMIN
WT
VAL
CLK 1, HOUR
==
VAL
SAV
FST 4, R1
GO
END
VAL
CLK 1, MINUTE
==
GO
END
WRTFLS VAL
END
Comment
5 Seconds Temporization
CKMIN
Verify Hour = 0
Control Flag = 0
WRTFLS
Verify Minute = 5
FST 4, R1
==
VAL
SAV
FLG 1, WRITE
VAL
SAV
FST 4, R1
EVT
WRT MENORY
END
Writing Flash Memory Configuration
Control Flag
FLG 1, WRITE
END
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
16
I-MA-4451.28-6250-27D-FRB-002
SHEET
HISTORY
16.1 STREAM 01
Point
Archive Type
Archive Point
Description
Totalize
ERN 1, MINTDY
Average
FLW 1, CURDP
Average
FLW 1, CURFP
Average
FLW 1, CURTMP
Average
FLW 1, IMV/BMV
Average
FLW 1, HWPF
Accumulated
FLW 1, CURFLO
Accumulated
FLW 1, ENERGY
Accumulated energy
Average
FLW 1, CURFLO
Static Pressure
Temperature
Constant of correction of the calculation AGA
Extension HWPF of the AGA3 1992
Flow accumulated corrected
10
Average
AGA 1, SPGR
12
Current Value
ERN1, FLOTDY
Specific Gravity
13
Current Value
ERN1, FLOMTH
16.2 STREAM 02
Point
Archive Type
Archive Point
Description
14
UNDEFINED
UNDEFINED
Reserve
15
UNDEFINED
UNDEFINED
Reserve
UNDEFINED
UNDEFINED
Reserve
17
UNDEFINED
UNDEFINED
Reserve
18
UNDEFINED
UNDEFINED
Reserve
19
UNDEFINED
UNDEFINED
Reserve
20
UNDEFINED
UNDEFINED
Reserve
21
UNDEFINED
UNDEFINED
Reserve
22
UNDEFINED
UNDEFINED
Reserve
23
UNDEFINED
UNDEFINED
Reserve
24
UNDEFINED
UNDEFINED
Reserve
25
UNDEFINED
UNDEFINED
Reserve
16.3 STREAM 03
Point
Archive Type
Archive Point
Description
26
UNDEFINED
UNDEFINED
Reserve
27
UNDEFINED
UNDEFINED
Reserve
28
UNDEFINED
UNDEFINED
Reserve
29
UNDEFINED
UNDEFINED
Reserve
30
UNDEFINED
UNDEFINED
Reserve
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
34 OF 73
NUMBER
MANUAL
JOB OR PROJECT
I-MA-4451.28-6250-27D-FRB-002
SHEET
AREA/UNIT:
TITLE
31
UNDEFINED
UNDEFINED
Reserve
32
UNDEFINED
UNDEFINED
Reserve
33
UNDEFINED
UNDEFINED
Reserve
34
UNDEFINED
UNDEFINED
Reserve
35
UNDEFINED
UNDEFINED
Reserve
36
UNDEFINED
UNDEFINED
Reserve
37
UNDEFINED
UNDEFINED
Reserve
16.4 STREAM 04
Point
Archive Type
Archive Point
38
UNDEFINED
UNDEFINED
Reserve
39
UNDEFINED
UNDEFINED
Reserve
40
UNDEFINED
UNDEFINED
Reserve
41
UNDEFINED
UNDEFINED
Reserve
42
UNDEFINED
UNDEFINED
Reserve
43
UNDEFINED
UNDEFINED
Reserve
44
UNDEFINED
UNDEFINED
Reserve
45
UNDEFINED
UNDEFINED
Reserve
46
UNDEFINED
UNDEFINED
Reserve
47
UNDEFINED
UNDEFINED
Reserve
48
UNDEFINED
UNDEFINED
Reserve
49
UNDEFINED
UNDEFINED
Reserve
17
Description
COMM PORTS
Description
Value
Baud Rate
Rate of Transmission
9600
Parity
Parity
None
Data Bits
Stop Bits
Key On Delay
Description
Value
Start Transmission
Inactive
Continuous Polling
Disabled
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
35 OF 73
NUMBER
MANUAL
JOB OR PROJECT
I-MA-4451.28-6250-27D-FRB-002
SHEET
AREA/UNIT:
REV
36 OF 73
TITLE
Description
Value
Baud Rate
Rate of Transmission
9600
Parity
Parity
None
Data Bits
Stop Bits
RTS/CTS Handshaking
Disabled
Key On Delay
0.02
0.01
Description
Value
Start Transmission
Inactive
Continuous Polling
Disabled
Description
Value
Baud Rate
Tax of Transmission
9600
Parity
Parity
None
Data Bits
Stop Bits
RTS/CTS Handshaking
Disabled
Key On Delay
0.02
0.01
Description
Value
Start Transmission
Inactive
Continuous Polling
Disabled
Obs: The Modem / RBX and Store & Forward Must be Configured on COM1 and COM2 as None / Disable and Same Port,
Respectively.
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
18
NUMBER
I-MA-4451.28-6250-27D-FRB-002
SHEET
REV
37 OF 73
FLAGS
18.1 FLAGS
18.1.1 ADVANCED
Item
Description
Transmitter Power +T
19
Value
on
CALCULATIONS OF FLOW
USER PROGRAMS
These User Programs should be downloaded to the Floboss:
FBMB1_60.H00 User Program protocol Modbus RTU port Comm 1 Version 2.01;
FBMB2_05.H00 User Program protocol Modbus RTU port Comm 2 Version 2.01.
