Setari generale ( pt.

intregul
Zona climatica III -18 Zona eoliana III in localitate

denumire / destinatie camera T inter. C 21


Supraf.
denumire Temp
h Supraf. de Rc H sol
element L Totala calcul
ext. a W
constructie peret.
l Lvitral. aprox. exact i fer./usi

perete 1 4.00 2.50 10.00 8.44 B -18 129.05 0.00


fereastra 1 1.30 1.20 1.56 6.20 T. Bun -18 94.91 0.050
fereastra 2 0.00 0.00 T. Bun -18 0.00 0.050
fereastra 3 0.00 0.00 T. Bun -18 0.00 0.050
usa 0.00 0.00 T. Bun -18 0.00 0.050

perete 3 2.50 0.00 0.00 B -18 0.00 0.00


fereastra 1 0.00 0.00 T. Bun -18 0.00 0.050
fereastra 2 0.00 0.00 T. Bun -18 0.00 0.050
usa 0.00 0.00 T. Bun -18 0.00 0.050

perete 5 2.50 0.00 0.00 B -18 0.00 0.00


fereastra 0.00 0.00 T. Bun -18 0.00 0.050
usa 0.00 0.00 T. Bun -18 0.00 0.050

perete 7 2.50 0.00 0.00 S 0.70 20 0.00


usa 0.00 0.00 G. Simplu 20 0.00 0.120
usa 0.00 0.00 G. Simplu 20 0.00 0.120

perete 9 2.50 0.00 0.00 S 0.70 20 0.00


usa 0.00 0.00 G. Simplu 20 0.00 0.120
usa 0.00 0.00 G. Simplu 20 0.00 0.120

perete 11 2.50 0.00 0.00 S 0.70 20 0.00


usa 0.00 0.00 G. Simplu 20 0.00 0.120

perete 13 2.50 0.00 0.00 S 0.70 20 0.00


usa 0.00 0.00 G. Simplu 20 0.00 0.120

podea 1 4.00 4.00 16.00 16.00 P7 20 vezi Qs 0.00


podea 2 0.00 P7 20 vezi Qs 0.00
podea 3 0.00 P7 20 vezi Qs 0.00
podea 4 0.00 P7 20 vezi Qs 0.00
podea 5 0.00 P7 20 vezi Qs 0.00

Aveti mai jos o serie de marimi si valorile lor, conform SR 1907, asa cum le utilizeaza si acest program. O parte provin din pag. Culise, o parte sint rezultat
cunostinte in domeniu isi pot adapta si mai bine calculele la experienta si nevoile lor, ca si in pagina Culise. Iar cei care se pricep mai putin, aveti grija ce d
rezultatul final, dupa care da

Punct Cardinal N-V AT 42.00 mediu 1.20


Ao 5.000 Ap 16.00 ms 0.50
Rm 4.06 Rp 3.70 ns 1.40
Ac Err:504 Abc 4.00 V 3/4 7.43
Adaosuri Err:504 R bc 0.77
Abcj 0.00
generale ( pt. intregul imobil ) :
in localitate 4.5 Adincimea pinzei de apa freatica 3.00 Coef. Etaj E 1.00

Necesar termic total W ### W/mc Err:504 W/mp

Supraf.
m elem. denumire Temp
h Supraf. de Rc
de element L Totala calcul
ext. a W
constr. constructie peret.
l Lvitral. aprox. exact

1.038 P perete 2 2.50 0.00 0.00 B -18 0.00


1.200 E fereastra 1 0.00 0.00 T. Bun -18 0.00
1.200 R fereastra 2 0.00 0.00 T. Bun -18 0.00
1.200 E fereastra 3 0.00 0.00 T. Bun -18 0.00
1.200 T usa 0.00 0.00 T. Bun -18 0.00
I
1.038 E perete 4 2.50 0.00 0.00 B -18 0.00
1.200 X fereastra 1 0.00 0.00 T. Bun -18 0.00
1.200 T fereastra 2 0.00 0.00 T. Bun -18 0.00
1.200 E usa 0.00 0.00 T. Bun -18 0.00
R
1.038 I perete 6 2.50 0.00 0.00 B -18 0.00
1.200 O fereastra 0.00 0.00 T. Bun -18 0.00
1.200 R usa 0.00 0.00 T. Bun -18 0.00

1.000 P perete 8 2.50 0.00 0.00 S 0.70 20 0.00


1.200 E usa 0.00 0.00 G. Simplu 20 0.00
1.200 R usa 0.00 0.00 G. Simplu 20 0.00
E
1.000 T perete 10 2.50 0.00 0.00 S 0.70 20 0.00
1.200 I usa 0.00 0.00 G. Simplu 20 0.00
1.200 I usa 0.00 0.00 G. Simplu 20 0.00
N
1.000 T perete 12 2.50 0.00 0.00 S 0.70 20 0.00
1.200 E usa 0.00 0.00 G. Simplu 20 0.00
R
1.000 I perete 14 2.50 0.00 0.00 S 0.70 20 0.00
1.200 O usa 0.00 0.00 G. Simplu 20 0.00
R

1.000 P tavan 1 4.00 4.00 16.00 16.00 T1 20 55.36


1.000 L tavan 2 0.00 0.00 0.00 0.00 T1 20 0.00
1.000 A tavan 3 0.00 0.00 0.00 0.00 T1 20 0.00
1.000 N tavan 4 0.00 0.00 0.00 0.00 T1 20 0.00
1.000 S tavan 5 0.00 0.00 0.00 0.00 T1 20 0.00
E fereastra 1 0.00 0.00 T. Bun -18 0.00
E fereastra 2 0.00 0.00 T. Bun -18 0.00

din pag. Culise, o parte sint rezultatul unor formule de calcul, iar o alta parte sint constante ce pot fi introduse de operator. Atentie sa nu stergeti din greseala vreo formula. C
e se pricep mai putin, aveti grija ce date introduceti aici ! Modificati DOAR daca : 1. sinteti sigur pe ceea ce faceti, sau 2. doriti doar sa vedeti cum afecteaza modificarea
rezultatul final, dupa care dati un "UNDO" = Ctrl+Z.

