USE : 3 - 100 kVA POLE MOUNTED TRANSFORMER 34.

5 kV

GENERAL NOTES AND SPECIFICATIONS:

1. ALL GENERAL ELECTRICAL WORKS SHALL BE EXECUTED IN ACCORDANCE WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE, LAWS AND ORDINANCES 2 SETS - 3 # 250mm THHN &
OF THE LOCAL MUNICIPALITY, RULES AND REGULATIONS OF THE LOCAL POWER.
2 SETS # 38mm THHN GRND WIRE in
POWER SERVICE ENTRANCE
2. POWER SERVICE TO THE BUILDING SHALL BE 230V, THREE PHASE, THREE WIRES, 60Hz. THREE PHASE, THREE WIRES, 460VAC, 60Hz

3. WIRING SHALL BE IN RIGID STEEL CONDUIT, ELECTRICAL METALLIC TUBING (EMT) OR AS INDICATED IN THE PLANS.
a.) SERVICE ENTRANCE - RIGID STEEL CONDUITS (RSC) OR INTERMEDIATE METALLIC CONDUITS (IMC).

b.) IN BETWEEN DOUBLE WALLS AND ABOVE CEILING - ELECTRICAL METALLIC (EMT) PIPES.

4. SMALLEST CONDUCTOR TO BE USED SHALL BE No. 3.5mm (12) AWG AND SMALLEST RACEWAY SHALL BE 15mm (21") DIAMETER TRADE SIZE CONDUIT. CONDUCTORS SHALL BE INSULATED
FOR 600 VOLTS TW, THHN, OR THW OR AS INDICATED IN THE PLANS, P.D. DURAFLEX, PHILFLEX, COLUMBIA OR EQUAL.

5. FEEDERS AND BRANCH CIRCUITS SHALL BE INSTALLED AS INDICATED IN THE PLANS. HOMERUN SHALL NOT BE COMBINED IN THE SAME RACEWAY UNLESS SO NOTED. MOTOR CONTROL CENTER 1 (MCC1)

6. NO BRANCH CIRCUIT CONDUCTOR SHALL HAVE A LOAD OF MORE THN 80% OF ITS RATING.
M 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
7. WIRE GUTTERS, SQUARE BOXES AND PULL BOXES SHALL BE PROVIDED ON CIRCUITS AND HOMERUN IN EXCESS OF 30 METERS OR WHERE NECESSARY.
kW-hr METER MAGNETIC STARTER W/
60/3 60/3 30/3 30/3 60/3 60/3 60/3 60/3 30/3 30/3
8. OUTLET BOXES SHALL BE GAUGE NO. 16 (MIN) PRESSED STEEL GALVANIZED DEEP TYPE. START/STOP PUSH
a.) CEILING LIGHT OUTLETS - 40mm (1 21") DEEP, 100mm (4") OCTAGONAL BOX FOR 1 OR 2 RACEWAY ENTRIES, 55mm (2 81") DEEP, 100mm (4") OCTAGONAL BOX FOR FOR 3 OR 4 BUTTON (TYPICAL)
RACEWAY ENTRIES. 3-100mm THHN & 1-22mm 3-5.5mm THHN & 1-3.5mm

b.) WALL SWITCHES - 55mm (2 81") DEEP, UTILITY BOX FOR 1 OR 2 SWITCHES ON STRAP, 40MM (1 21") DEEP, 100mm (4") SQUARE BOX WITH ONE GANG RAISED COVER FOR 3

3-14mm THHN & 1-5.5mm


SWITCHES ON STRAPS.
3-5mm THHN & 1-2mm 3-5.5mm THHN & 1-3.5mm

c.) WALL OR COLUMN RECEPTACLE - 55mm (2 81") DEEP, UTILITY BOX FOR 1 OR 2 RACEWAY ENTRIES, 40mm (1 21") DEEP, 100mm (4") SQUARE BOX WITH ONE GANG RAISED 3-3.5mm THHN & 1-1.6mm 3-5.5mm THHN & 1-3.5mm
COVER FOR 3 OR MORE RACEWAY ENTRIES.
3-2.0mm THHN & 1-1.6mm 3-5.5mm THHN & 1-3.5mm
9. ALL BRANCH CIRCUIT CONDUCTORS SHALL BE COLOR CODED AS PER REQUIREMENTS OF PEC ARTICLES 3.1.1.5. GROUNDED CONDUCTOR SHALL BE IDENTIFIED BY A CONTINUOUS
COLOR WHITE GROUNDING CONDUCTOR OF BRANCH CIRCUITS SHALL BE IDENTIFIED BY A CONTINUOUS GREEN COLOR UNLESS IT IS BARE.
3-2.0mm THHN & 1-1.6mm 3-5.5mm THHN & 1-3.5mm
10. EXPOSE WIRING FOR LIGHTING AND CONVENIENCE OUTLETS SHALL BE IN RIGID STEEL CONDUIT (RSC) PIPE RUN PARALLEL TO BEAMS AND TRUSSES

