Professional Documents
Culture Documents
1MRK505164-BEN G en Line Differential Protection IED RED670 Pre-Configured PDF
1MRK505164-BEN G en Line Differential Protection IED RED670 Pre-Configured PDF
Page 1
Features Four configuration alternatives for single- or - For automatic or manual synchrocheck and
multi-breaker arrangements available ready to with different settings
connect
Auto-reclosing function for single- two-, and/or
For overhead lines and cables three-phase reclosing:
For transformer feeders - Two functions with priority circuits for
multi-breaker arrangements
For single and/or three phase tripping
- Co-operation with synchrocheck function
High impedance differential protection for
tee-feeders - Can be switched On-Off from remote through
communication or with local switches through
Phase-segregated line differential protection binary inputs
with up to six stabilized inputs for up to five line
Selectable additional software functions such as
terminals with:
distance protection, control and monitoring
- Charging current compensation
Built-in data communication modules for station
- Separate inputs for each CT in double bus IEC 61850-8-1
breaker, ring and one and a half breaker
installations for improved through fault stabil- Data communication modules for station bus
ity IEC 60870-5-103, LON and SPA
- Suitable for multiplexed, route switched, as Integrated disturbance and event recorder for up
well as dedicated fibre, communication net- to 40 analog and 96 binary signals
works using C37.94 protocol Time synchronization over IEC 61850-8-1, LON,
- Power transformers can be included in the SPA, binary input or with optional GPS module
protected zone
Analog measurements accuracy up to below
- Transfer of up to eight binary signals 0.5% for power and 0.25% for current and volt-
- Time synchronization with the echo-method age and with site calibration to optimize total
or built-in GPS accuracy
Application The RED 670 IED is used for the protection, con- tection of heavily loaded lines and multi-terminal
trol and monitoring of overhead lines and cables in lines where the requirement for tripping is one-,
all types of networks. The IED can be used up to two-, and/or three pole. The IED is also suitable
the highest voltage levels. It is suitable for the pro-
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 2
for protection of cable feeders to generator block graphical configuration tool ensures simple and
transformers. fast testing and commissioning.
The phase segregated current differential protec- Serial data communication is via optical connec-
tion provides an excellent sensitivity for high tions to ensure immunity against disturbances.
resistive faults and gives a secure phase selection.
The availability of six stabilized current inputs The wide application flexibility makes this product
allows use on multi-breaker arrangements in three an excellent choice for both new installations and
terminal applications or up to five terminal appli- the refurbishment of existing installations.
cations with single breaker arrangements. Remote
communication based on the IEEE C37.94 stan- Four packages has been defined for following
dard can be redundant when required for important applications:
installations. Charging current compensation Single-breaker (double or single bus) with
allows high sensitivity also on long overhead lines
three phase tripping (A31)
and cables. A full scheme distance protection is
included as independent protection or as back-up Single-breaker (double or single bus) with sin-
at remote end communication failures. Eight chan- gle phase tripping (A32)
nels for intertrip and binary signals are available in Multi-breaker (one-and a half or ring) with
the communication between the IEDs.
three phase tripping (B31)
The auto-reclose for single-, two- and/or three Multi-breaker (one-and a half or ring) with sin-
phase reclosing includes priority circuits for gle phase tripping (B32)
multi-breaker arrangements. It co-operates with
the synchrocheck function with high-speed or The packages are configured and set with basic
delayed reclosing. functions active to allow direct use. Optional func-
High set instantaneous phase and earth overcur- tions are not configured but a maximum configura-
rent, four step directional or un-directional delayed tion with all optional functions are available as
phase and earth overcurrent, thermal overload and template in the graphical configuration tool. Inter-
two step under and overvoltage functions are face to analogue and binary IO are configurable
examples of the available functions allowing the from the Signal matrix tool without need of con-
user to fulfill any application requirement. figuration changes. Analogue and tripping IO has
been pre-defined for basic use on the, as standard
The IED can also be provided with a full control supplied one binary input module and one binary
and interlocking functionality including co-opera- output module. Add IO as required for your appli-
tion with the synchrocheck function to allow inte- cation at ordering. Other signals need to be applied
gration of the main or back-up control. as required for each application.
The advanced logic capability, where the user For details on included basic functions refer to sec-
logic is prepared with a graphical tool, allows spe- tion "Available functions".
cial applications such as automatic opening of dis-
connectors in multi-breaker arrangements, closing The applications are shown in figures 1 and 2 for
of breaker rings, load transfer logics etc. The single resp. multi-breaker arrangement.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 3
BUS B
BUS A
79 25
CLOSE
O->I SC/VC
94/86
TRIP
I->O
50BF
3I>
87L
3Id/I>
50/51
3I>
59
3U>
27
3U<
BUS A
TRIP BUSBAR
&CB2
79 25
CLOSE
O->I SC/VC
94/86 CB1
TRIP
I->O
79 25
O->I SC/VC
50BF
50/51
3I>
3I> TRIP
50BF
CB1/3
3I>
94/86
87L
I->O
CLOSE
59
3Id/I>
TRIP
3U>
27
3U< CB2
en05000303.vsd
TO REMOTE END:
FIBRE OPTIC OR TO MUX
Figure 2: The multi breaker packages for single- and three phase tripping typical arrangement for one pro-
tection sub-system is shown here. The differential function is more sensitive than any earth fault
or directional earth fault function and these functions are thus an option. Auto-reclose, Synchro-
check and Breaker failure functions are included for each of the two breakers.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 5
Available
functions
ANSI Function description Single breaker, Multi breaker, Singel breaker, Multi breaker,
3-phase tripping 3-phase tripping 1-phase tripping 1-phase tripping
(A31) (B31) (A32) (B32)
Basic Option Basic Option Basic Option Basic Option
(Qty/ (Qty/ (Qty/ (Qty/
option option option option
design) design) design) design)
Differential protection
