You are on page 1of 73

N

MANUAL
GAS & ENERGIA

CLIENT:
JOB:

I-MA-4451.28-6250-27D-FRB-002
SHEET

1 OF 73

LNG FLEXIBLE TERMINAL

REA:

PECEM PORT

TITLE:

GAS FLOW COMPUTERS CONFIGURATION MANUAL


CONTRACT

ENG. RESP.

INS-36789-MA-001

REVISON INDEX
REV
0
A
B

DESCRIPTION AND/OR AFFECTED SHEETS


ORIGINAL
ACCORDING TO COMMENTS
AS BUILT

DATE

REV. 0

REV. A

REV. B

01/07/08

06/26/08

07/21/08
AUTOMIND

AUTOMIND

AUTOMIND

EXECUTION

GGC

CMV

CMV

CHECK

AVNO

AVNO

AVNO

APPROVAL

AVNO

AVNO

AVNO

DESIGN

REV. C

REV. D

REV. E

REV. F

REV. G

REV. H

THE INFORMATIONS CONTAINED IN THIS DOCUMENT IS PETROBRAS PROPERY AND MAY NOT BE USED FOR PURPOSES OTHER THAN THOSE SPECIFICALLY INDICATED
HEREIN / FORM STANDARTIZED BY STANDARD PETROBRAS N-381 REV. G

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

NUMBER

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

SHEET

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

FQY - 413

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

2 OF 73

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

NUMBER

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

SHEET

REV

3 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL
NDICE

INTRODUCTION .................................................................................................................................................................... 7

REFERENCES ....................................................................................................................................................................... 7

CALCULATION AGA7 1996 ................................................................................................................................................... 7


3.1

3.2

3.3

3.4

STREAM: #1........................................................................................................................................................................ 7
3.1.1

GENERAL............................................................................................................................................................... 7

3.1.2

INPUTS................................................................................................................................................................... 7

3.1.3

GAS QUALITY ........................................................................................................................................................ 7

3.1.4

ADVANCED FEATURES ........................................................................................................................................ 8

3.1.5

ALARMS ................................................................................................................................................................. 8

STREAM: #2........................................................................................................................................................................ 9
3.2.1

GENERAL............................................................................................................................................................... 9

3.2.2

INPUTS................................................................................................................................................................... 9

3.2.3

GAS QUALITY ........................................................................................................................................................ 9

3.2.4

ADVANCED FEATURES ........................................................................................................................................ 10

3.2.5

ALARMS ................................................................................................................................................................. 10

STREAM: #3........................................................................................................................................................................ 10
3.3.1

GENERAL............................................................................................................................................................... 10

3.3.2

INPUTS................................................................................................................................................................... 10

3.3.3

GAS QUALITY ........................................................................................................................................................ 11

3.3.4

ADVANCED FEATURES ........................................................................................................................................ 11

3.3.5

ALARMS ................................................................................................................................................................. 12

STREAM: #4........................................................................................................................................................................ 12
3.4.1

GENERAL............................................................................................................................................................... 12

3.4.2

INPUTS................................................................................................................................................................... 12

3.4.3

GAS QUALITY ........................................................................................................................................................ 12

3.4.4

ADVANCED FEATURES ........................................................................................................................................ 13

3.4.5

ALARMS ................................................................................................................................................................. 13

MULTIVARIABLE SENSOR (MVS)......................................................................................................................................... 13


4.1

NUMBER POINT: MVS POINT #1....................................................................................................................................... 13

4.2

NUMBER POINT: MVS POINT #2....................................................................................................................................... 14

4.3

NUMBER POINT: MVS POINT #3....................................................................................................................................... 15

4.4

NUMBER POINT: MVS POINT #4....................................................................................................................................... 15


ANALOG INPUTS (AI) ............................................................................................................................................................ 16

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

5.1

5.2

5.3

5.4

5.5

5.6

NUMBER

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

SHEET

REV

4 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

NUMBER POINT: AI #1 (A1) TIT-413 .................................................................................................................................. 16


5.1.1

GENERAL............................................................................................................................................................... 16

5.1.2

ADVANCED ............................................................................................................................................................ 16

5.1.3

ALARMS ................................................................................................................................................................. 17

NUMBER POINT: AI #2 (A2) NOT APPLICABLE ................................................................................................................ 17


5.2.1

GENERAL............................................................................................................................................................... 17

5.2.2

ADVANCED ............................................................................................................................................................ 17

5.2.3

ALARMS ................................................................................................................................................................. 18

NUMBER POINT: AI #3 (A3) PIT-413.................................................................................................................................. 18


5.3.1

GENERAL............................................................................................................................................................... 18

5.3.2

ADVANCED ............................................................................................................................................................ 18

5.3.3

ALARMS ................................................................................................................................................................. 18

NUMBER POINT: AI #4 (E1) TAG: + T (POWER OUT)....................................................................................................... 19


5.4.1

GENERAL............................................................................................................................................................... 19

5.4.2

ADVANCED ............................................................................................................................................................ 19

5.4.3

ALARMS ................................................................................................................................................................. 19

NUMBER POINT: AI #5 (E2) TAG: POWER IN ................................................................................................................... 20


5.5.1

GENERAL............................................................................................................................................................... 20

5.5.2

ADVANCED ............................................................................................................................................................ 20

5.5.3

ALARMS ................................................................................................................................................................. 20

NUMBER POINT: AI #8 (E5) TAG: BRD TEMP................................................................................................................... 20


5.6.1

GENERAL............................................................................................................................................................... 20

5.6.2

ADVANCED ............................................................................................................................................................ 21

5.6.3

ALARMS ................................................................................................................................................................. 21

PULSE INPUTS (PI) ............................................................................................................................................................... 21


6.1

NUMBER POINT: PI #1 (A7) TAG: FIT-413......................................................................................................................... 21


6.1.1

GENERAL............................................................................................................................................................... 21

6.1.2

ADVANCED ............................................................................................................................................................ 22

6.1.3

ALARMS ................................................................................................................................................................. 22

MODBUS CONFIG COM1 ...................................................................................................................................................... 22


7.1

NUMBER POINT: #1 (CONFIGURATION MODBUS RTU RS-485)..................................................................................... 22


MODBUS FUNCT COM1(REGISTERS MODBUS RTU) ........................................................................................................ 23

8.1

NUMBER POINT: #3 FUNCT 3A ......................................................................................................................................... 23

8.2

NUMBER POINT: #4 FUNCT 3B ......................................................................................................................................... 23

8.3

NUMBER POINT: #5 FUNCT 3C ......................................................................................................................................... 23

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

SHEET

REV

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

NUMBER POINT: #1 (CONFIGURATION MODBUS RTU RS-485)..................................................................................... 24


MODBUS FUNCT COM2 (REGISTERS MODBUS RTU) ....................................................................................................... 24

10.1 NUMBER POINT: #6 FUNCT 4A ......................................................................................................................................... 24


10.2 NUMBER POINT: #7 FUNCT 4B ......................................................................................................................................... 25
10.3 NUMBER POINT: #8 FUNCT 4C ......................................................................................................................................... 25
10.4 NUMBER POINT: #12 FUNCT 16A ..................................................................................................................................... 25
11

MODBUS HOST COM2 .......................................................................................................................................................... 26

12

LCD USER LIST (DISPLAY FLOBOSS) ................................................................................................................................. 26


12.1 USER LIST: #1 .................................................................................................................................................................... 26

13

CONFIGURATION GENERAL - INFORMATION .................................................................................................................... 26


13.1 GENERAL ........................................................................................................................................................................... 26

14

SOFT POINT .......................................................................................................................................................................... 26


14.1 SOFT POINT #1 CONV .................................................................................................................................................... 27
14.2 SOFT POINT #2 MEDIAS................................................................................................................................................. 27
14.3 SOFT POINT #3 ACCUM ................................................................................................................................................. 27
14.4 SOFT POINT #4 DATA/HORA.......................................................................................................................................... 28
14.5 SOFT POINT #5 ALARMES ............................................................................................................................................. 28

15

FST'S...................................................................................................................................................................................... 28
15.1 FST 1................................................................................................................................................................................... 28
15.2 FST 2................................................................................................................................................................................... 30
15.3 FST 3................................................................................................................................................................................... 33
15.4 FST 4................................................................................................................................................................................... 33

16

HISTORY................................................................................................................................................................................ 34
16.1 STREAM 01......................................................................................................................................................................... 34
16.2 STREAM 02......................................................................................................................................................................... 34
16.3 STREAM 03......................................................................................................................................................................... 34
16.4 STREAM 04......................................................................................................................................................................... 35

17

COMM PORTS ....................................................................................................................................................................... 35


17.1 COMM PORT: #1 LOCAL PORT ......................................................................................................................................... 35
17.1.1 GENERAL............................................................................................................................................................... 35
17.1.2 MODBUS HOST PARAMETERS ............................................................................................................................ 35

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

5 OF 73

MODBUS CONFIG COM2 ...................................................................................................................................................... 24


9.1

10

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

NUMBER

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

SHEET

REV

6 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

17.2 COMM PORT: #2 COMM 1 ................................................................................................................................................. 36


17.2.1 GENERAL............................................................................................................................................................... 36
17.2.2 MODBUS HOST PARAMETERS ............................................................................................................................ 36
17.3 COMM PORT: #3 COMM 2 ................................................................................................................................................. 36
17.3.1 GENERAL............................................................................................................................................................... 36
17.3.2 MODBUS HOST PARAMETERS ............................................................................................................................ 36
18

FLAGS.................................................................................................................................................................................... 37
18.1 FLAGS................................................................................................................................................................................. 37
18.1.1 ADVANCED ............................................................................................................................................................ 37

19

CALCULATIONS OF FLOW ................................................................................................................................................... 37


19.1 ROC / INFORMATION......................................................................................................................................................... 37
19.1.1 POINTS................................................................................................................................................................... 37

20

USER PROGRAMS ................................................................................................................................................................ 37

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002
SHEET

LNG TERMINAL PROJECT

REV

7 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

INTRODUCTION
The purpose of this document is to detail the configuration of the Flow Computer FQY-413, of the Metering
System on LNG Flexible Terminal, at Pecm Port CE.

REFERENCES

Automation System Pecm I-DE-4451.28-6250-800-FRB-001 Rev. E;

Functional Specification I-ET-4451.28-6250-800-FRB-001 Rev. D.

CALCULATION AGA7 1996

3.1

STREAM: #1

3.1.1

GENERAL
Item

Description

Valor

Meter Tag

STREAM Identification

FIT-413

Meter Description

STREAM Description

Fiscal Metering STREAM 01

Meter Type

Meter Type

Turbine

Alarming

Alarms Enabled or Disabled

Enabled

Scan Period

Scan Period

1 Seconds

3.1.2

INPUTS
Item

Description

Value

Uncorrected Volume

Flow Uncorrected Input

PIN A7, EU

Static Pressure

Static Pressure Input

AIN A3, EU

Temperature

Temperature Input

AIN A1, EU

3.1.3

GAS QUALITY
Item

Description

Value

Nitrogen

Percent. Nitrogen gas composition

Input by Operator

CO2

Percent. Carbon Dioxide gas composition

Input by Operator

Methane

Percent. Methane gas composition

Input by Operator

Ethane

Percent. Ethane gas composition

Input by Operator

Propane

Percent. Propane gas composition

Input by Operator

n-Butane

Percent. n-Butane gas composition

Input by Operator

i-Butane

Percent. i-Butane gas composition

Input by Operator

n-Pentane

Percent. n-Pentane gas composition

Input by Operator

i-Pentane

Percent. i-Pentane gas composition

Input by Operator

Hexane

Percent. Hexane gas composition

Input by Operator

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

NUMBER

MANUAL
JOB OR PROJECT

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

Heptane

Percent. Heptane gas composition

Input by Operator

Octane

Percent. Octane gas composition

Input by Operator

Nonane

Percent. Nonane gas composition

Input by Operator

Decane

Percent. Decane gas composition

Input by Operator

H2S

Percent. Sulphydric Acid gas composition

Input by Operator

Water

Percent. Water gas composition

Input by Operator

Helium

Percent. Helium gas composition

Input by Operator

Oxygen

Percent. Oxygen gas composition

Input by Operator

CO

Percent. CO gas composition

Input by Operator

Hydrogen

Percent. Hydrogen gas composition

Input by Operator

Heating Value Basis

Heating Value Basis

Dry

Log Methane Adjust

Adjust of methane

Enabled

Heating Value

Heating Value

Calculate (MJ/M3)