A usi ext. 0.00 Qi1 Err:504 V - volumul camerei


n-nr.desch. 0 Qi2 Err:504
Qu 0 L rosturi 6.20 QS
alege destinatia camerei: aer 1.20 QT
bai Cp 1,011 QT*adaosuri
nao 0.00028 QT*ad.+Qi
CM 1.00

Err:504

H sol m elem.
de
constr.
i fer./usi

0.00 1.038
0.050 1.200
0.050 1.200
0.050 1.200
0.050 1.200

0.00 1.038
0.050 1.200
0.050 1.200
0.050 1.200

0.00 1.038
0.050 1.200
0.050 1.200

1.000
0.120 1.200
0.120 1.200

1.000
0.120 1.200
0.120 1.200

1.000
0.120 1.200

1.000
0.120 1.200

16.00 1.038
1.038
1.038
1.038
1.038
0.050 1.200
0.050 1.200

sa nu stergeti din greseala vreo formula. Cei care au


doar sa vedeti cum afecteaza modificarea unei valori

V - volumul camerei 40.00

QS 124.44
QT 404
QT*adaosuri Err:504
QT*ad.+Qi Err:504
Modul de stabilire al gradului de izolatie al peretilor exteriori sau planseelor -- orientativ!

Grosime Grosime Grad


Material component Strat izolator
( cm ) ( cm ) izolare

caramizi cu goluri verticale 30 vata minerala 18 FB


Rezistenta termica corectata, reala ( R c ) = 3.9076

Pe cei cu adevarat interesati ii invit sa-si calculeze si mai exact rezistenta termica a peretilor sau a planseelor, cu
ajutorul tabelului din dreapta ( col. T-W). De asemenea, pt. cei care nu stiu, aveti si mai in dreapta o serie de
definitii ( K, R, ), precum si o serie de formule de calcul simplificate din acest domeniu. Nota : programul face
calculele pierderilor de caldura conform formulelor din SR 1907, care sint mult mai "stufoase" !

Tabel Definitii Formule

Pentru PODEA si TAVAN, s-a luat in calcul o placa de beton de 15 cm grosime


+ un eventual strat izolator de 5 sau 10 cm (vezi mai jos):

Pt . acest program, .
1. pe interior, in sapa, un strat de polistiren extrudat de 5 cm
PODEA izolata inseamna : grosime.

2. pe exterior, placare cu polistiren expandat de 5 cm, cu sau fara


gips-carton. Valabil daca sub camera aveti o alta incapere in care
aveti acces, si careia de fapt ii izolati tavanul ( beci la casa, sau
casa scarilor la bloc etc).

TAVAN izolat inseamna : 1. pe interior, sub tavan, un strat de polistiren expandat (sau vata
minerala) de 10 cm, cu sau fara gips-carton.

2. pe exterior, placare cu polistiren de 10 cm grosime. Valabil daca


deasupra camerei aveti o alta incapere in care aveti acces, si
careia de fapt ii izolati podeaua (pod la casa etc).

Evident, aceste valori ale grosimii stratului izolator reprezinta un minimum necesar.
Pt detalii, vezi tabelul din aceasta pagina, celulele AF27:AL47 !!!

Creat de Aurel Grama


Tip constructiv fereastra - orientativ. Uw

Geam ORICE geam ante-termopan, cu 2-3 sticle float, montate in 1-2 cercevele
simplu (fara gaz inert, fara LowE), tamplarie lemn. 3.70

Termopan cu 2 foi de sticla float, fara Argon, sau cu Argon pus acum minim 10 ani, prin supape),
vechi fara Low-E, pe lemn sau PVC 3-4 camere (60mm) sau AL simplu. 2.50

cu 2 foi de sticla (pachet 24 mm grosime), cu Low-E sau 4S si Argon, cu tamplarie AL


Termopan
economic
cu rupere punte termica, lemn stratificat (60 mm grosime) sau PVC cu 3-4 camere 1.70
(max. 65 mm grosime), cu 2 garnituri de etansare.

cu 3 foi de sticla (pachet maxim 38 mm grosime), cu LowE si Argon, pe lemn stratificat


Tripan
bun
(70 mm grosime), AL cu rupere punte termica sau PVC cu 5-6 camere (maxim 80 mm 1.30
grosime), cu doar 2 garnituri de etansare.

cu 3 foi de sticla (pachet minim 40 mm grosime), cu 2 foi LowE (sau 4S+LowE), cu


Tripan
premium
Argon, cu baghete de AL sau "calde" (din plastic), pe lemn stratificat (80 mm) sau PVC 1.00
cu 6-7 camere (minim 80 mm grosime), cu 3 garnituri de etansare.

cu 3 foi de sticla (minim 44 mm), cu 2 foi LowE (sau 4S+LowE), cu Kripton, cu baghete
Tripan casa
pasiva
calde (nu din AL), pe lemn stratificat (90 mm) sau PVC cu 6-7 camere (minim 80 mm), 0.80
cu 3 garnituri, si (eventual) cu module termice in profile.
Calculul exact al rezistentei termice teoretice / reale (corec
R unui perete sau planseu, in functie de straturile care il c