(Only one alternative can be selected)
87 High impedance differential protection (PDIF) - 3/A02 - 3/A02 - 3/A02 - 3/A02
87L Line differential protection, 3 CT sets, 2-3 line ends (PDIF) 1 - - - 1 - - -
87L Line differential protection, 6 CT sets, 3-5 line ends (PDIF) - 1/A04 1 - - 1/A04 1 -
87LT Line differential protection 3 CT sets, with in-zone transformers, - 1/A05 - - - 1/A05 - -
2-3 line ends (PDIF)
87LT Line differential protection 6 CT sets, with in-zone transformers, - 1/A06 - 1/A06 - 1/A06 - 1/A06
3-5 line ends (PDIF)
Distance protection
21 Distance protection zones (PDIS) - 3/B01 - 3/B01 - 3/B01 - 3/B01
21 Phase selection with load enchroachment (PDIS) - 1/B01 - 1/B01 - 1/B01 - 1/B01
Directional impedance (RDIR) 1/B01 1/B01 1/B01 1/B01
78 Power swing detection (RPSB) - 1/B01 - 1/B01 - 1/B01 - 1/B01
Automatic switch onto fault logic (PSOF) - 1/B01 - 1/B01 - 1/B01 - 1/B01
Current protection
50 Instantaneous phase overcurrent protection (PIOC) 1 - 1 - 1 - 1 -
51/67 Four step phase overcurrent protection (POCM) 1 - 1 - 1 - 1 -
50N Instantaneous residual overcurrent protection (PIOC) - 1/C04 - 1/C04 - 1/C04 - 1/C04
51N/67N Four step residual overcurrent protection (PEFM) - 1/C04 - 1/C04 - 1/C04 - 1/C04
26 Thermal overload protection, one time constant (PTTR) 1 - 1 - 1 - 1 -
50BF Breaker failure protection (RBRF) 1 - 2 - 1 - 2 -
50STB Stub protection (PTOC) - - 1 - - - 1 -
52PD Pole discordance protection (RPLD) - - - - 1 - 2 -
Voltage protection
27 Two step undervoltage protection (PUVM) 1 - 1 - 1 - 1 -
59 Two step overvoltage protection (POVM) 1 - 1 - 1 - 1 -
59N Two step residual overvoltage protection (POVM) 1 - 1 - 1 - 1 -
Frequency protection
81 Underfrequency protection (PTUF) - 2/E02 - 2/E02 - 2/E02 - 2/E02
81 Overfrequency protection (PTOF) - 2/E02 - 2/E02 - 2/E02 - 2/E02
81 Rate-of-change frequency protection (PFRC) - 2/E02 - 2/E02 - 2/E02 - 2/E02
Multipurpose protection
General current and voltage protection (GAPC) - 4/F01 - 4/F01 - 4/F01 - 4/F01
Control
25 Synchrocheck and energizing check (RSYN) 1 - 2 - 1 - 2 -
79 Autorecloser (RREC) 1 - 2 - 1 - 2 -
Apparatus control for single bay, - 1/H07 - - - 1/H07 - -
max 8 apparatuses (1CB) incl. interlocking (APC8)
Apparatus control for single bay, - - - 1/H08 - - - 1/H08
max 15 apparatuses (2CBs) incl. interlocking (APC15)
Scheme communication
85 Scheme communication logic for distance protection (PSCH) - 1/B01 - 1/B01 - 1/B01 - 1/B01
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 6
ANSI Function description Single breaker, Multi breaker, Singel breaker, Multi breaker,
3-phase tripping 3-phase tripping 1-phase tripping 1-phase tripping
(A31) (B31) (A32) (B32)
Basic Option Basic Option Basic Option Basic Option
(Qty/ (Qty/ (Qty/ (Qty/
option option option option
design) design) design) design)
85 Current reversal and weak-end infeed logic for - 1/B01 - 1/B01 - 1/B01 - 1/B01
distance protection (PSCH)
Local acceleration logic (PLAL) - 1/B01 - 1/B01 - 1/B01 - 1/B01
85 Scheme communication logic for - 1/C04 - 1/C04 - 1/C04 - 1/C04
residual overcurrent protection (PSCH)
85 Current reversal and weak-end infeed logic for - 1/C04 - 1/C04 - 1/C04 - 1/C04
residual overcurrent protection (PSCH)
Logic
94 Tripping logic (PTRC) 1 - 2 - 1 - 2 -
Trip matrix logic (GGIO) 12 - 12 - 12 - 12 -
Monitoring
Measurements (MMXU) 3/10/3 - 3/10/3 - 3/10/3 - 3/10/3 -
Event counter (GGIO) 5 - 5 - 5 - 5 -
Disturbance report (RDRE) 1 - 1 - 1 - 1 -
Fault locator (RFLO) 1 - 1 - 1 - 1 -
Metering
Pulse counter logic (GGIO) 16 - 16 - 16 - 16 -
Station communication
IEC61850-8-1 Communication 1 - 1 - 1 - 1 -
LON communication protocol 1 - 1 - 1 - 1 -
SPA communication protocol 1 - 1 - 1 - 1 -
IEC60870-5-103 communication protocol 1 - 1 - 1 - 1 -
Single command, 16 signals 3 - 3 - 3 - 3 -
Multiple command and transmit 60/10 - 60/10 - 60/10 - 60/10 -
Remote communication
Binary signal transfer 4 - 4 - 4 - 4 -
Protected zone
en05000039.vsd
The six terminal version is used for conventional arrangements in both ends, as well as multi termi-
two-terminal lines with 1 1/2 circuit breaker nal lines with up to five terminals.
Protected zone
RED RED
670 Comm. Channel 670
en05000040.vsd
The current differential algorithm in RED 670 pro- considered to be negligible, and special measures
vides high sensitivity for internal faults, at the need only to be taken in the event of a short circuit
same time as it has excellent stability for external on the LV side of the transformer. In this applica-
faults. Current samples from all CTs are tion, the tripping of the differential protection can
exchanged between the IEDs in the line ends (mas- be time delayed for low differential currents in
ter-master mode) or sent to one IED (master-slave order to achieve coordination with down stream
mode) for evaluation. over current relays.
A restrained dual biased slope evaluation is made A line charging current compensation provides
where the bias current is the highest phase current increased sensitivity of the differential function.
in any line end giving a secure through fault stabil-
ity even with heavily saturated CTs. In addition to Line differential protection 3 or 6 CT sets,
the restrained evaluation, an unrestrained high dif- with in-zone transformers (PDIF, 87LT)
ferential current setting can be used for fast trip- One or two power transformers can be included in
ping of internal faults with very high currents. the line differential protection zone. Both two- and
three-winding transformers are correctly repre-
A special feature with RED 670 is that applica- sented with vector group compensations made in
tions with small power transformers (rated current the algorithm. The function includes 2nd and 5th
less than 50% of differential current setting) con- harmonic restraint and zero sequence current elim-
nected as line taps without measurement in the tap ination.
can be handled. The normal load current is here
Protected zone
Figure 5: Example of application on a three-terminal line with a power transformer in the protection zone
Analog signal transfer for and an evaluation is made in each terminal. This
line differential protection (MDIF) means that a 64 kbit/s communication channel is
The line differential communication can be needed between every IED included in the same
arranged as a master-master system or a mas- line differential protection zone. In the latter, cur-
ter-slave system alternatively. In the former, cur- rent samples are sent from all slave IEDs to one
rent samples are exchanged between all terminals, master IED where the evaluation is made, and trip
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 8
signals are sent to the remote ends when needed. In only needed between the master, and each one of
this system, a 64 kbit/s communication channel is the slave terminals.
