Professional Documents
Culture Documents
Underground Distribution Lines PDF
Underground Distribution Lines PDF
CHAPTER 7
minum will be justified based upon an analysis adequate cable protection. Special shielding or
using life, environmental, and cost factors. The coverings will not be specified, unless the designer
need for mechanical flexibility requires that con- has checked that the footage installed for each
ducts be stranded, and the NEC makes this man- different cable diameter is large enough for manu-
datory for cables larger than No. 8 AWG installed facturers to make the special runs required.
in raceways. The installation of conductors larger (b) Metallic-armored cable. Armored cable is
than 500 kcmil is not economical, and such large justified only when cable is installed under water
cables should be used only under exceptional (submarine cables) and sometimes when installed
circumstances. Large ampacities can be served by in cable trays or trenches. Armored cable will
parallel or multiple circuits. Three 15 kV, single- have XLP or EPR insulation covered with a
conductor, nonmetallic-jacketed cables larger than thermoplastic core covering and then provided
No. 4/0 AWG will require use of ducts larger than with an interlocked-metal tape armor. A nonmetal-
the standard four-inch size (i.e. three single- lic jacket is required for underground installations,
conductor cables making up a three-phase circuit where corrosion and moisture protection is re-
and each having individual overall diameters quired, for installations in outdoor cable trays, or
greater than 1.25 inches will need to be installed for submarine cables. Submarine cable may also
in a duct larger than four inches). One three- require a lead covering. Cable having a steel
conductor cable is more costly than three single- armor will be three-conductor type to avoid the
conductor cables, and use of multiple-conductor high hysteresis and eddy current losses which can
cable will be restricted to special conditions. result when single-conductor cable is used.
Metallic-armored cable is such a special condition. (c) Lead-covered cable. Lead-covered cables
b. Insulation and jacket material. The type of will not be used, unless extenuating circumstances
insulation used will be dependent upon the voltage prevail such as for submarine cable. The lead
level and type of service required. Factors affect- covering is both more costly and more difficult to
ing selection will be the effects of the surrounding handle. The use of laminated insulation such as
environment, the importance of the load in regard for paper-insulated-lead-covered (PILC) or for
to operation of the installation, and whether peak varnished-cambric-lead-covered (VCLC) instead of
loading is continuous or intermittent. the solid or extruded dielectrics such as
(1) Medium-voltage cable. Cable will be speci- crosslinked-polyethylene (XLP) or ethylenepropy-
tied as 133 percent insulation level (ungrounded) lene-rubber (EPR) is not approved. In addition,
which allows greater margin for voltage surges, these cables have lower temperature ratings.
insulation deterioration, and fault clearing time (2) Low-voltage cables. Cables suitable for be-
than does the use of the 100 percent insulation low grade installations are listed in the NEC.
level (grounded). When marking guide specifica- Insulation will be either XLP (NEMA WC 7) or
tions, refer to NFPA 70, which currently limits the EPR (NEMA WC 8) and jackets or other protection
minimum size to No. 1 AWG at 133 percent will be in accordance with the applicable Under-
insulation for 15 kV to 28 kV systems and No. 2 writers Laboratories (UL) specification covering
AWG at 133 percent insulation for 8 kV to 15 kV that NEC type. Use of metal-clad (MC) cable will
systems. Medium-voltage cable above 3 kV will be be limited as previously discussed for metallic-
shielded. armored cable. The use of the less expensive
(a) Nonmetallic-jacketed cable. Nonmetallic- Moisture-and-Heat-Resistant Thermoplastic
jacketed cable will be used, except where circum- (THWN) or Moisture-and-Heat-Resistant Cross-
stances warrant other coverings. Insulation will be Linked Synthetic Polymer (XHHW) is not recom-
either crosslinked-polyethylene (XLP) for short life mended for underground work as their thinner
requirements, or ethylene-propylene-rubber (EPR) insulation has been designed for interior usage.