0.270
Material component
0.400
aer interior
tencuial var
0.588 plci de ipsos 1100 kg/m3
EPS grafitat (AF Plus; Dalmatina)
Caramida termoeficienta cu goluri verticale Porotherm STH30
lemn pin i brad n lungul fibrelor
0.769

vat mineral tip 70


tencuial var-ciment
1.000 vat mineral tip 70
mortar ciment
aer exterior
1.250

coeficient punti term


rezistenta termica corec
nivelul gradului de izo

Exemplu de calcul al pierderilor de caldura care au loc printr-un perete (sau mai mult
W28) ca cel setat mai sus, si corespondentul acestora in W/m cub si W/m patrat, p
dimensiunile si ferestrele de mai jos :

( datele scrise cu rosu pot fi modificate de utilizator )


Lungimea camerei

Latimea camerei
Inaltimea camerei
Suprafata camerei
Volumul camerei
Suprafata peretilor exteriori, cu tot cu ferestre / usi
Suprafata totala a ferestrelor / usilor spre exterior
Coeficientul de transfer termic ( K ) al ferestrelor / usilor spre exterior
Temperatura interioara
Temperatura exterioara
Pierderile de caldura prin peretii propriu-zisi (doar prin zidarie)
Pierderile de caldura prin ferestrele / usile spre exterior
Pierderea TOTALA de caldura :

Pierderea de caldura raportata la volumul camerei


Pierderea de caldura raportata la suprafata camerei

Formula simplificata de calcul a pierderilor de caldura printr-un perete cu / fara geam este

Q = [ 1 / ( R perete din calcul tabel * coeficient punti termice ) ] * (suprafata perete - supraf
geam) * ( T interioara - T exterioara ) + K geam * suprafata geam * ( T interioara - T exterio

Daca intilniti materiale de constructie care nu apar in tabel,


le puteti scrie mai jos, astfel incit sa le puteti folosi la calcul:

Denumire, tip, caracteristici, producator


1 EPS grafitat (AF Plus; Dalmatina)
2 Panouri PUZ
3 C
4 D
5 E
6 F
7 G
8 H
9 I
10 J
etice / reale (corectate) a X

straturile care il compun:

d R = d/
cm ! W/mK m2K/W
0.00 8.000 0.1250
0.00 0.700 0.0000
0.00 0.410 0.0000
0.00 0.033 0.0000
30.00 0.155 1.9342
0.00 0.350 0.0000

20.00 0.045 4.4444

0.00 0.870 0.0000


0.00 0.045 0.0000
0.00 0.930 0.0000
--- 24.000 0.0420
50.00 6.5457
coeficient punti termice : 0.75
rezistenta termica corectata : 4.9093
nivelul gradului de izolare : col. H/T

-un perete (sau mai multi, vezi cel. W27 -


W/m cub si W/m patrat, pt. o camera cu
mai jos :

pereti ext.
4.00 m 2.00

4.00 m 2.00
2.50 m
16.00 mp
40.00 mc
40.00 mp
3.00 mp
Procent din
total pierderi
de caldura :
1.50 W/mpK Procent din
total pierderi
22 C de caldura :
-2 C
180.88 W 63%
108.00 W 37%
288.88 W
7.22 W / mc
18.06 W / mp

perete cu / fara geam este :

vezi si Formule
(suprafata perete - suprafata
* ( T interioara - T exterioara )


0.033
0.024
0.5
0.7
0.9

1.1
1.3
1.5

1.7
1.9
lambda
MATERIAL
W/mK

aer interior 8.000


aer interior - transfer de sus n jos 6.000
aer exterior 24.000
nimic 100.000
1 strat c.asf / 1 strat de bitum 100.000
2 straturi c.asf / 2 strat de bitum 100.000
2 straturi c.asf +1 strat panza asf. intre 4 str bitum 100.000
2 straturi c.asf intre 3 str de bitum 100.000

aluminiu 220.400
BCA tip GBN 35 - fii armate 0.229 0.208
BCA tip GBN 50 - fii armate 0.256 0.233
BCA Macon 0.121 0.110
BCA Prefab GBN 25 0.146 0.133
BCA Prefab GBN 35 0.174 0.158
BCA Prefabricate Vest - Verblok 0.128 0.116
BCA Soceram 0.146 0.133
BCA tip GBN 35 - zidrie cu rosturi obinuite 0.275 0.250
BCA tip GBN 35 - zidrie cu rosturi subiri 0.248 0.225
BCA tip GBN 50 - zidrie cu rosturi obinuite 0.311 0.283
BCA Ytong 0.110 0.100
BCU - zidrie blocuri mici pline din beton uor 1000 kg/m3 0.420
BCU - zidrie blocuri mici pline din beton uor 1200 kg/m3 0.500
BCU - zidrie blocuri mici pline din beton uor 1400 kg/m3 0.610