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
NUMBER
I-MA-4451.28-6250-27D-FRB-002
SHEET
FQY - 513
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
38 OF 73
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
NUMBER
I-MA-4451.28-6250-27D-FRB-002
SHEET
REV
39 OF 73
INTRODUCTION .................................................................................................................................................................... 43
REFERENCES ....................................................................................................................................................................... 43
3.2
3.3
3.4
STREAM: #1........................................................................................................................................................................ 43
3.1.1
GENERAL............................................................................................................................................................... 43
3.1.2
INPUTS................................................................................................................................................................... 43
3.1.3
3.1.4
3.1.5
ALARMS ................................................................................................................................................................. 43
STREAM: #2........................................................................................................................................................................ 43
3.2.1
GENERAL............................................................................................................................................................... 43
3.2.2
INPUTS................................................................................................................................................................... 43
3.2.3
3.2.4
3.2.5
ALARMS ................................................................................................................................................................. 43
STREAM: #3........................................................................................................................................................................ 43
3.3.1
GENERAL............................................................................................................................................................... 43
3.3.2
INPUTS................................................................................................................................................................... 43
3.3.3
3.3.4
3.3.5
ALARMS ................................................................................................................................................................. 43
STREAM: #4........................................................................................................................................................................ 43
3.4.1
GENERAL............................................................................................................................................................... 43
3.4.2
INPUTS................................................................................................................................................................... 43
3.4.3
3.4.4
3.4.5
ALARMS ................................................................................................................................................................. 43
4.2
4.3
4.4
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
5.1
5.2
5.3
5.4
5.5
5.6
NUMBER
I-MA-4451.28-6250-27D-FRB-002
SHEET
REV
40 OF 73
GENERAL............................................................................................................................................................... 43
5.1.2
ADVANCED ............................................................................................................................................................ 43
5.1.3
ALARMS ................................................................................................................................................................. 43
GENERAL............................................................................................................................................................... 43
5.2.2
ADVANCED ............................................................................................................................................................ 43
5.2.3
ALARMS ................................................................................................................................................................. 43
GENERAL............................................................................................................................................................... 43
5.3.2
ADVANCED ............................................................................................................................................................ 43
5.3.3
ALARMS ................................................................................................................................................................. 43
GENERAL............................................................................................................................................................... 43
5.4.2
ADVANCED ............................................................................................................................................................ 43
5.4.3
ALARMS ................................................................................................................................................................. 43
GENERAL............................................................................................................................................................... 43
5.5.2
ADVANCED ............................................................................................................................................................ 43
5.5.3
ALARMS ................................................................................................................................................................. 43
GENERAL............................................................................................................................................................... 43
5.6.2
ADVANCED ............................................................................................................................................................ 43
5.6.3