Spec Gravity

Specific Gravity

Calculate

3.1.4

SHEET

LNG TERMINAL PROJECT

AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002

ADVANCED FEATURES
Item

Description

Valor

FPV Method

Type Calculation

Detailed

Units

Units

Metric KM3/GJ

Base Temperature

Base Temperature

20 Deg C

Base Pressure

Base Pressure

101.325 kPa

Atmospheric Pressure

Atmospheric Pressure

Enter - 101.325 kPa

Elevation

Elevation

0.0 Meters

Latitude

Latitude

0.0 Deg

User Correction Factor

Gravity Correction

1.0

Pressure Tap

Pressure Tap

Gauge

Meter Factor

Meter Factor

1.0

3.1.5

ALARMS
Item

Description

Value

Low Alarm

Limit Alarm Low

1000

High Alarm

Limit Alarm High

7900

RBX Alarming

Alarm for exception

Disabled

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

8 OF 73

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

3.2

I-MA-4451.28-6250-27D-FRB-002
SHEET

LNG TERMINAL PROJECT


LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

STREAM: #2

3.2.1

GENERAL
Item

Description

Valor

Meter Tag

STREAM Identification

Not Applicable

Meter Description

STREAM Description

Not Applicable

Meter Type

Meter Type

Not Applicable

Alarming

Alarms Enabled or Disabled

Disabled

Scan Period

Scan Period

Not Applicable

3.2.2

INPUTS
Item

Description

Value

Uncorrected Volume

Flow Uncorrected Input

Manual

Static Pressure

Static Pressure Input

Manual

Temperature

Temperature Input

Manual

3.2.3

GAS QUALITY
Item

Description

Value

Nitrogen

Percent. Nitrogen gas composition

Not Applicable

CO2

Percent. Carbon Dioxide gas composition

Not Applicable

Methane

Percent. Methane gas composition

Not Applicable

Ethane

Percent. Ethane gas composition

Not Applicable

Propane

Percent. Propane gas composition

Not Applicable

n-Butane

Percent. n-Butane gas composition

Not Applicable

i-Butane

Percent. i-Butane gas composition

Not Applicable

n-Pentane

Percent. n-Pentane gas composition

Not Applicable

i-Pentane

Percent. i-Pentane gas composition

Not Applicable

Hexane

Percent. Hexane gas composition

Not Applicable

Heptane

Percent. Heptane gas composition

Not Applicable

Octane

Percent. Octane gas composition

Not Applicable

Nonane

Percent. Nonane gas composition

Not Applicable

Decane

Percent. Decane gas composition

Not Applicable

H2S

Percent. Sulphydric Acid gas composition

Not Applicable

Water

Percent. Water gas composition

Not Applicable

Helium

Percent. Helium gas composition

Not Applicable

Oxygen

Percent. Oxygen gas composition

Not Applicable

CO

Percent. CO gas composition

Not Applicable

Hydrogen

Percent. Hydrogen gas composition

Not Applicable

Heating Value Basis

Heating Value Basis

Not Applicable

Log Methane Adjust

Adjust of methane

Disabled

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

9 OF 73

NUMBER

MANUAL
JOB OR PROJECT

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

Heating Value

Heating Value

Not Applicable

Spec Gravity

Specific Gravity

Not Applicable

3.2.4

ADVANCED FEATURES
Item

Description

Valor

FPV Method

Type Calculation

Not Applicable

Units

Units

Not Applicable

Base Temperature

Base Temperature

Not Applicable

Base Pressure

Base Pressure

Not Applicable

Atmospheric Pressure

Atmospheric Pressure

Not Applicable

Elevation

Elevation

Not Applicable

Latitude

Latitude

Not Applicable

User Correction Factor

Gravity Correction

Not Applicable

Pressure Tap

Pressure Tap

Not Applicable

Meter Factor

Meter Factor

Not Applicable

3.2.5

ALARMS
Item

Description

Value

Low Alarm

Limit Alarm Low

Not Applicable

High Alarm

Limit Alarm High

Not Applicable

RBX Alarming

Alarm for exception

Disabled

3.3
3.3.1

STREAM: #3
GENERAL
Item

Description

Valor

Meter Tag

STREAM Identification

Not Applicable

Meter Description

STREAM Description

Not Applicable

Meter Type

Meter Type

Not Applicable

Alarming

Alarms Enabled or Disabled

Disabled

Scan Period

Scan Period

Not Applicable

3.3.2

SHEET

LNG TERMINAL PROJECT

AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002

INPUTS
Item

Description

Value

Uncorrected Volume

Flow Uncorrected Input

Manual

Static Pressure

Static Pressure Input

Manual

Temperature

Temperature Input

Manual

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

10 OF 73

NUMBER

MANUAL
JOB OR PROJECT

3.3.3

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

GAS QUALITY
Item

Nitrogen

Description

Value

Percent. Nitrogen gas composition

Not Applicable

CO2

Percent. Carbon Dioxide gas composition

Not Applicable

Methane

Percent. Methane gas composition

Not Applicable

Ethane

Percent. Ethane gas composition

Not Applicable

Propane

Percent. Propane gas composition

Not Applicable

n-Butane

Percent. n-Butane gas composition

Not Applicable

i-Butane

Percent. i-Butane gas composition

Not Applicable

n-Pentane

Percent. n-Pentane gas composition

Not Applicable

i-Pentane

Percent. i-Pentane gas composition

Not Applicable

Hexane

Percent. Hexane gas composition

Not Applicable

Heptane

Percent. Heptane gas composition

Not Applicable

Octane

Percent. Octane gas composition

Not Applicable

Nonane

Percent. Nonane gas composition

Not Applicable

Decane

Percent. Decane gas composition

Not Applicable

H2S

Percent. Sulphydric Acid gas composition

Not Applicable

Water

Percent. Water gas composition

Not Applicable

Helium

Percent. Helium gas composition

Not Applicable

Oxygen

Percent. Oxygen gas composition

Not Applicable

CO

Percent. CO gas composition

Not Applicable

Hydrogen

Percent. Hydrogen gas composition

Not Applicable

Heating Value Basis

Heating Value Basis

Not Applicable

Log Methane Adjust

Adjust of methane

Disabled

Heating Value

Heating Value

Not Applicable

Spec Gravity

Specific Gravity

Not Applicable

3.3.4

SHEET

LNG TERMINAL PROJECT

AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002

ADVANCED FEATURES
Item

Description

Valor

FPV Method

Type Calculation

Not Applicable

Units

Units

Not Applicable

Base Temperature

Base Temperature

Not Applicable

Base Pressure

Base Pressure

Not Applicable

Atmospheric Pressure

Atmospheric Pressure

Not Applicable

Elevation

Elevation

Not Applicable

Latitude

Latitude

Not Applicable

User Correction Factor

Gravity Correction

Not Applicable

Pressure Tap

Pressure Tap

Not Applicable

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

11 OF 73

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

3.3.5

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT


LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

ALARMS
Item

Description

Value

Low Alarm

Limit Alarm Low

Not Applicable

High Alarm

Limit Alarm High

Not Applicable

RBX Alarming

Alarm for exception

Disabled

3.4

SHEET

STREAM: #4

3.4.1

GENERAL
Item

Description

Valor

Meter Tag

STREAM Identification

Not Applicable

Meter Description

STREAM Description

Not Applicable

Meter Type

Meter Type

Not Applicable

Alarming

Alarms Enabled or Disabled

Disabled

Scan Period

Scan Period

Not Applicable

3.4.2

INPUTS
Item

Description

Value

Uncorrected Volume

Flow Uncorrected Input

Manual

Static Pressure

Static Pressure Input

Manual

Temperature

Temperature Input

Manual

3.4.3

GAS QUALITY
Item

Description

Value

Nitrogen

Percent. Nitrogen gas composition

Not Applicable

CO2

Percent. Carbon Dioxide gas composition

Not Applicable

Methane

Percent. Methane gas composition

Not Applicable

Ethane

Percent. Ethane gas composition

Not Applicable

Propane

Percent. Propane gas composition

Not Applicable

n-Butane

Percent. n-Butane gas composition

Not Applicable

i-Butane

Percent. i-Butane gas composition

Not Applicable

n-Pentane

Percent. n-Pentane gas composition

Not Applicable

i-Pentane

Percent. i-Pentane gas composition

Not Applicable

Hexane

Percent. Hexane gas composition

Not Applicable

Heptane

Percent. Heptane gas composition

Not Applicable

Octane

Percent. Octane gas composition

Not Applicable

Nonane

Percent. Nonane gas composition

Not Applicable

Decane

Percent. Decane gas composition

Not Applicable

H2S

Percent. Sulphydric Acid gas composition

Not Applicable

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

12 OF 73

NUMBER

MANUAL
JOB OR PROJECT

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

AREA/UNIT:

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

Water

Percent. Water gas composition

Not Applicable

Helium

Percent. Helium gas composition

Not Applicable

Oxygen

Percent. Oxygen gas composition

Not Applicable

CO

Percent. CO gas composition

Not Applicable

Hydrogen

Percent. Hydrogen gas composition

Not Applicable

Heating Value Basis

Heating Value Basis

Not Applicable

Log Methane Adjust

Adjust of methane

Disabled

Heating Value

Heating Value

Not Applicable

Spec Gravity

Specific Gravity

Not Applicable

3.4.4

ADVANCED FEATURES
Item

Description

Valor

FPV Method

Type Calculation

Not Applicable

Units

Units

Not Applicable

Base Temperature

Base Temperature

Not Applicable

Base Pressure

Base Pressure

Not Applicable

Atmospheric Pressure

Atmospheric Pressure

Not Applicable

Elevation

Elevation

Not Applicable

Latitude

Latitude

Not Applicable

User Correction Factor

Gravity Correction

Not Applicable

Pressure Tap

Pressure Tap

Not Applicable

3.4.5

ALARMS
Item

Description

Value

Low Alarm

Limit Alarm Low

Not Applicable

High Alarm

Limit Alarm High

Not Applicable

RBX Alarming

Alarm for exception

Disabled

SHEET

MULTIVARIABLE SENSOR (MVS)

4.1

NUMBER POINT: MVS POINT #1


Item

Description

Value

Tag

MVS Identification

Address

Address RS-485

Not Applicable
Not Applicable

Scanning

Scan Enabled or Disabled

Disabled

Units

Unit System

Not Applicable

Sensor Alarms

Sensor Alarm Enabled or Disabled

Disabled

Diff. Pressure Alarm

Diff. Pressure Alarm Enabled or Disabled

Disabled

Low Alarm Diff. Pressure

Not Applicable

Low Alarm

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

13 OF 73

NUMBER

MANUAL
JOB OR PROJECT

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

AREA/UNIT:

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

High Alarm

High Alarm Diff. Pressure

Not Applicable

Alarm Deadband

Alarm Deadband Diff. Pressure

Not Applicable

Fault Value

Fault Value Diff. Pressure

Not Applicable

Pressure Alarm Enabled or Disabled

Disabled

Pressure Alarm
Low Alarm

Low Alarm - Pressure

Not Applicable

High Alarm

High Alarm - Pressure

Not Applicable

Alarm Deadband

Alarm Deadband - Pressure

Not Applicable

Fault Value

Fault Value - Pressure

Not Applicable

Temperature Alarm Enabled or Disabled

Disabled

Temperature Alarm
Low Alarm

Low Alarm - Temperature

Not Applicable

High Alarm

High Alarm - Temperature

Not Applicable

Alarm Deadband

Alarm Deadband - Temperature

Not Applicable

Fault Value

Fault Value - Temperature

Not Applicable

Report Pressure As

Upstream or Downstream

Not Applicable

Action on Failure

Action on Failure

Not Applicable

RBX Alarming

Exception Alarm

Disabled

Reference Temperature

Reference Temperature

Not Applicable

4.2

SHEET

NUMBER POINT: MVS POINT #2


Item

Description

Value

Tag

MVS Identification

Not Applicable

Address

Address RS-485

Not Applicable

Scanning

Scan Enabled or Disabled

Disabled

Units

Unit System

Not Applicable

Sensor Alarms

Sensor Alarm Enabled or Disabled

Disabled

Diff. Pressure Alarm

Diff. Pressure Alarm Enabled or Disabled

Disabled

Low Alarm

Low Alarm Diff. Pressure

Not Applicable

High Alarm

High Alarm Diff. Pressure

Not Applicable

Alarm Deadband

Alarm Deadband - Diff Pressure

Not Applicable

Fault Value

Fault Value Diff. Pressure

Not Applicable

Pressure Alarm Enabled or Disabled

Disabled

Pressure Alarm
Low Alarm

Low Alarm - Pressure

Not Applicable

High Alarm

High Alarm - Pressure

Not Applicable

Alarm Deadband

Alarm Deadband - Pressure

Not Applicable

Fault Value

Fault Value - Pressure

Not Applicable

Temperature Alarm

Temperature Alarm Enabled or Disabled

Disabled

Low Alarm

Low Alarm - Temperature

Not Applicable

High Alarm

High Alarm - Temperature

Not Applicable

Alarm Deadband

Alarm Deadband - Temperature

Not Applicable

Fault Value
Report Pressure As

Fault Value - Temperature

Not Applicable

Upstream or Downstream

Not Applicable

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

14 OF 73

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT


LNG FLEXIBLE TERMINAL PECM PORT

TITLE

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

Action on Failure

Action on Failure

Not Applicable

RBX Alarming

Exception Alarm

Disabled

Reference Temperature

Reference Temperature

Not Applicable

4.3

NUMBER POINT: MVS POINT #3


Item

Description

Value

Tag

MVS Identification

Not Applicable

Address

Address RS-485

Not Applicable

Scanning

Scan Enabled or Disabled

Disabled

Units

Unit System

Not Applicable

Sensor Alarms

Sensor Alarm Enabled or Disabled

Disabled

Diff. Pressure Alarm

Diff. Pressure Alarm Enabled or Disabled

Disabled

Low Alarm

Low Alarm Diff. Pressure

Not Applicable

High Alarm

High Alarm Diff. Pressure

Not Applicable

Alarm Deadband

Alarm Deadband - Diff Pressure

Not Applicable

Fault Value
Pressure Alarm

Fault Value Diff. Pressure

Not Applicable

Pressure Alarm Enabled or Disabled

Disabled

Low Alarm

Low Alarm - Pressure

Not Applicable

High Alarm

High Alarm - Pressure

Not Applicable

Alarm Deadband

Alarm Deadband - Pressure

Not Applicable

Fault Value

Fault Value - Pressure

Not Applicable

Temperature Alarm

Temperature Alarm Enabled or Disabled

Disabled

Low Alarm

Low Alarm - Temperature

Not Applicable

High Alarm

High Alarm - Temperature

Not Applicable

Alarm Deadband

Alarm Deadband - Temperature

Not Applicable

Fault Value

Fault Value - Temperature

Not Applicable

Report Pressure As
Action on Failure

Upstream or Downstream
Action on Failure

Not Applicable
Not Applicable

RBX Alarming

Exception Alarm

Disabled

Reference Temperature

Reference Temperature

Not Applicable

4.4

SHEET

NUMBER POINT: MVS POINT #4


Item

Tag

Description
MVS Identification

Value
Not Applicable

Address

Address RS-485

Not Applicable

Scanning

Scan Enabled or Disabled

Disabled

Units

Unit System

Not Applicable

Sensor Alarms

Sensor Alarm Enabled or Disabled

Disabled

Diff. Pressure Alarm

Diff. Pressure Alarm Enabled or Disabled

Disabled

Low Alarm Diff. Pressure

Not Applicable

Low Alarm

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

15 OF 73

NUMBER

MANUAL
JOB OR PROJECT

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

High Alarm

High Alarm Diff. Pressure

Not Applicable

Alarm Deadband

Alarm Deadband Diff. Pressure

Not Applicable

Fault Value

Fault Value Diff. Pressure

Not Applicable

Pressure Alarm Enabled or Disabled

Disabled

Pressure Alarm
Low Alarm

Low Alarm - Pressure

Not Applicable

High Alarm

High Alarm - Pressure

Not Applicable

Alarm Deadband

Alarm Deadband - Pressure

Not Applicable

Fault Value

Fault Value - Pressure

Not Applicable

Temperature Alarm Enabled or Disabled

Disabled

Temperature Alarm
Low Alarm

Low Alarm - Temperature

Not Applicable

High Alarm

High Alarm - Temperature

Not Applicable

Alarm Deadband

Alarm Deadband - Temperature

Not Applicable

Fault Value

Fault Value - Temperature

Not Applicable

Report Pressure As

Upstream or Downstream

Not Applicable

Action on Failure

Action on Failure

Not Applicable

RBX Alarming

Exception Alarm

Disabled

Reference Temperature

Reference Temperature

Not Applicable

SHEET

LNG TERMINAL PROJECT

AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002

ANALOG INPUTS (AI)

5.1

NUMBER POINT: AI #1 (A1) TIT-413

5.1.1

GENERAL
Item

Description

Value

Scanning

Scan Enabled or Disabled

Enabled

Alarming

Alarm Enabled or Disabled

Enabled

Units

Unit of Engineering

Scan Period

Scan Period

1 Seconds

Low Reading EU

Low Reading - Range

High Reading EU

High Reading - Range

70

5.1.2

ADVANCED
Item

Description

Value

Filter

Filter

Adjusted A/D 0%

Adjusted 0% of the converter A/D

800

Adjusted A/D 100%

Adjusted 100% of the converter A/D

4000

Action on Failure

Action on Failure

Hold Last Value

Fault Value

Value on Failure

Not Applicable

Average Raw Value


Clipping

Average of the rude readings during scan


Enabled or Disabled
Inside keeps values of the limits of cut
when enabled

Enabled
Disabled

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

16 OF 73

NUMBER

MANUAL
JOB OR PROJECT

Temp Compensation

5.1.3

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL
Uses the FB board temperature to
compensate the AI when enabled

Disabled

ALARMS
Item

Description

Value

Low Alarm

Low Alarm

High Alarm

High Alarm

60

LoLo Alarm

LoLo Alarm

HiHi Alarm

HiHi Alarm

75

Rate Alarm

Rate Alarm

70

Alarm Deadband

Alarm Deadband

RBX Alarming

RBX Alarming

Disabled

5.2

SHEET

LNG TERMINAL PROJECT

AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002

NUMBER POINT: AI #2 (A2) NOT APPLICABLE

5.2.1

GENERAL
Item

Description

Value

Scanning

Scan Enabled or Disabled

Disabled

Alarming

Alarm Enabled or Disabled

Disabled

Units

Unit of Engineering

Not Applicable

Scan Period

Scan Period

Not Applicable

Low Reading EU

Low Reading - Range

Not Applicable

High Reading EU

High Reading - Range

Not Applicable

5.2.2

ADVANCED
Item

Filter

Description

Value

Filter

Not Applicable

Adjusted A/D 0%

Adjusted 0% of the converter A/D

Not Applicable

Adjusted A/D 100%

Adjusted 100% of the converter A/D

Not Applicable

Action on Failure

Action on Failure

Not Applicable

Fault Value

Value on Failure

Not Applicable

Average Raw Value


Clipping
Temp Compensation

Average of the rude readings during scan


Enabled or Disabled
Inside keeps values of the limits of cut when
enabled
Uses the FB board temperature to compensate
the AI when enabled

Disabled
Disabled
Disabled

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

17 OF 73

NUMBER

MANUAL
JOB OR PROJECT

5.2.3

SHEET

LNG TERMINAL PROJECT

AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

ALARMS
Item

Description

Value

Low Alarm

Low Alarm

High Alarm

High Alarm

Not Applicable

LoLo Alarm

LoLo Alarm - Disabled

Not Applicable

HiHi Alarm

HiHi Alarm - Disabled

Not Applicable

Rate Alarm

Rate Alarm

Not Applicable

Alarm Deadband

Alarm Deadband

Not Applicable

RBX Alarming

RBX Alarming

Disabled

5.3

Not Applicable

NUMBER POINT: AI #3 (A3) PIT-413

5.3.1

GENERAL
Item

Description

Value

Scanning

Scan Enabled or Disabled

Enabled

Alarming

Alarm Enabled or Disabled

Enabled

Units

Unit of Engineering

kPa

Scan Period

Scan Period

1 Seconds

Low Reading EU

Low Reading - Range

High Reading EU

High Reading - Range

9317

5.3.2

ADVANCED
Item

Filter

Description

Value

Filter

Adjusted A/D 0%

Adjusted 0% of the converter A/D

800

Adjusted A/D 100%

Adjusted 100% of the converter A/D

4000

Action on Failure

Action on Failure

Hold Last Value

Fault Value

Value on Failure

Not Applicable

Average Raw Value


Clipping
Temp Compensation

5.3.3

Average of the rude readings during scan


Enabled or Disabled
Inside keeps values of the limits of cut when
enabled
Uses the FB board temperature to compensate
the AI when enabled