BCU - zidrie blocuri mici pline din beton uor 1600 kg/m3 0.750
BCU - zidrie blocuri mici pline din beton uor 1800 kg/m3 0.930
BCU - zidrie blocuri mici pline din beton uor 2000 kg/m3 1.160
beton armat 2400 kg/m3 1.620
beton armat 2500 kg/m3 1.740
beton armat 2600 kg/m3 2.030
beton asfaltic 1.040
beton cu granulit 400 kg/m3 0.170
beton cu granulit 600 kg/m3 0.230
beton cu granulit 800 kg/m3 0.290
beton cu granulit 1000 kg/m3 0.350
beton cu granulit 1600 kg/m3 0.700
beton cu granulit 1700 kg/m3 0.760
beton cu granulit 1800 kg/m3 0.810
beton cu perlit 600 kg/m3 0.170
beton cu perlit 800 kg/m3 0.260
beton cu perlit 1000 kg/m3 0.330
beton cu perlit 1200 kg/m3 0.410
beton cu zgura de cazan 1000 kg/m3 0.410
beton cu zgura de cazan 1200 kg/m3 0.520
beton cu zgura de cazan 1400 kg/m3 0.640
beton cu zgura de cazan 1600 kg/m3 0.750
beton cu zgura de cazan 1800 kg/m3 0.870
beton cu zgura expandata 1200 kg/m3 0.410
beton cu zgura expandata 1400 kg/m3 0.460
beton cu zgura expandata 1600 kg/m3 0.580
beton cu zgura granulata 1200 kg/m3 0.460
beton cu zgura granulata 1400 kg/m3 0.520
beton cu zgura granulata 1600 kg/m3 0.580
beton cu zgura granulata 1800 kg/m3 0.640
beton simplu cu agregate naturale 1000 kg/m3 0.370
beton simplu cu agregate naturale 1200 kg/m3 0.460
beton simplu cu agregate naturale 1400 kg/m3 0.580
beton simplu cu agregate naturale 1600 kg/m3 0.750
beton simplu cu agregate naturale 1800 kg/m3 0.930
beton simplu cu agregate naturale 2000 kg/m3 1.160
beton simplu cu agregate naturale 2200 kg/m3 1.390
beton simplu cu agregate naturale 2400 kg/m3 1.620
bitum 0.170
Caramida termoeficienta cu goluri verticale Brikston BKS 20 0.336 0.305
Caramida termoeficienta cu goluri verticale Brikston BKS 25 0.234 0.213
Caramida termoeficienta cu goluri verticale Brikston BKSs 30 0.239 0.217
Caramida termoeficienta cu goluri verticale Brikston GV290,138 0.267 0.242
Caramida termoeficienta cu goluri verticale Brikston GV 365,188 0.238 0.216
Caramida termoeficienta cu goluri verticale Porotherm PTH 45 0.561 0.510
Caramida termoeficienta cu goluri verticale Porotherm PTH 60 0.561 0.510
Caramida termoeficienta cu goluri verticale Porotherm S 0.186 0.169
Caramida termoeficienta cu goluri verticale Porotherm STH30 0.155 0.141
Caramida termoeficienta cu goluri verticale Porotherm STH38 0.155 0.141
Caramida termoeficienta cu goluri verticale Porotherm20 N+F 0.363 0.330
Caramida termoeficienta cu goluri verticale Porotherm25 0.209 0.190
Caramida termoeficienta cu goluri verticale Porotherm25 Light 0.347 0.315
Caramida termoeficienta cu goluri verticale Porotherm30 0.208 0.189
Caramida termoeficienta cu goluri verticale Porotherm30 Light 0.259 0.235
Caramida termoeficienta cu goluri verticale Porotherm38 0.175 0.159
Caramida termoeficienta cu goluri verticale Prefab 0.482 0.438
Caramida termoeficienta cu goluri verticale Siceram Termobloc T 38 Et 0.383 0.348
Caramida termoeficienta cu goluri verticale Siceram Termobloc T 30 Et 0.449 0.408
Caramida termoeficienta cu goluri verticale Soceram Durotherm 0.297 0.270
Caramida termoeficienta cu goluri verticale Soceram Durotherm 0.257 0.234
caramida plin Brikstone CP 0.435
crmizi pline - zidrie din crmizi pline vechi 0.800
cenusa si zgura de termocentrala 650 kg/m3 0.290
covor pvc cu suport textil 1 0.290
covor pvc cu suport textil 2 0.230
covor pvc fr suport textil 1 0.380
covor pvc fr suport textil 2 0.330
diatomit 0.220
email alchidic in 2 straturi 100.000
email clorcauciuc 100.000
email copolimervinilic 100.000
folie aluminiu lipita 0.05 mm 220.000
folie aluminiu lipita 0.1 mm 220.000
