Design Data:

Design standard : NFPA-15 / EUS Specification


Type of system : Deluge water spray system
Design density of discharge : 10.2 Lpm/m2 for Transformer body &
6.1 Lpm/m2 for non absorbing ground surface area
Reference drawings:

Transformer Details :
Length : 6.4 m
Width : 4.3 m
Height : 5.3 m
Theoretical Water Demand Calculations for ICT Transformer

A. Transformer absorbing surface are ( side and top) = 140.94 m square


B. Transformer non absorbing surface ( ground) = 27.52 m square
C. Water required for absorbing area = 140.94 * 10.2 = 1437.588 lpm
D. Water required for non absorbing area = 27.52 * 6.1 = 167.872 lpm
E. Total water required = 1437.588 + 167.872 =
1605.46 lpm
Actual water required based on hydraulic calculation =

Dimensions of the Transformer body


LENGTH (M) Width (M) Height (M)
6.4 4.3 5.3
a Surface area of top surface (L x W) x 1 27.52
b Surface area of front & back surface (L 67.84
x H) x 2

c Surface area of side-1 & side-2 surface 45.58


(W x H)X 2
d Total protected area (a + b + c) 140.94
e Design density as per NFPA-15 10.2 10.2
Absorbing area
Design density as per NFPA-15 10.2
Non Absorbing area
f Water requirement (d x e) 1437.588