You are on page 1of 28

TO BE DIFFERENTIATE

THE TYPE FOR SCREED


& NO SCREED ALSO SAME
TO BE UPDATE IN SAP
TABLE - 1
SUPPORT DATA
SUPPORT TAG / NOM. PIPE O.D. OF INSULATION O.D. OF PIPE
'L' ' L1 ' 'T' BOLT SIZE 'V' 'W' 'X' 'Y'
SAP CODE DIA. D (NB) PIPE (MM) THK. INSULATION (MM.)

SE032-1-015 15 21.3 13 49.3 40 50 6 M10 x 45 53.3 61.3 100 140


SE032-1-025 25 33.4 13 61.4 40 50 6 M10 x 45 65.4 73.4 112 152
SE032-1-032 32 42.2 13 70.2 40 50 6 M10 x 45 74.2 82.2 122 162
SE032-1-040 40 48.3 13 76.3 40 50 6 M10 x 45 80.3 88.3 128 168
SE032-1-050 50 60.3 13 88.3 40 50 6 M10 x 45 92.3 100.3 140 180
SE032-1-065 65 73 13 101 40 50 6 M10 x 45 105 113 152 192
SE032-1-080 80 88.9 13 116.9 50 68 10 M10 x 45 124.9 136.9 176 216
SE032-1-100 100 114.3 13 142.3 50 68 10 M10 x 45 150.3 162.3 202 242
SE032-1-125 125 141.3 13 169.3 50 68 10 M12 x 45 177.3 189.3 240 290
SE032-1-150 150 168.3 13 196.3 50 68 10 M12 x 45 204.3 216.3 266 316
SE032-1-200 200 219.1 13 247.1 50 68 10 M12 x 45 255.1 267.1 316 366
SE032-1-250 250 273 13 301 50 68 12 M12 x 45 311 325 376 426
SE032-1-300 300 323.8 13 351.8 80 93 12 M12 x 45 361.8 375.8 426 476
SE032-1-350 350 355.6 13 383.6 80 93 12 M12 x 45 393.6 407.6 456 506
SE032-1-400 400 406.4 13 434.4 80 93 12 M16 x 45 444.4 458.4 518 578
SE032-1-450 450 457 13 485 80 93 12 M16 x 45 495 509 570 630
SE032-1-500 500 508 13 536 80 93 12 M16 x 45 546 560 620 680
SE032-1-550 550 559 13 587 80 93 12 M16 x 45 597 611 670 730
SE032-1-600 600 610 13 638 80 93 12 M16 x 45 648 662 722 782