s i g m a m o n i t o r r e l a y
X0
POWER SOURCE
1A 1A
ST
CONTROL POWER
120 VAC SECONDARY
1A
1000 : 1 CT
X2
X1
NEUTRAL
GROUNDING
RESISTOR GM - AM1
N 0-1 mA DC AMMETER
NGRS WITH 0-100% SCALE
SENSE G
RESISTOR R 20 40 60 80
100
0
%
(N) NEUTRAL
+ -
(G) GROUND
(R) RELAY
REMOTE 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52
PWR GND NGR ZONE NA NA NA
FLT FLT GR NC NC S G
NO NO
MODE DELAY LEVEL 50 NGR CURRENT SENSE G/F
NGR FAULT GND FAULT RES. CT METER
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 SIGMA MONITOR
60 ZONE
POWER TRIP RELA Y I/L TEST RESET INHIBIT
G L N NC NO NO NO NO NO
RESET TEST
1 2 3 4 5 6 MODBUS 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
Technical Specifications
Electrical Ratings Control Power: 110-240V AC/DC 50/60Hz 5VAac or 5Wdc
Maximum: -45% to +10% (60-264V AC/DC)
Output Relay Contacts Main Trip Relay: Type: Form Z (NO and NC pair)
Rating: 10A@240Vac, 10A@30Vdc, 1/2HP@240Vac
Auxiliary Ground Fault Relay: Type: 1 Form C (NO/NC)
Rating: 10A@240Vac, 8A@24Vdc, 1/2HP@240Vac
Auxiliary NGR Fault Relay: Type: 1 Form C (NO/NC)
Rating: 10A@240Vac, 8A@24Vdc, 1/2HP@240Vac
Electrical Tests Surge test: @ 3kV Dielectric test: @ 2kV for 1 minute
Temperature Range Operating: -40C to +60C Storage: -50C to +70C
Physical Dimensions: Length: 157 mm (6.18 in.) Width: 86 mm (3.39 in.)
Height: 58 mm (2.28 in.) Weight: 344 g
Ground Fault Circuit CT Input: Non-Isolated. One side of the CT input, terminal 22, is internally grounded.
CT Ratio: T2A, T3A or equivalent 1000:1
DIP Switch Settings Trip Level: 8 settings: 5%, 10%, 15%, 20%, 25%, 30%, 40%, and 50% of the set
NGR Current Setting Trip Time: 32 settings, 0-60 msec.,
150 msec. to 3.15 sec. in 100 msec. steps
Accuracy: Repeat: 1% Trip Time: 10%, 10 msec.
Trip Current: 10% Meter Output: 2% at full scale.
Thermal Characteristics: Short Time Withstand 400A for 1 sec.