Professional Documents
Culture Documents
REV. NO. 1
ENGINEERING STANDARD DATE MAR 2004
PAGE 1 OF 10
This document is issued by Engineering Standards Section, SABIC Engineering and Project Management, Kingdom of Saudi Arabia.
The information contained in this document is the confidential property of SABIC. It can not be disclosed, copied or used for any purpose
without prior approval from SABIC. If you are not authorized to posses this document, please destroy it immediately.
NUMBER E22-S01
REV. NO. 1
Cables, Low Voltage (NEC and IEC)
DATE MAR 2004
ENGINEERING STANDARD PAGE 2 OF 10
CONTENTS
1. SCOPE................................................................................................. 3
2. REFERENCES 3
3. GENERAL 3
4. OPERATION CONDITIONS................................................................. 4
4.1 Site Conditions 4
4.2 Service Conditions 4
5. LOW VOLTAGE CABLE - IEC.............................................................. 4
6. LOW VOLTAGE CABLE - ICEA 5
7. NUMBER AND SIZE OF CABLES 7
7.1 Power Cables.................................................................................. 7
7.2 Control Cables 7
7.3 Ground Conductors 7
8. AMPACITY ........................................................................................... 8
9. SINGLE CONDUCTOR CABLES 8
10. MULTICONDUCTOR CABLES 8
10.1 Non-armored Cables....................................................................... 8
10.2 Armored Cables 8
11. TESTING AND INSPECTION 9
12. IDENTIFICATION AND TAGGING ....................................................... 9
13. PREPARATION FOR SHIPMENT 10
TABLE
I Minimum Acceptable Insulation Thicknesses 5
II Minimum Acceptable Jacket Thickness for Armored and
Non-armored Multiconductor Cables ................................................... 5
III Minimum Acceptable Insulation Thicknesses 6
IV Minimum Acceptable Jacket Thicknesses for Multiconductor
Non-armored Cables 6
V Minimum Acceptable Jacket Thicknesses for Multiconductor
Armored Cables .................................................................................. 7
VI Wire and Cable Size Cross Reference Table 7
VII Minimum Acceptable Grounding Conductor Sizes 8
NUMBER E22-S01
REV. NO. 1
Cables, Low Voltage (NEC and IEC)
DATE MAR 2004
ENGINEERING STANDARD
PAGE 3 OF 10
1. Scope
1.1 This specification is for manufacturing, testing and shipping of low voltage power and control cables.
1.2 This specification shall be used in conjunction with SES E22-X01.
2. References
Reference is made in this specification to the following documents. The latest issues, amendments, and
supplements to these documents shall apply unless otherwise indicated.
SABIC Engineering Standards (SES)
E22-X01 Cables, Low Voltage (NEC and IEC) - Data Sheet
Z01-G04 Measurement Units for Use in SABIC Projects
American Society for Testing and Materials (ASTM)
B 3 Specification for Soft or Annealed Copper Wire
B 8 Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft
Institute of Electrical and Electronic Engineers (IEEE)
383 Type Test of Class 1E Electric Cables
1202 Flame Testing of Cables for Use In Cable Trays
Insulated Cable Engineers Association / National Electric Manufacturers Association (ICEA/NEMA)
ICEA S-66-524/NEMA WC-7 Cross-Linked-Thermosetting-Polyethylene-Insulated Wire and Cable for
the Transmission and Distribution of Electric Energy
International Electrotechnical Commission (IEC)
60038 IEC Standard Voltages
60228 Conductors of Insulated Cables
60332-3 Tests on Electric Cables under Fire Conditions - Part 3: Tests on Bunched Wires or Cables
60502 Extruded Solid Dielectric Insulated Power Cables for Rated Voltages from 1 kV up to 30 kV
National Fire Protection Association (NFPA)
70 National Electrical Code (NEC), 1999 Edition
Underwriters Laboratories, Inc. (UL)
44 Rubber-Insulated Wires and Cable
1569 Metal Clad Cables
3. General
3.1 This specification prescribes the general requirements for low voltage power cables. See
SES E22-X01 for specific requirements.
3.2 Low voltage power cable shall be manufactured and tested in accordance with IEC 60502 or
ICEA S-66-524, as specified on SES E22-X01.
3.3 Cable manufactured to IEC 60502 shall conform to section 5.
3.4 Cable manufactured to ICEA S-66-524 shall conform to section 6.
3.5 Units of measure associated with the cable, for example technical requirements, reel lengths, and
purchase quantities shall be in accordance with SES Z01-G04. However, the cable size shall be indicated
in the actual unit of measure (AWG or mm2), as applicable, based on the purchased cable.