Enabled
Disabled
Disabled

ALARMS
Item

Description

Value

Low Alarm

Low Alarm

High Alarm

High Alarm

9300

LoLo Alarm

LoLo Alarm - Disabled

HiHi Alarm

HiHi Alarm - Disabled

9317

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

18 OF 73

NUMBER

MANUAL
JOB OR PROJECT

LNG TERMINAL PROJECT

AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

Rate Alarm

Rate Alarm

9317

Alarm Deadband

Alarm Deadband

RBX Alarming

RBX Alarming

Disabled

5.4

SHEET

NUMBER POINT: AI #4 (E1) TAG: + T (POWER OUT)

5.4.1

GENERAL
Item

Description

Value

Scanning

Scan Enabled or Disabled

Enabled

Alarming

Alarm Enabled or Disabled

Enabled

Units

Unit of Engineering

Volts

Scan Period

Scan Period

5 Secs

Low Reading EU

Low Reading - Range

0.0

High Reading EU

High Reading - Range

38.0

5.4.2

ADVANCED
Item

Description

Value

Filter

Filter

Adjusted A/D 0%

Adjusted 0% of the converter A/D

Adjusted A/D 100%

Adjusted 100% of the converter A/D

4000

Average Raw Value


Clipping
Temp Compensation

5.4.3

Average of the rude readings during scan


Enabled or Disabled
Inside keeps values of the limits of cut when
enabled
Uses the FB board temperature to compensate
the AI when enabled

Disabled
Disabled
Disabled

ALARMS
Item

Description

Value

Low Alarm

Low Alarm

10.0

High Alarm

High Alarm

30.0

LoLo Alarm

LoLo Alarm

8.0

HiHi Alarm

HiHi Alarm

32.0

Rate Alarm

Rate Alarm

5.0

Alarm Deadband

Alarm Deadband

2.0

RBX Alarming

RBX Alarming

Disabled

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

19 OF 73

NUMBER

MANUAL
JOB OR PROJECT

LNG TERMINAL PROJECT

AREA/UNIT:
TITLE

5.5

I-MA-4451.28-6250-27D-FRB-002

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

NUMBER POINT: AI #5 (E2) TAG: POWER IN

5.5.1

GENERAL
Item

Description

Value

Scanning

Scan Enabled or Disabled

Enabled

Alarming

Alarm Enabled or Disabled

Enabled

Units

Unit of Engineering

Volts

Scan Period

Scan Period

5 Secs

Low Reading EU

Low Reading - Range

0.0

High Reading EU

High Reading - Range

38.0

5.5.2

ADVANCED
Item

Description

Value

Filter

Filter

Adjusted A/D 0%

Adjusted 0% of the converter A/D

800

Adjusted A/D 100%

Adjusted 100% of the converter A/D

4000

Average Raw Value


Clipping
Temp Compensation

5.5.3

Average of the rude readings during scan


Enabled or Disabled
Inside keeps values of the limits of cut when
enabled
Uses the FB board temperature to compensate
the AI when enabled

Disabled
Disabled
Disabled

ALARMS
Item

Description

Value

Low Alarm

Low Alarm

10.00

High Alarm

High Alarm

30.00

LoLo Alarm

LoLo Alarm

8.00

HiHi Alarm

HiHi Alarm

32.00

Rate Alarm

Rate Alarm

5.00

Alarm Deadband

Alarm Deadband

2.00

RBX Alarming

RBX Alarming

Disabled

5.6

SHEET

NUMBER POINT: AI #8 (E5) TAG: BRD TEMP

5.6.1

GENERAL
Item

Description

Value

Scanning

Scan Enabled or Disabled

Enabled

Alarming

Alarm Enabled or Disabled

Enabled

Units

Unit of Engineering

Scan Period

Scan Period

5 Secs

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

20 OF 73

NUMBER

MANUAL
JOB OR PROJECT

LNG TERMINAL PROJECT

AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

Low Reading EU

Low Reading - Range

-272.77

High Reading EU

High Reading - Range

140.55

5.6.2

SHEET

ADVANCED
Item

Description

Value

Filter

Filter

Adjusted A/D 0%

Adjusted 0% of the converter A/D

Adjusted A/D 100%

Adjusted 100% of the converter A/D

4000

Average Raw Value


Clipping
Temp Compensation

5.6.3

Average of the rude readings during scan


Enabled or Disabled
Inside keeps values of the limits of cut when
enabled
Uses the FB board temperature to compensate
the AI when enabled

Disabled
Disabled
Disabled

ALARMS
Item

Description

Value

Low Alarm

Low Alarm

10.0

High Alarm

High Alarm

50.0

LoLo Alarm

LoLo Alarm

-272.77

HiHi Alarm

HiHi Alarm

140.55

Rate Alarm

Rate Alarm

400.00

Alarm Deadband

Alarm Deadband

20.00

RBX Alarming

RBX Alarming

Disabled

Obs: Others Analog Inputs must be Configured With Scan and Alarms DISABLED.

PULSE INPUTS (PI)

6.1

NUMBER POINT: PI #1 (A7) TAG: FIT-413

6.1.1

GENERAL
Item

Description

Value

Scanning

Scan Enabled or Disabled

Enabled

Alarming

Alarm Enabled or Disabled

Disabled

Units

Unit of Engineering

Counts

Scan Period

Scan Period

1.0 secs

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

21 OF 73

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

6.1.2

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

SHEET

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

ADVANCED
Item

Description

Value

EU Options

Value Options

Rate (Max Rollover)

Conversion

Type of Conversion

Pulses/EU

Conversion/K-Factor

Factor of conversion

10937

Rate Period

Rate Period

EU/day

EU Units

Unit of Engineering

MCF/M3

6.1.3

ALARMS
Item

Description

Value

Low Alarm

Limit Low Alarm

Not Applicable

High Alarm

Limit High Alarm

Not Applicable

LoLo Alarm

Limit LoLo Alarm

Not Applicable

HiHi Alarm

Limit HiHi Alarm

Not Applicable

Rate Alarm

Limit Rate Alarm

Not Applicable

Alarm Deadband

Alarm Deadband

Not Applicable

RBX Alarming

Alarm for exception

Disabled

MODBUS CONFIG COM1

7.1

NUMBER POINT: #1 (CONFIGURATION MODBUS RTU RS-485)


Item

Description

Value

ASCII = 0, RTU = 1

Defines type Protocol Modbus - ASCII our RTU

Byte Order 1 = MSB 1 First

Byte Order Modbus

Host Enabled = 1

Host Enabled

Log Data 1 = Yes

Changing Parameters Register

Init Memory = 1

Init Memory

Port Switch En = 1

Enabled / Disabled of Protocol Changing

DCD = 0, DI = 1, STP = 2

Define Type of Protocol Changing

Modbus Baud Rate

Band Rate Protocol Modbus Enron

9600

Switch Baud Rate

Band Rate Protocol ROC

9600

Input Data Start

Input Data Start

100

Output Data Start

Output Data Start

300

HI Integer Scale

HI Integer Scale

4095

Low Integer Scale

Low Integer Scale

Obs: All the fields of Float Scale must be filled with 0.

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

22 OF 73

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:

8.1

LNG TERMINAL PROJECT

SHEET

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

MODBUS FUNCT COM1(REGISTERS MODBUS RTU)


NUMBER POINT: #3 FUNCT 3A
Start Reg End Reg Pt Type

Lgl# Param Conv

Description

TYPE

40101

40102

17

128

70

Instantaneous Static Pressure

Var. Instant.

40103

40104

10

70

Instantaneous Temperature

Var. Instant.

40105

40106

10

70

Standard Volume Flowrate

Var. Instant.

40107

40108

10

70

Energy Flowrate

Var. Instant.

40109

40110

70

Relative Density

Var. Instant.

40111

40112

10

16

70

Compressibility Factor

Var. Instant.

40113

40114

17

129

11

70

Previous Hour Corrected Total Volume

Var. Instant.

40115

40116

42

70

Current Day Corrected Total Volume

Var. Instant.

40117

40118

42

70

Previous Day Corrected Total Volume

Var. Instant.

10

40119

40120

17

129

12

70

Previous Hour Total Energy

Var. Instant.

8.2

NUMBER POINT: #4 FUNCT 3B


Start Reg End Reg Pt Type

Lgl# Param Conv

Description

TYPE

40121

40122

42

11

70

Current Day Total Energy

Var. Instant.

40123

40124

42

12

70

Previous Day Total Energy

Var. Instant.

40125

40126

28

70

Gas Composition - Methane

Parameters

40127

40128

29

70

Gas Composition - Ethane

Parameters

40129

40130

30

70

Gas Composition - Propane

Parameters

40131

40132

32

70

Gas Composition - I-Butane

Parameters

40133

40134

31

70

Gas Composition - N-Butane

Parameters

40135

40136

34

70

Gas Composition - I-Pentane

Parameters

40137

40138

33

70

Gas Composition - N-Pentane

Parameters

10

40139

40140

35

70

Gas Composition - Hexane

Parameters

8.3

NUMBER POINT: #5 FUNCT 3C


Start Reg End Reg Pt Type

40141

40142

40143

40144

40145

40150

7
8
9

Lgl# Param Conv

Description

TYPE

23

70

Gas Composition - Nitrogen

Parameters

24

70

Gas Composition - Carbon Dioxide

Parameters

17

131

39

Day, Month, Year, Hour, Minute and Second

Parameters

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

23 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

REV

I-MA-4451.28-6250-27D-FRB-002

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:

LNG TERMINAL PROJECT

SHEET

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

MODBUS CONFIG COM2

9.1

NUMBER POINT: #1 (CONFIGURATION MODBUS RTU RS-485)


Item

Description

Value

ASCII = 0, RTU = 1

Defines type Protocol Modbus - ASCII our RTU

Byte Order 1 = MSB 1 First

Byte Order Modbus

Host Enabled = 1

Host Enabled

Log Data 1 = Yes

Changing Parameters Register

Init Memory = 1

Init Memory

Port Switch En = 1

Enabled / Disabled of Protocol Changing

DCD = 0, DI = 1, STP = 2

Define Type of Protocol Changing

Modbus Baud Rate

Band Rate Protocol Modbus Enron

9600

Switch Baud Rate

Band Rate Protocol ROC

9600

Input Data Start

Input Data Start

100

Output Data Start

Output Data Start

300

HI Integer Scale

HI Integer Scale

4095

Low Integer Scale

Low Integer Scale

Obs: All the fields of Float Scale must be filled with 0.

10

MODBUS FUNCT COM2 (REGISTERS MODBUS RTU)

10.1 NUMBER POINT: #6 FUNCT 4A


Start Reg End Reg Pt Type

Lgl# Param Conv

Description

TYPE

30216

30217

17

128

66

Instantaneous Static Pressure

Var. Instant.

30218

30219

10

66

Instantaneous Temperature

Var. Instant.

30220

30221

17

66

Standard Volume Flowrate

Var. Instant.

30222

30223

10

66

Reserve

Reserve

30224

30231

17

128

66

Flow Totalized Today, Mounth, Energy Totalized Month and


Var. Instant.
Flow Totalized Accumulated

30232

30233

66

Relative Density

Var. Instant.

30234

30235

10

16

66

Compressibility Factor

Var. Instant.

30236

30251

128

28

66

Gas Composition

Parameters

30252

30255

128

23

66

Gas Composition

Parameters

10

30256

30257

66

Heating Value

Var. Instant.

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

24 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

10

REV

I-MA-4451.28-6250-27D-FRB-002

NUMBER

MANUAL
JOB OR PROJECT

LNG TERMINAL PROJECT

AREA/UNIT:

REV

I-MA-4451.28-6250-27D-FRB-002
SHEET

25 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

10.2 NUMBER POINT: #7 FUNCT 4B


Start Reg End Reg Pt Type

Lgl# Param Conv

Description

TYPE

30258

30260

12

128

33

Second, Minute and Hour

Parameters

30261

30263

12

128

33

Day, Month and Year

Parameters

30500

30501

17

129

66

Previous Hour Pressure Average

Var. Instant.

30502

30503

17

129

66

Previous Hour Flow Average

Var. Instant.

30504

30505

17

129

10

66

Previous Hour Accumulated Volume

Var. Instant.

30600

30603

17

129

66

Yesterday Average Temperature and Pressure

Var. Instant.

30604

30605

42

66

Yesterday Total Volume

Var. Instant.

30606

30607

42

12

66

Yesterday Total Energy

Var. Instant.

30608

30609

17

128

15

66

Yesterday Density Relative Average

Var. Instant.

10

30800

30803

17

128

11

66

Previous Month Corrected Total Volume and Energy

Var. Instant.

10.3 NUMBER POINT: #8 FUNCT 4C


Start Reg End Reg Pt Type

Lgl# Param Conv

Description

TYPE

30113

30113

14

33

Alarms Volume Flowrate

30114

30114

130

16

33

Alarms Instataneous Static Pressure

Alarms

30115

30115

128

16

33

Alarms Instantaneous Temperature

Alarms

30116

30116

132

16

33

Alarms Power Supply Voltage

Alarms

30117

30117

135

16

33

Alarms Temperature Flow Computer Board

Alarms

10

Alarms

10.4 NUMBER POINT: #12 FUNCT 16A


Start Reg End Reg Pt Type

Lgl# Param Conv

Description

TYPE

30301

30326

128

23

66

Gas Composition Chromatograph

Parameters

30327

30332

12

128

34

Second, minute, hour, day, month and year

Parameters

10

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

NUMBER

MANUAL
JOB OR PROJECT

LNG TERMINAL PROJECT

AREA/UNIT:

SHEET

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

MODBUS HOST COM2


All points of Modbus Host COM2 must be filled with 0.

12

LCD USER LIST (DISPLAY FLOBOSS)

12.1 USER LIST: #1


Text

Device Parameter

Text

Device Parameter

FI-413

FLW 1, CURFLO

FQI-413-LM

ERN 1, FLOPRV

TI-413

FLW 1, CURTMP

10

PI-413

FLW 1, CURFP

11

FIn-413

FLW 1, CURDP

12

-5

FQI-413

ERN 1, FLOACC

13

FQI-413-TD

ERN 1, FLOTDY

14

FQI-413-LD

ERN 1, FLOYDY

15

FQI-413-M

ERN 1, FLOMTH

16

13

CONFIGURATION GENERAL - INFORMATION

13.1 GENERAL
Item

Description

Value

Station Name

Floboss Identification

FQY-413

Address

Floboss Address

Group

Floboss Group

Contract Hour

Contract Hour

00:00

14

SOFT POINT
NUMBER

TAG

#1

CONV

#2

MDIAS

Hour and Day Average

#3

ACCUM

Accumulated Average

#4

DATA/HORA

#5

ALARMES

26 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

11

REV

I-MA-4451.28-6250-27D-FRB-002

DESCRIPTION
Units Conversion

Move Date and Hour


Alarms of Temperature, Pressure and Flow

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

NUMBER

MANUAL
JOB OR PROJECT

SHEET

LNG TERMINAL PROJECT

AREA/UNIT:

REV

I-MA-4451.28-6250-27D-FRB-002

27 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

14.1 SOFT POINT #1 CONV


COD. FLOBOSS

DESCRIPTION

COD. FLOBOSS

DESCRIPTION

Inst. Pressure (kgf/cm2)

11

Previous Month Total Energy (kwh)

Inst. Flow (m/dia)

12

Today Total Volume (m)

13

Month Total Volume (m)

14

Month Total Energy (kwh)

15

Total Accumulated Volume (m)

16

Heating Value (kJ/m)

17

Yesterday Total Volume (m)

18

2
3

Yesterday Total Energy (kwh)

19

10

Previous Month Total Volume (m)

20

Energy Accumulated

14.2 SOFT POINT #2 MEDIAS


COD. FLOBOSS

DESCRIPTION

Hour Inst. Pressure

Hour Temperature

12

Hour Inst.Flow

13

Hour Relative Density

14

Day Inst. Pressure

15

Day Temperature

16

Day Inst.Flow

17

Day Relative Density

18

COD. FLOBOSS
11

Previous Hour Total Volume (m)

19

10

Previous Hour Total Volume (km)

20

DESCRIPTION
-

14.3 SOFT POINT #3 ACCUM


COD. FLOBOSS
1

DESCRIPTION

COD. FLOBOSS

DESCRIPTION

Count Pressure

11

Accumulated Pressure

12

Count Temperature

13

Accumulated Temperature

14

Count Flow

15

Accumulated Flow

16

Count Relative Density

17

Accumulated Relative Density

18

19

10

20

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

NUMBER

MANUAL
JOB OR PROJECT

SHEET

LNG TERMINAL PROJECT

AREA/UNIT:

REV

I-MA-4451.28-6250-27D-FRB-002

28 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

14.4 SOFT POINT #4 DATA/HORA


COD. FLOBOSS
1

DESCRIPTION

COD. FLOBOSS

DESCRIPTION

Current Day

11

Current Month

12

Current Year

13

Current Hour

14

Current Minute

15

Current Second

16

17

18

19

10

20

14.5 SOFT POINT #5 ALARMES


COD. FLOBOSS
1

DESCRIPTION

COD. FLOBOSS

DESCRIPTION

Flow Alarms

11

Temperature Alarms

12

Pressure Alarms

13

14

15

16

17

18

19

10

20

15

FST'S

15.1 FST 1
Units Conversion
Label

CMD
WT
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV

Argument 1

Argument 2

Comment

1
FLW 1, CURFP

Pressure Base Conversion (kgf/cm for kPa)

0.010197
SFP 1, DATA1
FLW 1, CURFLO

Inst. Flow Conversion (km/dia to m/dia)

1000
SFP 1, DATA2
FLW 1, TDYFLO

Today Flow (km to m)

1000
SFP 1, DATA3

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV

END

ERN 1, FLOMTH

NUMBER

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

SHEET

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL
Moth Flow (km to m)

1000
SFP 1, DATA4
ERN 1, ENGMTH

Month Energy (GJ to KWh)

0.0036
SFP 1, DATA5
ERN 1, FLOACC

Accumulated Flow (km to m)

1000
SFP 1, DATA6
AGA 1, GASHV

Heating Value (MJ/m to KJ/m)

1000
SFP 1, DATA7
ERN 1, FLOYDY

Yesterday Total Flow (km to m)

1000
SFP 1, DATA8
ERN 1, ENGYDY

Today Total Energy (GJ to KWh)

0.0036
SFP 1, DATA9
ERN 1, FLOPRV

Prev. Month Flow (km to m)

1000
SFP 1, DATA10
ERN 1, ENGPRV

Prev. Month Energy (GJ to KWh)

0.0036
SFP 1, DATA11

VAL

ERN 1, ENGACC

SAV

SFP 1, DATA20

VAL

CLK 1, DAY

SAV

SFP 4, DATA1

VAL

CLK 1, MONTH

SAV

SFP 4, DATA2

VAL

CLK 1, YEAR

SAV

SFP 4, DATA3

VAL

CLK 1, HOUR

SAV

SFP 4, DATA4

VAL

CLK 1, MINUTE

SAV

SFP 4, DATA5

VAL

CLK 1, SECOND

SAV

SFP 4, DATA6

VAL

AGA 1, ALARM

SAV

SFP 5, DATA1

VAL

AIN A1, ALARM

SAV

SFP 5, DATA2

VAL

AIN A3, ALARM

SAV

SFP 5, DATA3

Energy Accumulated

Move Day to Soft Point


Move Month to Soft Point
Move Year to Soft Point
Move Hour to Soft Point
Move Minute to Soft Point
Move Second to Soft Point
Move Flow Alarms to Soft Point
Move Temperature Alarms to Soft Point
Move Pressure Alarms to Soft Point

END

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

29 OF 73

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

REV

I-MA-4451.28-6250-27D-FRB-002
SHEET

LNG TERMINAL PROJECT

30 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

15.2 FST 2
Load Alarms Table and Save Flash Memory Once a Day
Label

CMD
10

VAL

AIN A3, ALARM

>=
VAL
+

P1

64

Argument 2

Comment
10 Seconds Temporization

P1

Fault Pressure

SFP 3, DATA1
1

SAV

SFP 3, DATA1

VAL

SFP 3, DATA2

Count. Pressure Average

SFP 1, DATA1

Inst. Pressure (kgf/cm)

SAV

SFP 3, DATA2

Accumulated Pressure Average

VAL

AIN A1, ALARM

>=

64

VAL

SFP 3, DATA3

P2

Fault Temperature

SAV

SFP 3, DATA3

VAL

SFP 3, DATA4

+
P2

Argument 1

WT

Count. Temperature Average

FLW 1, CURTMP

Temperature oC

SAV

SFP 3, DATA4

Accumulated Temperature Average

VAL

SFP 3, DATA5

SAV

SFP 3, DATA5

VAL

SFP 3, DATA6

Count. Flow Average

SFP 1, DATA2

Flow (m/dia)

SAV

SFP 3, DATA6

Accumulated Flow Average

VAL

SFP 3, DATA7

SAV

SFP 3, DATA7

VAL

SFP 3, DATA8

Count. Relative Density

AGA 1, SPGR

Relative Density

SAV

SFP 3, DATA8

Accumulated Relative Density Average

VAL

CLK 1, MINUTE

!=
VAL

==

VAL

SAV

FST 2, R1

VAL

SFP 3, DATA1

==

VAL

SFP 3, DATA2

SFP 3, DATA1

SAV

SFP 2, DATA1

VAL

SFP 3, DATA9

P41

FST 2, R1

Verify Minutes = 0
Verify Condition Control Flag

P42

P8
Hour Pressure Average
Count. Today Pressurte Average

SAV

SFP 3, DATA9

VAL

SFP 3, DATA10

SFP 2, DATA1

SAV

SFP 3, DATA10

Accumulated Today Pressure

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

GO

P9

P8

VAL

-1

SAV

SFP 2, DATA1

P9

VAL

SFP 3, DATA3

==

SFP 3, DATA4

SFP 3, DATA3

SAV

SFP 2, DATA2

VAL

SFP 3, DATA11

P10
P11

SFP 3, DATA11

VAL

SFP 3, DATA12

SFP 2, DATA2

SAV

SFP 3, DATA12

GO

P11

VAL

-1

SAV

SFP 2, DATA2

VAL

SFP 3, DATA5

P13

SFP 3, DATA6

SFP 3, DATA5

SAV

SFP 2, DATA3

VAL

SFP 3, DATA13
SFP 3, DATA13

VAL

SFP 3, DATA14

SFP 2, DATA3

SAV

SFP 3, DATA14

GO

P13

VAL

-1

SAV

SFP 2, DATA3

VAL

SFP 3, DATA7

P15

SFP 3, DATA8

SFP 3, DATA7

SAV

SFP 2, DATA4

VAL

SFP 3, DATA15
SFP 3, DATA15

VAL

SFP 3, DATA16

SFP 2, DATA4

SAV

SFP 3, DATA16

GO

P15

VAL

-1

SAV

SFP 2, DATA4

VAL

SFP 1, DATA6

P10
Hour Today Temperature
Count. Today Temperature Average

Accumulated Today Temperature

P12
Hour Flow Average
Count. Today Flow Average

Accumulated Today Flow

P14

Hour Density Average


Count. Today Densuty Average

SAV

SAV

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

VAL

LNG FLEXIBLE TERMINAL PECM PORT

SAV

==

P14

VAL

LNG TERMINAL PROJECT

SHEET

SAV

==

P12

VAL

I-MA-4451.28-6250-27D-FRB-002

Accumulated Today Density

FST 2, R2
SFP 2, DATA9

Previous Hour Accumulated Volume

1000

SAV

SFP 2, DATA10

VAL

SFP 1, DATA6

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

31 OF 73

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

SAV

FST 2, R2

VAL

SFP 1, DATA20

SFP 2, DATA11

VAL

SFP 1, DATA20

SAV

FST 2, R3

VAL

CLK 1, HOUR

!=
==

0
0
SFP 3, DATA10

SFP 3, DATA9

SAV

SFP 2, DATA5

GO

P25

P24

VAL

-1

SAV

SFP 2, DATA5

P25

VAL

SFP 3, DATA11
0

VAL

SFP 3, DATA12

SFP 3, DATA11

SAV

SFP 2, DATA6

GO

P27

P26

VAL

-1

SAV

SFP 2, DATA6

P27

VAL

SFP 3, DATA13

==

VAL

SFP 3, DATA14

SFP 3, DATA13

SAV

SFP 2, DATA7

GO

P29

P28

VAL

-1

SAV

SFP 2, DATA7

P29

VAL

SFP 3, DATA15

==

VAL

SFP 3, DATA16

SFP 3, DATA15

SAV

SFP 2, DATA8

GO

P31

P30

VAL

-1

SAV

SFP 2, DATA8

P31

VAL

SAV

SFP 3, DATA9

SAV

SFP 3, DATA10

SAV

SFP 3, DATA11

SAV

SFP 3, DATA12

SAV

SFP 3, DATA13

SAV

SFP 3, DATA14

SAV

SFP 3, DATA15

P40

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

P40

SAV

SFP 3, DATA16

VAL

SAV

SFP 3, DATA1

Verify Hour = 0

P24
Today Pressure Average

P26
Today Temperature Average

P28
Today Flow Average

P30
Today Density Average

Zera Today Accumulator and Accountant

Zera Hour Accumulator and Accountant

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

32 OF 73

SFP 3, DATA9

VAL

==

LNG TERMINAL PROJECT

SHEET

FST 2, R3

SAV

VAL

REV

I-MA-4451.28-6250-27D-FRB-002

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

P41
P42

SAV

SFP 3, DATA2

SAV

SFP 3, DATA3

SAV

SFP 3, DATA4

SAV

SFP 3, DATA5

SAV

SFP 3, DATA6

SAV

SFP 3, DATA7

SAV

SFP 3, DATA8

GO

P42

VAL

SAV

FST 2, R1

I-MA-4451.28-6250-27D-FRB-002
SHEET

LNG TERMINAL PROJECT

REV

33 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

END

15.3 FST 3
It updates the gas composition values for the Z calculation
Label
CMD
Argument 1
Argument 2

END

WT

300

VAL

SAV

FLW 1, RECALCZS

Comment
300 Seconds Temporization
Update Z Calculation for Gas Composition

END

15.4 FST 4
It updates the gas composition values for the Z calculation
Label
CMD
Argument 1
Argument 2

CKMIN

WT

VAL

CLK 1, HOUR

==

VAL

SAV

FST 4, R1

GO

END

VAL

CLK 1, MINUTE

==

GO

END

WRTFLS VAL

END

Comment
5 Seconds Temporization

CKMIN

Verify Hour = 0
Control Flag = 0

WRTFLS

Verify Minute = 5

FST 4, R1

==

VAL

SAV

FLG 1, WRITE

VAL

SAV

FST 4, R1

EVT

WRT MENORY

END
Writing Flash Memory Configuration
Control Flag
FLG 1, WRITE

END

Obs: These FSTs Must Be Activated on FST Registers Options.

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

16

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

SHEET

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

HISTORY

16.1 STREAM 01
Point

Archive Type

Archive Point

Description

Totalize

ERN 1, MINTDY

Minutes with Flow

Average

FLW 1, CURDP

Instantaneous Flow Uncorrected

Average

FLW 1, CURFP

Average

FLW 1, CURTMP

Average

FLW 1, IMV/BMV

Average

FLW 1, HWPF

Accumulated

FLW 1, CURFLO

Accumulated

FLW 1, ENERGY

Accumulated energy

Average

FLW 1, CURFLO

Instantaneous Flow Corrected

Static Pressure
Temperature
Constant of correction of the calculation AGA
Extension HWPF of the AGA3 1992
Flow accumulated corrected

10

Average

AGA 1, SPGR

12

Current Value

ERN1, FLOTDY

Flow Today Accumulated

Specific Gravity

13

Current Value

ERN1, FLOMTH

Flow Month Accumulated

16.2 STREAM 02
Point

Archive Type

Archive Point

Description

14

UNDEFINED

UNDEFINED

Reserve

15

UNDEFINED

UNDEFINED

Reserve

UNDEFINED

UNDEFINED

Reserve

17

UNDEFINED

UNDEFINED

Reserve

18

UNDEFINED

UNDEFINED

Reserve

19

UNDEFINED

UNDEFINED

Reserve

20

UNDEFINED

UNDEFINED

Reserve

21

UNDEFINED

UNDEFINED

Reserve

22

UNDEFINED

UNDEFINED

Reserve

23

UNDEFINED

UNDEFINED

Reserve

24

UNDEFINED

UNDEFINED

Reserve

25

UNDEFINED

UNDEFINED

Reserve

16.3 STREAM 03
Point

Archive Type

Archive Point

Description

26

UNDEFINED

UNDEFINED

Reserve

27

UNDEFINED

UNDEFINED

Reserve

28

UNDEFINED

UNDEFINED

Reserve

29

UNDEFINED

UNDEFINED

Reserve

30

UNDEFINED

UNDEFINED

Reserve

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

34 OF 73

NUMBER

MANUAL
JOB OR PROJECT

I-MA-4451.28-6250-27D-FRB-002
SHEET

LNG TERMINAL PROJECT

AREA/UNIT:

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

31

UNDEFINED

UNDEFINED

Reserve

32

UNDEFINED

UNDEFINED

Reserve

33

UNDEFINED

UNDEFINED

Reserve

34

UNDEFINED

UNDEFINED

Reserve

35

UNDEFINED

UNDEFINED

Reserve

36

UNDEFINED

UNDEFINED

Reserve

37

UNDEFINED

UNDEFINED

Reserve

16.4 STREAM 04
Point

Archive Type

Archive Point

38

UNDEFINED

UNDEFINED

Reserve

39

UNDEFINED

UNDEFINED

Reserve

40

UNDEFINED

UNDEFINED

Reserve

41

UNDEFINED

UNDEFINED

Reserve

42

UNDEFINED

UNDEFINED

Reserve

43

UNDEFINED

UNDEFINED

Reserve

44

UNDEFINED

UNDEFINED

Reserve

45

UNDEFINED

UNDEFINED

Reserve

46

UNDEFINED

UNDEFINED

Reserve

47

UNDEFINED

UNDEFINED

Reserve

48

UNDEFINED

UNDEFINED

Reserve

49

UNDEFINED

UNDEFINED

Reserve

17

Description

COMM PORTS

17.1 COMM PORT: #1 LOCAL PORT


17.1.1 GENERAL
Item

Description

Value

Baud Rate

Rate of Transmission

9600

Parity

Parity

None

Data Bits

Number of Data Bits

Stop Bits

Number of Stop Bits

Key On Delay

Delay Time to Activate RTS

Key Off Delay

Delay Time to Deactivate RTS.

17.1.2 MODBUS HOST PARAMETERS


Item

Description

Value

Start Transmission

Inactive

Continuous Polling

Disabled

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

35 OF 73

NUMBER

MANUAL
JOB OR PROJECT

I-MA-4451.28-6250-27D-FRB-002
SHEET

LNG TERMINAL PROJECT

AREA/UNIT:

REV

36 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

17.2 COMM PORT: #2 COMM 1


17.2.1 GENERAL
Item

Description

Value

Baud Rate

Rate of Transmission

9600

Parity

Parity

None

Data Bits

Number of Data Bits

Stop Bits

Number of Stop Bits

RTS/CTS Handshaking

RTS/CTS Enabled or Disabled

Disabled

Key On Delay

Delay Time to Activate RTS

0.02

Key Off Delay

Delay Time to Deactivate RTS.

0.01

17.2.2 MODBUS HOST PARAMETERS


Item

Description

Value

Start Transmission

Inactive

Continuous Polling

Disabled

17.3 COMM PORT: #3 COMM 2


17.3.1 GENERAL
Item

Description

Value

Baud Rate

Tax of Transmission

9600

Parity

Parity

None

Data Bits

Amount of bits of Data

Stop Bits

Amount of bits of stopped

RTS/CTS Handshaking

RTS/CTS Enabled or Disabled

Disabled

Key On Delay

Delay Time to Activate RTS

0.02

Key Off Delay

Delay Time to Deactivate RTS.

0.01

17.3.2 MODBUS HOST PARAMETERS


Item

Description

Value

Start Transmission

Inactive

Continuous Polling

Disabled

Obs: The Modem / RBX and Store & Forward Must be Configured on COM1 and COM2 as None / Disable and Same Port,
Respectively.

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

18

NUMBER

I-MA-4451.28-6250-27D-FRB-002
SHEET

LNG TERMINAL PROJECT

REV

37 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

FLAGS

18.1 FLAGS
18.1.1 ADVANCED
Item

Description

Transmitter Power +T

19

Inform Value of the Power Supply

Value
on

CALCULATIONS OF FLOW

19.1 ROC / INFORMATION


19.1.1 POINTS
At AGAS Active Options, Choose 4, Make Possible That Floboss 407 Perform 4 Flow Calculations.
20

USER PROGRAMS
These User Programs should be downloaded to the Floboss:

FB_HVCAL.H00 User Program for calculation of energy 20oC Version 2.00;

FBMB1_60.H00 User Program protocol Modbus RTU port Comm 1 Version 2.01;

FBMB2_05.H00 User Program protocol Modbus RTU port Comm 2 Version 2.01.

