Professional Documents
Culture Documents
2. Voltage quality:
Deviations of the voltage from a sinusoidal waveform.
3. Current quality:
Deviations of the current from a sinusoidal waveform.
4. Frequency Deviation:
An increase or decrease in the power frequency.
5. Impulsive transient:
A sudden, non power frequency change in the steady state condition of voltage or current
that is unidirectional in polarity.
6. Oscillatory transients:
A sudden, non power frequency change in the steady state condition of voltage or current
that is bidirectional in polarity.
7. DC Offset:
The presence of a DC voltage or current in an AC power system.
8. Noises:
An unwanted electric signal in the power system.
11. Sag:
A decrease in RMS value of voltage or current for durations of 0.5 cycles to 1 min.
12. Swell:
A Temporary increase in RMS value of voltage or current for durations of 0.5 cycles to 1
min.
15. Voltage fluctuation:
A cyclical variation of the voltage that results in flicker of lightning.
17. Harmonic:
It is a sinusoidal component of a periodic wave or quantity having a frequency that is an
integral multiple of the fundamental power frequency.
18. Distortion:
Any deviation from the normal sine wave for an AC quantity.
20. Interruption:
The complete loss of voltage on one or more phase conductors for a time greater than 1
min.
Voltage Based power quality problem
◦ Power frequency variation
◦ Voltage swell
◦ Harmonics and inter-harmonics
◦ Voltage Unbalance
◦ Flicker
◦ Voltage sags and momentary interruption
◦ Transient
1. Impulsive Transient
An impulsive transient is a sudden non–power frequency change in the steady-state
condition of voltage, current, or both that is unidirectional in polarity (either positive or
negative).
• Impulsive transients are normally characterized by either rise and decay times.
Example , a 1.2 X 50-μs 2000-V Lightning stroke impulsive transient
• Over voltage
• Under Voltage
• Sustained Interruption
An overvoltage is an increase in the rms ac
voltage greater than 110 percent at the power
frequency for a duration longer than 1 min.
Potential effects: loss of data, system damage and /or shutdown, tripping
of protective devices, stoppage of sensitive equipment like ASDs , PCs,PLCs
A brief decrease in the rms line voltage of 10 to 90% of nominal line
voltage.
The most Common causes: Faults on transmission or distribution
network, the starting of large motors and/or the -initial starting of
large loads (air conditioning systems),.
DC Offset
Harmonics are sinusoidal voltages or currents having frequencies
that are integer multiples of the frequency at which the supply
system is designed to operate.
Vrms = 𝑣 I
1 1
= 𝐼
2 1 , ms 2 1
1 2 1
𝑣𝑟𝑚𝑠 = σℎ𝑚𝑎𝑥
ℎ=1 ( 𝑣ℎ ) = 𝑣12 + 𝑣22 + 𝑣32 … …
2 2
0
Average power( Active power)
If v(t) and i(t) contains harmonics
Harmonic distortion levels are described by quantity, the total
harmonic distortion (THD), as a measure of the effective value
of harmonic distortion.
THD can be calculated for either current or voltage.
It is defined as the ratio of total harmonics in rms to the value
at fundamental rms frequency component in %
𝑉ℎ𝑟𝑚𝑠
=
𝑉1𝑟𝑚𝑠
𝐼ℎ𝑟𝑚𝑠
=
𝐼1𝑟𝑚𝑠
THD can be misleading when analyzing current
harmonics.
THD can be referenced to the amplitude of the
fundamental.
The voltage fundamental value is always present in
non-faulted conditions.
Not necessarily true for current.
The current amplitude will fluctuate with the loads
impedance.
As loads turn off, the fundamental current amplitude
decreases.
If the current being drawn by the load is low (near
zero) then the THD value will appear to be very high.
If the total harmonic current is 0.2A
and the fundamental current being drawn by the load
is 200A
THD will equal 3.16%
THD = √(0.2/200) x 100 = 3.16%
If the fundamental current being drawn by the load
then drops to 200mA then the THD will equal 100%
THD = √(0.2/0.200) x 100 = 100%