You are on page 1of 2

HARDWIRED I/O LIST FOR STEAM TURBINE AND AUXILIARIES 4GCH00776_Rev.

10

Turbine Loop Test Summary


Note ; "1" Note ; "1" is for Unit 1 or "2" is for Unit 2 is superseded to the mark "*" at the top of the "SIGNAL TAG NO." Unit #1

SIGNAL TAG NO. SIGNAL DESCRIPTION


I/O LOWER UPPER SIGNAL
NO. FROM TO UNITS Loop Test Done Date REMARKS
TYPE RANGE RANGE LEVEL
*(Less than 16 characters) *(Less than 40 characters)

64 AI LOCAL EHC P*LBA10CT013 MAIN STEAM TEMP(A)(SECOND PIPE) 0 600 degC 4-20 mA OK 3/26/2017(Need Scaffolding)
Wrong Temp Indicating HMI.
Need To Reconfirm the loop

145 AI AVR/GCP EHC P*CJN01GT001 GEN VT 0 23500 V 0-110

146 AI AVR/GCP EHC P*CJN01GT002 GEN CT 0 22000 A 0-5A

147 AI AVR/GCP EHC P*CJN01GT003 LINE VT 0 500 kV 0-110V

160 ANALOG LOCAL DCS P*MAA10CT011B TURBINE 1ST STAGE INNER METAL TEMP 0 600 degC 4-20 mA Not Ok Sunday, March 26, 2017
From Juction box to sensor cable
Missing

Toshibha TA Confirmed Need to change Logic


186 DO EHC DCS P*MAY30EW005A TURBINE TRIPPED(A) - - - 24VDC OK 42754
Invert from EHC side.

Toshibha TA Confirmed Need to change Logic


187 DO EHC DCS P*MAY30EW005B TURBINE TRIPPED(B) - - - 24VDC OK 42754
Invert from EHC side.

Toshibha TA Confirmed Need to change Logic


188 DO EHC DCS P*MAY30EW005C TURBINE TRIPPED(C) - - - 24VDC OK 42754
Invert from EHC side.

314 DI GMCB EHC P*BAC01GH001XB1 GCB OPEN - - - 48VDC

315 DI AVR/GCP EHC P*CJN01EY001 500kV CB OPEN - - - 48VDC

316 DI GPR EHC P*CHA01EY001A 86 LOCKOUT RELAY OPERATED(A) - - - 48VDC

317 DI GPR EHC P*CHA01EY001B 86 LOCKOUT RELAY OPERATED(B) - - - 48VDC

318 DI GPR EHC P*CHA01EY001C 86 LOCKOUT RELAY OPERATED(C) - - - 48VDC

Stop feedback Signal assigned Turbine trip


319 DI MCC EHC P*MAV10AP001XB2 MOP(A) STOPPED - - - 48VDC
protection card .so need to check later

Stop feedback Signal assigned Turbine trip


320 DI MCC EHC P*MAV10AP002XB2 MOP(B) STOPPED - - - 48VDC
protection card .so need to check later

425 DO EHC GPR P*MAY60EW001 TURBINE TRIPPED(A)(TO GPR) - - - 220VDC

426 DO EHC GPR P*MAY60EW002 TURBINE TRIPPED(B)(TO GPR) - - - 220VDC

AVR/
449 DO EHC P*MAY50EW001 TURBINE TRIPPED(TO AVR) - - - 220VDC
GCP

3 /37 Proprietary Information


(C) Toshiba Corporation 2014,
All Rights Reserved
HARDWIRED I/O LIST FOR STEAM TURBINE AND AUXILIARIES 4GCH00776_Rev.10

System Name

Main Steam System

Dcs Interface Signal

Dcs Interface Signal

Dcs Interface Signal

4 /37 Proprietary Information


(C) Toshiba Corporation 2014,
All Rights Reserved

You might also like