folie aluminiu lipita 0.2 mm 220.000
folie polietilena 0.2 mm 100.000
folie pvc 100.000
gresie i cuarite 2.030
ipsos celular 500 kg/m3 0.180
lemn pin i brad n lungul fibrelor 0.350
lemn pin i brad perpendicular pe fibre 0.170
lemn stejar i fag perpendicular pe fibre 0.230
marmur, granit, bazalt 3.480
mortar asfaltic 0.750
mortar ciment 0.930
mortar var 0.700
mortar var-ciment 0.870
oel de construcii 58.000
PAL - plci omogene cu goluri 450 kg/m3 0.156
PAL - plci omogene cu goluri 500 kg/m3 0.168
PAL - plci omogene pline 600 kg/m3 0.216
PAL - plci tip PAL 650 kg/m3 0.204
PAL - plci tip PAL 350 kg/m3 0.101
PAL - plci tip PAL stratificate 700 kg/m3 0.264
PAL - plci tip PAL termoizolante 550 kg/m3 0.180
pmnt ntre la cota -3,00 i cota -7,00 4.000
pmnt pn la cota -3,00 m 2.000
pmnt vegetal n stare umed 1.160
pnz bitumat, carton bitumat etc. 0.170
psl mineral tip P40 0.043
psl mineral tip P60 0.040
psl mineral tip P90 0.040
perlit 0.085
PFL moale - plci B i BA 0.094
PFL moale - plci S 0.084
piese de font 49.880
pietre calcaroase 1 1.160
pietre calcaroase 2 0.930
placaj ncleiat 0.170
placi aglomerate din puzderie tip PAP 300 kg/m3 0.101
placi termoizolante din coaja de rasinoase tip IZOTER 350 kg/m3 0.125
placi termoizolante din coaja de rasinoase tip PACOSIP 750 kg/m3 0.216
placi termoizolante din perlit liate cu ciment 270 kg/m3 0.160
placi termoizolante din talas 0.140
plci aglomerate fibrolemnoase tip PAF 0.084
plci de ipsos 1000 kg/m3 0.370
plci de ipsos 1100 kg/m3 0.410
plci de ipsos cu umplutura organica 700 kg/m3 0.230
plci rigide din fibre de bazalt tip PB160 0.050
polistiren expandat EPS 120 0.038
polistiren expandat EPS 200 0.035
polistiren expandat EPS 50 0.045
polistiren expandat EPS 70 0.042
polistiren expandat EPS 80 - pt. fatade 0.040
polistiren expandat grafitat - pt. fatade 0.033
polistiren extrudat XPS 0.033
poliuretan celular 0.042
rumegu 0.090
scorie bazaltic 0.260
spume de pvc 0.050
sticl 0.750
sticl spongioas 140 kg/m3 0.075
sticl spongioas 300 kg/m3 0.120
sticl spongioas 400 kg/m3 0.140
strat de bitum aplicat la cald cu peria 100.000
strat de carton asfaltat 100.000
strat de mastic de bitum aplicat la cald in 2 straturi 100.000
stufit presat 0.110
tencuial din ciment 0.930
tencuial var 0.700
tencuial var-ciment 0.870
tuf calcaros 0.520
umplutur din nisip 0.580
umplutur din pietri 0.700
vat de sticl - cal. I 80 kg/m3 0.036
vat de sticl - cal. II 100 kg/m3 0.041
vat mineral saltele - tip SCI 60, SCO 60, SPS 60 0.040
vat mineral saltele - tip SPS 70 0.045
vat mineral tip 60 0.042
vat mineral tip 70 0.045
vat mineral tip AP140 - plci 0.044
vat mineral tip G100 - plci 0.048
vat mineral tip G140 - plci 0.040
vopsea de ulei in doua straturi 100.000
zgura de cazan 1000 kg/m3 0.350
zgura de cazan 700 kg/m3 0.260
zgura expandata 500 kg/m3 0.190
zgura expandata 900 kg/m3 0.310
zgura granulata 1100 kg/m3 0.360
zidrie din crmizi cu guri verticale 1200 kg/m3 0.580
zidrie din crmizi cu guri verticale 1325 kg/m3 0.640
zidrie din crmizi cu guri verticale 1475 kg/m3 0.700
zidrie din crmizi cu guri verticale 950 kg/m3 0.460
zidrie din crmizi cu guri verticale tip GVP 1675 kg/m3 0.750
zidrie din crmizi de diatomit 1000 kg/m3 0.520
zidrie din pietre de form regulat 1200 kg/m3 0.510
zidrie din pietre de form regulat 2000 kg/m3 1.130
zidrie din pietre de form regulat 2800 kg/m3 3.190
zidrie din pietre neregulate 1200 kg/m3 0.600
zidrie din pietre neregulate 2000 kg/m3 1.060
zidrie din pietre neregulate 2800 kg/m3 2.550
EPS grafitat (AF Plus; Dalmatina) 0.033
Panouri PUZ 0.024
C 0.5
D 0.7
E 0.9
F 1.1
G 1.3
H 1.5
I 1.7
J 1.9

