You are on page 1of 1

MANUAL FOR Date : 1999-10-19

24 V DC CHARGING RECTIFIERS FOR Page : 17 of 17


EMERGENCY BATTERY

*
F.I.- Oscilloscope Pictures from the Thyristor Bridge
5 ms / div.
Correct voltage over the thyristor-bridge.
*
* The voltage is measured by means of an
oscilloscope connected directly over the + and -
of the thyristor bridge.

5 ms / div.

q
\
l\ Vv1 -\\i\,w,
\ \ \l \ \
u\
r\ \ ' \i1 u\ v1 \1\
\ \\
1 i i
Ul
A thyristor is not conducting.

Defective thyristor or lacking gate voltage from


the control PCBs.

jl
* 5 ms / div.
i Two thyristors in same branch are not

, \\ conducting.

VV\ i\
\ \
\lr- ~_
t
\
\
"Y \
Defective thyristors or lacking gate voltage from
the control PCBs.

5 ms / div. 1 V / div.
i Correct gate signal measured on one of the gate
j cables of the thyristor.
t 111 HI
\< C

*
PS. The real oscilloscope pictures may differ a little from the drawn "oscilloscope pictures" on this page.