for long life requirements, in accordance with Moisture-and-Heat Resistant Thermoplastic (THW)
NEMA WC-7 and WC-8. Comparisons of various wiring does have the same thickness of insulation
cable insulations, as shown in table 7-1, indicate as Heat-Resistant Rubber (RHH)/Moisture-and-
the advantages of these two insulations over other Heat Resistant Rubber (RHW)/Underground
types. Coverings (jackets) will be any of the rubber Service-Entrance (USE) wire, but polyvinyl-
or plastic options covered by NEMA specifications. chloride insulation is considered to have only fair
This option allows the use of cables which are electrical and mechanical insulation properties as
available as stock items in small quantities. In compared to the excellent properties exhibited by
some environments, however, selection of other XLP and EPR insulation. UF cable may have a
jacket materials may be necessary because proper- greater insulation thickness, but some sizes have a
ties of some jacket materials may not provide lower ampacity rating than does USE cable.
7-2
TM 5-811-1/AFJMAN 32-1080
c. Cable ampacity. The current carrying capaci- ing cables. Calculations of the position effect indi-
ties of cable will be in accordance with ampacities cate that, to equalize operating temperatures, full-
given in the NEC and IEEE/ICEA publications. load ratings of cables appropriate for isolated
There are many factors taken into account in (one-way) ducts should be decreased for multiple
determining these allowable ampacities such as duct banks. For example, in an eight-way-duct
operating temperatures, soil effects, shielding bank the recommended full-load percentage de-
losses, and conductor configurations, but the vari- crease for each corner duct is 95 percent and for
ables which cause the most concern are circuit each interior duct is 83 percent giving an average
loading and location in a duct bank. Because of load percentage decrease of 89 percent. This derat-
load diversity, peak demands for cables in a duct ing still allows provision for loads in excess of the
bank will not occur concurrently in most cases. normal feeder capacity usually found on military
This diversity factor will be taken into account installations, as the summation of feeder capaci-
when computating expected heat build-up in a ties is generally from three to eight times the
duct bank. Heat dissipation from a cable is also overall capacity of a main electric supply station.
influenced by the position occupied by the cable in d. Power cable joints. A splice which connects
a duck bank. Cables in duck bank corners dissi- cables rated 2.5 kV and above is known as a power
pate heat more effectively than cables in interior cable joint. Cable joints are composed of connectors
ducts, because of the greater soil dissipating area to join two or more cables for the purpose of
and the smaller heat contribution from neighbor- providing a continuous electric path plus necessary
DUCT ENTRANCE
CABLE JOINT
REQUIREMENTS
Fireproof only medium-voltage circuits (over 600-volts). Fireproof cables their entire length within
the manhole and Into the duct entrance as indicated.
7-3
TM 5-811-1/AFJMAN 32-1080
components for maintaining symmetrical stress ing. Whenever separable insulated connectors are
distribution, minimizing voltage gradients, and used for this application, they should be of the
maximizing environmental protection. loadbreak type. The preformed kit must be suit-
(1) Connectors. Connectors will be of the com- able for the cable insulation and correctly sized for
pression type or the plug-in type. Mechanical the cable diameter. Separable insulated connectors
connectors of the bolted or screw type or thermal will not be used in manholes, except where neces-
connectors of the soldered, brazed, or welded type sary for reasons of clearance at airfields. Separable
will be used only in special cases where the insulated connectors will not be used in direct
application so warrants. Compression connectors burial applications.
above 5 kV need to be of the tapered-end type, or (3) Choice. Any of the cable joints discussed
have semiconducting (semicon) tape or molded may be permitted as a Contractors option, whose
construction to give the same effect and thus limit selection is made by balancing labor savings
stresses. against material costs. Disconnectable loadbreak
(2) Other necessary joint components. The separable connectors, which are the most expen-
other necessary components are contained with the sive type of cable joints, will be used only where
connectors in kits to provide joints which range the disconnect feature is necessary. Metallic-
from the fully field-assembled type (taped) to those armored cable splices will be enclosed in
kits with mostly factory-formed parts (preformed) compound-filled metal splice boxes. Splice and
which require less installation labor. Factory pre- terminator kits will be selected as recommended
formed kits are preferred. The field-assembled kits by the cable manufacturer.