Protected zone
RED RED
670 670
Comm.
Channels
en05000043.vsd
Protected zone
RED RED
670 670
Comm.
Channels
en05000044.vsd
Current samples from IEDs located geographically resistive faults on heavily loaded lines (see
apart from each other, must be time coordinated so figure 8).
that the current differential algorithm can be exe-
cuted correctly. In RED 670 it is possible to make
this coordination in two different ways. The echo X
method of time synchronizing is normally used
whereas for applications where transmit and
receive times can differ, the optional built in GPS Forward
receivers shall be used. operation
The function has a functionality for load encroach- The independent measurement of impedance for
ment which increases the possibility to detect high each fault loop together with a sensitive and reli-
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 9
able built in phase selection makes the function eighty percent of the power line at minimum
suitable in applications with single phase source impedance. The function can be configured
auto-reclosing. to measure the residual current from the three
phase current inputs or the current from a separate
Built-in adaptive load compensation algorithm current input.
prevents overreaching of zone1 at load exporting
end at phase-to-earth faults on heavily loaded Four step residual overcurrent
power lines. protection (PEFM, 51N/67N)
The four step single input overcurrent function has
The distance protection zones can operate, inde-
an inverse or definite time delay independent for
pendent of each other, in directional (forward or
each step separately.
reverse) or non-directional mode. This makes them
suitable, together with different communication All IEC and ANSI time delayed characteristics are
schemes, for the protection of power lines and available together with an optional user defined
cables in complex network configurations, such as characteristic.
parallel lines, multi-terminal lines etc.
The function can be set to be directional, forward,
Power swing detection (RPSB, 78) reverse or non-directional independently for each
Power swings may occur after disconnection of of the steps.
heavy loads or trip of big generation plants.
A second harmonic blocking can be set individu-
Power swing detection function is used to detect ally for each step.
power swings and initiate block of selected dis-
tance protection zones. Occurrence of earth fault The function can be used as main protection for
currents during a power swing can block the power phase to earth faults.
swing detection function to allow fault clearance.
The function can be used to provide a system
back-up e.g. in the case of the primary protection
Automatic switch onto fault logic (PSOF)
being out of service due to communication or volt-
Automatic switch onto fault logic is a function that
age transformer circuit failure.
gives an instantaneous trip at closing of breaker
onto a fault. A dead line detection check is pro- Directional operation can be combined together
vided to activate the function when the line is with corresponding communication blocks into
dead. permissive or blocking teleprotection scheme.
Current reversal and weak-end infeed functionality
Current protection are available as well.
All IEC and ANSI time delayed characteristics are The three phase current measuring function has an
available together with an optional user defined I2t characteristic with settable time constant and a
time characteristic. thermal memory.
The function can be set to be directional or An alarm level gives early warning to allow opera-
non-directional independently for each of the tors to take action well before the line will be
steps. tripped.
A current check with extremely short reset time is Two step overvoltage
used as a check criteria to achieve a high security protection (POVM, 59)
against unnecessary operation. Overvoltages will occur in the power system dur-
ing abnormal conditions such as sudden power
The breaker failure protection can be single- or loss, tap changer regulating failures, open line
three-phase started to allow use with single phase ends on long lines.
tripping applications. For the three-phase version
of the breaker failure protection the current criteria The function can be used as open line end detector,
can be set to operate only if two out of four e.g. normally then combined with directional reactive
two phases or one phase plus the residual current over-power function or as system voltage supervi-
starts. This gives a higher security to the back-up sion, normally then giving alarm only or switching
trip command. in reactors or switch out capacitor banks to control
the voltage.
The function can be programmed to give a single-
or three phase re-trip of the own breaker to avoid The function has two voltage steps, each of them
unnecessary tripping of surrounding breakers at an with inverse or definite time delayed.
incorrect starting due to mistakes during testing.
The overvoltage function has an extremely high
Stub protection (PTOC, 50STB) reset ratio to allow setting close to system service
When a power line is taken out of service for voltage.
maintenance and the line disconnector is opened in
multi-breaker arrangements the voltage transform- Two step residual overvoltage
ers will mostly be outside on the disconnected part. protection (POVM, 59N)
The primary line distance protection will thus not Residual voltages will occur in the power system
be able to operate and must be blocked. during earth faults.
The stub protection covers the zone between the The function can be configured to calculate the
current transformers and the open disconnector. residual voltage from the three phase voltage input
The three phase instantaneous overcurrent function transformers or from a single phase voltage input
is released from a NO (b) auxiliary contact on the transformer fed from an open delta or neutral point
line disconnector. voltage transformer.
phase, phase-to-phase or positive sequence voltage A detection of a difference indicates a fault in the
measurement. circuit and is used as alarm or to block protection
functions expected to give unwanted tripping.
Up to two independent over frequency function
instances are available. Fuse failure supervision (RFUF)
Failures in the secondary circuits of the voltage
Rate-of-change frequency transformer can cause unwanted operation of dis-
protection (PFRC, 81) tance protection, undervoltage protection, neutral
Rate of change of frequency function gives an point voltage protection, energizing function (syn-
early indication of a main disturbance in the sys- chrocheck) etc. The fuse failure supervision func-
tem. tion prevents such unwanted operations.
The function can be used for generation shedding, There are three methods to detect fuse failures.
load shedding, remedial action schemes etc.
The method based on detection of zero sequence
The function is provided with an undervoltage voltage without any zero sequence current. This is
blocking. The operation may be based on single a useful principle in a directly earthed system and
phase, phase-to-phase or positive sequence voltage can detect one or two phase fuse failures.
measurement.
The method based on detection of negative
Each step can discriminate between positive or sequence voltage without any negative sequence
negative change of frequency. current. This is a useful principle in a non-directly
earthed system and can detect one or two phase
Up to two independent rate-of-change frequency fuse failures.
function instances are available.
The method based on detection of du/dt-di/dt
where a change of the voltage is compared to a
Multipurpose protection change in the current. Only voltage changes means
a voltage transformer fault. This principle can
General current and voltage detect one, two or three phase fuse failures.
protection (GAPC)
The function can be utilized as a negative
sequence current protection detecting unsymmetri- Control
cal conditions such as open phase or unsymmetri-
cal faults. Synchrocheck and energizing check
(RSYN, 25)
The function can also be used to improve phase The synchrocheck function checks that the volt-
selection for high resistive earth faults, outside the ages on both sides of the circuit breaker are in syn-
distance protection reach, for the transmission line. chronism, or with at least one side dead to ensure
Three functions are used which measures the neu- that closing can be done safely.
tral current and each of the three phase voltages.