ALARMS ................................................................................................................................................................. 43
GENERAL............................................................................................................................................................... 43
6.1.2
ADVANCED ............................................................................................................................................................ 43
6.1.3
ALARMS ................................................................................................................................................................. 43
8.1
8.2
8.3
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
SHEET
REV
12
13
14
15
FST'S...................................................................................................................................................................................... 43
15.1 FST 1................................................................................................................................................................................... 43
15.2 FST 2................................................................................................................................................................................... 43
15.3 FST 3................................................................................................................................................................................... 43
15.4 FST 4................................................................................................................................................................................... 43
16
HISTORY................................................................................................................................................................................ 43
16.1 STREAM 01......................................................................................................................................................................... 43
16.2 STREAM 02......................................................................................................................................................................... 43
16.3 STREAM 03......................................................................................................................................................................... 43
16.4 STREAM 04......................................................................................................................................................................... 43
17
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
41 OF 73
10
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
NUMBER
I-MA-4451.28-6250-27D-FRB-002
SHEET
REV
42 OF 73
FLAGS.................................................................................................................................................................................... 43
18.1 FLAGS................................................................................................................................................................................. 43
18.1.1 ADVANCED ............................................................................................................................................................ 43
19
20
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
SHEET
REV
43 OF 73
INTRODUCTION
The purpose of this document is to detail the configuration of the Flow Computer FQY-513, of the Metering
System on LNG Flexible Terminal, at Pecm Port CE.
REFERENCES
3.1
STREAM: #1
3.1.1
GENERAL
Item
Description
Valor
Meter Tag
STREAM Identification
FIT-513
Meter Description
STREAM Description
Meter Type
Meter Type
Turbine
Alarming
Enabled
Scan Period
Scan Period
1 Seconds
3.1.2
INPUTS
Item
Description
Value
Uncorrected Volume
PIN A7, EU
Static Pressure
AIN A3, EU
Temperature
Temperature Input
AIN A1, EU
3.1.3
GAS QUALITY
Item
Description
Value
Nitrogen
Input by Operator
CO2
Input by Operator
Methane
Input by Operator
Ethane
Input by Operator
Propane
Input by Operator
n-Butane
Input by Operator
i-Butane
Input by Operator
n-Pentane
Input by Operator
i-Pentane
Input by Operator
Hexane
Input by Operator
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
NUMBER
MANUAL
JOB OR PROJECT
Heptane
Input by Operator
Octane
Input by Operator
Nonane
Input by Operator
Decane
Input by Operator
H2S
Input by Operator
Water
Input by Operator
Helium
Input by Operator
Oxygen
Input by Operator
CO
Input by Operator
Hydrogen
Input by Operator
Dry
Adjust of methane
Enabled
Heating Value
Heating Value
Calculate (MJ/M3)
Spec Gravity
Specific Gravity
Calculate
3.1.4
SHEET
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
ADVANCED FEATURES
Item
Description
Valor
FPV Method
Type Calculation
Detailed
Units
Units
Metric KM3/GJ
Base Temperature
Base Temperature
20 Deg C
Base Pressure
Base Pressure
101.325 kPa
Atmospheric Pressure
Atmospheric Pressure
Elevation
Elevation
0.0 Meters
Latitude
Latitude
0.0 Deg
Gravity Correction
1.0
Pressure Tap
Pressure Tap
Gauge
Meter Factor
Meter Factor
1.0
3.1.5
ALARMS
Item
Description
Value
Low Alarm
High Alarm
1000
7900
RBX Alarming
Disabled
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
44 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
3.2
I-MA-4451.28-6250-27D-FRB-002
SHEET
STREAM: #2
3.2.1
GENERAL
Item
Description
Valor
Meter Tag
STREAM Identification
Not Applicable
Meter Description
STREAM Description
Not Applicable
Meter Type
Meter Type
Not Applicable
Alarming
Disabled
Scan Period
Scan Period
Not Applicable
3.2.2
INPUTS
Item
Description
Value
Uncorrected Volume
Manual
Static Pressure
Manual
Temperature
Temperature Input
Manual
3.2.3
GAS QUALITY
Item
Description
Value
Nitrogen
Not Applicable
CO2
Not Applicable
Methane
Not Applicable
Ethane
Not Applicable
Propane
Not Applicable
n-Butane
Not Applicable
i-Butane
Not Applicable
n-Pentane
Not Applicable
i-Pentane
Not Applicable
Hexane
Not Applicable
Heptane
Not Applicable
Octane
Not Applicable
Nonane
Not Applicable
Decane
Not Applicable
H2S
Not Applicable
Water
Not Applicable
Helium
Not Applicable
Oxygen
Not Applicable
CO
Not Applicable
Hydrogen
Not Applicable
Not Applicable
Adjust of methane
Disabled
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
45 OF 73
NUMBER
MANUAL
JOB OR PROJECT
Heating Value
Heating Value
Not Applicable
Spec Gravity
Specific Gravity
Not Applicable
3.2.4
ADVANCED FEATURES
Item
Description
Valor
FPV Method
Type Calculation
Not Applicable
Units
Units
Not Applicable
Base Temperature
Base Temperature
Not Applicable
Base Pressure
Base Pressure
Not Applicable