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

NUMBER

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

SHEET

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

FQY - 513

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

38 OF 73

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

NUMBER

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

SHEET

REV

39 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL
NDICE

INTRODUCTION .................................................................................................................................................................... 43

REFERENCES ....................................................................................................................................................................... 43

CALCULATION AGA7 1996 ................................................................................................................................................... 43


3.1

3.2

3.3

3.4

STREAM: #1........................................................................................................................................................................ 43
3.1.1

GENERAL............................................................................................................................................................... 43

3.1.2

INPUTS................................................................................................................................................................... 43

3.1.3

GAS QUALITY ........................................................................................................................................................ 43

3.1.4

ADVANCED FEATURES ........................................................................................................................................ 43

3.1.5

ALARMS ................................................................................................................................................................. 43

STREAM: #2........................................................................................................................................................................ 43
3.2.1

GENERAL............................................................................................................................................................... 43

3.2.2

INPUTS................................................................................................................................................................... 43

3.2.3

GAS QUALITY ........................................................................................................................................................ 43

3.2.4

ADVANCED FEATURES ........................................................................................................................................ 43

3.2.5

ALARMS ................................................................................................................................................................. 43

STREAM: #3........................................................................................................................................................................ 43
3.3.1

GENERAL............................................................................................................................................................... 43

3.3.2

INPUTS................................................................................................................................................................... 43

3.3.3

GAS QUALITY ........................................................................................................................................................ 43

3.3.4

ADVANCED FEATURES ........................................................................................................................................ 43

3.3.5

ALARMS ................................................................................................................................................................. 43

STREAM: #4........................................................................................................................................................................ 43
3.4.1

GENERAL............................................................................................................................................................... 43

3.4.2

INPUTS................................................................................................................................................................... 43

3.4.3

GAS QUALITY ........................................................................................................................................................ 43

3.4.4

ADVANCED FEATURES ........................................................................................................................................ 43

3.4.5

ALARMS ................................................................................................................................................................. 43

MULTIVARIABLE SENSOR (MVS)......................................................................................................................................... 43


4.1

NUMBER POINT: MVS POINT #1....................................................................................................................................... 43

4.2

NUMBER POINT: MVS POINT #2....................................................................................................................................... 43

4.3

NUMBER POINT: MVS POINT #3....................................................................................................................................... 43

4.4

NUMBER POINT: MVS POINT #4....................................................................................................................................... 43


ANALOG INPUTS (AI) ............................................................................................................................................................ 43

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

5.1

5.2

5.3

5.4

5.5

5.6

NUMBER

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

SHEET

REV

40 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

NUMBER POINT: AI #1 (A1) TIT-513 .................................................................................................................................. 43


5.1.1

GENERAL............................................................................................................................................................... 43

5.1.2

ADVANCED ............................................................................................................................................................ 43

5.1.3

ALARMS ................................................................................................................................................................. 43

NUMBER POINT: AI #2 (A2) NOT APPLICABLE ................................................................................................................ 43


5.2.1

GENERAL............................................................................................................................................................... 43

5.2.2

ADVANCED ............................................................................................................................................................ 43

5.2.3

ALARMS ................................................................................................................................................................. 43

NUMBER POINT: AI #3 (A3) PIT-513.................................................................................................................................. 43


5.3.1

GENERAL............................................................................................................................................................... 43

5.3.2

ADVANCED ............................................................................................................................................................ 43

5.3.3

ALARMS ................................................................................................................................................................. 43

NUMBER POINT: AI #4 (E1) TAG: + T (POWER OUT)....................................................................................................... 43


5.4.1

GENERAL............................................................................................................................................................... 43

5.4.2

ADVANCED ............................................................................................................................................................ 43

5.4.3

ALARMS ................................................................................................................................................................. 43

NUMBER POINT: AI #5 (E2) TAG: POWER IN ................................................................................................................... 43


5.5.1

GENERAL............................................................................................................................................................... 43

5.5.2

ADVANCED ............................................................................................................................................................ 43

5.5.3

ALARMS ................................................................................................................................................................. 43

NUMBER POINT: AI #8 (E5) TAG: BRD TEMP................................................................................................................... 43


5.6.1

GENERAL............................................................................................................................................................... 43

5.6.2

ADVANCED ............................................................................................................................................................ 43

5.6.3

ALARMS ................................................................................................................................................................. 43

PULSE INPUTS (PI) ............................................................................................................................................................... 43


6.1

NUMBER POINT: PI #1 (A7) TAG: FIT-513......................................................................................................................... 43


6.1.1

GENERAL............................................................................................................................................................... 43

6.1.2

ADVANCED ............................................................................................................................................................ 43

6.1.3

ALARMS ................................................................................................................................................................. 43

MODBUS CONFIG COM1 ...................................................................................................................................................... 43


7.1

NUMBER POINT: #1 (CONFIGURATION MODBUS RTU RS-485)..................................................................................... 43


MODBUS FUNCT COM1 (REGISTERS MODBUS RTU) ....................................................................................................... 43

8.1

NUMBER POINT: #3 FUNCT 3A ......................................................................................................................................... 43

8.2

NUMBER POINT: #4 FUNCT 3B ......................................................................................................................................... 43

8.3

NUMBER POINT: #5 FUNCT 3C ......................................................................................................................................... 43

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

SHEET

REV

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

NUMBER POINT: #1 (CONFIGURATION MODBUS RTU RS-485)..................................................................................... 43


MODBUS FUNCT COM2 (REGISTERS MODBUS RTU) ....................................................................................................... 43

10.1 NUMBER POINT: #6 FUNCT 4A ......................................................................................................................................... 43


10.2 NUMBER POINT: #7 FUNCT 4B ......................................................................................................................................... 43
10.3 NUMBER POINT: #8 FUNCT 4C ......................................................................................................................................... 43
10.4 NUMBER POINT: #12 FUNCT 16A ..................................................................................................................................... 43
11

MODBUS HOST COM2 .......................................................................................................................................................... 43

12

LCD USER LIST (DISPLAY FLOBOSS) ................................................................................................................................. 43


12.1 USER LIST: #1 .................................................................................................................................................................... 43

13

CONFIGURATION GENERAL - INFORMATION .................................................................................................................... 43


13.1 GENERAL ........................................................................................................................................................................... 43

14

SOFT POINT .......................................................................................................................................................................... 43


14.1 SOFT POINT #1 CONV .................................................................................................................................................... 43
14.2 SOFT POINT #2 MEDIAS................................................................................................................................................. 43
14.3 SOFT POINT #3 ACCUM ................................................................................................................................................. 43
14.4 SOFT POINT #4 DATA/HORA........................................................................................................................................... 43
14.5 SOFT POINT #5 ALARMES .............................................................................................................................................. 43

15

FST'S...................................................................................................................................................................................... 43
15.1 FST 1................................................................................................................................................................................... 43
15.2 FST 2................................................................................................................................................................................... 43
15.3 FST 3................................................................................................................................................................................... 43
15.4 FST 4................................................................................................................................................................................... 43

16

HISTORY................................................................................................................................................................................ 43
16.1 STREAM 01......................................................................................................................................................................... 43
16.2 STREAM 02......................................................................................................................................................................... 43
16.3 STREAM 03......................................................................................................................................................................... 43
16.4 STREAM 04......................................................................................................................................................................... 43

17

COMM PORTS ....................................................................................................................................................................... 43


17.1 COMM PORT: #1 LOCAL PORT ......................................................................................................................................... 43
17.1.1 GENERAL............................................................................................................................................................... 43
17.1.2 MODBUS HOST PARAMETERS ............................................................................................................................ 43

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

41 OF 73

MODBUS CONFIG COM2 ...................................................................................................................................................... 43


9.1

10

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

NUMBER

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

SHEET

REV

42 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

17.2 COMM PORT: #2 COMM 1 ................................................................................................................................................. 43


17.2.1 GENERAL............................................................................................................................................................... 43
17.2.2 MODBUS HOST PARAMETERS ............................................................................................................................ 43
17.3 COMM PORT: #3 COMM 2 ................................................................................................................................................. 43
17.3.1 GENERAL............................................................................................................................................................... 43
17.3.2 MODBUS HOST PARAMETERS ............................................................................................................................ 43
18

FLAGS.................................................................................................................................................................................... 43
18.1 FLAGS................................................................................................................................................................................. 43
18.1.1 ADVANCED ............................................................................................................................................................ 43

19

CALCULATIONS OF FLOW ................................................................................................................................................... 43


19.1 ROC / INFORMATION......................................................................................................................................................... 43
19.1.1 POINTS................................................................................................................................................................... 43

20

USER PROGRAMS ................................................................................................................................................................ 43

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002
SHEET

LNG TERMINAL PROJECT

REV

43 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

INTRODUCTION
The purpose of this document is to detail the configuration of the Flow Computer FQY-513, of the Metering
System on LNG Flexible Terminal, at Pecm Port CE.

REFERENCES

Automation System Pecm I-DE-4451.28-6250-800-FRB-001 Rev. E;

Functional Specification I-ET-4451.28-6250-800-FRB-001 Rev. D.

CALCULATION AGA7 1996

3.1

STREAM: #1

3.1.1

GENERAL
Item

Description

Valor

Meter Tag

STREAM Identification

FIT-513

Meter Description

STREAM Description

Fiscal Metering STREAM 01

Meter Type

Meter Type

Turbine

Alarming

Alarms Enabled or Disabled

Enabled

Scan Period

Scan Period

1 Seconds

3.1.2

INPUTS
Item

Description

Value

Uncorrected Volume

Flow Uncorrected Input

PIN A7, EU

Static Pressure

Static Pressure Input

AIN A3, EU

Temperature

Temperature Input

AIN A1, EU

3.1.3

GAS QUALITY
Item

Description

Value

Nitrogen

Percent. Nitrogen gas composition

Input by Operator

CO2

Percent. Carbon Dioxide gas composition

Input by Operator

Methane

Percent. Methane gas composition

Input by Operator

Ethane

Percent. Ethane gas composition

Input by Operator

Propane

Percent. Propane gas composition

Input by Operator

n-Butane

Percent. n-Butane gas composition

Input by Operator

i-Butane

Percent. i-Butane gas composition

Input by Operator

n-Pentane

Percent. n-Pentane gas composition

Input by Operator

i-Pentane

Percent. i-Pentane gas composition

Input by Operator

Hexane

Percent. Hexane gas composition

Input by Operator

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

NUMBER

MANUAL
JOB OR PROJECT

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

Heptane

Percent. Heptane gas composition

Input by Operator

Octane

Percent. Octane gas composition

Input by Operator

Nonane

Percent. Nonane gas composition

Input by Operator

Decane

Percent. Decane gas composition

Input by Operator

H2S

Percent. Sulphydric Acid gas composition

Input by Operator

Water

Percent. Water gas composition

Input by Operator

Helium

Percent. Helium gas composition

Input by Operator

Oxygen

Percent. Oxygen gas composition

Input by Operator

CO

Percent. CO gas composition

Input by Operator

Hydrogen

Percent. Hydrogen gas composition

Input by Operator

Heating Value Basis

Heating Value Basis

Dry

Log Methane Adjust

Adjust of methane

Enabled

Heating Value

Heating Value

Calculate (MJ/M3)