This will give an independence from load currents The function includes a built-in voltage selection
and this phase selection will be used in conjunc- scheme for double bus and one- and a half or ring
tion with the detection of the earth fault from the busbar arrangements.
directional earth fault protection function.
Manual closing as well as automatic reclosing can
be checked by the function and can have different
Secondary system supervision settings, e.g. the allowed frequency difference can
be set to allow wider limits for the auto-reclose
Current circuit supervision (RDIF) attempt than for the manual closing.
Open or short circuited current transformer cores
can cause unwanted operation of many protection Autorecloser (RREC, 79)
functions such as differential, earth fault current The autoreclosing function provides high-speed
and negative sequence current functions. and/or delayed auto-reclosing for single or
multi-breaker applications.
It must be remembered that a blocking of protec-
tion functions at an occurring open CT circuit will Up to five reclosing attempts can be programmed.
mean that the situation will remain and extremely The first attempt can be single-, two and/or three
high voltages will stress the secondary circuit. phase for single phase or multi-phase faults
respectively.
The current circuit supervision function compares
the residual current from a three phase set of cur- Multiple autoreclosing functions are provided for
rent transformer cores with the neutral point cur- multi-breaker arrangements. A priority circuit
rent on a separate input taken from another set of allows one circuit breaker to close first and the
cores on the current transformer. second will only close if the fault proved to be
transient.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 12
Each autoreclosing function can be configured to using permissive overreach protection schemes in
co-operate with a synchrocheck function. application with parallel lines when the overreach
from the two ends overlaps on the parallel line.
Apparatus control (APC)
The apparatus control is a function for control and The weak-end infeed logic is used in cases where
supervision of circuit breakers, disconnectors and the apparent power behind the protection can be
earthing switches within a bay. Permission to oper- too low to activate the distance protection func-
ate is given after evaluation of conditions from tion. When activated, received carrier signal
other functions such as interlocking, synchro- together with local under voltage criteria and no
check, operator place selection and external or reverse zone operation gives an instantaneous trip.
internal blockings. The received signal is also echoed back to acceler-
ate the sending end.
Interlocking
The interlocking function blocks the possibility to Local acceleration logic (PLAL)
operate primary switching devices, for instance To achieve fast clearing of faults on the whole line,
when a disconnector is under load, in order to pre- when no communication channel is available, local
vent material damage and/or accidental human acceleration logic (ZCLC) can be used. This logic
injury. enables fast fault clearing during certain condi-
tions, but naturally, it can not fully replace a com-
Each apparatus control function has interlocking munication channel.
modules included for different switchyard arrange-
ments, where each function handles interlocking of The logic can be controlled either by the auto
one bay. The interlocking function is distributed to re-closer (zone extension) or by the loss of load
each IED and is not dependent on any central func- current (loss-of-load acceleration).
tion. For the station-wide interlocking, the IEDs
communicate via the system-wide interbay bus Logic
(IEC 61850-8-1) or by using hard wired binary
inputs/outputs. The interlocking conditions depend
on the circuit configuration and apparatus position Tripping logic (PTRC, 94)
status at any given time. A function block for protection tripping is pro-
vided for each circuit breaker involved in the trip-
For easy and safe implementation of the interlock- ping of the fault. It provides the pulse prolongation
ing function, the IED is delivered with standard- to ensure a trip pulse of sufficient length, as well as
ized and tested software interlocking modules all functionality necessary for correct co-operation
containing logic for the interlocking conditions. with autoreclosing functions.
The interlocking conditions can be altered, to meet
the customers specific requirements, by adding The trip function block includes functionality for
configurable logic by means of the graphical con- evolving faults and breaker lock-out.
figuration tool.
Trip matrix logic (GGIO, 94X)
Twelve trip matrix logic blocks are included in the
Scheme communication IED. The function blocks are used in the configu-
ration of the IED to route trip signals and/or other
Scheme communication logic for logical output signals to the different output relays.
distance protection and directional
residual overcurrent protection (PSCH, 85) The matrix and the physical outputs will be seen in
To achieve instantaneous fault clearance for all the PCM 600 engineering tool and this allows the
line faults, a scheme communication logic is pro- user to adapt the signals to the physical tripping
vided. All types of communication schemes e.g. outputs according to the specific application needs.
permissive underreach, permissive overreach,
blocking, intertrip etc. are available. The built-in Configurable logic blocks
communication module (LDCM) can be used for A high number of logic blocks and timers are
scheme communication signalling when included. available for user to adapt the configuration to the
specific application needs.
Logic for loss of load and/or local acceleration in
co-operation with autoreclose function is also pro- Fixed signal function block
vided for application where no communication The fixed signals function block generates a num-
channel is available. ber of pre-set (fixed) signals that can be used in the
configuration of an IED, either for forcing the
Current reversal and weak-end infeed logic unused inputs in the other function blocks to a cer-
for distance protection and directional tain level/value, or for creating a certain logic.
residual overcurrent protection (PSCH, 85)
The current reversal function is used to prevent
unwanted operations due to current reversal when
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 13
measured voltages, currents, frequency, active, The function is characterized by great flexibility
reactive and apparent power and power factor, regarding configuration, starting conditions,
recording times and large storage capacity.
the primary and secondary phasors,
differential currents, bias currents, A disturbance is defined as an activation of an
input in the DRAx or DRBy function blocks which
positive, negative and zero sequence currents
is set to trigger the disturbance recorder. All sig-
and voltages, nals from start of pre-fault time to the end of
mA, post-fault time, will be included in the recording.
pulse counters, Every disturbance report recording is saved in the
measured values and other information of the IED in the standard Comtrade format. The same
different parameters for included functions, applies to all events, which are continuously saved
in a ring-buffer. The Local Human Machine Inter-
logical values of all binary in- and outputs and
face (LHMI) is used to get information about the
general IED information. recordings, but the disturbance report files may be
uploaded to the PCM 600 (Protection and Control
Supervision of mA input signals (MVGGIO) IED Manager) and further analysis using the dis-
The main purpose of the function is to measure turbance handling tool.
and process signals from different measuring
transducers. Many devices used in process control Event list (RDRE)
represent various parameters such as frequency, Continuous event-logging is useful for monitoring
temperature and DC battery voltage as low current of the system from an overview perspective and is
values, usually in the range 4-20 mA or 0-20 mA. a complement to specific disturbance recorder
functions.
Alarm limits can be set and used as triggers, e.g. to
generate trip or alarm signals. The event list logs all binary input signals con-
nected to the Disturbance report function. The list
The function requires that the IED is equipped may contain of up to 1000 time-tagged events
with the mA input module. stored in a ring-buffer.
actions) and in the long term (e.g. Functional Event function block. The event function block is
Analysis). used for LON and SPA communication.