will not be used unless the Contractor cannot (4) Dissimilar material. Both aluminum-to-
locate the preformed kits, and the Contractor copper conductor and nonmetallic-jacketed to lead-
employes a cable splicer approved by the Contract- covered cable connections are easily made when
ing Officer. connectors and splicing materials are correctly
(a) Conventional taped or resin system splice utilized and installed. While transitions from one
kits. These kits cost the least for materials and are material to another will not be permitted when
used to make up a significant number of cable installing new lines, such transitions between
joints, but this type requires the most labor to existing and new work are acceptable for exten-
install. Joints are longer and bulkier than other sions and additions.
types. Quality is dependent upon the splicers skill e. High-voltage cable terminations. A device used
level, so joint workmanship can vary widely. Any for terminating alternating-current power cables
kit selected must have splice tapes suitable for the having extruded, solid, or laminated insulation
cable insulation. Refer to IEEE Std 141 for details which is rated 2.5 kV and above is known as a
and specifications of cable joints. high-voltage cable termination.
(b) Heat-shrinkable splice kits. These kits (1) Provisions. Such terminations are covered
include factory preformed splices which are heat- by IEEE Std 48 which requires terminations to be
treated in the field to fit the conductor. This type able to provide one or more of the following:
is simpler to install than the conventional taped or (a) Electric stress control for the cable insu-
resin type, and provides a less bulky splice than lation shield terminus.
any of the other types. A kit will fit a range of (b) Complete external leakage insulation be-
cable sizes, but kits may not be available for other tween the cable conductors and ground.
than solid dielectric single-conductor cables. (c) A seal at the end of the cable against the
(c) Separable insulated connectors. Such con- entrance of the external environment which also
nectors are fully factory preformed into the mini- maintains the pressure, if any, of the cable system.
mum of parts necessary to adapt either the recep- (2) Types. Termination types are defined by
tacle and plug or the connector and splice body to IEEE Std 48 as Class 1, which provides all of the
the cable insulation, shielding, and jacket. Such above three conditions (and includes potheads, a
joints cannot be used for laminated insulations, term now rapidly becoming obsolete), Class 2
but provide a waterproof and totally submersible which provides the first two conditions, and Class
joint for solid or extruded dielectric insulations. 3 which provides only the first condition. The first
These joints are the quickest to install, but the two classes include both indoor and outdoor types,
labor savings may be outweighed by the highest but Class 3 can only be used indoors. Protection
initial cost. Greater reliability has been reported from direct exposure to solar radiation or precipi-
by utility and industry records for these joints. tation is required for outdoor types.
Connections do provide disconnectability for future (3) Requirements. Class 2 terminations with
taps or for cable sectionalizing during fault test- their unsealed ends are subject to tracking when
7-4
TM 5-811-1/AFJMAN 32-1080
exposed to humidity changes occurring inside out- cable with a fireproofing tape, spraying the cable
door equipment. Class 3 terminations, with their with a foreproofing coating, or installing fire stops
exposed length in addition to the exposed end, can in the manhole. Medium-voltage cables and con-
be more difficult to maintain plus more dangerous ductors in manholes that are taped or coated with
to maintenance personnel. Since the use of the a fireproofing material will be taped or coated for
more expensive Class 1 type causes an almost their entire length on an individual cable basis.
unnoticable overall cost increase in the provision Figure 7-1 shows cable fireproofing details for a
of a medium-voltage cable installation, only Class taped installation. Polymeric elastomer tapes will
1 terminations will be used. Either taped or be used. Asbestos tapes are not permitted. Where
preformed Class 1 terminations are acceptable. cables have been lubricated to enhance pulling
Use of the next higher BIL rating in contaminated into ducts, the lubricant will be removed from
areas is not recommended, as it is preferable to cables exposed in the manhole before fireproofing.