Spec Gravity

Specific Gravity

Calculate

3.1.4

SHEET

LNG TERMINAL PROJECT

AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002

ADVANCED FEATURES
Item

Description

Valor

FPV Method

Type Calculation

Detailed

Units

Units

Metric KM3/GJ

Base Temperature

Base Temperature

20 Deg C

Base Pressure

Base Pressure

101.325 kPa

Atmospheric Pressure

Atmospheric Pressure

Enter - 101.325 kPa

Elevation

Elevation

0.0 Meters

Latitude

Latitude

0.0 Deg

User Correction Factor

Gravity Correction

1.0

Pressure Tap

Pressure Tap

Gauge

Meter Factor

Meter Factor

1.0

3.1.5

ALARMS
Item

Description

Value

Low Alarm

Limit Alarm Low

High Alarm

Limit Alarm High

1000
7900

RBX Alarming

Alarm for exception

Disabled

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

44 OF 73

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

3.2

I-MA-4451.28-6250-27D-FRB-002
SHEET

LNG TERMINAL PROJECT


LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

STREAM: #2

3.2.1

GENERAL
Item

Description

Valor

Meter Tag

STREAM Identification

Not Applicable

Meter Description

STREAM Description

Not Applicable

Meter Type

Meter Type

Not Applicable

Alarming

Alarms Enabled or Disabled

Disabled

Scan Period

Scan Period

Not Applicable

3.2.2

INPUTS
Item

Description

Value

Uncorrected Volume

Flow Uncorrected Input

Manual

Static Pressure

Static Pressure Input

Manual

Temperature

Temperature Input

Manual

3.2.3

GAS QUALITY
Item

Description

Value

Nitrogen

Percent. Nitrogen gas composition

Not Applicable

CO2

Percent. Carbon Dioxide gas composition

Not Applicable

Methane

Percent. Methane gas composition

Not Applicable

Ethane

Percent. Ethane gas composition

Not Applicable

Propane

Percent. Propane gas composition

Not Applicable

n-Butane

Percent. n-Butane gas composition

Not Applicable

i-Butane

Percent. i-Butane gas composition

Not Applicable

n-Pentane

Percent. n-Pentane gas composition

Not Applicable

i-Pentane

Percent. i-Pentane gas composition

Not Applicable

Hexane

Percent. Hexane gas composition

Not Applicable

Heptane

Percent. Heptane gas composition

Not Applicable

Octane

Percent. Octane gas composition

Not Applicable

Nonane

Percent. Nonane gas composition

Not Applicable

Decane

Percent. Decane gas composition

Not Applicable

H2S

Percent. Sulphydric Acid gas composition

Not Applicable

Water

Percent. Water gas composition

Not Applicable

Helium

Percent. Helium gas composition

Not Applicable

Oxygen

Percent. Oxygen gas composition

Not Applicable

CO

Percent. CO gas composition

Not Applicable

Hydrogen

Percent. Hydrogen gas composition

Not Applicable

Heating Value Basis

Heating Value Basis

Not Applicable

Log Methane Adjust

Adjust of methane

Disabled

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

45 OF 73

NUMBER

MANUAL
JOB OR PROJECT

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

Heating Value

Heating Value

Not Applicable

Spec Gravity

Specific Gravity

Not Applicable

3.2.4

ADVANCED FEATURES
Item

Description

Valor

FPV Method

Type Calculation

Not Applicable

Units

Units

Not Applicable

Base Temperature

Base Temperature

Not Applicable

Base Pressure

Base Pressure

Not Applicable

Atmospheric Pressure

Atmospheric Pressure

Not Applicable

Elevation

Elevation

Not Applicable

Latitude

Latitude

Not Applicable

User Correction Factor

Gravity Correction

Not Applicable

Pressure Tap

Pressure Tap

Not Applicable

Meter Factor

Meter Factor

Not Applicable

3.2.5

ALARMS
Item

Description

Value

Low Alarm

Limit Alarm Low

Not Applicable

High Alarm

Limit Alarm High

Not Applicable

RBX Alarming

Alarm for exception

Disabled

3.3
3.3.1

STREAM: #3
GENERAL
Item

Description

Valor

Meter Tag

STREAM Identification

Not Applicable

Meter Description

STREAM Description

Not Applicable

Meter Type

Meter Type

Not Applicable

Alarming

Alarms Enabled or Disabled

Disabled

Scan Period

Scan Period

Not Applicable

3.3.2

SHEET

LNG TERMINAL PROJECT

AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002

INPUTS
Item

Description

Value

Uncorrected Volume

Flow Uncorrected Input

Manual

Static Pressure

Static Pressure Input

Manual

Temperature

Temperature Input

Manual

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

46 OF 73

NUMBER

MANUAL
JOB OR PROJECT

3.3.3

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

GAS QUALITY
Item

Nitrogen

Description

Value

Percent. Nitrogen gas composition

Not Applicable

CO2

Percent. Carbon Dioxide gas composition

Not Applicable

Methane

Percent. Methane gas composition

Not Applicable

Ethane

Percent. Ethane gas composition

Not Applicable

Propane

Percent. Propane gas composition

Not Applicable

n-Butane

Percent. n-Butane gas composition

Not Applicable

i-Butane

Percent. i-Butane gas composition

Not Applicable

n-Pentane

Percent. n-Pentane gas composition

Not Applicable

i-Pentane

Percent. i-Pentane gas composition

Not Applicable

Hexane

Percent. Hexane gas composition

Not Applicable

Heptane

Percent. Heptane gas composition

Not Applicable

Octane

Percent. Octane gas composition

Not Applicable

Nonane

Percent. Nonane gas composition

Not Applicable

Decane

Percent. Decane gas composition

Not Applicable

H2S

Percent. Sulphydric Acid gas composition

Not Applicable

Water

Percent. Water gas composition

Not Applicable

Helium

Percent. Helium gas composition

Not Applicable

Oxygen

Percent. Oxygen gas composition

Not Applicable

CO

Percent. CO gas composition

Not Applicable

Hydrogen

Percent. Hydrogen gas composition

Not Applicable

Heating Value Basis

Heating Value Basis

Not Applicable

Log Methane Adjust

Adjust of methane

Disabled

Heating Value

Heating Value

Not Applicable

Spec Gravity

Specific Gravity

Not Applicable

3.3.4

SHEET

LNG TERMINAL PROJECT

AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002

ADVANCED FEATURES
Item

Description

Valor

FPV Method

Type Calculation

Not Applicable

Units

Units

Not Applicable

Base Temperature

Base Temperature

Not Applicable

Base Pressure

Base Pressure

Not Applicable

Atmospheric Pressure

Atmospheric Pressure

Not Applicable

Elevation

Elevation

Not Applicable

Latitude

Latitude

Not Applicable

User Correction Factor

Gravity Correction

Not Applicable

Pressure Tap

Pressure Tap

Not Applicable

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

47 OF 73

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

3.3.5

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT


LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

ALARMS
Item

Description

Value

Low Alarm

Limit Alarm Low

Not Applicable

High Alarm

Limit Alarm High

Not Applicable

RBX Alarming

Alarm for exception

Disabled

3.4

SHEET

STREAM: #4

3.4.1

GENERAL
Item

Description

Valor

Meter Tag

STREAM Identification

Not Applicable

Meter Description

STREAM Description

Not Applicable

Meter Type

Meter Type

Not Applicable

Alarming

Alarms Enabled or Disabled

Disabled

Scan Period

Scan Period

Not Applicable

3.4.2

INPUTS
Item

Description

Value

Uncorrected Volume

Flow Uncorrected Input

Manual

Static Pressure

Static Pressure Input

Manual

Temperature

Temperature Input

Manual

3.4.3

GAS QUALITY
Item

Description

Value

Nitrogen

Percent. Nitrogen gas composition

Not Applicable

CO2

Percent. Carbon Dioxide gas composition

Not Applicable

Methane

Percent. Methane gas composition

Not Applicable

Ethane

Percent. Ethane gas composition

Not Applicable

Propane

Percent. Propane gas composition

Not Applicable

n-Butane

Percent. n-Butane gas composition

Not Applicable

i-Butane

Percent. i-Butane gas composition

Not Applicable

n-Pentane

Percent. n-Pentane gas composition

Not Applicable

i-Pentane

Percent. i-Pentane gas composition

Not Applicable

Hexane

Percent. Hexane gas composition

Not Applicable

Heptane

Percent. Heptane gas composition

Not Applicable

Octane

Percent. Octane gas composition

Not Applicable

Nonane

Percent. Nonane gas composition

Not Applicable

Decane

Percent. Decane gas composition

Not Applicable

H2S

Percent. Sulphydric Acid gas composition

Not Applicable

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

48 OF 73

NUMBER

MANUAL
JOB OR PROJECT

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

AREA/UNIT:

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

Water

Percent. Water gas composition

Not Applicable

Helium

Percent. Helium gas composition

Not Applicable

Oxygen

Percent. Oxygen gas composition

Not Applicable

CO

Percent. CO gas composition

Not Applicable

Hydrogen

Percent. Hydrogen gas composition

Not Applicable

Heating Value Basis

Heating Value Basis

Not Applicable

Log Methane Adjust

Adjust of methane

Disabled

Heating Value

Heating Value

Not Applicable

Spec Gravity

Specific Gravity

Not Applicable

3.4.4

ADVANCED FEATURES
Item

Description

Valor

FPV Method

Type Calculation

Not Applicable

Units

Units

Not Applicable

Base Temperature

Base Temperature

Not Applicable

Base Pressure

Base Pressure

Not Applicable

Atmospheric Pressure

Atmospheric Pressure

Not Applicable

Elevation

Elevation

Not Applicable

Latitude

Latitude

Not Applicable

User Correction Factor

Gravity Correction

Not Applicable

Pressure Tap

Pressure Tap

Not Applicable

3.4.5

ALARMS
Item

Description

Value

Low Alarm

Limit Alarm Low

Not Applicable

High Alarm

Limit Alarm High

Not Applicable

RBX Alarming

Alarm for exception

Disabled

SHEET

MULTIVARIABLE SENSOR (MVS)

4.1

NUMBER POINT: MVS POINT #1


Item

Description

Value

Tag

MVS Identification

Address

Address RS-485

Not Applicable
Not Applicable

Scanning

Scan Enabled or Disabled

Disabled

Units

Unit System

Not Applicable

Sensor Alarms

Sensor Alarm Enabled or Disabled

Disabled

Diff. Pressure Alarm

Diff. Pressure Alarm Enabled or Disabled

Disabled

Low Alarm Diff. Pressure

Not Applicable

Low Alarm

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

49 OF 73

NUMBER

MANUAL
JOB OR PROJECT

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

AREA/UNIT:

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

High Alarm

High Alarm Diff. Pressure

Not Applicable

Alarm Deadband

Alarm Deadband Diff. Pressure

Not Applicable

Fault Value

Fault Value Diff. Pressure

Not Applicable

Pressure Alarm Enabled or Disabled

Disabled

Pressure Alarm
Low Alarm

Low Alarm - Pressure

Not Applicable

High Alarm

High Alarm - Pressure

Not Applicable

Alarm Deadband

Alarm Deadband - Pressure

Not Applicable

Fault Value

Fault Value - Pressure

Not Applicable

Temperature Alarm Enabled or Disabled

Disabled

Temperature Alarm
Low Alarm

Low Alarm - Temperature

Not Applicable

High Alarm

High Alarm - Temperature

Not Applicable

Alarm Deadband

Alarm Deadband - Temperature

Not Applicable

Fault Value

Fault Value - Temperature

Not Applicable

Report Pressure As

Upstream or Downstream

Not Applicable

Action on Failure

Action on Failure

Not Applicable

RBX Alarming

Exception Alarm

Disabled

Reference Temperature

Reference Temperature

Not Applicable

4.2

SHEET

NUMBER POINT: MVS POINT #2


Item

Description

Value

Tag

MVS Identification

Not Applicable

Address

Address RS-485

Not Applicable

Scanning

Scan Enabled or Disabled

Disabled

Units

Unit System

Not Applicable

Sensor Alarms

Sensor Alarm Enabled or Disabled

Disabled

Diff. Pressure Alarm

Diff. Pressure Alarm Enabled or Disabled

Disabled

Low Alarm

Low Alarm Diff. Pressure

Not Applicable

High Alarm

High Alarm Diff. Pressure

Not Applicable

Alarm Deadband

Alarm Deadband - Diff Pressure

Not Applicable

Fault Value

Fault Value Diff. Pressure

Not Applicable

Pressure Alarm Enabled or Disabled

Disabled

Pressure Alarm
Low Alarm

Low Alarm - Pressure

Not Applicable

High Alarm

High Alarm - Pressure

Not Applicable

Alarm Deadband

Alarm Deadband - Pressure

Not Applicable

Fault Value

Fault Value - Pressure

Not Applicable

Temperature Alarm

Temperature Alarm Enabled or Disabled

Disabled

Low Alarm

Low Alarm - Temperature

Not Applicable

High Alarm

High Alarm - Temperature

Not Applicable

Alarm Deadband

Alarm Deadband - Temperature

Not Applicable

Fault Value
Report Pressure As

Fault Value - Temperature

Not Applicable

Upstream or Downstream

Not Applicable

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

50 OF 73

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT


LNG FLEXIBLE TERMINAL PECM PORT

TITLE

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

Action on Failure

Action on Failure

Not Applicable

RBX Alarming

Exception Alarm

Disabled

Reference Temperature

Reference Temperature

Not Applicable

4.3

NUMBER POINT: MVS POINT #3


Item

Description

Value

Tag

MVS Identification

Not Applicable

Address

Address RS-485

Not Applicable

Scanning

Scan Enabled or Disabled

Disabled

Units

Unit System

Not Applicable

Sensor Alarms

Sensor Alarm Enabled or Disabled

Disabled

Diff. Pressure Alarm

Diff. Pressure Alarm Enabled or Disabled

Disabled

Low Alarm

Low Alarm Diff. Pressure

Not Applicable

High Alarm

High Alarm Diff. Pressure

Not Applicable

Alarm Deadband

Alarm Deadband - Diff Pressure

Not Applicable

Fault Value
Pressure Alarm

Fault Value Diff. Pressure

Not Applicable

Pressure Alarm Enabled or Disabled

Disabled

Low Alarm

Low Alarm - Pressure

Not Applicable

High Alarm

High Alarm - Pressure

Not Applicable

Alarm Deadband

Alarm Deadband - Pressure

Not Applicable

Fault Value

Fault Value - Pressure

Not Applicable

Temperature Alarm

Temperature Alarm Enabled or Disabled

Disabled

Low Alarm

Low Alarm - Temperature

Not Applicable

High Alarm

High Alarm - Temperature

Not Applicable

Alarm Deadband

Alarm Deadband - Temperature

Not Applicable

Fault Value

Fault Value - Temperature

Not Applicable

Report Pressure As
Action on Failure

Upstream or Downstream
Action on Failure

Not Applicable
Not Applicable

RBX Alarming

Exception Alarm

Disabled

Reference Temperature

Reference Temperature

Not Applicable

4.4

SHEET

NUMBER POINT: MVS POINT #4


Item

Tag

Description
MVS Identification

Value
Not Applicable

Address

Address RS-485

Not Applicable

Scanning

Scan Enabled or Disabled

Disabled

Units

Unit System

Not Applicable

Sensor Alarms

Sensor Alarm Enabled or Disabled

Disabled

Diff. Pressure Alarm

Diff. Pressure Alarm Enabled or Disabled

Disabled

Low Alarm Diff. Pressure

Not Applicable

Low Alarm

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

51 OF 73

NUMBER

MANUAL
JOB OR PROJECT

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

High Alarm

High Alarm Diff. Pressure

Not Applicable

Alarm Deadband

Alarm Deadband Diff. Pressure

Not Applicable

Fault Value

Fault Value Diff. Pressure

Not Applicable

Pressure Alarm Enabled or Disabled

Disabled

Pressure Alarm
Low Alarm

Low Alarm - Pressure

Not Applicable

High Alarm

High Alarm - Pressure

Not Applicable

Alarm Deadband

Alarm Deadband - Pressure

Not Applicable

Fault Value

Fault Value - Pressure

Not Applicable

Temperature Alarm Enabled or Disabled

Disabled

Temperature Alarm
Low Alarm

Low Alarm - Temperature

Not Applicable

High Alarm

High Alarm - Temperature

Not Applicable

Alarm Deadband

Alarm Deadband - Temperature

Not Applicable

Fault Value

Fault Value - Temperature

Not Applicable

Report Pressure As

Upstream or Downstream

Not Applicable

Action on Failure

Action on Failure

Not Applicable

RBX Alarming

Exception Alarm

Disabled

Reference Temperature

Reference Temperature

Not Applicable

SHEET

LNG TERMINAL PROJECT

AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002

ANALOG INPUTS (AI)

5.1

NUMBER POINT: AI #1 (A1) TIT-513

5.1.1

GENERAL
Item

Description

Value

Scanning

Scan Enabled or Disabled

Enabled

Alarming

Alarm Enabled or Disabled

Enabled

Units

Unit of Engineering

Scan Period

Scan Period

1 Seconds

Low Reading EU

Low Reading - Range

High Reading EU

High Reading - Range

70

5.1.2

ADVANCED
Item

Description

Value

Filter

Filter

Adjusted A/D 0%

Adjusted 0% of the converter A/D

800

Adjusted A/D 100%

Adjusted 100% of the converter A/D

4000

Action on Failure

Action on Failure

Hold Last Value

Fault Value

Value on Failure

Not Applicable

Average Raw Value


Clipping

Average of the rude readings during scan


Enabled or Disabled
Inside keeps values of the limits of cut
when enabled

Enabled
Disabled

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

52 OF 73

NUMBER

MANUAL
JOB OR PROJECT

Temp Compensation

5.1.3

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL
Uses the FB board temperature to
compensate the AI when enabled

Disabled

ALARMS
Item

Description

Value

Low Alarm

Low Alarm

High Alarm

High Alarm

60

LoLo Alarm

LoLo Alarm

HiHi Alarm

HiHi Alarm

75

Rate Alarm

Rate Alarm

70

Alarm Deadband

Alarm Deadband

RBX Alarming

RBX Alarming

Disabled

5.2

SHEET

LNG TERMINAL PROJECT

AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002

NUMBER POINT: AI #2 (A2) NOT APPLICABLE

5.2.1

GENERAL
Item

Description

Value

Scanning

Scan Enabled or Disabled

Disabled

Alarming

Alarm Enabled or Disabled

Disabled

Units

Unit of Engineering

Not Applicable

Scan Period

Scan Period

Not Applicable

Low Reading EU

Low Reading - Range

Not Applicable

High Reading EU

High Reading - Range

Not Applicable

5.2.2

ADVANCED
Item

Filter

Description

Value

Filter

Not Applicable

Adjusted A/D 0%

Adjusted 0% of the converter A/D

Not Applicable

Adjusted A/D 100%

Adjusted 100% of the converter A/D

Not Applicable

Action on Failure

Action on Failure

Not Applicable

Fault Value

Value on Failure

Not Applicable

Average Raw Value


Clipping
Temp Compensation

Average of the rude readings during scan


Enabled or Disabled
Inside keeps values of the limits of cut when
enabled
Uses the FB board temperature to compensate
the AI when enabled

Disabled
Disabled
Disabled

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

53 OF 73

NUMBER

MANUAL
JOB OR PROJECT

5.2.3

SHEET

LNG TERMINAL PROJECT

AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

ALARMS
Item

Description

Value

Low Alarm

Low Alarm

High Alarm

High Alarm

Not Applicable

LoLo Alarm

LoLo Alarm - Disabled

Not Applicable

HiHi Alarm

HiHi Alarm - Disabled

Not Applicable

Rate Alarm

Rate Alarm

Not Applicable

Alarm Deadband

Alarm Deadband

Not Applicable

RBX Alarming

RBX Alarming

Disabled

5.3

Not Applicable

NUMBER POINT: AI #3 (A3) PIT-513

5.3.1

GENERAL
Item

Description

Value

Scanning

Scan Enabled or Disabled

Enabled

Alarming

Alarm Enabled or Disabled

Enabled

Units

Unit of Engineering

kPa

Scan Period

Scan Period

1 Seconds

Low Reading EU

Low Reading - Range

High Reading EU

High Reading - Range

9317

5.3.2

ADVANCED
Item

Filter

Description

Value

Filter

Adjusted A/D 0%

Adjusted 0% of the converter A/D

800

Adjusted A/D 100%

Adjusted 100% of the converter A/D

4000

Action on Failure

Action on Failure

Hold Last Value

Fault Value

Value on Failure

Not Applicable

Average Raw Value


Clipping
Temp Compensation

5.3.3

Average of the rude readings during scan


Enabled or Disabled
Inside keeps values of the limits of cut when
enabled
Uses the FB board temperature to compensate
the AI when enabled

Enabled
Disabled
Disabled

ALARMS
Item

Description

Value

Low Alarm

Low Alarm

High Alarm

High Alarm

9300

LoLo Alarm

LoLo Alarm - Disabled

HiHi Alarm

HiHi Alarm - Disabled

9317

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

54 OF 73

NUMBER

MANUAL
JOB OR PROJECT

LNG TERMINAL PROJECT

AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

Rate Alarm

Rate Alarm

9317

Alarm Deadband

Alarm Deadband

RBX Alarming

RBX Alarming

Disabled

5.4

SHEET

NUMBER POINT: AI #4 (E1) TAG: + T (POWER OUT)