Atmospheric Pressure
Atmospheric Pressure
Not Applicable
Elevation
Elevation
Not Applicable
Latitude
Latitude
Not Applicable
Gravity Correction
Not Applicable
Pressure Tap
Pressure Tap
Not Applicable
Meter Factor
Meter Factor
Not Applicable
3.2.5
ALARMS
Item
Description
Value
Low Alarm
Not Applicable
High Alarm
Not Applicable
RBX Alarming
Disabled
3.3
3.3.1
STREAM: #3
GENERAL
Item
Description
Valor
Meter Tag
STREAM Identification
Not Applicable
Meter Description
STREAM Description
Not Applicable
Meter Type
Meter Type
Not Applicable
Alarming
Disabled
Scan Period
Scan Period
Not Applicable
3.3.2
SHEET
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
INPUTS
Item
Description
Value
Uncorrected Volume
Manual
Static Pressure
Manual
Temperature
Temperature Input
Manual
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
46 OF 73
NUMBER
MANUAL
JOB OR PROJECT
3.3.3
GAS QUALITY
Item
Nitrogen
Description
Value
Not Applicable
CO2
Not Applicable
Methane
Not Applicable
Ethane
Not Applicable
Propane
Not Applicable
n-Butane
Not Applicable
i-Butane
Not Applicable
n-Pentane
Not Applicable
i-Pentane
Not Applicable
Hexane
Not Applicable
Heptane
Not Applicable
Octane
Not Applicable
Nonane
Not Applicable
Decane
Not Applicable
H2S
Not Applicable
Water
Not Applicable
Helium
Not Applicable
Oxygen
Not Applicable
CO
Not Applicable
Hydrogen
Not Applicable
Not Applicable
Adjust of methane
Disabled
Heating Value
Heating Value
Not Applicable
Spec Gravity
Specific Gravity
Not Applicable
3.3.4
SHEET
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
ADVANCED FEATURES
Item
Description
Valor
FPV Method
Type Calculation
Not Applicable
Units
Units
Not Applicable
Base Temperature
Base Temperature
Not Applicable
Base Pressure
Base Pressure
Not Applicable
Atmospheric Pressure
Atmospheric Pressure
Not Applicable
Elevation
Elevation
Not Applicable
Latitude
Latitude
Not Applicable
Gravity Correction
Not Applicable
Pressure Tap
Pressure Tap
Not Applicable
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
47 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
3.3.5
I-MA-4451.28-6250-27D-FRB-002
ALARMS
Item
Description
Value
Low Alarm
Not Applicable
High Alarm
Not Applicable
RBX Alarming
Disabled
3.4
SHEET
STREAM: #4
3.4.1
GENERAL
Item
Description
Valor
Meter Tag
STREAM Identification
Not Applicable
Meter Description
STREAM Description
Not Applicable
Meter Type
Meter Type
Not Applicable
Alarming
Disabled
Scan Period
Scan Period
Not Applicable
3.4.2
INPUTS
Item
Description
Value
Uncorrected Volume
Manual
Static Pressure
Manual
Temperature
Temperature Input
Manual
3.4.3
GAS QUALITY
Item
Description
Value
Nitrogen
Not Applicable
CO2
Not Applicable
Methane
Not Applicable
Ethane
Not Applicable
Propane
Not Applicable
n-Butane
Not Applicable
i-Butane
Not Applicable
n-Pentane
Not Applicable
i-Pentane
Not Applicable
Hexane
Not Applicable
Heptane
Not Applicable
Octane
Not Applicable
Nonane
Not Applicable
Decane
Not Applicable
H2S
Not Applicable
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
48 OF 73
NUMBER
MANUAL
JOB OR PROJECT
I-MA-4451.28-6250-27D-FRB-002
AREA/UNIT:
TITLE
Water
Not Applicable
Helium
Not Applicable
Oxygen
Not Applicable
CO
Not Applicable
Hydrogen
Not Applicable
Not Applicable
Adjust of methane
Disabled
Heating Value
Heating Value
Not Applicable
Spec Gravity
Specific Gravity
Not Applicable
3.4.4
ADVANCED FEATURES
Item
Description
Valor
FPV Method
Type Calculation
Not Applicable
Units
Units
Not Applicable
Base Temperature
Base Temperature
Not Applicable
Base Pressure
Base Pressure
Not Applicable
Atmospheric Pressure
Atmospheric Pressure
Not Applicable
Elevation
Elevation
Not Applicable
Latitude
Latitude
Not Applicable
Gravity Correction
Not Applicable
Pressure Tap
Pressure Tap
Not Applicable
3.4.5
ALARMS
Item
Description
Value
Low Alarm
Not Applicable
High Alarm
Not Applicable
RBX Alarming
Disabled
SHEET
4.1
Description
Value
Tag
MVS Identification
Address
Address RS-485
Not Applicable
Not Applicable
Scanning
Disabled
Units
Unit System
Not Applicable
Sensor Alarms
Disabled
Disabled
Not Applicable
Low Alarm
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
49 OF 73
NUMBER
MANUAL
JOB OR PROJECT
I-MA-4451.28-6250-27D-FRB-002
AREA/UNIT:
TITLE
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Disabled
Pressure Alarm
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Disabled
Temperature Alarm
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Report Pressure As
Upstream or Downstream
Not Applicable
Action on Failure
Action on Failure
Not Applicable
RBX Alarming
Exception Alarm
Disabled
Reference Temperature
Reference Temperature
Not Applicable
4.2
SHEET
Description
Value
Tag
MVS Identification
Not Applicable
Address
Address RS-485
Not Applicable
Scanning
Disabled
Units
Unit System
Not Applicable
Sensor Alarms
Disabled
Disabled
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Disabled
Pressure Alarm
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Temperature Alarm
Disabled
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Report Pressure As
Not Applicable
Upstream or Downstream
Not Applicable
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
50 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
I-MA-4451.28-6250-27D-FRB-002
TITLE
Action on Failure
Action on Failure
Not Applicable
RBX Alarming
Exception Alarm
Disabled
Reference Temperature
Reference Temperature
Not Applicable
4.3
Description
Value
Tag
MVS Identification
Not Applicable
Address
Address RS-485
Not Applicable
Scanning
Disabled
Units
Unit System
Not Applicable
Sensor Alarms
Disabled
Disabled
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Pressure Alarm
Not Applicable
Disabled
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Temperature Alarm
Disabled
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Report Pressure As
Action on Failure
Upstream or Downstream
Action on Failure
Not Applicable
Not Applicable
RBX Alarming
Exception Alarm
Disabled
Reference Temperature
Reference Temperature
Not Applicable
4.4
SHEET
Tag
Description
MVS Identification
Value
Not Applicable
Address
Address RS-485
Not Applicable
Scanning
Disabled
Units
Unit System
Not Applicable
Sensor Alarms
Disabled
Disabled
Not Applicable
Low Alarm
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
51 OF 73
NUMBER
MANUAL
JOB OR PROJECT
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Disabled
Pressure Alarm
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Disabled
Temperature Alarm
Low Alarm
Not Applicable
High Alarm
Not Applicable
Alarm Deadband
Not Applicable
Fault Value
Not Applicable
Report Pressure As
Upstream or Downstream
Not Applicable
Action on Failure
Action on Failure
Not Applicable
RBX Alarming
Exception Alarm
Disabled
