DIESEL GENERATOR SET

STANDBY
800 ekW 1000 kVA
50 Hz 1500 rpm 400 Volts
Caterpillar is leading the power generation
marketplace with Power Solutions engineered
to deliver unmatched flexibility, expandability,
reliability, and cost-effectiveness.
Image shown may not
reflect actual package.

FEATURES
FUEL/EMISSIONS STRATEGY CAT C32 ATAAC DIESEL ENGINE
Low fuel consumption
Utilizes ACERT Technology
DESIGN CRITERIA Reliable, rugged, durable design
The generator set accepts rated load in one step Four-cycle diesel engine combines consistent
performance and excellent fuel economy with
FULL RANGE OF ATTACHMENTS minimum weight
Wide range of bolt-on system expansion Electronic engine control
attachments, factory designed and tested
CAT SR4B GENERATOR
WORLDWIDE PRODUCT SUPPORT
Worldwide parts availability through the Designed to match performance and output
Caterpillar dealer network characteristics of Caterpillar diesel engines
With over 1844 dealer branch stores operating in Optimum winding pitch for minimum total
200 countries, you're never far from the harmonic distortion and maximum efficiency
Caterpillar part you need Single point access to accessory connections
99.7% of parts orders filled within 24 hours. The UL 1446 recognized Class H insulation system
best product support record in the industry. Digital Voltage Regulator
Caterpillar dealers service technicians are trained
to service every aspect of your electric power
generation system CAT EMCP 3 SERIES CONTROL PANELS
Preventative maintenance agreements
The Cat SOS program effectively detects internal Controls designed to meet individual customer
engine component condition, even the presence needs
of unwanted fluids and combustion by products EMCP 3 provides the option for full-featured
power metering and protective relaying

STANDBY 800 ekW 1000 kVA


50 Hz 1500 rpm 400 Volts

FACTORY INSTALLED STANDARD & OPTIONAL EQUIPMENT

System Standard Optional


Air Inlet Single element canister type air cleaner Dual element air cleaners
Service indicator Air inlet adapters
Cooling Radiator with guard (43C) Radiator with 27C ambient capability
Low profile (frontal area) Jacket water heater
Low airflow
Coolant drain line with valve
Fan and belt guards
Caterpillar Extended Life Coolant
Coolant level sensors
Radiator duct flange
Exhaust Dry exhaust manifold Stainless steel exhaust flex fittings
Flanged faced outlets Elbows, flanges, expanders & Y adapters
Fuel Primary fuel filter with water separator
Secondary fuel filter
Fuel priming pump
Flexible fuel lines
Fuel cooler
Generators Permanent magnet excited Oversize & premium generators
Class H insulation
Class F temperature (105C prime/130C standby)
Winding temperature detectors (select models)
Anti-condensation space heaters
Power Termination Bus bar (NEMA and IEC mechanical lug holes) -right Circuit breakers, UL listed, 3 pole with shunt trip, 80%
side standard or 100% rated, choice of trip units, manual or
Bottom cable entry electrically operated (low voltage only)
Circuit breakers, IEC compliant, 3 or 4 pole with shunt
trip (low voltage only), choice of trip units, manual or
electrically operated
Shroud cover for bottom cable entry
Power terminations can be located on the left and/or
rear as an option. Also, multiple circuit breakers can
be ordered (up to 3)
Top cable entry
Governor ADEM A4 Load Share Module

Control Panels User Interface panel (UIP) - rear mount EMCP 3.2 and EMCP 3.3
EMCP 3.1 generator set controller Option for right or left mount UIP
Speed adjust Option for rear or left mount Customer wiring area
AC & DC customer wiring area (right side) Local & remote annunciator modules
CAT Digital Voltage Regulator (CDVR) with KVAR/PF Discrete I/0 Module
control, 3-phase sensing Generator temperature monitoring & protection
Emergency Stop Push button Voltage raise/lower switch
Lube Lubricating oil and filter Deep sump oil pan
Oil drain line with valves
Fumes disposal
Gear type lube oil pump
Mounting Structual steel tube
Anti-vibration mounts (shipped loose)
Starting/Charging 24 volt starting motor(s) Battery chargers (10 Amp)
Batteries with rack and cables 45 amp charging alternator
Battery disconnect Oversize batteries
Ether starting aid
General Right-hand service UL 2200
Paint - Caterpillar Yellow (except rails and radiators CSA certification
gloss black) EU Declaration of Incorporation
SAE standard rotation EEC Declaration of Conformity
Flywheel and Flywheel housing - SAE No. 0