5.4.1

GENERAL
Item

Description

Value

Scanning

Scan Enabled or Disabled

Enabled

Alarming

Alarm Enabled or Disabled

Enabled

Units

Unit of Engineering

Volts

Scan Period

Scan Period

5 Secs

Low Reading EU

Low Reading - Range

0.0

High Reading EU

High Reading - Range

38.0

5.4.2

ADVANCED
Item

Description

Value

Filter

Filter

Adjusted A/D 0%

Adjusted 0% of the converter A/D

Adjusted A/D 100%

Adjusted 100% of the converter A/D

4000

Average Raw Value


Clipping
Temp Compensation

5.4.3

Average of the rude readings during scan


Enabled or Disabled
Inside keeps values of the limits of cut when
enabled
Uses the FB board temperature to compensate
the AI when enabled

Disabled
Disabled
Disabled

ALARMS
Item

Description

Value

Low Alarm

Low Alarm

10.0

High Alarm

High Alarm

30.0

LoLo Alarm

LoLo Alarm

8.0

HiHi Alarm

HiHi Alarm

32.0

Rate Alarm

Rate Alarm

5.0

Alarm Deadband

Alarm Deadband

2.0

RBX Alarming

RBX Alarming

Disabled

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

55 OF 73

NUMBER

MANUAL
JOB OR PROJECT

LNG TERMINAL PROJECT

AREA/UNIT:
TITLE

5.5

I-MA-4451.28-6250-27D-FRB-002

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

NUMBER POINT: AI #5 (E2) TAG: POWER IN

5.5.1

GENERAL
Item

Description

Value

Scanning

Scan Enabled or Disabled

Enabled

Alarming

Alarm Enabled or Disabled

Enabled

Units

Unit of Engineering

Volts

Scan Period

Scan Period

5 Secs

Low Reading EU

Low Reading - Range

0.0

High Reading EU

High Reading - Range

38.0

5.5.2

ADVANCED
Item

Description

Value

Filter

Filter

Adjusted A/D 0%

Adjusted 0% of the converter A/D

800

Adjusted A/D 100%

Adjusted 100% of the converter A/D

4000

Average Raw Value


Clipping
Temp Compensation

5.5.3

Average of the rude readings during scan


Enabled or Disabled
Inside keeps values of the limits of cut when
enabled
Uses the FB board temperature to compensate
the AI when enabled

Disabled
Disabled
Disabled

ALARMS
Item

Description

Value

Low Alarm

Low Alarm

10.00

High Alarm

High Alarm

30.00

LoLo Alarm

LoLo Alarm

8.00

HiHi Alarm

HiHi Alarm

32.00

Rate Alarm

Rate Alarm

5.00

Alarm Deadband

Alarm Deadband

2.00

RBX Alarming

RBX Alarming

Disabled

5.6

SHEET

NUMBER POINT: AI #8 (E5) TAG: BRD TEMP

5.6.1

GENERAL
Item

Description

Value

Scanning

Scan Enabled or Disabled

Enabled

Alarming

Alarm Enabled or Disabled

Enabled

Units

Unit of Engineering

Scan Period

Scan Period

5 Secs

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

56 OF 73

NUMBER

MANUAL
JOB OR PROJECT

LNG TERMINAL PROJECT

AREA/UNIT:
TITLE

I-MA-4451.28-6250-27D-FRB-002

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

Low Reading EU

Low Reading - Range

-272.77

High Reading EU

High Reading - Range

140.55

5.6.2

SHEET

ADVANCED
Item

Description

Value

Filter

Filter

Adjusted A/D 0%

Adjusted 0% of the converter A/D

Adjusted A/D 100%

Adjusted 100% of the converter A/D

4000

Average Raw Value


Clipping
Temp Compensation

5.6.3

Average of the rude readings during scan


Enabled or Disabled
Inside keeps values of the limits of cut when
enabled
Uses the FB board temperature to compensate
the AI when enabled

Disabled
Disabled
Disabled

ALARMS
Item

Description

Value

Low Alarm

Low Alarm

10.0

High Alarm

High Alarm

50.0

LoLo Alarm

LoLo Alarm

-272.77

HiHi Alarm

HiHi Alarm

140.55

Rate Alarm

Rate Alarm

400.00

Alarm Deadband

Alarm Deadband

20.00

RBX Alarming

RBX Alarming

Disabled

Obs: Others Analog Inputs must be Configured With Scan and Alarms DISABLED.

PULSE INPUTS (PI)

6.1

NUMBER POINT: PI #1 (A7) TAG: FIT-513

6.1.1

GENERAL
Item

Description

Value

Scanning

Scan Enabled or Disabled

Enabled

Alarming

Alarm Enabled or Disabled

Disabled

Units

Unit of Engineering

Counts

Scan Period

Scan Period

1.0 secs

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

57 OF 73

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

6.1.2

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

SHEET

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

ADVANCED
Item

Description

Value

EU Options

Value Options

Rate (Max Rollover)

Conversion

Type of Conversion

Pulses/EU

Conversion/K-Factor

Factor of conversion

10937

Rate Period

Rate Period

EU/day

EU Units

Unit of Engineering

MCF/M3

6.1.3

ALARMS
Item

Description

Value

Low Alarm

Limit Low Alarm

Not Applicable

High Alarm

Limit High Alarm

Not Applicable

LoLo Alarm

Limit LoLo Alarm

Not Applicable

HiHi Alarm

Limit HiHi Alarm

Not Applicable

Rate Alarm

Limit Rate Alarm

Not Applicable

Alarm Deadband

Alarm Deadband

Not Applicable

RBX Alarming

Alarm for exception

Disabled

MODBUS CONFIG COM1

7.1

NUMBER POINT: #1 (CONFIGURATION MODBUS RTU RS-485)


Item

Description

Value

ASCII = 0, RTU = 1

Defines type Protocol Modbus - ASCII our RTU

Byte Order 1 = MSB 1 First

Byte Order Modbus

Host Enabled = 1

Host Enabled

Log Data 1 = Yes

Changing Parameters Register

Init Memory = 1

Init Memory

Port Switch En = 1

Enabled / Disabled of Protocol Changing

DCD = 0, DI = 1, STP = 2

Define Type of Protocol Changing

Modbus Baud Rate

Band Rate Protocol Modbus Enron

9600

Switch Baud Rate

Band Rate Protocol ROC

9600

Input Data Start

Input Data Start

100

Output Data Start

Output Data Start

300

HI Integer Scale

HI Integer Scale

4095

Low Integer Scale

Low Integer Scale

Obs: All the fields of Float Scale must be filled with 0.

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

58 OF 73

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:

8.1

LNG TERMINAL PROJECT

SHEET

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

MODBUS FUNCT COM1 (REGISTERS MODBUS RTU)


NUMBER POINT: #3 FUNCT 3A
Start Reg End Reg Pt Type

Lgl# Param Conv

Description

TYPE

40201

40202

17

128

70

Instantaneous Static Pressure

Var. Instant.

40203

40204

10

70

Instantaneous Temperature

Var. Instant.

40205

40206

10

70

Standard Volume Flowrate

Var. Instant.

40207

40208

10

70

Energy Flowrate

Var. Instant.

40209

40210

70

Relative Density

Var. Instant.

40211

40212

10

16

70

Compressibility Factor

Var. Instant.

40213

40214

17

129

11

70

Previous Hour Corrected Total Volume

Var. Instant.

40215

40216

42

70

Current Day Corrected Total Volume

Var. Instant.

40217

40218

42

70

Previous Day Corrected Total Volume

Var. Instant.

10

40219

40220

17

129

12

70

Previous Hour Total Energy

Var. Instant.

8.2

NUMBER POINT: #4 FUNCT 3B


Start Reg End Reg Pt Type

Lgl# Param Conv

Description

TYPE

40221

40222

42

11

70

Current Day Total Energy

Var. Instant.

40223

40224

42

12

70

Previous Day Total Energy

Var. Instant.

40225

40226

28

70

Gas Composition - Methane

Parameters

40227

40228

29

70

Gas Composition - Ethane

Parameters

40229

40230

30

70

Gas Composition - Propane

Parameters

40231

40232

32

70

Gas Composition - I-Butane

Parameters

40233

40234

31

70

Gas Composition - N-Butane

Parameters

40235

40236

34

70

Gas Composition - I-Pentane

Parameters

40237

40238

33

70

Gas Composition - N-Pentane

Parameters

10

40239

40240

35

70

Gas Composition - Hexane

Parameters

8.3

NUMBER POINT: #5 FUNCT 3C


Start Reg End Reg Pt Type

40241

40242

40243

40244

40245

40250

7
8
9

Lgl# Param Conv

Description

TYPE

23

70

Gas Composition - Nitrogen

Parameters

24

70

Gas Composition - Carbon Dioxide

Parameters

17

131

39

Day, Month, Year, Hour, Minute and Second

Parameters

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

59 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

REV

I-MA-4451.28-6250-27D-FRB-002

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:

LNG TERMINAL PROJECT

SHEET

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

MODBUS CONFIG COM2

9.1

NUMBER POINT: #1 (CONFIGURATION MODBUS RTU RS-485)


Item

Description

Value

ASCII = 0, RTU = 1

Defines type Protocol Modbus - ASCII our RTU

Byte Order 1 = MSB 1 First

Byte Order Modbus

Host Enabled = 1

Host Enabled

Log Data 1 = Yes

Changing Parameters Register

Init Memory = 1

Init Memory

Port Switch En = 1

Enabled / Disabled of Protocol Changing

DCD = 0, DI = 1, STP = 2

Define Type of Protocol Changing

Modbus Baud Rate

Band Rate Protocol Modbus Enron

9600

Switch Baud Rate

Band Rate Protocol ROC

9600

Input Data Start

Input Data Start

100

Output Data Start

Output Data Start

300

HI Integer Scale

HI Integer Scale

4095

Low Integer Scale

Low Integer Scale

Obs: All the fields of Float Scale must be filled with 0.

10

MODBUS FUNCT COM2 (REGISTERS MODBUS RTU)

10.1 NUMBER POINT: #6 FUNCT 4A


Start Reg End Reg Pt Type

Lgl# Param Conv

Description

TYPE

30264

30265

17

128

66

Instantaneous Static Pressure

Var. Instant.

30266

30267

10

66

Instantaneous Temperature

Var. Instant.

30268

30269

17

66

Standard Volume Flowrate

Var. Instant.

30270

30271

10

66

Reserve

Reserve

30272

30279

17

128

66

Flow Totalized Today, Mounth, Energy Totalized Month and


Var. Instant.
Flow Totalized Accumulated

30280

30281

66

Relative Density

Var. Instant.

30282

30283

10

16

66

Compressibility Factor

Var. Instant.

30284

30299

128

28

66

Gas Composition

Parameters

30300

30303

128

23

66

Gas Composition

Parameters

10

30304

30305

66

Heating Value

Var. Instant.

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

60 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

10

REV

I-MA-4451.28-6250-27D-FRB-002

NUMBER

MANUAL
JOB OR PROJECT

LNG TERMINAL PROJECT

AREA/UNIT:

REV

I-MA-4451.28-6250-27D-FRB-002
SHEET

61 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

10.2 NUMBER POINT: #7 FUNCT 4B


Start Reg End Reg Pt Type

Lgl# Param Conv

Description

TYPE

30306

30308

12

128

33

Second, Minute and Hour

Parameters

30309

30311

12

128

33

Day, Month and Year

Parameters

30506

30507

17

129

66

Previous Hour Pressure Average

Var. Instant.

30508

30509

17

129

66

Previous Hour Flow Average

Var. Instant.

30510

30511

17

129

10

66

Previous Hour Accumulated Volume

Var. Instant.

30610

30613

17

129

66

Yesterday Average Temperature and Pressure

Var. Instant.

30614

30615

42

66

Yesterday Total Volume

Var. Instant.

30616

30617

42

12

66

Yesterday Total Energy

Var. Instant.

30618

30619

17

128

15

66

Yesterday Density Relative Average

Var. Instant.

10

30804

30807

17

128

11

66

Previous Month Corrected Total Volume and Energy

Var. Instant.

10.3 NUMBER POINT: #8 FUNCT 4C


Start Reg End Reg Pt Type

Lgl# Param Conv

Description

TYPE

30113

30113

14

33

Alarms Volume Flowrate

30114

30114

130

16

33

Alarms Instataneous Static Pressure

Alarms

30115

30115

128

16

33

Alarms Instantaneous Temperature

Alarms

30116

30116

132

16

33

Alarms Power Supply Voltage

Alarms

30117

30117

135

16

33

Alarms Temperature Flow Computer Board

Alarms

10

Alarms

10.4 NUMBER POINT: #12 FUNCT 16A


Start Reg End Reg Pt Type

Lgl# Param Conv

Description

TYPE

30301

30326

128

23

66

Gas Composition Chromatograph

Parameters

30327

30332

12

128

34

Second, minute, hour, day, month and year

Parameters

10

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

NUMBER

MANUAL
JOB OR PROJECT

LNG TERMINAL PROJECT

AREA/UNIT:

SHEET

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

MODBUS HOST COM2


All points of Modbus Host COM2 must be filled with 0.

12

LCD USER LIST (DISPLAY FLOBOSS)

12.1 USER LIST: #1


Text

Device Parameter

Text

Device Parameter

FI-513

FLW 1, CURFLO

FQI-513-LM

ERN 1, FLOPRV

TI-513

FLW 1, CURTMP

10

PI-513

FLW 1, CURFP

11

FIn-513

FLW 1, CURDP

12

FQI-513

ERN 1, FLOACC

13

FQI-513-TD

ERN 1, FLOTDY

14

FQI-513-LD

ERN 1, FLOYDY

15

FQI-513-M

ERN 1, FLOMTH

16

13

CONFIGURATION GENERAL - INFORMATION

13.1 GENERAL
Item

Description

Value

Station Name

Floboss Identification

FQY-513

Address

Floboss Address

Group

Floboss Group

Contract Hour

Contract Hour

00:00

14

SOFT POINT
NUMBER

TAG

#1

CONV

#2

MDIAS

Hour and Day Average

#3

ACCUM

Accumulated Average

#4

DATA/HORA

#5

ALARMES

62 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

11

REV

I-MA-4451.28-6250-27D-FRB-002

DESCRIPTION
Units Conversion

Move Date and Hour


Alarms of Temperature, Pressure and Flow

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

NUMBER

MANUAL
JOB OR PROJECT

SHEET

LNG TERMINAL PROJECT

AREA/UNIT:

REV

I-MA-4451.28-6250-27D-FRB-002

63 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

14.1 SOFT POINT #1 CONV


COD. FLOBOSS

DESCRIPTION

COD. FLOBOSS

DESCRIPTION

Inst. Pressure (kgf/cm2)

11

Previous Month Total Energy (kwh)

Inst. Flow (m/dia)

12

Today Total Volume (m)

13

Month Total Volume (m)

14

Month Total Energy (kwh)

15

Total Accumulated Volume (m)

16

Heating Value (kJ/m)

17

Yesterday Total Volume (m)

18

2
3

Yesterday Total Energy (kwh)

19

10

Previous Month Total Volume (m)

20

Energy Accumulated

14.2 SOFT POINT #2 MEDIAS


COD. FLOBOSS
1

DESCRIPTION

COD. FLOBOSS
11

Hour Inst. Pressure

Hour Temperature

12

Hour Inst.Flow

13

Hour Relative Density

14

Day Inst. Pressure

15

Day Temperature

16

Day Inst.Flow

17

Day Relative Density

18

19

10

20

DESCRIPTION

14.3 SOFT POINT #3 ACCUM


COD. FLOBOSS
1

DESCRIPTION

COD. FLOBOSS

DESCRIPTION

Count Pressure

11

Accumulated Pressure

12

Count Temperature

13

Accumulated Temperature

14

Count Flow

15

Accumulated Flow

16

Count Relative Density

17

Accumulated Relative Density

18

Total Accumulated Flow

19

10

20

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

NUMBER

MANUAL
JOB OR PROJECT

SHEET

LNG TERMINAL PROJECT

AREA/UNIT:

REV

I-MA-4451.28-6250-27D-FRB-002

64 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

14.4 SOFT POINT #4 DATA/HORA


COD. FLOBOSS
1

DESCRIPTION

COD. FLOBOSS
11

DESCRIPTION

Current Day

Current Month

12

Current Year

13

Current Hour

14

Current Minute

15

Current Second

16

17

18

19

10

20

14.5 SOFT POINT #5 ALARMES


COD. FLOBOSS
1

DESCRIPTION

COD. FLOBOSS
11

DESCRIPTION

Flow Alarms

Temperature Alarms

12

Pressure Alarms

13

14

15

16

17

18

19

10

20

15

FST'S

15.1 FST 1
Units Conversion
Label

CMD
WT
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV

Argument 1

Argument 2

Comment

1
FLW 1, CURFP

Pressure Base Conversion (kgf/cm for kPa)