Reference Temperature
Reference Temperature
Not Applicable
SHEET
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
5.1
5.1.1
GENERAL
Item
Description
Value
Scanning
Enabled
Alarming
Enabled
Units
Unit of Engineering
Scan Period
Scan Period
1 Seconds
Low Reading EU
High Reading EU
70
5.1.2
ADVANCED
Item
Description
Value
Filter
Filter
Adjusted A/D 0%
800
4000
Action on Failure
Action on Failure
Fault Value
Value on Failure
Not Applicable
Enabled
Disabled
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
52 OF 73
NUMBER
MANUAL
JOB OR PROJECT
Temp Compensation
5.1.3
Disabled
ALARMS
Item
Description
Value
Low Alarm
Low Alarm
High Alarm
High Alarm
60
LoLo Alarm
LoLo Alarm
HiHi Alarm
HiHi Alarm
75
Rate Alarm
Rate Alarm
70
Alarm Deadband
Alarm Deadband
RBX Alarming
RBX Alarming
Disabled
5.2
SHEET
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
5.2.1
GENERAL
Item
Description
Value
Scanning
Disabled
Alarming
Disabled
Units
Unit of Engineering
Not Applicable
Scan Period
Scan Period
Not Applicable
Low Reading EU
Not Applicable
High Reading EU
Not Applicable
5.2.2
ADVANCED
Item
Filter
Description
Value
Filter
Not Applicable
Adjusted A/D 0%
Not Applicable
Not Applicable
Action on Failure
Action on Failure
Not Applicable
Fault Value
Value on Failure
Not Applicable
Disabled
Disabled
Disabled
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
53 OF 73
NUMBER
MANUAL
JOB OR PROJECT
5.2.3
SHEET
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
ALARMS
Item
Description
Value
Low Alarm
Low Alarm
High Alarm
High Alarm
Not Applicable
LoLo Alarm
Not Applicable
HiHi Alarm
Not Applicable
Rate Alarm
Rate Alarm
Not Applicable
Alarm Deadband
Alarm Deadband
Not Applicable
RBX Alarming
RBX Alarming
Disabled
5.3
Not Applicable
5.3.1
GENERAL
Item
Description
Value
Scanning
Enabled
Alarming
Enabled
Units
Unit of Engineering
kPa
Scan Period
Scan Period
1 Seconds
Low Reading EU
High Reading EU
9317
5.3.2
ADVANCED
Item
Filter
Description
Value
Filter
Adjusted A/D 0%
800
4000
Action on Failure
Action on Failure
Fault Value
Value on Failure
Not Applicable
5.3.3
Enabled
Disabled
Disabled
ALARMS
Item
Description
Value
Low Alarm
Low Alarm
High Alarm
High Alarm
9300
LoLo Alarm
HiHi Alarm
9317
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
54 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
Rate Alarm
Rate Alarm
9317
Alarm Deadband
Alarm Deadband
RBX Alarming
RBX Alarming
Disabled
5.4
SHEET
5.4.1
GENERAL
Item
Description
Value
Scanning
Enabled
Alarming
Enabled
Units
Unit of Engineering
Volts
Scan Period
Scan Period
5 Secs
Low Reading EU
0.0
High Reading EU
38.0
5.4.2
ADVANCED
Item
Description
Value
Filter
Filter
Adjusted A/D 0%
4000
5.4.3
Disabled
Disabled
Disabled
ALARMS
Item
Description
Value
Low Alarm
Low Alarm
10.0
High Alarm
High Alarm
30.0
LoLo Alarm
LoLo Alarm
8.0
HiHi Alarm
HiHi Alarm
32.0
Rate Alarm
Rate Alarm
5.0
Alarm Deadband
Alarm Deadband
2.0
RBX Alarming
RBX Alarming
Disabled
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
55 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
5.5
I-MA-4451.28-6250-27D-FRB-002
5.5.1
GENERAL
Item
Description
Value
Scanning
Enabled
Alarming
Enabled
Units
Unit of Engineering
Volts
Scan Period
Scan Period
5 Secs
Low Reading EU
0.0
High Reading EU
38.0
5.5.2
ADVANCED
Item
Description
Value
Filter
Filter
Adjusted A/D 0%
800
4000
5.5.3
Disabled
Disabled
Disabled
ALARMS
Item
Description
Value
Low Alarm
Low Alarm
10.00
High Alarm
High Alarm
30.00
LoLo Alarm
LoLo Alarm
8.00
HiHi Alarm
HiHi Alarm
32.00
Rate Alarm
Rate Alarm
5.00
Alarm Deadband
Alarm Deadband
2.00
RBX Alarming
RBX Alarming
Disabled
5.6
SHEET
5.6.1
GENERAL
Item
Description
Value
Scanning
Enabled
Alarming
Enabled
Units
Unit of Engineering
Scan Period
Scan Period
5 Secs
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
56 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
I-MA-4451.28-6250-27D-FRB-002
Low Reading EU
-272.77
High Reading EU
140.55
5.6.2
SHEET
ADVANCED
Item
Description
Value
Filter
Filter
Adjusted A/D 0%
4000
5.6.3
Disabled
Disabled
Disabled
ALARMS
Item
Description
Value
Low Alarm
Low Alarm
10.0
High Alarm
High Alarm
50.0
LoLo Alarm
LoLo Alarm
-272.77
HiHi Alarm
HiHi Alarm
140.55
Rate Alarm
Rate Alarm
400.00
Alarm Deadband
Alarm Deadband
20.00
RBX Alarming
RBX Alarming
Disabled
Obs: Others Analog Inputs must be Configured With Scan and Alarms DISABLED.
6.1
6.1.1
GENERAL
Item
Description
Value
Scanning
Enabled
Alarming
Disabled
Units
Unit of Engineering
Counts
Scan Period
Scan Period
1.0 secs
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
57 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
6.1.2
I-MA-4451.28-6250-27D-FRB-002
SHEET
ADVANCED
Item
Description
Value
EU Options
Value Options
Conversion
Type of Conversion
Pulses/EU
Conversion/K-Factor
Factor of conversion
10937
Rate Period
Rate Period
EU/day
EU Units
Unit of Engineering
MCF/M3
6.1.3
ALARMS
Item
Description
Value
Low Alarm
Not Applicable
High Alarm
Not Applicable
LoLo Alarm
Not Applicable
HiHi Alarm
Not Applicable
Rate Alarm
Not Applicable
Alarm Deadband
Alarm Deadband
Not Applicable
RBX Alarming
Disabled
7.1
Description
Value
ASCII = 0, RTU = 1
Host Enabled = 1
Host Enabled
Init Memory = 1
Init Memory
Port Switch En = 1
DCD = 0, DI = 1, STP = 2
9600
9600
100
300
HI Integer Scale
HI Integer Scale
4095
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
58 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
8.1
SHEET
Description
TYPE
40201
40202
17
128
70
Var. Instant.
40203
40204
10
70
Instantaneous Temperature
Var. Instant.
40205
40206
10
70
Var. Instant.
40207
40208
10
70
Energy Flowrate
Var. Instant.
40209
40210
70
Relative Density
Var. Instant.
40211
40212
10
16
70
Compressibility Factor
Var. Instant.
40213
40214
17
129
11
70
Var. Instant.
40215
40216
42
70
Var. Instant.
40217
40218
42
70
Var. Instant.
10
40219
40220
17
129
12
70
Var. Instant.
8.2
Description
TYPE
40221
40222
42
11
70
Var. Instant.
40223
40224
42
12
70
Var. Instant.
40225
40226
28
70
Parameters
40227
40228
29
70
Parameters
40229
40230
30
70
Parameters
40231
40232
32
70
Parameters
40233
40234
31
70
Parameters
40235
40236
34
70
Parameters
40237
40238
33
70
Parameters
10
40239
40240
35
70
Parameters
8.3
40241
40242
40243
40244
40245
40250
7
8
9
Description
TYPE
23
70
Parameters
24
70
Parameters
17
131
39
Parameters
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
59 OF 73
TITLE
REV
I-MA-4451.28-6250-27D-FRB-002
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
SHEET
9.1
Description
Value
ASCII = 0, RTU = 1
Host Enabled = 1
Host Enabled
Init Memory = 1
Init Memory
Port Switch En = 1
DCD = 0, DI = 1, STP = 2
9600
9600
100
300
HI Integer Scale
HI Integer Scale
4095
10
Description
TYPE
30264
30265
17
128
66
Var. Instant.
