You are on page 1of 13

Product Support Bulletin

Issue Date:
Service December 27, 2015
Global Lit Num: CPGC - S - 00000009 - 1

Revision: 1

Revision Date:

Title: Update the feature code of C250D5,C220D5,C225D6 with PC1.2 System.

Model(s) C250D5(PMG), C250D5(shunt), C220D5(PMG), C220D5(shunt),C225D6(PMG),


C225D6(shunt) built in
CPGC (China).
Please find a list of affected GSNs and ESNs attached.

Background/Description:
This is revised version of the PSB CPGC-S-00000009

Corrective Actions:

1. Below procedures are designated for C250 D5(PMG)

1.1 Open InPower and connect to PCC1302, update the feature code as below list.
Go to Device ->Update Features.

2015 Cummins Power Generation, Inc. All rights reserved


Page 1 of 13
1.2 Following the feature code updated above, below parameters need to be modified:

1.2.1 Go to Adjustments -> Alternator Protection, modify below parameters:

Parameter Name Value units

Overfrequency Threshold 10 Hz

Underfrequency Threshold 10 Hz

1.2.2 Go to Adjustments->Adjustments -> Engine Protection, Adjustments, modify below


parameters:

Parameter Name Value units

Overspeed Shutdown Threshold 50Hz 1875 rpm

LCL Response Type shutdown

LOP Shutdown Threshold 25 Psig

LOP Warning Threshold 30 Psig

1.2.3 Go to Adjustments->Adjustments -> Governor->Gain, modify below parameters:

2015 Cummins Power Generation, Inc. All rights reserved


Page 2 of 13
Parameter Name Value units

Governor Damping Effect (50Hz) 0.95

1.2.4 Go to Adjustments->Adjustments -> Governor-> Startup, modify below parameters:

Parameter Name Value units

Initial Crank Fueling Command 50 %

Initial Crank Fueling Period 2 seconds

Crank Fueling Ramp Rate 30 %sec

Crank Exit Fueling Command 60 %

Governor Enable Speed 1100 rpm

Maximum Governor Duty Cycle 60 %

Important Note: The feature code and modify parameters are suitable for C250 D5
genset with PMG.

2. Below procedures are designated for C250 D5(shunt)

2.1 Open InPower and connect to PCC1302, update the feature code as below list.
Go to Device ->Update Features.

2015 Cummins Power Generation, Inc. All rights reserved


Page 3 of 13
2.2 Following the feature code updated above, below parameters need to be modified:

2.2.1 Go to Adjustments -> Alternator Protection, modify below parameters:

Parameter Name Value units

Overfrequency Threshold 10 Hz

Underfrequency Threshold 10 Hz

2.2.2 Go to Adjustments->Adjustments -> Engine Protection Adjustments, modify below


parameters:

Parameter Name Value units

Overspeed Shutdown Threshold 50Hz 1875 rpm

LCL Response Type shutdown

LOP Shutdown Threshold 25 Psig

LOP Warning Threshold 30 Psig

2015 Cummins Power Generation, Inc. All rights reserved


Page 4 of 13
2.2.3 Go to Adjustments->Adjustments -> Governor->Gain, modify below parameters:

Parameter Name Value units

Governor Damping Effect (50Hz) 0.95

2.2.4 Go to Adjustments->Adjustments -> Governor-> Startup, modify below


parameters:

Parameter Name Value units

Initial Crank Fueling Command 50 %

Initial Crank Fueling Period 2 seconds

Crank Fueling Ramp Rate 30 %sec

Crank Exit Fueling Command 60 %

Governor Enable Speed 1100 rpm

Maximum Governor Duty Cycle 60 %

Important Note: The feature code and modify parameters are suitable for C250 D5
genset without PMG.

3. Below procedures are designated for C220 D5(PMG)

3. 1 Open InPower and connect to PCC1302, update the feature code as below list.

Go to Device ->Update Features.

2015 Cummins Power Generation, Inc. All rights reserved


Page 5 of 13
3. 2 Following the feature code updated above, below parameters need to be modified:

3.2.1 Go to Adjustments -> Alternator Protection, modify below parameters:

Parameter Name Value units

Overfrequency Threshold 10 Hz

Underfrequency Threshold 10 Hz

3.2.2 Go to Adjustments -> Engine Protection Adjustments, modify below parameters:

Parameter Name Value units

Overspeed Shutdown Threshold 50Hz 1875 rpm

LCL Response Type shutdown

LOP Shutdown Threshold 25 Psig

LOP Warning Threshold 30 Psig

3.2.3 Go to Adjustments -> Governor->Gain, modify below parameters

2015 Cummins Power Generation, Inc. All rights reserved


Page 6 of 13
Parameter Name Value units

Governor Damping Effect (50Hz) 0.95

3.2.4 Go to Adjustments -> Governor->Startup, modify below parameters


Parameter Name Value units

Initial Crank Fueling Command 50 %

Initial Crank Fueling Period 2 seconds

Crank Fueling Ramp Rate 30 %sec

Crank Exit Fueling Command 60 %

Governor Enable Speed 1100 rpm

Maximum Governor Duty Cycle 60 %

Important Note: The feature code and modify parameters are suitable for C220 D5
genset with PMG.

