Introduction
SF6 in a lifecycle process
CO2-footprint reduction of GIS
Handling of SF6
Regulations on SF6
Conclusion
Copyright Siemens AG
Page 2 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations
Power Transmission
is a Part of the Power Matrix
Copyright Siemens AG
Page 4 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations
Characteristics of SF6
SF6 has
h excellent
ll t electrical
l t i l characteristics
h t i ti
* Global Warming Potential; ** according to EU-F-Gas regulation Copyright Siemens AG
Page 5 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations
SF6-emissions
in the lifecycle process of switchgear
ng
al
processin
industria
Development Entwicklung
Producing
HerstellungSF6 Produktion Manufacturing Commissioning
Tests Pr fung
p
SF6 is used in a closed cycle
ocessing
individual
Recycling of SF6 decommissioning Use
-
for reuse
pro
( =possible emission)
Copyright Siemens AG
Page 6 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations
Definition of SF6 Emission
SF6
Emission
SF6-handling losses
+ SF6-leakage
Copyright Siemens AG
Page 7 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations
Permanent CO2-footprint
footprint reduction of GIS
8D2
[[%]]
Size of building
100
example: the development of the
Space requirement
Siemens GIS 145 kV
90 Packing volume
80
70 8D6
8D8 8DN9
60
50 8DN8
40
30
20
10
source: Siemens
0
68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 2010
98
year
The developments within the last decades have led to smaller gas
compartments of the switchgear and thus to considerably less used
amount of SF6 at the same performance data.
Copyright Siemens AG
Page 8 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations
Significant reduced amount of SF6 in the equipment
- 75%
- 77%
- 68%
The component
t ti mustt assure
testing
very low SF6
emission by using
state-of-the-art-
handling equipment
in the factories
State-of-the-art-handling
State of the art handling
equipment
Environmentally respondsible
behavior and state-of-the-art
equipments
i t leads
l d tto llow SF6-
emission in the factory
2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010
Copyright Siemens AG
Page 13 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations
Optimized gas work needs
State-of-the-Art
State-of-the-Art equipment especially on site
Source: DILO
Copyright Siemens AG
Page 14 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations
SF6 Recollection
during measurements of gas quality
Copyright Siemens AG
Page 16 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations
Optimized SF6 handling
SF6-residual quantity (emission) dependence on the SF6 rated filling pressure /
compartment size / SF6 residual pressure
10
kg]
SF6 residual quantity [k
9
420 kV-circuit breaker, 3-pole
8 420 kV-disconnector, 3-pole
- volume: approx. 7000 l
- volume: approx. 870 l
7
- working pressure: 6,6 bar abs. - working pressure: 4,8bar abs.
6
- SF6-amount: approx. 300 kg - SF6-amount: approx. 27 kg
0
0 20 40 60 80 100 120 140 160 180 200
SF6 residual pressure [m bar]
Source: Cigr-Guide no. 276; Application of table 25
Axial direction
of rotation
Dynamic solution,
Movement
of main contacts example for 145 kV GIS CB
Number of
installed bays
GIS
The image cannot be display ed. Your computer may not hav e enough memory to open the image, or the image may hav e been corrupted. Restart y our computer, and then open the file again. If the red x still appears, y ou may hav e to delete the image and then insert it
again.
Todays
experience 2012
Acc. to CIGR study
Acc
Originally - No generic life limitation
expected - Issues of aging and deterioration
life-time Gas leakages
The image cannot be display ed. Your computer may not hav e enough memory to open the image, or the image may hav e been corrupted. Restart y our computer, and then open the file again. If the red x still appears, y ou may hav e to delete the image and then insert it
again.
0 10 20 30 40 50
Years in service
Continuous development assures the sustainable performance
Copyright Siemens AG
Page 20 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations
GIS-Concepts for low SF6-emission
Mission:
SF6-emissions should be avoided wherever possible.