11. MOUNTING HEIGHTS SHALL BE AS FOLLOWS: 3-14mm THHN & 1-5.5mm 3-5.5mm THHN & 1-3.5mm
a.) LIGHT CONTROL SWITCHES - 1.40m ABOVE FLOOR FIN.
3-14mm THHN & 1-5.5mm 3-5.5mm THHN & 1-3.5mm
b.) CONVENIENCE OUTLET - .30m ABOVE FLOOR FIN.

3-14mm THHN & 1-5.5mm 3-30mm THHN & 1-8.0mm


c.) TELEPHONE OUTLET - .30m ABOVE FLOOR FIN.
3-14mm THHN & 1-5.5mm 3-30mm THHN & 1-8.0mm
d.) PANEL BOARDS & CABINETS - 1.80m ABOVE FLOOR FIN.

e.) COUNTER TOP OUTLET - 0.15m ABOVE COUNTER TABLE

12. ALL FLUORESCENT LIGHTING FIXTURES SHALL BE PROVIDED WITH THE HIGH POWER FACTOR BALLAST WITH SPRING LOADED LAMP HOLDERS.
M
13. CONDUITS AND METAL FRAMES OF EQUIPMENT SHALL BE BOUNDED TOGETHER BY MEANS OF COPPER STRAPS. CONDUITS OF SYSTEM SHALL BE PROPERLY GROUNDED TO THE WATER M M M M M M
SUPPLY SERVICE PIPES WHENEVER POSSIBLE OR GROUND ROD INSTALLED FOR THE PURPOSE. GROUND ROD SHALL BE 20mm DIAMETER x 3000mm COPPER CLAD STEEL EMBEDDED TO M M DEEP WELL PUMP M M
THE GROUND WITH ITS TOP ACCESSIBLE FOR INSPECTION. COMPRESSOR TUBE ICE CUTTER SCREW CONVEYOR HEATER CONDENSER AHU
FAN BLOWER CONDENSER PUMP R.O. VERT. PUMP HEAD COVER PUMP
14. LIGHT CONTROL SWITCHES FOR SWITCH BANK SHALL BE RATED 15A, 300VAC APPELLATION SWITCH "B" SINGLE POLE WN 5061-801 NATIONAL.

15. UNDERGROUND RUN OF CONDUITS SHALL BE EMBEDDED AT LEAST 610mm (24") FROM FINISH GRADE LINE. CONCRETE ENVELOPES FOR CONDUITS RUN ACROSS OR CROSSING STREETS
AND DRIVEWAYS SHALL BE REINFORCED AND SHALL HAVE THE STRENGTH CAPABLE TO WITHSTAND THE STRESSES TO WHICH THESE SHALL BE SUBJECTED.
M M M M M M M M
16. ALL MATERIALS SHALL BE NEW AND APPROVED TYPE FOR THE LOCATION AND PURPOSE IN WHICH THEY ARE INTENDED TO BE INSTALLED.
CHILLED WATER PUMP SCREW CONVEYOR FAN BLOWER R.O. VERT. PUMP CHILLER COMPRESSOR CONDENSER AHU
17. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OF SERVICE ENTRANCE FOR CONNECTION TO THE POWER SUPPLY, AND ALSO THE ACTUAL LOCATION OF THE
FAN BLOWER
TELEPHONE SYSTEM SERVICE ENTRANCE TO THE LOCAL TELEPHONE CABLE FACILITIES.

18. FOR EACH SPARE BRANCH CIRCUIT OF PANEL BOARDS, PROVIDE 20mm (34") DIAMETER EMPTY CONDUIT TERMINATED TO 100mm x 100mm SQUARE BOX ABOVE THE CEILING.

19. ALL ELECTRICAL SHALL BE UNDER THE SUPERVISION OF AN EXPERIENCED DULY LICENSED ELECTRICAL ENGINEER.

4 SINGLE LINE DIAGRAM (460-V LINE)


E-4 E-4 SCALE : NTS

4 SHORT CIRCUIT ANALYSIS


SCALE : NTS
E-4 E-4

OBP
OSWALD B. PUZON PROPOSED TWO STOREY COMM'L BUILDING
AND WAREHOUSE SPS. MARTIN & MA. THERESA AGUIRRE AS SHOWN JECG
E-4