3.6 Any conflict(s) between this specification, SES and industry standards, engineering drawings, and
contract documents shall be resolved at the discretion of SABIC.
NUMBER E22-S01
REV. NO. 1
Cables, Low Voltage (NEC and IEC)
DATE MAR 2004
ENGINEERING STANDARD PAGE 4 OF 10
4. Operation Conditions
4.1 Site Conditions
4.1.1 Indoor Conditions
Temperature range: air-conditioned. 0 qC to 40 qC.
4.1.2 Outdoor Conditions
Ambient temperature: 1 qC to 50 qC
Metallic surface temperatures reaching 75 qC due to solar radiation
Corrosive desert atmosphere with blowing sand and dust
Relative humidity: 10 to 100 percent
4.1.3 Storage / Transport Conditions
Ambient temperature: 2 qC to 70 qC
Relative humidity: 1 to 95 percent
4.2 Service Conditions
4.2.1 The cable material and construction shall be suitable for storage, installation and operation in
climatic conditions stated in 4.1. Impact of the higher ambient temperature on ampacity will be factored in
cable selection and application during system design.
4.2.2 The cable insulation and all components shall be suitable for normal operation at 90 qC conductor
temperature, and 250 qC for short circuit conditions.
4.2.3 Cables shall be suitable for wet or dry locations.
Table I
Minimum Acceptable Insulation Thicknesses
2.5 to 16 0.7
35 0.9
50 1.0
70 to 95 1.1
120 1.2
150 1.4
185 1.6
240 1.7
300 1.8
400 2.0
500 2.2
5.4 Multiconductor cables shall have a flame retardant and termite resistant PVC jacket. The material for
the cable jacket shall be extruded directly onto the surface to be covered. Table II lists the minimum
acceptable jacket thickness for armored and nonarmored multiconductor cables. The cable jacket shall be
continuous, homogeneous, voidless, seamless, and free of foreign material.
Table II
Minimum Acceptable Jacket Thickness for Armored
and Non-armored Multiconductor Cables
1.5 to 70 1.8
95 to 150 2.0
185 to 300 2.4
400 and 500 3.0
5.5 Cable shall conform to flame retardance test in accordance with IEC 60332-3.
6.3 Low voltage single conductor cable shall be insulated with cross-linked polyethylene (XLPE) insulation
extruded directly over the copper conductors or ethylene propylene rubber (EPR). Table III lists the
minimum acceptable insulation thickness of the cables. The cable construction shall be in accordance with
UL 44.
Table III
Minimum Acceptable Insulation Thicknesses
INSULATION THICKNESS
CONDUCTOR SIZE
mm
14 to 10 AWG 0.76
8 to 2 AWG 1.1
1 to 4/0 AWG 1.4
250 to 500 MCM 1.6
750 to 1000 MCM 2.0
6.4 Multiconductor cables shall have an overall PVC jacket consisting of an extruded layer of black PVC
suitable for the operating temperature of the cable. Tables IV and V list the minimum acceptable jacket
thickness. The cable jacket shall be continuous, homogeneous, voidless, seamless, and free of foreign
material. The PVC jacket shall be flame retardant and termite resistant.
Table IV
Minimum Acceptable Jacket Thicknesses for
Multiconductor Non-armored Cables
INSULATION THICKNESS
CONDUCTOR SIZE
mm
14 to 10 AWG 1.14
8 to 4 AWG 1.52
2 to 4/0 AWG 2.03
250 to 750 MCM 2.79
1000 MCM 3.56
NUMBER E22-S01
REV. NO. 1
Cables, Low Voltage (NEC and IEC)
DATE MAR 2004
ENGINEERING STANDARD
PAGE 7 OF 10
Table V
Minimum Acceptable Jacket Thicknesses for
Multiconductor Armored Cables
INSULATION THICKNESS
CONDUCTOR SIZE
mm
Table VI
Wire and Cable Size Cross Reference Table
Table VII
Minimum Acceptable Grounding Conductor Sizes
SIZE OF CIRCUIT
MINIMUM GROUNDING CONDUCTOR SIZE
CONDUCTOR
8. Ampacity
The base current carrying capacity of cables shall be in accordance with NFPA 70, Tables 310-16 to
310-20. SABIC will reduce the ampacity in accordance with the appropriate requirements of the NEC,
based on installation method and site conditions.