have a cable failure at the termination rather g. Insulation tests. Cable testing will be speci-
than within the cable length. fied to be performed and successfully completed for
f. Fireproofing. High current arcs can cause all medium-voltage cable installations. Cable test-
heat or even flames which can destroy cables ing will include the testing of the adequacy of all
adjacent to the arc. To limit damage, cables are cable splices and terminations, as applicable. Ca-
often fireproofed in manholes and vaults. Fire- bles will be disconnected from equipment during
proofing should be limited to cables rated above the testing process. The first testing of new cables
600 V. Fireproofing methods include wrapping the is performed by the cable manufacturer at the
7-5
TM 5-811-1/AFJMAN 32-1080
7-6
TM 5-811-1/AFJMAN 32-1080
7-7
TM 5-811-1/AFJMAN 32-1080
7-8
TM 5-811-1/AFJMAN 32-1080
by the Using Agency, and then equipment will be from manhole and ductline systems or other
of the type which can be submersed. Where the sources for low-voltage power and communication
water table is high enough to flood manholes, supply to building services. A handhole suitable
water will be removed by portable pumps operated for most electric power or communication usage is
on a regular schedule. Permanently connected shown on figure 7-8. At least four racks will be
sump pumps will not be installed, except in special installed. Where more than two splices occur, a
instances. Permanent ladders will not be installed; manhole may be more appropriate.
portable ladders will be used when required. (2) Pullboxes. Pullboxes are used for electric
(4) Manhole appurtenances. Ground rods will circuits supplying low-voltage electric loads which
be installed in one corner of each electric manhole require conductors no larger than No. 1/0 AWG
for metallic shield or sheath grounding to reduce and no more than one 2-inch conduit entrance at
induced potential gradients. Dangerous gradients each side. Where larger conduits are installed,
are not induced by communication circuits, so rods handholes or manholes will be used. Because
will not be installed in communication manholes. pullbox depths are less than two feet, conduits
Other manhole appurtenances are shown on figure must always slope up into the pullbox. Pullboxes
7-7. Square covers will not be used because of the are also suitable for fire alarm, public address, and
danger of the cover slipping through the opening. control circuits. Pullboxes will not be used for
The traffic cover shown on figure 7-7 is suitable telephone circuits without the approval of the
for AASHTO H20 wheel loadings. Pulling-in irons appropriate communication agency. Figure 7-9
will be provided opposite each duct entrance or shows standard sizes of pullboxes used for low-
where there are provisions for future duct en- voltage installations. Pullboxes will not be used in
trances. Sufficient cable racks will be installed to areas subject to vehicular traffic. In such areas,
properly support cables on both sides of any cable handholes will be installed. The use of a pullbox at
splice and elsewhere as needed. Rack horizontal the base of a lighting pole is unnecessary in most
spacing will be 3 feet to 4- feet for electric cases.
power cables dependent upon the nature of the c. Manholes at Air Force installations.
cable bends. At least two racks will be located on (1) General requirements. Manholes shall be
each wall, except, racks will not be more than 30 adequately sized, shall comply with applicable
inches apart horizontally. requirements of OSHA, and AASHTO, and may be
(5) Communication manholes are to be de- precast or cast-in-place. Openings should be round
signed in accordance with Army Field Manual and not less than 32 inches in diameter.
11-486-5, Telecommunications Engineering Out- (2) Manholes for aircraft operating and park-
side Plant Telephones, paragraphs 7-17 to 7-30. ing aprons. Electrical manholes in aprons shall be
b. Other Types of Cable Access Points. Where avoided. Cables shall be installed beyond the
splicing or pulling of cables requires an access periphery of aprons. Electrical manholes shall
point, but the volume provided by a manhole is maintain a distance of 50 feet from the edge of
unnecessary, handholes or pullboxes will be pro- paving and 50 feet from any hydrant lateral
vided as appropriate. control pit and 200 feet from a fueling point.
(1) Handholes. Handholes are used on laterals
7-9
TM 5-811-1/AFJMAN 32-1080
PLAN ELEVATION
7-10
TM 5-811-1/AFJMAN 32-1080
Note: For
see
7-11
TM 5-811-1/AFJMAN 32-1080
PLAN
SECTION A - A
7-12
TM 5-811-1/AFJMAN 32-1080
a
Modified to suit a 36-inch frame.
b
Circular instead of square shaped.
7-13
TM 5-811-1/AFJMAN 32-1080
PLAN
SECTION A-A
7-14
TM 5-811-1/AFJMAN 32-1080
7-15
TM 5-811-1/AFJMAN 32-1080
7-16