STG SET Point list Issues Doc No 4GCH00879 Rev1

TAG NO Document Setting Value Logic Setting Value

1.P1&P2MKF05CT001XQ01

SCW Gen Inlet Temp High Alarm 48C 50C

2.P1&P2MKF30CF001XV01

GEN Inlet Cooling Water Flow 880 L/MIN 940 L/MIN

3.P1&P2MAD01CG001A,B&C

Thrust Position Low/High Alarm High +0.51/Low -0.51 High +1/Low -0.51

4.P1&P2MAD01CG001A,B&C

Thrust Position A,B&C HI HI TBN Trip 1.02 mm 1.51 mm

5.P1&P2MAA10CT006&7A,B&C

HP TBN EXHAUST(1) & (2) HI HI Trip >480 >480 (1 Hour Time Delay)

>510 Immediate Trip