The event recorder logs all selected binary input Analog and double indication values are also
signals connected to the Disturbance Report func- transferred through the event block.
tion. Each recording can contain up to 150
time-tagged events. Fault locator (RFLO)
The accurate fault locator is an essential compo-
The event recorder information is available for the nent to minimize the outages after a persistent fault
disturbances locally in the IED. and/or to pin-point a weak spot on the line.
The event recording information is an integrated The built-in fault locator is an impedance measur-
part of the disturbance record (Comtrade file). ing function giving the distance to the fault in per-
cent, km or miles. The main advantage is the high
Trip value recorder (RDRE) accuracy achieved by compensating for load cur-
Information about the pre-fault and fault values for rent and for the mutual zero sequence effect on
currents and voltages are vital for the disturbance double circuit lines.
evaluation.
The compensation includes setting of the remote
The Trip value recorder calculates the values of all and local sources and calculation of the distribu-
selected analogue input signals connected to the tion of fault currents from each side. This distribu-
Disturbance report function. The result is magni- tion of fault current, together with recorded load
tude and phase angle before and during the fault (pre-fault) currents, is used to exactly calculate the
for each analogue input signal. fault position. The fault can be recalculated with
new source data at the actual fault to further
The trip value recorder information is available for increase the accuracy.
the disturbances locally in the IED.
Specially on heavily loaded long lines (where the
The trip value recorder information is an inte- fault locator is most important) where the source
grated part of the disturbance record (Comtrade voltage angles can be up to 35-40 degrees apart the
file). accuracy can be still maintained with the advanced
compensation included in fault locator.
Disturbance recorder (RDRE)
The Disturbance Recorder function supplies fast,
complete and reliable information about distur- Metering
bances in the power system. It facilitates under-
standing system behavior and related primary and Pulse counter logic (GGIO)
secondary equipment during and after a distur- The pulse counter logic function counts externally
bance. Recorded information is used for different generated binary pulses, for instance pulses com-
purposes in the short perspective (e.g. corrective ing from an external energy meter, for calculation
actions) and long perspective (e.g. Functional of energy consumption values. The pulses are cap-
Analysis). tured by the binary input module and then read by
the pulse counter function. A scaled service value
The Disturbance Recorder acquires sampled data is available over the station bus. The special
from all selected analogue input and binary signals Binary input module with enhanced pulse counting
connected to the Disturbance Report function capabilities must be ordered to achieve this func-
(maximum 40 analog and 96 binary signals). The tionality.
binary signals are the same signals as available
under the event recorder function.
Basic IED functions
The function is characterized by great flexibility
and is not dependent on the operation of protection
Time synchronization
functions. It can record disturbances not detected
Use the time synchronization source selector to
by protection functions.
select a common source of absolute time for the
The disturbance recorder information for the last IED when it is a part of a protection system. This
100 disturbances are saved in the IED and the makes comparison of events and disturbance data
Local Human Machine Interface (LHMI) is used between all IEDs in a SA system possible.
to view the list of recordings.
Human machine interface
Event function (EV) The local human machine interface is available in
When using a Substation Automation system with a small, and a medium sized model. The principle
LON or SPA communication, time-tagged events difference between the two is the size of the LCD.
can be sent at change or cyclically from the IED to The small size LCD can display seven line of text
the station level. These events are created from any and the medium size LCD can display the single
available signal in the IED that is connected to the line diagram with up to 15 objects on each page.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 15
Station communication
Overview
Each IED is provided with a communication inter-
face, enabling it to connect to one or many substa-
tion level systems or equipment, either on the
Substation Automation (SA) bus or Substation
Monitoring (SM) bus.
module has two optical ports for plastic/plastic, Transformer input module (TRM)
plastic/glass, or glass/glass. The transformer input module is used to galvani-
cally separate and transform the secondary cur-
Line data communication module (LDCM) rents and voltages generated by the measuring
The line data communication module is used for transformers. The module has twelve inputs in dif-
binary signal transfer. Each module has one optical ferent combinations.
port, one for each remote end to which the IED
communicates. High impedance resistor unit
The high impedance resistor unit, with resistors for
Alternative cards for Short range (900 nm multi pick-up value setting and a voltage dependent
mode) are available. resistor, is available in a single phase unit and a
three phase unit. Both are mounted on a 1/1 19
GPS time synchronization module (GSM) inch apparatus plate with compression type term-
This module includes the GPS receiver used for nals.
time synchronization. The GPS has one SMA con-