Material lambda
beton simplu / armat 1.700
BCA 0.250
caramizi cu goluri verticale 0.350
caramizi pline 0.800
lemn 0.300
polistiren 0.044
vata minerala 0.043
DEFINITII de BAZA:
Capacitatea de izolare termica a unui element de constructie (de ex. perete exterior, acoperis, pardoseala, etc.) este exprim
termic ( notata si U ).

K = coeficientul de tranfer termic : reprezinta cantitatea de caldura exprimata in Wh (watti ora) transmisa printr-un mp
diferenta de 1 grad C intre interior si exterior.

Nivelul de conductivitate termica a unui material este exprimat prin = coeficient de cond

= (coeficientul de) conductivitate termica a unui material : reprezinta cantitatea de caldura exprimata in Wh care trece
grosime de 1 m, in timp de o ora, la o diferenta de 1 grad C intre cele 2 suprafete ale m

efectiva = valoarea teoretica a conductivitatii termice a unui material; se calculeaza in laborator de catre producatorii
materialul in stare perfect uscata; de obicei este valoarea care apare pe eticheta produ

calcul = valoarea reala, folosita in calcule, a conductivitatii termice a unui material; este mai mare decit efectiva
normale de exploatare ale materialelor.

Capacitatea unui element de constructie de a se opune transferului de caldura prin masa lui este exprimata de R = rezi
materialului respectiv, si este inversul lui K . Depinde de grosimea materialului analizat. Cu ajutorul lui se pot compara prop
elemente de constructie eterogene cu grosimi diferite si cu conductivitati termice d

R c (notata si R' ) = rezistenta termica corectata, reala, a materialului respectiv = rezistenta termica teoretica
termice.

n prezent, valorile propuse in constructii, ale gradului de protecie termic Rc , pt. asigurarea unui confort term
termica prin pierderile de caldura sunt mrite mai mult, conform C107/1 mo

REZISTENTA TERMICA CORECTATA MINIMA Rc (min) pt elementele de constructie ale une


cladiri de locuit:
REZISTENTA TERMICA CORECTATA MINIMA Rc (min) pt elementele de constructie ale une
cladiri de locuit:

Nr. Elementul de constructie

1. Pereti exteriori (exclusiv suprafetele vitrate, inclusiv peretii adiacenti rosturilor deschise)

2. Tamplarie exterioara
3 Plansee peste ultimul nivel, sub terase sau poduri
4. Plansee peste subsoluri neincalzite si pivnite
5. Pereti adiacenti rosturilor inchise

6. Plansee care delimiteaza cladirea la partea inferioara, de exterior (la bowindouri, ganguri de trecere etc.)

7. Placi pe sol (peste CTS)


8. Placi la partea inferioara a demisolurilor sau a subsolurilor incalzite (sub CTS)
9. Pereti exteriori, sub CTS, la demisolurile sau la subsolurile incalzite

Punti termice = zona / zone in structura (compozitia) unui element de constructie care "strica" om
termica mai mare, respectiv o rezistenta termica mai mica decit restul elementulu

Exemple de situatii in care exista punti termice la peretii exteriori :

1* buiandrug din beton la ferestre sau usi, la un zid confectionat din materiale de constructie cu o mai buna rezistenta termica
2* rosturi mai mari intre caramizi, sau "umplute" neglijent cu mortar: cu goluri etc.

3* perete / zone de perete realizate din resturi ( bucati de BCA, caramida etc.), deci cu rosturi mai dese si mai mari dec

4* izolatie termica realizata neglijent. Ex.: placi de polistiren intre care exista spatii pe lateral; zone de vata minerala "turtita";
circula aerul de la o placa la alta etc.

5* finisari neglijente ale izolatiei termice in diferite zone : la ferestre, usi, colturi de zid etc

6* materiale de constructie (BCA, caramizi, vata etc) depozitate si / sau folosite mult timp in conditii improprii (mai ale
proprietatile termoizolante.
7* izolatie proasta a usilor / ferestrelor in faza de montare : spuma poliuretanica (prea) putina sau prost / neglijent amplasa
8* stilpii de sustinere din beton neizolati termic de la colturile cladirii.

9* caramizi cu goluri verticale ... amplasate orizontal, pe directia interior - exterior ( caz "penal" - vezi poza de la artic

10* ETC.
or, acoperis, pardoseala, etc.) este exprimata de valoarea K = coeficient de transfer
notata si U ).

in Wh (watti ora) transmisa printr-un mp de element de constructie timp de o ora la o


intre interior si exterior.

te exprimat prin = coeficient de conductivitate termica.

a de caldura exprimata in Wh care trece printr-o suprafata de 1mp, a unui material cu o


de 1 grad C intre cele 2 suprafete ale materialului.

uleaza in laborator de catre producatorii de materiale de constructii, la 10 grade C si cu


e valoarea care apare pe eticheta produsului finit.

material; este mai mare decit efectiva si tine cont de umiditatea naturala in conditiile
atare ale materialelor.

n masa lui este exprimata de R = rezistenta termica ( sau rezistivitatea termica ) a


izat. Cu ajutorul lui se pot compara proprietatile termoizolatoare ale unor materiale sau
simi diferite si cu conductivitati termice diferite.

espectiv = rezistenta termica teoretica (din tabele) x coeficientul datorat puntilor


mice.

Rc , pt. asigurarea unui confort termic sporit si pt. reducerea risipei de energie
mrite mai mult, conform C107/1 modificat:

dupa inainte de
1 dupa
elementele de constructie ale unei 1
1 ianuarie
ianuarie ianuarie
1998
2011 1998
dupa inainte de
dupa
1 1
1 ianuarie
ianuarie ianuarie
1998
2011 1998

Rc(minim) Rc(minim) Rc(minim)


[m2K/W] [m2K/W] [m2K/W]

hise) 1.80 1.40 1.20

0.77 0.50 0.40


5.00 3.00 2.00
2.90 1.65 1.10
1.10 1.10 0.90

anguri de trecere etc.) 4.50 4.50 3.00

4.50 4.50 3.00


4.80 4.80 4.20
2.90 2.40 2.00

t de constructie care "strica" omogenitatea lui, avind o conductivitate


mai mica decit restul elementului de constructie dat.

structie cu o mai buna rezistenta termica decit betonul (din BCA, de exemplu)

deci cu rosturi mai dese si mai mari decit in cazul bucatilor "standard".

lateral; zone de vata minerala "turtita"; placi de polistiren pe sub care poate
aca la alta etc.

zone : la ferestre, usi, colturi de zid etc.

mult timp in conditii improprii (mai ales umezeala), ceea ce le altereaza


oizolante.
rea) putina sau prost / neglijent amplasata (strat prea subtire, cu goluri etc)

terior ( caz "penal" - vezi poza de la articolul "Asa NU" de pe blog !)


FORMULE simplificate :

Q = K x S x T C
fluxul termic = Tint. - Text.
coeficientul suprafata
(W) de transfer perete diferenta de
termic ( m2 ) temp. :
interior
minus
exterior

1 R d
K = ; teoreti =
c
Rc ca
coeficientul inversul rezistenta d = grosime
de transfer rezistentei termica material
termic termice teoretica
corectate, c = conductivitate
reale termica de calcul,
reala

R
( R1 + R2 + +Rn ) +
teoreti =
0,167
ca
R1, R2, Rn = rezistenta termica a stratului
rezistenta 1, 2, n din care e alcatuit peretele
termica totala
a peretelui,
teoretica 0,167 = rezistenta termica insumata a straturilor de
aer de pe cele 2 suprafate ale peretelui.