30266
30267
10
66
Instantaneous Temperature
Var. Instant.
30268
30269
17
66
Var. Instant.
30270
30271
10
66
Reserve
Reserve
30272
30279
17
128
66
30280
30281
66
Relative Density
Var. Instant.
30282
30283
10
16
66
Compressibility Factor
Var. Instant.
30284
30299
128
28
66
Gas Composition
Parameters
30300
30303
128
23
66
Gas Composition
Parameters
10
30304
30305
66
Heating Value
Var. Instant.
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
60 OF 73
TITLE
10
REV
I-MA-4451.28-6250-27D-FRB-002
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
REV
I-MA-4451.28-6250-27D-FRB-002
SHEET
61 OF 73
TITLE
Description
TYPE
30306
30308
12
128
33
Parameters
30309
30311
12
128
33
Parameters
30506
30507
17
129
66
Var. Instant.
30508
30509
17
129
66
Var. Instant.
30510
30511
17
129
10
66
Var. Instant.
30610
30613
17
129
66
Var. Instant.
30614
30615
42
66
Var. Instant.
30616
30617
42
12
66
Var. Instant.
30618
30619
17
128
15
66
Var. Instant.
10
30804
30807
17
128
11
66
Var. Instant.
Description
TYPE
30113
30113
14
33
30114
30114
130
16
33
Alarms
30115
30115
128
16
33
Alarms
30116
30116
132
16
33
Alarms
30117
30117
135
16
33
Alarms
10
Alarms
Description
TYPE
30301
30326
128
23
66
Parameters
30327
30332
12
128
34
Parameters
10
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
SHEET
12
Device Parameter
Text
Device Parameter
FI-513
FLW 1, CURFLO
FQI-513-LM
ERN 1, FLOPRV
TI-513
FLW 1, CURTMP
10
PI-513
FLW 1, CURFP
11
FIn-513
FLW 1, CURDP
12
FQI-513
ERN 1, FLOACC
13
FQI-513-TD
ERN 1, FLOTDY
14
FQI-513-LD
ERN 1, FLOYDY
15
FQI-513-M
ERN 1, FLOMTH
16
13
13.1 GENERAL
Item
Description
Value
Station Name
Floboss Identification
FQY-513
Address
Floboss Address
Group
Floboss Group
Contract Hour
Contract Hour
00:00
14
SOFT POINT
NUMBER
TAG
#1
CONV
#2
MDIAS
#3
ACCUM
Accumulated Average
#4
DATA/HORA
#5
ALARMES
62 OF 73
TITLE
11
REV
I-MA-4451.28-6250-27D-FRB-002
DESCRIPTION
Units Conversion
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
NUMBER
MANUAL
JOB OR PROJECT
SHEET
AREA/UNIT:
REV
I-MA-4451.28-6250-27D-FRB-002
63 OF 73
TITLE
DESCRIPTION
COD. FLOBOSS
DESCRIPTION
11
12
13
14
15
16
17
18
2
3
19
10
20
Energy Accumulated
DESCRIPTION
COD. FLOBOSS
11
Hour Temperature
12
Hour Inst.Flow
13
14
15
Day Temperature
16
Day Inst.Flow
17
18
19
10
20
DESCRIPTION
DESCRIPTION
COD. FLOBOSS
DESCRIPTION
Count Pressure
11
Accumulated Pressure
12
Count Temperature
13
Accumulated Temperature
14
Count Flow
15
Accumulated Flow
16
17
18
19
10
20
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
NUMBER
MANUAL
JOB OR PROJECT
SHEET
AREA/UNIT:
REV
I-MA-4451.28-6250-27D-FRB-002
64 OF 73
TITLE
DESCRIPTION
COD. FLOBOSS
11
DESCRIPTION
Current Day
Current Month
12
Current Year
13
Current Hour
14
Current Minute
15
Current Second
16
17
18
19
10
20
DESCRIPTION
COD. FLOBOSS
11
DESCRIPTION
Flow Alarms
Temperature Alarms
12
Pressure Alarms
13
14
15
16
17
18
19
10
20
15
FST'S
15.1 FST 1
Units Conversion
Label
CMD
WT
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
Argument 1
Argument 2
Comment
1
FLW 1, CURFP
0.010197
SFP 1, DATA1
FLW 1, CURFLO
1000
SFP 1, DATA2
FLW 1, TDYFLO
1000
SFP 1, DATA3
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
END
ERN 1, FLOMTH
NUMBER
I-MA-4451.28-6250-27D-FRB-002
SHEET
1000
SFP 1, DATA4
ERN 1, ENGMTH
0.0036
SFP 1, DATA5
ERN 1, FLOACC
1000
SFP 1, DATA6
AGA 1, GASHV
1000
SFP 1, DATA7
ERN 1, FLOYDY
1000
SFP 1, DATA8
ERN 1, ENGYDY
0.0036
SFP 1, DATA9
ERN 1, FLOPRV
1000
SFP 1, DATA10
ERN 1, ENGPRV
0.0036
SFP 1, DATA11
VAL
ERN 1, ENGACC
SAV
SFP 1, DATA20
VAL
CLK 1, DAY
SAV
SFP 4, DATA1
VAL
CLK 1, MONTH
SAV
SFP 4, DATA2
VAL
CLK 1, YEAR
SAV
SFP 4, DATA3
VAL
CLK 1, HOUR
SAV
SFP 4, DATA4
VAL
CLK 1, MINUTE
SAV
SFP 4, DATA5
VAL
CLK 1, SECOND
SAV
SFP 4, DATA6
VAL
AGA 1, ALARM
SAV
SFP 5, DATA1
VAL
SAV
SFP 5, DATA2
VAL