4. Below procedures are designated for C220 D5(shunt)

4. 1 Open InPower and connect to PCC1302, update the feature code as below list.

Go to Device ->Update Features.

2015 Cummins Power Generation, Inc. All rights reserved


Page 7 of 13
4. 2 Following the feature code updated above, below parameters need to be modified:

4.2.1 Go to Adjustments -> Alternator Protection, modify below parameters:

Parameter Name Value units

Overfrequency Threshold 10 Hz

Underfrequency Threshold 10 Hz

4.2.2 Go to Adjustments -> Engine Protection Adjustments, modify below parameters:

Parameter Name Value units

Overspeed Shutdown Threshold 50Hz 1875 rpm

LCL Response Type shutdown

LOP Shutdown Threshold 25 Psig

LOP Warning Threshold 30 Psig

4.2.3 Go to Adjustments -> Governor->Gain, modify below parameters:

2015 Cummins Power Generation, Inc. All rights reserved


Page 8 of 13
Parameter Name Value units

Governor Damping Effect (50Hz) 0.95

4.2.4 Go to Adjustments -> Governor-> Startup, modify below parameters:

Parameter Name Value units

Initial Crank Fueling Command 50 %

Initial Crank Fueling Period 2 seconds

Crank Fueling Ramp Rate 30 %sec

Crank Exit Fueling Command 60 %

Governor Enable Speed 1100 rpm

Maximum Governor Duty Cycle 60 %

Important Note: The feature code and modify parameters are suitable for C220 D5
genset without PMG.

5. Below procedures are designated for C225 D6(PMG)

5. 1 Open InPower and connect to PCC1302, update the feature code as below list.

Go to Device ->Update Features.

2015 Cummins Power Generation, Inc. All rights reserved


Page 9 of 13
5. 2 Following the feature code updated above, below parameters need to be modified:

5.2.1 Go to Adjustments -> Alternator Protection, modify below parameters:

Parameter Name Value units

Overfrequency Threshold 10 Hz

Underfrequency Threshold 10 Hz

5.2.2 Go to Adjustments -> Engine Protection Adjustments, modify below parameters:

Parameter Name Value units

LCL Response Type shutdown

LOP Shutdown Threshold 25 Psig

LOP Warning Threshold 30 Psig

5.2.3 Go to Adjustments -> Governor->Gain, modify below parameters:

2015 Cummins Power Generation, Inc. All rights reserved


Page 10 of 13
Parameter Name Value units

Governor Damping Effect (50Hz) 0.95

5.2.4 Go to Adjustments -> Governor->Startup, modify below parameters:

Parameter Name Value units

Initial Crank Fueling Command 50 %

Initial Crank Fueling Period 2 seconds

Crank Fueling Ramp Rate 30 %sec

Crank Exit Fueling Command 60 %

Governor Enable Speed 1100 rpm

Maximum Governor Duty Cycle 60 %

Important Note: The feature code and modify parameters are suitable for C225 D6
genset with PMG.

6. Below procedures are designated for C225 D6(shunt)

6. 1 Open InPower and connect to PCC1302, update the feature code as below list.

Go to Device ->Update Features.

2015 Cummins Power Generation, Inc. All rights reserved


Page 11 of 13
6.2 Following the feature code updated above, below parameters need to be modified:

6.2.1 Go to Adjustments -> Alternator Protection, modify below parameters:

Parameter Name Value units

Overfrequency Threshold 10 Hz

Underfrequency Threshold 10 Hz

6.2.2 Go to Adjustments -> Engine Protection Adjustments, modify below parameters:

Parameter Name Value units

LCL Response Type shutdown

LOP Shutdown Threshold 25 Psig

LOP Warning Threshold 30 Psig

6.2.3 Go to Adjustments -> Governor->Gain., modify below parameters:

2015 Cummins Power Generation, Inc. All rights reserved


Page 12 of 13
Parameter Name Value units

Governor Damping Effect (50Hz) 0.95

6.2.4 Go to Adjustments -> Governor-> Startup, modify below parameters:

Parameter Name Value units

Initial Crank Fueling Command 50 %

Initial Crank Fueling Period 2 seconds

Crank Fueling Ramp Rate 30 %sec

Crank Exit Fueling Command 60 %

Governor Enable Speed 1100 rpm

Maximum Governor Duty Cycle 60 %

Important Note: The feature code and modify parameters are suitable for C225 D6
genset without PMG.

Warranty Statement:
Any work described in this PSB is covered by standard SRTs. See below.

Contact:
For help and assistance on this issue please contact any of the following:
In ASIA: Grace Lee (grace.lee@cummins.com)
In Europe, Middle East or Africa: Chris Tragner (chris.tragner@cummins.com)
In Africa: Peter Neale (peter.neale@cummins.com)
In China: Haoming Liu (haoming.liu@cummins.com)
In the Americas: Robert Simmons (robert.simmons@cummins.com

2015 Cummins Power Generation, Inc. All rights reserved


Page 13 of 13

You might also like