R
Rc = teoret x
ica
coeficient de corectie
rezistenta calculat cu
termica datorat prezentei
valorile eventualelor punti
corectata, din tabele
reala, a termice
peretelui

n n
T T
t1/t2 t1/t2
q t1 / t2 = q 75/65 x f =
T T
75/65 75/65

caldura degajata caldura degajata


de un radiator la de un radiator la n = exponent termic, dat de
temperaturile de temperaturile de producatorii de radiatoare, care
tur / retur t1 / t2 si tur / retur 75 / 65 difera, pt. fiecare model de radiator, f = un factor de corectie. Unii
cu inaltimea lui. Are valori cuprinse producatori de radiatoare ofera
la o oarecare si la o oarecare
intre 1,1 si 1,5 , insa poate fi tabele cu valorile lui f, in
temp. t interior temp. t interior functie de temp. de tur /retur
aproximat linistit la valoarea de 1,30.
/interior, si cu valori ale lui n
calculate de ei.

unde :
T t1 + t2
-
= t interior
t1/t2 2

Exemple :
T 75 + 65
-
= 20 = 50
75/65 2

T 50 + 40
-
= 20 = 25
50/40 2

T 90 + 70
-
= 20 = 60
90/70 2

1.3 1.3
25
f 50/40 =
50
= 0.5 = 0.4061

Deci un radiator, care la temp. de tur / retur de 75 / 65 si la o temp. a


camerei t interior de 20 C, degaja 1000 W, atunci la temp. de tur / retur
de 50 / 40 si la o temp. a camerei t interior tot de 20 C, va degaja doar
406 W, adica aprox. 40 %. De aceea, in acest caz, trebuie ales un radiator
cu o dimensiune mult mai mare, care la 75/65 sa ofere (1000 / 0,4061) =
2,463 W, iar la 50 / 40 tot acei 1000 W initiali, necesari camerei.
Deci un radiator, care la temp. de tur / retur de 75 / 65 si la o temp. a
camerei t interior de 20 C, degaja 1000 W, atunci la temp. de tur / retur
de 50 / 40 si la o temp. a camerei t interior tot de 20 C, va degaja doar
406 W, adica aprox. 40 %. De aceea, in acest caz, trebuie ales un radiator
cu o dimensiune mult mai mare, care la 75/65 sa ofere (1000 / 0,4061) =
2,463 W, iar la 50 / 40 tot acei 1000 W initiali, necesari camerei.
M-am hotarit sa dau o tenta de "open source" acestui program, prezentind modul de calcul si oferind
care se pricepe sa modifice anumite date utilizate de "program", pt. obtinerea unor rezultate adaptate expe
- valorile scrise cu rosu pot fi modificate ! -

1. Date referitoare la izolatia peretilor exteriori si interiori, a tavanului si podelei, precum si a suprafetelor vitrate : valorile re
clasificarea gradului de izolatie a peretilor exteriori, a tavanului, a podelei si a suprafetelor vitrate, precum si valorile de c
calcularea pierderilor de caldura. Pt. geamuri, valorile coeficientul de infiltratie " i ".
0.6 1 1.5 2.1 2.7 3.4 10
clasificarea gradului de izolare : FS S S-M M M-B B FB
valorile rezist. termice minim 0.30 0.71 1.11 1.61 2.31 3.21 4.51
( R ) pt. fiecare nivel : maxim 0.70 1.10 1.60 2.30 3.20 4.50 10.00
valoarea de calcul a rezistentei 0.33 0.78 1.22 1.77 2.54 3.53 4.96
termice ( R c ) pt. peretii exteriori : 0.25 0.59 0.92 1.33 1.91 2.65 3.72

Pt. peretii interiori am folosit o valoare de calcul a rezistentei termice corectate Rc de :

valoarea de calcul a rezistentei T1 T2 T3 T4 T5 T6 T7


termice ( R c ) pt. TAVAN : 0.30 0.30 2.10 0.30 2.10 0.30 2.10

valoarea de calcul a rezistentei P1 P2 P3 P4 P5 P6 P7


termice ( R c ) pt. PODEA : 0.30 0.30 1.20 0.30 1.20 0.40 1.20

tip fereastra G. Simplu T. Vechi T. Economic T. Bun T. Premium


coeficienti K 3.70 2.50 1.70 1.30 1.00
coeficienti R 0.27 0.40 0.59 0.77 1.00
coeficienti i 0.120 0.080 0.060 0.050 0.045

2. Adaosul pt. orientarea camerei : un procent cu care se mareste sau se micsoreaza QT = fluxul termic prin transmisie, al in

Punct Cardinal Nord Sud Est Vest N-E N-V S-E S-V
coeficienti * 5.00 -5.00 0.00 0.00 5.00 5.00 -5.00 -5.00

3. Temperaturile exterioare de calcul pt. tavan cu pod sau fara, izolat sau neizolat, si pt. podea cu beci, in functie de zona cl

Tavan : valoarea temp. T1 T2 T3 T4 T5 T6 T7 Zona climatic


exterioare de calcul C : 20 -13 -13 -7 -7 -18 -18 I
-12
Podea : valoarea temp. P1 P2 P3 P4 P5 P6 P7 -8
exterioare de calcul C : 20 9 9 -18 -18 9 9 11

In cazul unui acoperis izolat termic al podului, temp. de calcul creste, fata de temp. din tabelul de mai sus, cu :
4. Valorile Ac = adaosul pt. compensarea efectului suprafetelor reci, in functie de Rm = rezistenta termica medie a incaperii