SAV
SFP 5, DATA3
END
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
65 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
REV
I-MA-4451.28-6250-27D-FRB-002
SHEET
66 OF 73
15.2 FST 2
Load Alarms Table and Save Flash Memory Once a Day
Label
CMD
10
VAL
>=
VAL
+
P1
64
Argument 2
Comment
10 Seconds Temporization
P1
Fault Pressure
SFP 3, DATA1
1
SAV
SFP 3, DATA1
VAL
SFP 3, DATA2
SFP 1, DATA1
SAV
SFP 3, DATA2
VAL
>=
64
VAL
SFP 3, DATA3
P2
Fault Temperature
SAV
SFP 3, DATA3
VAL
SFP 3, DATA4
+
P2
Argument 1
WT
FLW 1, CURTMP
Temperature oC
SAV
SFP 3, DATA4
VAL
SFP 3, DATA5
SAV
SFP 3, DATA5
VAL
SFP 3, DATA6
SFP 1, DATA2
Flow (m/dia)
SAV
SFP 3, DATA6
VAL
SFP 3, DATA7
SAV
SFP 3, DATA7
VAL
SFP 3, DATA8
AGA 1, SPGR
Relative Density
SAV
SFP 3, DATA8
VAL
CLK 1, MINUTE
!=
VAL
==
VAL
SAV
FST 2, R1
VAL
SFP 3, DATA1
==
VAL
SFP 3, DATA2
SFP 3, DATA1
SAV
SFP 2, DATA1
VAL
SFP 3, DATA9
P41
FST 2, R1
Verify Minutes = 0
Verify Condition Control Flag
P42
P8
Hour Pressure Average
Count. Today Pressurte Average
SAV
SFP 3, DATA9
VAL
SFP 3, DATA10
SFP 2, DATA1
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
P8
P9
SAV
SFP 3, DATA10
GO
P9
VAL
-1
SAV
SFP 2, DATA1
VAL
SFP 3, DATA3
==
SFP 3, DATA4
SFP 3, DATA3
SAV
SFP 2, DATA2
VAL
SFP 3, DATA11
P10
P11
SFP 3, DATA11
VAL
SFP 3, DATA12
SFP 2, DATA2
SAV
SFP 3, DATA12
GO
P11
VAL
-1
SAV
SFP 2, DATA2
VAL
SFP 3, DATA5
P13
SFP 3, DATA6
SFP 3, DATA5
SAV
SFP 2, DATA3
VAL
SFP 3, DATA13
SFP 3, DATA13
VAL
SFP 3, DATA14
SFP 2, DATA3
SAV
SFP 3, DATA14
GO
P13
VAL
-1
SAV
SFP 2, DATA3
VAL
SFP 3, DATA7
P15
SFP 3, DATA8
SFP 3, DATA7
SAV
SFP 2, DATA4
VAL
SFP 3, DATA15
SFP 3, DATA15
VAL
SFP 3, DATA16
SFP 2, DATA4
SAV
SFP 3, DATA16
GO
P15
VAL
-1
SAV
SFP 2, DATA4
VAL
SFP 1, DATA6
/
VAL
P10
Hour Today Temperature
Count. Today Temperature Average
P12
Hour Flow Average
Count. Today Flow Average
P14
SAV
SAV
VAL
SAV
==
P14
VAL
SHEET
SAV
==
P12
VAL
I-MA-4451.28-6250-27D-FRB-002
FST 2, R2
SFP 2, DATA9
1000
SFP 2, DATA10
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
67 OF 73
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
VAL
FST 2, R2
VAL
SFP 1, DATA20
SFP 2, DATA11
VAL
SFP 1, DATA20
SAV
FST 2, R3
VAL
CLK 1, HOUR
!=
==
0
0
SFP 3, DATA10
SFP 3, DATA9
SAV
SFP 2, DATA5
GO
P25
P24
VAL
-1
SAV
SFP 2, DATA5
P25
VAL
SFP 3, DATA11
0
VAL
SFP 3, DATA12
SFP 3, DATA11
SAV
SFP 2, DATA6
GO
P27
P26
VAL
-1
SAV
SFP 2, DATA6
P27
VAL
SFP 3, DATA13
==
VAL
SFP 3, DATA14
SFP 3, DATA13
SAV
SFP 2, DATA7
GO
P29
P28
VAL
-1
SAV
SFP 2, DATA7
P29
VAL
SFP 3, DATA15
==
Verify Hour = 0
P24
Today Pressure Average
P26
Today Temperature Average
P28
Today Flow Average
VAL
SFP 3, DATA16
SFP 3, DATA15
SAV
SFP 2, DATA8
GO
P31
P30
VAL
-1
SAV
SFP 2, DATA8
P31
VAL
SAV
SFP 3, DATA9
SAV
SFP 3, DATA10
SAV
SFP 3, DATA11
SAV
SFP 3, DATA12
SAV
SFP 3, DATA13
SAV
SFP 3, DATA14
SAV
SFP 3, DATA15
P40
SFP 3, DATA9
VAL
==
P40
SAV
SFP 3, DATA16
VAL
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
68 OF 73
FST 2, R3
SAV
VAL
SHEET
SFP 1, DATA6
SAV
-
REV
I-MA-4451.28-6250-27D-FRB-002
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
P41
P42
SAV
SFP 3, DATA1
SAV
SFP 3, DATA2
SAV
SFP 3, DATA3
SAV
SFP 3, DATA4
SAV
SFP 3, DATA5
SAV
SFP 3, DATA6
SAV
SFP 3, DATA7
SAV
SFP 3, DATA8
GO
P42
VAL
SAV
FST 2, R1
I-MA-4451.28-6250-27D-FRB-002
SHEET
REV
69 OF 73
END
15.3 FST 3
It updates the gas composition values for the Z calculation
Label
CMD
Argument 1
Argument 2
END
WT
300
VAL
SAV
FLW 1, RECALCZS
Comment
300 Seconds Temporization
Update Z Calculation for Gas Composition
END
15.4 FST 4
It updates the gas composition values for the Z calculation
Label
CMD
Argument 1
Argument 2
CKMIN
WT
VAL
CLK 1, HOUR
==
VAL
SAV
FST 4, R1
GO
END
VAL
CLK 1, MINUTE
==
GO
END
WRTFLS VAL
END
Comment
5 Seconds Temporization
CKMIN
Verify Hour = 0
Control Flag = 0