tact for connection to an antenna.
B C
D
xx05000003.vsd
xx05000004.vsd
Figure 11: 1/2 x 19 case with rear cover Figure 12: Side-by-side mounting
Case size A B C D E F
6U, 1/2 x 19 265.9 223.7 201.1 242.1 252.9 205.7
6U, 3/4 x 19 265.9 336.0 201.1 242.1 252.9 318.0
6U, 1/1 x 19 265.9 448.1 201.1 242.1 252.9 430.3
(mm)
Figure 14: Binary input module (BIM). Input contacts named XA Figure 15: mA input module (MIM)
corresponds to rear position X31, X41, etc. and input
contacts named XB to rear position X32, X42, etc.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 20
Figure 20: Binary output module (BOM). Output contacts named XA corresponds to rear position X31,
X41, etc. and output contacts named XB to rear position X32, X42, etc.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 22
BUS A
BBP-TRIP BUS B
QB1-OPEN
ST BFP L1 *) QB1-CL
ST BFP L2 *) QB2-OPEN
ST BFP L3 *) QB2-CL -QB1
ST BFP 3PH -QB2
START AR
INHIBIT AR
TRM1:10
3PH TRIP *) MCB-OK
IN TEST
TRM1:11
MAN CLOSE MCB-OK
-QA1
CLOSE QA1 C
C
CLOSE Reinf
*) TRIP QA1 L1,L2,L3 REL/RED 3 Phase T
C
*) TRIP Reinf MAIN 2 TRIP T
QA1-OPEN C
QA1-CL
SIGNALLING
QA1-PD
FAULT
QA1-SPR UNCH
-BI1 P1
TRM1:1-3
TO MAIN 2 RELAY
BUSBAR TRIP
PERMIT 1PH *) TO BUS PROT
TRIP MAIN 2
1PH AR IN PROG *)
CR Z<
CS Z<
TO/FROM PLC/MUX
QB9-OPEN
QB9-CL
CR DEF
CS DEF
-QB9
CR DIT
MCB OR
FUSE -BU1
CS DIT
TRM1:7-9
MCB-OK
Figure 21: Typical connection diagram for a single breaker arrangement with control integrated.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 23
BUS A
BBP-TRIP
QB1-OPEN
ST BFP L1 *) QB1-CL -BU1
ST BFP L2 *) QB6-OPEN
-QB1
ST BFP L3 *) QB6-CL
ST BFP 3PH
START AR MCB OR
FUSE
INHIBIT AR
TRM1:11
3PH TRIP *) MCB-OK
=1-QA1
MAN CLOSE =1 CLOSE QA1 C
C
CLOSE Reinf
TRIP QA1 L1,L2,L3 REL/RED 3 Phase
*) T
C
*) TRIP Reinf MAIN 2 TRIP
T
QA1-OPEN
SIGNALLING
C
QA1-CL
FAULT
QA1-PD
QA1-SPR UNCH
-BI1 P1
TRM1:1-3
ST BFP L1 TO MAIN 2 RELAY
ST BFP L2
=2-QB9-OPEN
ST BFP L3 TO BUS PROT
=2-QB9-CL
ST BFP 3PH For Voltage
=2-QA1-OPEN
selection
START AR =2-QA1-CL
MCB OR -BU1 -QB6
INHIBIT AR FUSE
TRM1:7-9
3PH TRIP -QB9
MCB-OK
IN TEST QB9-OPEN
QB9-CL
-QB61
MAN CLOSE =3
TO MAIN 2 RELAY -BI1
BUSBAR TRIP
TRM2:1-3
TRIP =2-QA1 Reserved for parallal line IN P1
PERMIT 1PH TRIP TRM1:5 at mutual comp of FL =3-QA1
MAIN 2, =1 *) CLOSE QA1 C
C
PERMIT 1PH TRIP CLOSE Reinf
MAIN 2, =3 *) TRIP QA1 L1,L2,L3 T
C
1PH AR IN PROG *) TRIP Reinf MAIN 2 TRIP T
QA1-OPEN C
CR Z< QA1-CL
CS Z< QA1-PD
TO/FROM PLC/MUX
QA1-SPR
CR DEF UNCH
-QB62 -QB9
CS DEF MCB-OK
-BU1 -QB6
CR DIT TRM2:11
MCB OR
CS DIT
TRM1:12 FUSE
DIT2 Line 2 MCB OR =2-QA1 NOTE! CB CLosed is
MCB-OK FUSE
CB Closed L1&L2&L3
CB Open is CB Open
X11 O -BU1 L1 OR L2 OR L3
3 IRFX11 2
5 4
- + REMOTE END -QB2 BUS B
COMMUNICATION
*) is only valid for single phase tripping arrangements en05000267.vsd
Figure 22: Typical connection diagram for a multi breaker arrangement (1 1/2 CB) with control integrated.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 24
Reference value:
The specified value of an influencing factor to which are referred the characteristics of the equipment.
Nominal range:
The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the
specified requirements.
Operative range:
The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform
its intended functions according to the specified requirements.
Auxiliary DC voltage
Table 6: PSM - Power supply module
Quantity Rated value Nominal range
Auxiliary dc voltage, EL (input) EL = (24 - 60) V EL 20%
EL = (90 - 250) V EL 20%
Power consumption 50 W typically -
Auxiliary DC power in-rush < 5 A during 0.1 s -
Table 8: BIM - Binary input module with enhanced pulse counting capabilities
Quantity Rated value Nominal range
Binary inputs 16 -
DC voltage, RL RL24 (24/40) V RL 20%
RL48 (48/60) V RL 20%
RL110 (110/125) V RL 20%
RL220 (220/250) V RL 20%
Power consumption
RL24 = (24/40) V max. 0.05 W/input -
RL48 = (48/60) V max. 0.1 W/input
RL110 = (110/125) V max. 0.2 W/input
RL220 = (220/250) V max. 0.4 W/input
Counter input frequency 10 pulses/s max -
Balanced counter input frequency 40 pulses/s max -
Oscillating signal discriminator Blocking settable 140 Hz
Release settable 130 Hz
Table 10: IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel reed relay)
Binary outputs 10 2
Max system voltage 250 V AC, DC 250 V AC, DC
Test voltage across open contact, 1 min 1000 V rms 800 V DC
Current carrying capacity
Continuous 8A 8A
1s 10 A 10 A
Making capacity at inductive load with
L/R>10 ms
0.2 s 30 A 0.4 A
1.0 s 10 A 0.4 A
Breaking capacity for AC, cos > 0.4 250 V/8.0 A 250 V/8.0 A
Breaking capacity for DC with L/R < 40 48 V/1 A 48 V/1 A
ms 110 V/0.4 A 110 V/0.4 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A
Maximum capacitive load - 10 nF
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 26
Table 11: BOM - Binary output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and Signal relays
Binary outputs 24
Max system voltage 250 V AC, DC
Test voltage across open contact, 1 min 1000 V rms
Current carrying capacity
Continuous 8A
1s 10 A
Making capacity at inductive load with L/R>10 ms
0.2 s 30 A
1.0 s 10 A
Breaking capacity for AC, cos >0.4 250 V/8.0 A
Breaking capacity for DC with L/R < 40 ms 48 V/1 A
110 V/0.4 A
220 V/0.2 A
250 V/0.15 A
Influencing factors
Table 12: Temperature and humidity influence
Parameter Reference value Nominal range Influence
Ambient temperature, oper- +20 C -10 C to +55 C 0.02% /C
ate value
Relative humidity 10%-90% 10%-90% -
Operative range 0%-95%
Storage temperature -40 C to +70 C - -
Differential protection
Table 20: High impedance differential protection (PDIF, 87)
Function Range or value Accuracy
Operate voltage (20-400) V 1.0% of Ur for U < Ur
1.0% of U for U > Ur
Reset ratio >95% -
Maximum continuous voltage U>Trip2/series resistor 200 W -