Rm 0.60 0.70 0.80 1.00 1.20 1.40 1.60 1.80 2.00 2.30 2.60 3.00
Ac 16.20 14.25 12.30 11.00 9.70 8.90 8.35 7.75 7.45 7.00 6.60 6.40

Daca valoarea calculata a Rm difera de valorile de mai sus, se va alege Ac care corespunde valorii imediat inferioare a
0,9, se va alege valoarea de la 0,8 ( adica Ac = 12,30 ), iar daca Rm este 4,5, atunci se va alege Ac = 5,75, corespun

5. Viteza de calcul a vintului, in functie de zona eoliana a cladirii si de amplasamentul acesteia, in localitate sau inafara loca

Zona in localitate inafara localitatii Acestea sint valabile pt. nivelurile 1 - 12 ale cladirilor, si pina la altitud
eoliana v v v v
I 8.0 16.00 10.0 21.54
II 5.0 8.55 7.0 13.39
III 4.5 7.45 6.0 10.90
IV 4.0 6.35 4.0 6.35

6. Rezistenta termica specifica a benzii de contur, Rbc, pt. o grosime a fundatiei de 45 cm, in functie de adincimea de ingro
adincimea pinzei de apa freatica ( H ). Folosita la calcularea Qs = pierderile de caldura prin so

H(m)
h (m) 4 6 8 10 <-- valori SR
0 - 4,5 4,5 - 7 7 - 9 9 - 10 <-- valori program
0.0 0.768 0.645 0.574 0.530 0 - 0,5
1.0 0.490 0.430 0.398 0.377 0,5-1,5
2.0 0.448 0.380 0.347 0.327 1,5 -
^ valori SR

7. Valorile recomandate pt. nao = numarul de schimburi de aer necesar in incapere in conditii de confort fiziologic :

destinatia incaperii nao (m3/s)/m3 nao (m3/h)/m3


camere de locuit 0.00022 0.792
bucatarii 0.00033 1.190
bai 0.00028 1.000
scoli, crese, spitale nao*Vol. = 0,007*Nr. Persoane

8. Valorile unor constante, utilizate de program :

Notare CM E m podea m per. ext. m tavan m geam


Valoare 1.00 1.000 1.000 1.038 1.038 1.200

9. "Factorul de supradimensionare" = o nascocire pur personala, fara nici o legatura cu vreun STAS, adresata celor care NU
supradimensioneze radiatoarele si care, oricit de precis ar face calculele, se tot intreaba "N-o fi prea putin ?" :) . Reprezin
marirea necesarului termic al fiecarei camere, fata de valoarea rezultata din calcule facute de acest program.
"Factorul de supradimensionare" = o nascocire pur personala, fara nici o legatura cu vreun STAS, adresata celor care NU
supradimensioneze radiatoarele si care, oricit de precis ar face calculele, se tot intreaba "N-o fi prea putin ?" :) . Reprezin
marirea necesarului termic al fiecarei camere, fata de valoarea rezultata din calcule facute de acest program.

Bineinteles, valoarea implicita este zero, insa o puteti modifica aici :

10. O harta a Romaniei, cu impartirea RECENTA pe zone CLIMATICE :

- 12 C - 15 C - 18 C - 21 C
cu maro = zona I cu galben = zona II cu verde = zona III cu bleu = zona IV

11. De asemenea, o harta cu impartirea Romaniei pe zone EOLIENE :


modul de calcul si oferind posibilitatea utilizatorului
unor rezultate adaptate experientei si preferintelor sale.

suprafetelor vitrate : valorile rezistentei termice dupa care se face


vitrate, precum si valorile de calcul pt. fiecare treapta, folosite pt.
coeficientul de infiltratie " i ".
valorile vechi de pe randul 12
Pt. peretii exteriori

- valorile scrise cu rosu pot fi modificate.


--> valoarea propusa (din tabel) pt. calculul rezistentei termice, pt. fiecare nivel.
--> valoarea de calcul corectata, REALA, obtinuta astfel : valoarea
propusa mai sus x coeficientul de mai jos:
0.700
Coeficientul general care ia in calcul
existenta puntilor termice din pereti;
scade valoarea reala a rezistentei
termice calculate.
0.75

T.C. Pasiva
0.80
1.25
0.040 clasificarea gradului de izolare :
valoarea de calcul a rezistentei
termice ( R c ) pt. peretii exteriori :
xul termic prin transmisie, al intregii camere.

cu beci, in functie de zona climatica setata :

Zona climatica setata


II III IV V
-15 -18 -21 -25 Temp. ext. aferenta zonei
-11 -13 -16 -20 Temp. in pod neizolat
10 9 8 7 Temp. sol/beci NEincalzit

ul de mai sus, cu : 6 grade C.


ta termica medie a incaperii = CM*AT*(tint-text) / QT

3.50 4.00 5.00 6.00 8.00 10.00


6.00 5.75 5.50 5.25 5.00 4.80

de valorii imediat inferioare a Rm. De ex., daca Rm este


va alege Ac = 5,75, corespunzatoare lui Rm = 4,00.

in localitate sau inafara localitatii :

ale cladirilor, si pina la altitudinea de 1.100 m.

unctie de adincimea de ingropare a pardoselii ( h ) si de


= pierderile de caldura prin sol.

e confort fiziologic :

m per. int.
1.000

STAS, adresata celor care NU se pot abtine sa nu


o fi prea putin ?" :) . Reprezinta procentul ( % ) cu care se doreste
e acest program.
%

- 25 C
cu albastru inchis= zona V
FS S S-M M M-B B FB
0.25 0.59 0.92 1.33 1.91 2.65 3.72