0.010197
SFP 1, DATA1
FLW 1, CURFLO

Inst. Flow Conversion (km/dia to m/dia)

1000
SFP 1, DATA2
FLW 1, TDYFLO

Today Flow (km to m)

1000
SFP 1, DATA3

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV
VAL
*
SAV

END

ERN 1, FLOMTH

NUMBER

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

SHEET

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL
Moth Flow (km to m)

1000
SFP 1, DATA4
ERN 1, ENGMTH

Month Energy (GJ to KWh)

0.0036
SFP 1, DATA5
ERN 1, FLOACC

Accumulated Flow (km to m)

1000
SFP 1, DATA6
AGA 1, GASHV

Heating Value (MJ/m to KJ/m)

1000
SFP 1, DATA7
ERN 1, FLOYDY

Yesterday Total Flow (km to m)

1000
SFP 1, DATA8
ERN 1, ENGYDY

Today Total Energy (GJ to KWh)

0.0036
SFP 1, DATA9
ERN 1, FLOPRV

Prev. Month Flow (km to m)

1000
SFP 1, DATA10
ERN 1, ENGPRV

Prev. Month Energy (GJ to KWh)

0.0036
SFP 1, DATA11

VAL

ERN 1, ENGACC

SAV

SFP 1, DATA20

VAL

CLK 1, DAY

SAV

SFP 4, DATA1

VAL

CLK 1, MONTH

SAV

SFP 4, DATA2

VAL

CLK 1, YEAR

SAV

SFP 4, DATA3

VAL

CLK 1, HOUR

SAV

SFP 4, DATA4

VAL

CLK 1, MINUTE

SAV

SFP 4, DATA5

VAL

CLK 1, SECOND

SAV

SFP 4, DATA6

VAL

AGA 1, ALARM

SAV

SFP 5, DATA1

VAL

AIN A1, ALARM

SAV

SFP 5, DATA2

VAL

AIN A3, ALARM

SAV

SFP 5, DATA3

Move Day to Soft Point


Move Month to Soft Point

Move Second to Soft Point


Move Flow Alarms to Soft Point
Move Temperature Alarms to Soft Point
Move Pressure Alarms to Soft Point

END

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

65 OF 73

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

REV

I-MA-4451.28-6250-27D-FRB-002
SHEET

LNG TERMINAL PROJECT

66 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

15.2 FST 2
Load Alarms Table and Save Flash Memory Once a Day
Label

CMD
10

VAL

AIN A3, ALARM

>=
VAL
+

P1

64

Argument 2

Comment
10 Seconds Temporization

P1

Fault Pressure

SFP 3, DATA1
1

SAV

SFP 3, DATA1

VAL

SFP 3, DATA2

Count. Pressure Average

SFP 1, DATA1

Inst. Pressure (kgf/cm)

SAV

SFP 3, DATA2

Accumulated Pressure Average

VAL

AIN A1, ALARM

>=

64

VAL

SFP 3, DATA3

P2

Fault Temperature

SAV

SFP 3, DATA3

VAL

SFP 3, DATA4

+
P2

Argument 1

WT

Count. Temperature Average

FLW 1, CURTMP

Temperature oC

SAV

SFP 3, DATA4

Accumulated Temperature Average

VAL

SFP 3, DATA5

SAV

SFP 3, DATA5

VAL

SFP 3, DATA6

Count. Flow Average

SFP 1, DATA2

Flow (m/dia)

SAV

SFP 3, DATA6

Accumulated Flow Average

VAL

SFP 3, DATA7

SAV

SFP 3, DATA7

VAL

SFP 3, DATA8

Count. Relative Density

AGA 1, SPGR

Relative Density

SAV

SFP 3, DATA8

Accumulated Relative Density Average

VAL

CLK 1, MINUTE

!=
VAL

==

VAL

SAV

FST 2, R1

VAL

SFP 3, DATA1

==

VAL

SFP 3, DATA2

SFP 3, DATA1

SAV

SFP 2, DATA1

VAL

SFP 3, DATA9

P41

FST 2, R1

Verify Minutes = 0
Verify Condition Control Flag

P42

P8
Hour Pressure Average
Count. Today Pressurte Average

SAV

SFP 3, DATA9

VAL

SFP 3, DATA10

SFP 2, DATA1

Accumulated Today Pressure

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

P8
P9

SAV

SFP 3, DATA10

GO

P9

VAL

-1

SAV

SFP 2, DATA1

VAL

SFP 3, DATA3

==

SFP 3, DATA4

SFP 3, DATA3

SAV

SFP 2, DATA2

VAL

SFP 3, DATA11

P10
P11

SFP 3, DATA11

VAL

SFP 3, DATA12

SFP 2, DATA2

SAV

SFP 3, DATA12

GO

P11

VAL

-1

SAV

SFP 2, DATA2

VAL

SFP 3, DATA5

P13

SFP 3, DATA6

SFP 3, DATA5

SAV

SFP 2, DATA3

VAL

SFP 3, DATA13
SFP 3, DATA13

VAL

SFP 3, DATA14

SFP 2, DATA3

SAV

SFP 3, DATA14

GO

P13

VAL

-1

SAV

SFP 2, DATA3

VAL

SFP 3, DATA7

P15

SFP 3, DATA8

SFP 3, DATA7

SAV

SFP 2, DATA4

VAL

SFP 3, DATA15
SFP 3, DATA15

VAL

SFP 3, DATA16

SFP 2, DATA4

SAV

SFP 3, DATA16

GO

P15

VAL

-1

SAV

SFP 2, DATA4

VAL

SFP 1, DATA6

/
VAL

P10
Hour Today Temperature
Count. Today Temperature Average

Accumulated Today Temperature

P12
Hour Flow Average
Count. Today Flow Average

Accumulated Today Flow

P14

Hour Density Average


Count. Today Densuty Average

SAV

SAV

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

VAL

LNG FLEXIBLE TERMINAL PECM PORT

SAV

==

P14

VAL

LNG TERMINAL PROJECT

SHEET

SAV

==

P12

VAL

I-MA-4451.28-6250-27D-FRB-002

Accumulated Today Density

FST 2, R2
SFP 2, DATA9

Previous Hour Accumulated Volume

1000
SFP 2, DATA10

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

67 OF 73

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

VAL

FST 2, R2

VAL

SFP 1, DATA20
SFP 2, DATA11

VAL

SFP 1, DATA20

SAV

FST 2, R3

VAL

CLK 1, HOUR

!=
==

0
0
SFP 3, DATA10

SFP 3, DATA9

SAV

SFP 2, DATA5

GO

P25

P24

VAL

-1

SAV

SFP 2, DATA5

P25

VAL

SFP 3, DATA11
0

VAL

SFP 3, DATA12

SFP 3, DATA11

SAV

SFP 2, DATA6

GO

P27

P26

VAL

-1

SAV

SFP 2, DATA6

P27

VAL

SFP 3, DATA13

==

VAL

SFP 3, DATA14

SFP 3, DATA13

SAV

SFP 2, DATA7

GO

P29

P28

VAL

-1

SAV

SFP 2, DATA7

P29

VAL

SFP 3, DATA15

==

Verify Hour = 0

P24
Today Pressure Average

P26
Today Temperature Average

P28
Today Flow Average

VAL

SFP 3, DATA16

SFP 3, DATA15

SAV

SFP 2, DATA8

GO

P31

P30

VAL

-1

SAV

SFP 2, DATA8

P31

VAL

SAV

SFP 3, DATA9

SAV

SFP 3, DATA10

SAV

SFP 3, DATA11

SAV

SFP 3, DATA12

SAV

SFP 3, DATA13

SAV

SFP 3, DATA14

SAV

SFP 3, DATA15

P40

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

SFP 3, DATA9

VAL

==

LNG FLEXIBLE TERMINAL PECM PORT

P40

SAV

SFP 3, DATA16

VAL

Today Density Average

Zera Today Accumulator and Accountant

Zera Hour Accumulator and Accountant

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

68 OF 73

FST 2, R3

SAV

VAL

LNG TERMINAL PROJECT

SHEET

SFP 1, DATA6

SAV
-

REV

I-MA-4451.28-6250-27D-FRB-002

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

P41
P42

SAV

SFP 3, DATA1

SAV

SFP 3, DATA2

SAV

SFP 3, DATA3

SAV

SFP 3, DATA4

SAV

SFP 3, DATA5

SAV

SFP 3, DATA6

SAV

SFP 3, DATA7

SAV

SFP 3, DATA8

GO

P42

VAL

SAV

FST 2, R1

I-MA-4451.28-6250-27D-FRB-002
SHEET

LNG TERMINAL PROJECT

REV

69 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

END

15.3 FST 3
It updates the gas composition values for the Z calculation
Label
CMD
Argument 1
Argument 2

END

WT

300

VAL

SAV

FLW 1, RECALCZS

Comment
300 Seconds Temporization
Update Z Calculation for Gas Composition

END

15.4 FST 4
It updates the gas composition values for the Z calculation
Label
CMD
Argument 1
Argument 2

CKMIN

WT

VAL

CLK 1, HOUR

==

VAL

SAV

FST 4, R1

GO

END

VAL

CLK 1, MINUTE

==

GO

END

WRTFLS VAL

END

Comment
5 Seconds Temporization

CKMIN

Verify Hour = 0
Control Flag = 0

WRTFLS

Verify Minute = 5

FST 4, R1

==

VAL

SAV

FLG 1, WRITE

VAL

SAV

FST 4, R1

EVT

WRT MENORY

END
Writing Flash Memory Configuration
Control Flag
FLG 1, WRITE

END

Obs: These FSTs Must Be Activated on FST Registers Options.

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

NUMBER

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

16

I-MA-4451.28-6250-27D-FRB-002

LNG TERMINAL PROJECT

SHEET

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

HISTORY

16.1 STREAM 01
Point

Archive Type

Archive Point

Description

Totalize

ERN 1, MINTDY

Minutes with Flow

Average

FLW 1, CURDP

Instantaneous Flow Uncorrected

Average

FLW 1, CURFP

Average

FLW 1, CURTMP

Average

FLW 1, IMV/BMV

Average

FLW 1, HWPF

Accumulated

FLW 1, CURFLO

Accumulated

FLW 1, ENERGY

Accumulated energy

Average

FLW 1, CURFLO

Instantaneous Flow Corrected

Static Pressure
Temperature
Constant of correction of the calculation AGA
Extension HWPF of the AGA3 1992
Flow accumulated corrected

10

Average

AGA 1, SPGR

11

Current Value

ERN1, FLOACC

Specific Gravity

12

Current Value

ERN1, FLOTDY

Flow Today Accumulated

13

Current Value

ERN1, FLOMTH

Flow Month Accumulated

Flow Accumulated with Reset

16.2 STREAM 02
Point

Archive Type

Archive Point

14

UNDEFINED

UNDEFINED

Reserve

Description

15

UNDEFINED

UNDEFINED

Reserve

16

UNDEFINED

UNDEFINED

Reserve

17

UNDEFINED

UNDEFINED

Reserve

18

UNDEFINED

UNDEFINED

Reserve

19

UNDEFINED

UNDEFINED

Reserve

20

UNDEFINED

UNDEFINED

Reserve

21

UNDEFINED

UNDEFINED

Reserve

22

UNDEFINED

UNDEFINED

Reserve

23

UNDEFINED

UNDEFINED

Reserve

24

UNDEFINED

UNDEFINED

Reserve

25

UNDEFINED

UNDEFINED

Reserve

16.3 STREAM 03
Point

Archive Type

Archive Point

26

UNDEFINED

UNDEFINED

Reserve

Description

27

UNDEFINED

UNDEFINED

Reserve

28

UNDEFINED

UNDEFINED

Reserve

29

UNDEFINED

UNDEFINED

Reserve

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

70 OF 73

NUMBER

MANUAL
JOB OR PROJECT

I-MA-4451.28-6250-27D-FRB-002
SHEET

LNG TERMINAL PROJECT

AREA/UNIT:

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

30

UNDEFINED

UNDEFINED

Reserve

31

UNDEFINED

UNDEFINED

Reserve

32

UNDEFINED

UNDEFINED

Reserve

33

UNDEFINED

UNDEFINED

Reserve

34

UNDEFINED

UNDEFINED

Reserve

35

UNDEFINED

UNDEFINED

Reserve

36

UNDEFINED

UNDEFINED

Reserve

37

UNDEFINED

UNDEFINED

Reserve

16.4 STREAM 04
Point

Archive Type

Archive Point

38

UNDEFINED

UNDEFINED

Reserve

39

UNDEFINED

UNDEFINED

Reserve

40

UNDEFINED

UNDEFINED

Reserve

41

UNDEFINED

UNDEFINED

Reserve

42

UNDEFINED

UNDEFINED

Reserve

43

UNDEFINED

UNDEFINED

Reserve

44

UNDEFINED

UNDEFINED

Reserve

45

UNDEFINED

UNDEFINED

Reserve

46

UNDEFINED

UNDEFINED

Reserve

47

UNDEFINED

UNDEFINED

Reserve

48

UNDEFINED

UNDEFINED

Reserve

49

UNDEFINED

UNDEFINED

Reserve

17

Description

COMM PORTS

17.1 COMM PORT: #1 LOCAL PORT


17.1.1 GENERAL
Item
Baud Rate

Description

Value

Rate of Transmission

9600

Parity

Parity

None

Data Bits

Number of Data Bits

Stop Bits

Number of Stop Bits

Key On Delay

Delay Time to Activate RTS

Key Off Delay

Delay Time to Deactivate RTS.

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

71 OF 73

NUMBER

MANUAL
JOB OR PROJECT

I-MA-4451.28-6250-27D-FRB-002
SHEET

LNG TERMINAL PROJECT

AREA/UNIT:

LNG FLEXIBLE TERMINAL PECM PORT

TITLE

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

17.1.2 MODBUS HOST PARAMETERS


Item

Description

Value

Start Transmission

Inactive

Continuous Polling

Disabled

17.2 COMM PORT: #2 COMM 1


17.2.1 GENERAL
Item

Description

Value

Baud Rate

Rate of Transmission

9600

Parity

Parity

None

Data Bits

Number of Data Bits

Stop Bits

Number of Stop Bits

RTS/CTS Handshaking

RTS/CTS Enabled or Disabled

Disabled

Key On Delay

Delay Time to Activate RTS

0.02

Key Off Delay

Delay Time to Deactivate RTS.

0.01

17.2.2 MODBUS HOST PARAMETERS


Item

Description

Value

Start Transmission

Inactive

Continuous Polling

Disabled

17.3 COMM PORT: #3 COMM 2


17.3.1 GENERAL
Item

Description

Value

Baud Rate

Tax of Transmission

9600

Parity

Parity

None

Data Bits

Amount of bits of Data

Stop Bits

Amount of bits of stopped

RTS/CTS Handshaking

RTS/CTS Enabled or Disabled

Disabled

Key On Delay

Delay Time to Activate RTS

0.02

Key Off Delay

Delay Time to Deactivate RTS.

0.01

17.3.2 MODBUS HOST PARAMETERS


Item

Description

Value

Start Transmission

Inactive

Continuous Polling

Disabled

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.

REV

72 OF 73

MANUAL
JOB OR PROJECT
AREA/UNIT:
TITLE

NUMBER

I-MA-4451.28-6250-27D-FRB-002
SHEET

LNG TERMINAL PROJECT

REV

73 OF 73

LNG FLEXIBLE TERMINAL PECM PORT

GAS FLOW COMPUTERS CONFIGURATION


MANUAL

Obs: The Modem / RBX and Store & Forward Must be Configured on COM1 and COM2 as None / Disable and Same Port,
Respectively.

18

FLAGS

18.1 FLAGS
18.1.1 ADVANCED
Item

Description

Transmitter Power +T

19

Inform Value of the Power Supply

Value
on

CALCULATIONS OF FLOW

19.1 ROC / INFORMATION


19.1.1 POINTS
At AGAS Active Options, Choose 4, Make Possible That Floboss 407 Perform 4 Flow Calculations.
20

USER PROGRAMS
These User Programs should be downloaded to the Floboss:
o

FB_HVCAL.H00 User Program for calculation of energy 20 C Version 2.00;

FBMB1_60.H00 User Program protocol Modbus RTU port Comm 1 Version 2.01;

FBMB2_05.H00 User Program protocol Modbus RTU port Comm 2 Version 2.01.

THE INFORMATION OF THIS DOCUMENT ARE PROPERTY OF LNG, BEING FORBIDDEN THE USE OFF THIS PURPOSE.