Operate time 10 ms typically at 0 to 10 x Ud -
Reset time 90 ms typically at 10 to 0 x Ud -
Critical impulse time 2 ms typically at 0 to 10 x Ud -
Distance protection
Table 22: Distance protection zones (PDIS, 21)
Function Range or value Accuracy
Number of zones 3 with selectable direction -
Minimum operate current (10-30)% of Ibase -
Positive sequence reactance (0.50-3000.00) /phase 2.0% static accuracy
Positive sequence resistance (0.10-1000.00) /phase 2.0 degrees static angular accuracy
Zero sequence reactance (0.50-9000.00) /phase Conditions:
Zero sequence resistance (0.50-3000.00) /phase Voltage range: (0.1-1.1) x Ur
Fault resistance, Ph-E (1.00-9000.00) /loop Current range: (0.5-30) x Ir
Fault resistance, Ph-Ph (1.00-3000.00) /loop Angle: at 0 degrees and 85 degrees
Dynamic overreach <5% at 85 degrees measured with -
CVTs and 0.5<SIR<30
Impedance zone timers (0.000-60.000) s 0.5% 10 ms
Operate time 24 ms typically -
Reset ratio 105% typically -
Reset time 30 ms typically -
Fault resistance, phase-earth faults, for- (1.009000.00) /loop Angle: at 0 degrees and 85 degrees
ward and reverse
Fault resistance, phase-phase faults, (0.503000.00) /loop
forward and reverse
Load encroachment criteria:
Load resistance, forward and reverse (1.003000.00) /phase
Safety load impedance angle
(5-70) degrees
Reset ratio 105% typically -
Current protection
Table 26: Instantaneous phase overcurrent protection (PIOC, 50)
Function Range or value Accuracy
Operate current (1-2500)% of lbase 1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio > 95% -
Operate time 25 ms typically at 0 to 2 x Iset -
Reset time 25 ms typically at 2 to 0 x Iset -
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Operate time 10 ms typically at 0 to 10 x Iset -
Reset time 35 ms typically at 10 to 0 x Iset -
Critical impulse time 2 ms typically at 0 to 10 x Iset -
Dynamic overreach < 5% at = 100 ms -
Table 30: Thermal overload protection, one time constant (PTTR, 26)
Function Range or value Accuracy
Reference current (0-400)% of Ibase 1.0% of Ir
Start temperature reference (0-400)C 1.0C
Operate time: Ip = load current before overload occurs IEC 60255-8, class 5 + 200 ms
Time constant = (01000) minutes
I 2 I p2
t = ln 2
I Ib 2
I = Imeasured
Alarm temperature (0-200)C 2.0% of heat content trip
Trip temperature (0-400)C 2.0% of heat content trip
Reset level temperature (0-400)C 2.0% of heat content trip
Voltage protection
Table 34: Two step undervoltage protection (PUVM, 27)
Function Range or value Accuracy
Operate voltage, low and high step (1100)% of Ubase 1.0% of Ur
Absolute hysteresis (0100)% of Ubase 1.0% of Ur
Internal blocking level, low and high (1100)% of Ubase 1.0% of Ur
step
Inverse time characteristics for low - See table 73
and high step, see table 73
Definite time delays (0.000-60.000) s 0.5% 10 ms
Minimum operate time, inverse char- (0.00060.000) s 0.5% 10 ms
acteristics
Operate time, start function 25 ms typically at 2 to 0 x Uset -
Reset time, start function 25 ms typically at 0 to 2 x Uset -
Critical impulse time 10 ms typically at 2 to 0 x Uset -
Impulse margin time 15 ms typically -
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 31
Frequency protection
Table 37: Underfrequency protection (PTUF, 81)
Function Range or value Accuracy
Operate value, start function (35.00-75.00) Hz 2.0 mHz
Operate time, start function 100 ms typically -
Reset time, start function 100 ms typically -
Operate time, definite time function (0.000-60.000)s 0.5% + 10 ms
Reset time, definite time function (0.000-60.000)s 0.5% + 10 ms
Voltage dependent time delay Settings: Class 5 + 200 ms
UNom=(50-150)% of Ubase
UMin=(50-150)% of Ubase
Exponent
U UMin
t= ( tMax tMin ) + tMin Exponent=0.0-5.0
UNom UMin tMax=(0.001-60.000)s
tMin=(0.000-60.000)s
U=Umeasured
Multipurpose protection
Table 40: General current and voltage protection (GAPC)
Function Range or value Accuracy
Measuring current input phase1, phase2, phase3, PosSeq, -
NegSeq, 3*ZeroSeq, MaxPh, MinPh,
UnbalancePh, phase1-phase2,
phase2-phase3, phase3-phase1,
MaxPh-Ph, MinPh-Ph, Unbalan-
cePh-Ph
Base current (1 - 99999) A -
Measuring voltage input phase1, phase2, phase3, PosSeq, -
-NegSeq, -3*ZeroSeq, MaxPh, MinPh,
UnbalancePh, phase1-phase2,
phase2-phase3, phase3-phase1,
MaxPh-Ph, MinPh-Ph, Unbalan-
cePh-Ph
Base voltage (0.05 - 2000.00) kV -
Start overcurrent, step 1 and 2 (2 - 5000)% of Ibase 1.0% of Ir for I<Ir
1.0% of I for I>Ir
Start undercurrent, step 1 and 2 (2 - 150)% of Ibase 1.0% of Ir for I<Ir
1.0% of I for I>Ir
Definite time delay (0.00 - 6000.00) s 0.5% 10 ms
Operate time start overcurrent 25 ms typically at 0 to 2 x Iset -
Reset time start overcurrent 25 ms typically at 2 to 0 x Iset -
Operate time start undercurrent 25 ms typically at 2 to 0 x Iset -
Reset time start undercurrent 25 ms typically at 0 to 2 x Iset -
See table 71 and table 72 Parameter ranges for customer See table 71 and table 72
defined characteristic no 17:
k: 0.05 - 999.00
A: 0.0000 - 999.0000
B: 0.0000 - 99.0000
C: 0.0000 - 1.0000
P: 0.0001 - 10.0000
PR: 0.005 - 3.000
TR: 0.005 - 600.000
CR: 0.1 - 10.0
Voltage level where voltage memory (0.0 - 5.0)% of Ubase 1.0% of Ur
takes over
Start overvoltage, step 1 and 2 (2.0 - 200.0)% of Ubase 1.0% of Ur for U<Ur
1.0% of U for U>Ur
Start undervoltage, step 1 and 2 (2.0 - 150.0)% of Ubase 1.0% of Ur for U<Ur
1.0% of U for U>Ur
Operate time, start overvoltage 25 ms typically at 0 to 2 x Uset -
Reset time, start overvoltage 25 ms typically at 2 to 0 x Uset -
Operate time start undervoltage 25 ms typically 2 to 0 x Uset -
Reset time start undervoltage 25 ms typically at 0 to 2 x Uset -
High and low voltage limit, voltage (1.0 - 200.0)% of Ubase 1.0% of Ur for U<Ur
dependent operation 1.0% of U for U>Ur
Directional function Settable: NonDir, forward and reverse -
