:Transformer Details:
Transformer Capacity 25 MVA
Primary Voltage (HT) 66 KV
Secondary Voltage(LT) 11 KV
Rated Primary Current (Ip) 218.7 Amp
Rated Secondary Current (Is) 1312.2 Amp
Max.Earth Fault Current at HV Side (L-G) 1100 Amp
Min.Earth Fault Current at HV Side (L-G) 1000 Amp
Max.Earth Fault Current at LV Side (LG) 900 Amp
Min.Earth Fault Current at LV Side (L-G) 800 Amp
Max.Earth Fault Current at Downstrem of TC (L-G) 700 Amp
Min.Earth Fault Current at Downstrem of TC (L-G) 600 Amp
Max.Fault Current at HV Side (L-L) 5000 Amp
Min.Fault Current at HV Side (L-L) 5500 Amp
Max.Fault Current at LV Side (L-L) 4500 Amp
Min.Fault Current at LV Side (L-L) 4000 Amp
Max.Fault Current at Downstrem Side of TC (L-L) 3500 Amp
Min.Fault Current at Downstrem Side of TC (L-L) 3000 Amp
CT for O/C & Earth Fault Protection:
CT Ratio (LT Side)
Prim. Current (Amp) 500
Sec. Current (Amp) 5
CT Ratio (HT Side)
Prim. Current (Amp) 100
Sec. Current (Amp) 5
CT for Differential Protection:
CT Ratio (LT Side)
Prim. Current (Amp) 1000
Sec. Current (Amp) 5.11
CT Ratio (HT Side)
Prim. Current (Amp) 200
Sec. Current (Amp) 5
HT Side Details
Over Load Current : 125% X Ip
Over Load Current :(In) 273 Amp
Required Over Current Relay Plug Setting 2.73 2.73 A X In
Actual Plug Setting of Over Current Relay (I>) 128% 1.28 A X In
Pick Up Setting of Over Current Relay (PMS): (I>) 6.4 Amp
Fault Current At CT Secondary Side 250 Amp
Plug Setting Multiplier (PSM): 39.06 Amp
Curve Selection: Normal Inverse (NI)
Time Dial Setting of Over current Relay(TMS): 0.1 Sec
Time of Operation of Relay 1.841 Sec
Actual Operaion Time of Relay: (t>) 0.184 Sec
Back Up Protection for Down Stream
Actual Plug Setting of Over Current Relay (I>>) 160% 1.6 A X In
Pick Up Setting of Over Current Relay (PMS): (I>>) 8 Amp
Fault Current At CT Secondary Side 200 Amp
Plug Setting Multiplier (PSM): 25.000 Amp
Curve Selection: Normal Inverse (NI)
Time Dial Setting of Over current Relay(TMS): 0.1 Sec
Time of Operation of Relay 2.105
Actual Operaion Time of Relay: (t>>) 0.211 Sec
3500
35 700
56
Jignesh.parmar,www.electricalnotes.wordpress.com,jiguparmar@yahoo.com
HT Side Details
Earth Fault Current : 20% X In
Earth Fault Current :(Inf) 55 Amp
Required Earth Fault Relay Plug Setting 0.55 0.55 A X In
Actual Plug Setting of Earth Fault Relay (Ie>) 25% 0.25 A X In
Pick Up Setting of Over Current Relay (PMS): (Ie>) 1.25 Amp
Fault Current At CT Secondary Side 55 Amp
Plug Setting Multiplier (PSM): 44.00 Amp
Curve Selection: Normal Inverse (NI)
Time Dial Setting of Earth Fault Relay(TMS): 0.1 Sec
Time of Operation of Relay 1.781 Sec
Actual Operaion Time of Relay: (te>) 0.178 Sec
Back Up Protection for Down Stream
Actual Plug Setting of Earth Fault Relay (Ie>>) 25% 0.25 A X In
Pick Up Setting of Over Current Relay (PMS): (Ie>>) 1.25 Amp
Fault Current At CT Secondary Side 40 Amp
Plug Setting Multiplier (PSM): 32.000 Amp
Curve Selection: Normal Inverse (NI)
Time Dial Setting of Over current Relay(TMS): 0.1 Sec
Time of Operation of Relay 1.951
Actual Operaion Time of Relay: (te>>) 0.195 Sec
LT Side
Full Load Current 1312.2 Amp
Current in Sec. Side of CT 6.705 Amp
HT Side
Full Load Current 218.70 Amp
Current in Sec. Side of CT 5.467 Amp
Spil Over current in Relay -1.238 Amp
Percentage Differntial Current -20.3 %