2 14 March 2006 5:54 AM


STANDBY 800 ekW 1000 kVA


50 Hz 1500 rpm 400 Volts

SPECIFICATIONS

CAT GENERATOR CAT EMCP 3 SERIES CONTROLS

EMCP 3.1 (Standard)


SR4B Generator
Integral to generator terminal box
Frame size......................................................................... 692
Single location for customer connection
Excitation................................................ Permanent Magnet
IP 23 enclosure
Pitch.............................................................................. 0.7143
24 Volt DC Control
Number of poles...................................................................4
UL/CSA
Number of bearings......................................................... 002
Lockable hinged door (option)
Insulation....................... UL 1446 Recognized Class H with
Run/Auto/Stop control
tropicalization and antiabrasion
IP rating..........................................................Drip Proof IP22 True RMS metering, 3-phase
Alignment....................................................... Close Coupled Speed Adjust
Overspeed capability - % of rated................................... 180 Voltage adjust (optional on 3.1)
Wave form....................................................................003.00 Digital indications for:
Voltage regulator.3 Phase sensing with selectible volts/Hz - RPM
Voltage regulation............Less than +/- 1/2% (steady state) - Operating hours
Less than +/- 1% (no load to full load) - Oil pressure
Telephone Influence Factor.............................. Less than 50 - Coolant temperature
Harmonic distortion......................................... Less than 5% - System DC volts
CAT DIESEL ENGINE - L-L volts, L-N volts, phase amps, Hz
- ekW, kVA, kVAR, kW-hr, %kW, PF(*)
Shutdowns with indicating lights (with optional
C32 TA, V-12, 4-stroke watercooled diesel annunciator):
Bore - mm.............................................. 145.00 mm (5.71 in) - Low oil pressure
Stroke - mm........................................... 162.00 mm (6.38 in) - High coolant temperature
Displacement - L................................... 32.10 L (1958.86 in3) - Overspeed
Compression ratio........................................................... 15:1 - Emergency stop
Aspiration........................................................................... TA - Failure to start (overcrank)
Fuel system....................................................................MEUI Programmable protective relaying functions (*):
Governor type.....................................................ADEM A4 - Under and over voltage
- Under and over frequency
- Reverse power
- Overcurrent
MODBUS isolated data link (RS-485 half-duplex)
supports serial communication at data rate up to 115.2
kbaud (*)
(*) Available on EMCP 3.2 & EMCP 3.3

3 14 March 2006 5:54 AM


STANDBY 800 ekW 1000 kVA


50 Hz 1500 rpm 400 Volts

TECHNICAL DATA

Open Generator Set - - 1500 rpm/50 Hz/400 Volts DM8145


Package Performance
Genset Power rating @ 0.8 pf 1000 kVA
Genset Power rating with fan 800 ekW
Low Fuel Consumption