WRTFLS
Verify Minute = 5
FST 4, R1
==
VAL
SAV
FLG 1, WRITE
VAL
SAV
FST 4, R1
EVT
WRT MENORY
END
Writing Flash Memory Configuration
Control Flag
FLG 1, WRITE
END
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
NUMBER
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
16
I-MA-4451.28-6250-27D-FRB-002
SHEET
HISTORY
16.1 STREAM 01
Point
Archive Type
Archive Point
Description
Totalize
ERN 1, MINTDY
Average
FLW 1, CURDP
Average
FLW 1, CURFP
Average
FLW 1, CURTMP
Average
FLW 1, IMV/BMV
Average
FLW 1, HWPF
Accumulated
FLW 1, CURFLO
Accumulated
FLW 1, ENERGY
Accumulated energy
Average
FLW 1, CURFLO
Static Pressure
Temperature
Constant of correction of the calculation AGA
Extension HWPF of the AGA3 1992
Flow accumulated corrected
10
Average
AGA 1, SPGR
11
Current Value
ERN1, FLOACC
Specific Gravity
12
Current Value
ERN1, FLOTDY
13
Current Value
ERN1, FLOMTH
16.2 STREAM 02
Point
Archive Type
Archive Point
14
UNDEFINED
UNDEFINED
Reserve
Description
15
UNDEFINED
UNDEFINED
Reserve
16
UNDEFINED
UNDEFINED
Reserve
17
UNDEFINED
UNDEFINED
Reserve
18
UNDEFINED
UNDEFINED
Reserve
19
UNDEFINED
UNDEFINED
Reserve
20
UNDEFINED
UNDEFINED
Reserve
21
UNDEFINED
UNDEFINED
Reserve
22
UNDEFINED
UNDEFINED
Reserve
23
UNDEFINED
UNDEFINED
Reserve
24
UNDEFINED
UNDEFINED
Reserve
25
UNDEFINED
UNDEFINED
Reserve
16.3 STREAM 03
Point
Archive Type
Archive Point
26
UNDEFINED
UNDEFINED
Reserve
Description
27
UNDEFINED
UNDEFINED
Reserve
28
UNDEFINED
UNDEFINED
Reserve
29
UNDEFINED
UNDEFINED
Reserve
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
70 OF 73
NUMBER
MANUAL
JOB OR PROJECT
I-MA-4451.28-6250-27D-FRB-002
SHEET
AREA/UNIT:
TITLE
30
UNDEFINED
UNDEFINED
Reserve
31
UNDEFINED
UNDEFINED
Reserve
32
UNDEFINED
UNDEFINED
Reserve
33
UNDEFINED
UNDEFINED
Reserve
34
UNDEFINED
UNDEFINED
Reserve
35
UNDEFINED
UNDEFINED
Reserve
36
UNDEFINED
UNDEFINED
Reserve
37
UNDEFINED
UNDEFINED
Reserve
16.4 STREAM 04
Point
Archive Type
Archive Point
38
UNDEFINED
UNDEFINED
Reserve
39
UNDEFINED
UNDEFINED
Reserve
40
UNDEFINED
UNDEFINED
Reserve
41
UNDEFINED
UNDEFINED
Reserve
42
UNDEFINED
UNDEFINED
Reserve
43
UNDEFINED
UNDEFINED
Reserve
44
UNDEFINED
UNDEFINED
Reserve
45
UNDEFINED
UNDEFINED
Reserve
46
UNDEFINED
UNDEFINED
Reserve
47
UNDEFINED
UNDEFINED
Reserve
48
UNDEFINED
UNDEFINED
Reserve
49
UNDEFINED
UNDEFINED
Reserve
17
Description
COMM PORTS
Description
Value
Rate of Transmission
9600
Parity
Parity
None
Data Bits
Stop Bits
Key On Delay
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
71 OF 73
NUMBER
MANUAL
JOB OR PROJECT
I-MA-4451.28-6250-27D-FRB-002
SHEET
AREA/UNIT:
TITLE
Description
Value
Start Transmission
Inactive
Continuous Polling
Disabled
Description
Value
Baud Rate
Rate of Transmission
9600
Parity
Parity
None
Data Bits
Stop Bits
RTS/CTS Handshaking
Disabled
Key On Delay
0.02
0.01
Description
Value
Start Transmission
Inactive
Continuous Polling
Disabled
Description
Value
Baud Rate
Tax of Transmission
9600
Parity
Parity
None
Data Bits
Stop Bits
RTS/CTS Handshaking
Disabled
Key On Delay
0.02
0.01
Description
Value
Start Transmission
Inactive
Continuous Polling
Disabled
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.
REV
72 OF 73
MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE
NUMBER
I-MA-4451.28-6250-27D-FRB-002
SHEET
REV
73 OF 73
Obs: The Modem / RBX and Store & Forward Must be Configured on COM1 and COM2 as None / Disable and Same Port,
Respectively.
18
FLAGS
18.1 FLAGS
18.1.1 ADVANCED
Item
Description
Transmitter Power +T
19
Value
on
CALCULATIONS OF FLOW
USER PROGRAMS
These User Programs should be downloaded to the Floboss:
o
FBMB1_60.H00 User Program protocol Modbus RTU port Comm 1 Version 2.01;
FBMB2_05.H00 User Program protocol Modbus RTU port Comm 2 Version 2.01.
THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.