The specific quantity of SF6 used to fulfill functions is
to be minimized.
minimized
Copyright Siemens AG
Page 22 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations
German SF6 data bank
1.200.000 1,1
Bestand ((kg)
g) Emissionsrate ((%))
1.150.000 1
1.100.000 0,9
1.050.000
0,8
1 000 000
1.000.000
0,7
950.000
0,6
in kg
in %
900.000
0,5
850.000
0,4
800.000
0,3
750.000
700.000 0,2
650.000 01
0,1
600.000 0
2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010
ng
al
processin
industria
Development Entwicklung
Producing
HerstellungSF6 Produktion Manufacturing Commissioning
Tests Pr fung
p
SF6 is used in a closed cycle
ocessing
individual
Recycling of SF6 decommissioning Use
-
for reuse
pro
The EU-F-Gas regulation concentrates
( =possible emission)
on the individual processing
Copyright Siemens AG
Page 24 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations
EU-F-Gas regulation 842/2006
((a
a bit
bit like new regulation of CARB*)
CARB )
Article 4 Recovery
Recovery Recovery by certified staff only
*) certain fluorinated greenhouse gases means hydrofluorocarbons (HFCs), perfluorocarbons (PFCs) and sulphur hexafluoride (SF6)
Copyright Siemens AG
Page 26 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations
European F-Gas-regulation 842/2006, article 2
Definitions
Definitions
Definitions for SF6-handling
Recovery
Collection and storage of SF6 from electric power equipment or containers
in practice: taking out SF6 from equipment and putting it into a container
Recycling
Reuse off recovered SF
S 6 following
f a basic cleaning process
in practice: recycling of SF6 on site
Reclamation
Reprocessing of recovered SF6 in order to meet a specific standard
standard* of
performance
in practice: used SF6 is reprocessed (e.g. SF6-production plant)
Destruction
Transformation or destruction into one or more stable substances which are not
fluorinated GHG
in practice: burning of SF6
*)) - IEC 60376 Specification
p of technical grade
g sulfur hexafluoride (SF
( 6) for use in electrical equipment
q p
- IEC 60480 Guidelines for the checking and treatment of sulfur hexafluoride (SF6) taken from electrical equipment and specification for its re-use
Copyright Siemens AG
Page 27 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations
European F-Gas-regulation 842/2006, article 5
Training
Training and certification
certification together with regulation 305/2008*
305/2008
Training Evaluation
Certification
(not subject to body/ Proof of Individual
b d issues
body i
conditions of Examination competence certificate
regulation)
certifications
(content defined)
Copyright Siemens AG
Page 28 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations
European F-Gas-regulation 842/2006, article 6
Reporting
Reporting together with regulation 1493/2007
European
Union
Import Export
country A SF6 > 1 t SF6 > 1 t country B
outside EU in container in container outside EU
or bottles or bottles
Standards required SF6-weight already in the past: declaration of weight of gas according to
IEEE C37.122 or IEC 62271-203
*)) Content defined in the regulation but the form can vary
between the different manufactures
Copyright Siemens AG
Page 30 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations
Review EU F-Gas-regulation in progress
Link: http://ec.europa.eu/clima/policies/f-gas/index_en.htm
Copyright Siemens AG
Page 31 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations
Cigr publications on SF6
SF6 RECYCLING
GUIDE Assure long term use of SF6
No. 234
SF6 HANDLING
Avoid SF6 handling
2003 GUIDE losses due to state-of-
the-art handling
No. 276
2012
IEC 62271
62271-1
1 Common specifications
C ifi ti ffor SF6-insulated
i l t d and
d
air-insulated high-voltage switchgear and controlgear
IEC 62271-200 Standard of medium-voltage SF6-GIS
IEC 62271-203
62271 203 High voltage switchgear and controlgear >52 kV
High-voltage
Revision published in 9/2011
IEC 62271-3031 Use and handling of SF6
IEC 603762 Specification for new SF6-gas
IEC 604802 Checking and treatment of sulfur hexafluoride (SF6)
taken from electric equipment
IEEE C37.122 Gas Insulated Substations
IEEE C37.122 IEEE Guide for Sulphur
p Hexaflouride
ASTM D2472-00 SF6-gas
1 Revision in progress: IEC 62271-4
2 Maintenance of the standard scheduled until 2014.
Copyright Siemens AG
Page 34 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations
Conclusion
Copyright Siemens AG
Page 35 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations
Thank you for your attention!
Dr. Ch
D Christian
i ti Wallner
W ll Peter
P t Glaubitz
Gl bit
Tel. +49 9131 7 33811 Tel. +49 9131 7 35010
eMail christian.wallner@siemens.com eMail peter.glaubitz@siemens.com
Copyright Siemens AG
Page 36 Christian Wallner Energy Sector - Power Transmission - High Voltage Substations