Coolant to aftercooler
Coolant to aftercooler temp max 49 C 120 F
Fuel Consumption
100% load with fan 211.0 L/hr 55.7 Gal/hr
75% load with fan 162.7 L/hr 43.0 Gal/hr
50% load with fan 115.2 L/hr 30.4 Gal/hr
Cooling System1
Ambient air temperature 59 C 138 F
Air flow restriction (system) 0.12 kPa 0.48 in. water
Air flow (max @ rated speed for radiator arrangement) 1205 m/min 42554 cfm
Engine coolant capacity 55.0 L 14.5 gal
Radiator coolant capacity 13.5 L 3.6 gal
Engine Coolant capacity with radiator/exp. tank 68.5 L 18.1 gal
Inlet Air
Combustion air inlet flow rate 57.5 m/min 2030.6 cfm
Exhaust System
Exhaust stack gas temperature 527.8 C 982.0 F
Exhaust gas flow rate 163.3 m/min 5766.9 cfm
Exhaust flange size (internal diameter) 203 mm 8 in
Exhaust system backpressure (maximum allowable) 10.0 kPa 40.2 in. water
Heat Rejection
Heat rejection to coolant (total) 318 kW 18085 Btu/min
Heat rejection to exhaust (total) 868 kW 49363 Btu/min
Heat rejection to aftercooler 131 kW 7450 Btu/min
Heat rejection to atmosphere from engine 49 kW 2787 Btu/min
Heat rejection to atmosphere from generator 47.5 kW 2701.3 Btu/min
Alternator2
Motor starting capability @ 30% voltage dip 1694 skVA
Frame 692
Temperature Rise 130 C 266 F
Lube System
Sump refill with filter 68.0 L 18.0 gal
Emissions (Nominal)3
NOx g/hp-hr 6.25 g/hp-hr
CO g/hp-hr .62 g/hp-hr
HC g/hp-hr .02 g/hp-hr
PM g/hp-hr .022 g/hp-hr
1
Ambient capability at 300m (984 ft) above sea level. For ambient capability at other altitudes, consult your Caterpillar dealer.
2
UL 2200 Listed packages may have oversized generators with a different temperature rise and motor starting characteristics. Generator
temperature rise is based on a 40C ambient per NEMA MG1-32.
3
Emissions data measurements are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for measuring
HC, CO, PM, NOx. This engine's exhaust emissions are in compliance with the US EPA and California nonroad regulations as identified
above. Data shown is based on steady state operating conditions of 77F, 28.42 in HG and number 2 diesel fuel with 35 API and LHV of
18,390 btu/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and engine to engine variations.

4 14 March 2006 5:54 AM


STANDBY 800 ekW 1000 kVA


50 Hz 1500 rpm 400 Volts

RATING DEFINITIONS AND CONDITIONS

Meets or Exceeds International Specifications: AS1359, Ratings are based on SAE J1995 standard conditions.
BS4999, EGSA101P, ISO3046, ISO8528, NEMA MG 1-32, These ratings also apply at ISO3046/1, DIN6271, and
89/336/EEC, 98/37/EEC, 72/23/EEC, CSA, UL 508 and IEC BS5514 standard conditions.
60034 Fuel Rates are based on fuel oil of 35 API (16 C or 60 F)
Standby - Output available with varying load for the gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb)
duration of the interruption of the normal source power. when used at 29 C (85 F) and weighing 838.9 g/liter
Standby power in accordance with ISO8528. Fuel stop (7.001 lbs/U.S. gal.).
power in accordance with ISO3046/1, AS2789, DIN6271, Additional Ratings may be available for specific
and BS5514. Standby ambients shown indicate ambient customer requirements. Consult your Caterpillar
temperature at 100 percent load which results in a representative for details.
coolant top tank temperature just below the shutdown
temperature.

5 14 March 2006 5:54 AM


STANDBY 800 ekW 1000 kVA


50 Hz 1500 rpm 400 Volts

DIMENSIONS

Package Dimensions
Note: Do not use for installation design.
Length 4766.9 mm 187.67 in See general dimension drawings for
Width 2024.3 mm 79.7 in detail (Drawing #2763027).
Height 2254.0 mm 88.74 in
Weight 8046 kg 17,738 lb

CONTACT INFORMATION

Barloworld STET, Portugal can supply general dimension drawings.

Contact Name: Dep. Sistemas de Energia


Contact Phone: 800 206 707
apoioaclientes@stet.pt
Email: stet@stet.pt

www.CAT-ElectricPower.com
2006 Caterpillar
All rights reserved.
Performance No.: DM8145
Materials and specifications are subject to change without notice.
Feature Code:: C32DE01 The International System of Units (SI) is used in this publication.