Relay characteristic angle (-180 to +180) degrees 2.0 degrees
Relay operate angle (1 to 90) degrees 2.0 degrees
Reset ratio, overcurrent > 95% -
Reset ratio, undercurrent < 105% -
Reset ratio, overvoltage > 95% -
Reset ratio, undervoltage < 105% -
Overcurrent:
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Impulse margin time 15 ms typically -
Undercurrent:
Critical impulse time 10 ms typically at 2 to 0 x Iset -
Impulse margin time 15 ms typically -
Overvoltage:
Critical impulse time 10 ms typically at 0 to 2 x Uset -
Impulse margin time 15 ms typically -
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 33
Control
Table 43: Synchrocheck and energizing check (RSYN, 25)
Function Range or value Accuracy
Phase shift, line - bus (-180 to 180) degrees -
Voltage ratio, Ubus/Uline (0.20-5.00)% of Ubase -
Voltage high limit for synchrocheck (50.0-120.0)% of Ubase 1.0% of Ur at U Ur
1.0% of U at U > Ur
Reset ratio, synchrocheck > 95% -
Frequency difference limit between bus (0.003-1.000) Hz 2.0 mHz
and line
Phase angle difference limit between (5.0-90.0) degrees 2.0 degrees
bus and line
Voltage difference limit between bus (2.0-50.0)% of Ubase 1.0% of Ur
and line
Time delay output for synchrocheck (0.000-60.000) s 0.5% 10 ms
Voltage high limit for energizing check (50.0-120.0)% of Ubase 1.0% of Ur at U Ur
1.0% of U at U > Ur
Reset ratio, voltage high limit > 95% -
Voltage low limit for energizing check (10.0-80.0)% of Ubase 1.0% of Ur
Reset ratio, voltage low limit < 105% -
Maximum voltage for energizing (80.0-140.0)% of Ubase 1.0% of Ur at U Ur
1.0% of U at U > Ur
Time delay for energizing check (0.000-60.000) s 0.5% 10 ms
Operate time for synchrocheck function 160 ms typically -
Operate time for energizing function 80 ms typically -
Scheme communication
Table 45: Scheme communication logic for distance protection (PSCH, 85)
Function Range or value Accuracy
Scheme type Intertrip -
Permissive UR
Permissive OR
Blocking
Co-ordination time for blocking communica- (0.000-60.000) s 0.5% 10 ms
tion scheme
Minimum duration of a carrier send signal (0.000-60.000) s 0.5% 10 ms
Security timer for loss of carrier guard (0.000-60.000) s 0.5% 10 ms
detection
Operation mode of unblocking logic Off -
NoRestart
Restart
Table 46: Current reversal and weak-end infeed logic for distance protection (PSCH, 85)
Function Range or value Accuracy
Detection level phase to neutral voltage (10-90)% of Ubase 1.0% of Ur
Detection level phase to phase voltage (10-90)% of Ubase 1.0% of Ur
Reset ratio <105% -
Operate time for current reversal (0.000-60.000) s 0.5% 10 ms
Delay time for current reversal (0.000-60.000) s 0.5% 10 ms
Coordination time for weak-end infeed (0.000-60.000) s 0.5% 10 ms
logic
Table 47: Scheme communication logic for residual overcurrent protection (PSCH, 85)
Function Range or value Accuracy
Communication scheme coordination (0.000-60.000) s 0.5% 10 ms
time
Scheme type Permissive UR -
Permissive OR
Blocking
Table 48: Current reversal and weak-end infeed logic for residual overcurrent protection (PSCH, 85)
Function Range or value Accuracy
Operate voltage 3Uo for WEI trip (5-70)% of Ubase 1.0% of Ur
Reset ratio >95% -
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 35
Logic
Table 49: Tripping logic (PTRC, 94)
Function Range or value Accuracy
Trip action 3-ph, 1/3-ph, 1/2/3-ph -
Minimum trip pulse length (0.000-60.000) s 0.5% 10 ms
Timers (0.000-60.000) s 0.5% 10 ms
Monitoring
Table 51: Measurements (MMXU)
Function Range or value Accuracy
Frequency (0.95-1.05) fr 2.0 mHz
Voltage (0.1-1.5) Ur 0.5% of Ur at U Ur
0.5% of U at U > Ur
Connected current (0.2-4.0) Ir 0.5% of Ir at I Ir
0.5% of I at I > Ir
Active power, P 0.1 x Ur < U < 1.5 x Ur 1.0% of Sr at S Sr
0.2 x Ir < I < 4.0 x Ir 1.0% of S at S > Sr
Reactive power, Q 0.1 x Ur < U < 1.5 x Ur 1.0% of Sr at S Sr
0.2 x Ir < I < 4.0 x Ir 1.0% of S at S > Sr
Apparent power, S 0.1 x Ur < U < 1.5 x Ur 1.0% of Sr at S Sr
0.2 x Ir < I < 4.0 x Ir 1.0% of S at S > Sr
Power factor, cos () 0.1 x Ur < U < 1.5 x Ur 0.02
0.2 x Ir < I < 4.0 x Ir
Metering
Table 56: Pulse counter logic (GGIO)
Function Setting range Accuracy
Input frequency See Binary Input Module (BIM) -
Cycle time for report of counter value (03600) s -
Station communication
Table 57: IEC 61850-8-1 communication protocol
Function Value
Protocol IEC 61850-8-1
Communication speed for the IEDs 100BASE-FX
Remote communication
Table 63: Line data communication module (LDCM)
Quantity Range or value
Type of fibre Graded-index multimode 62.5/125 m or 50/125 m
Wave length 820 nm
Optical budget
Graded-index multimode 62.5/125 m 13 dB (typical distance 3 km *)
Graded-index multimode 50/125 m 9 dB (typical distance 2 km *)
Optical connector Type ST
Protocol C37.94
Data transmission Synchronous
Transmission rate 64 kbit/s
Clock source Internal or derived from received signal
*) depending on optical budget calculation
Hardware
IED
Table 64: Case
Material Steel sheet
Front plate Steel sheet profile with cut-out for HMI
Surface treatment Aluzink preplated steel
Finish Light grey (RAL 7035)
Table 65: Water and dust protection level according to IEC 60529
Front IP40 (IP54 with sealing strip)
Rear, sides, top and bottom IP20
Connection system
Table 67: CT and VT circuit connectors
Connector type Rated voltage and current Maximum conductor area
Terminal blocks of feed through type 250 V AC, 20 A 4 mm2
Inverse characteristics
Table 71: Inverse time characteristics ANSI
Function Range or value Accuracy
Operate characteristic: k = 0.05-999 in steps of 0.01 -
unless otherwise stated
A
t = P + B k
( I 1)
Reset characteristic:
tr
t = k
(I 2
)
1
I = Imeasured/Iset
ANSI Extremely Inverse no 1 A=28.2, B=0.1217, P=2.0, ANSI/IEEE C37.112, class 5 + 30 ms
tr=29.1
ANSI Very inverse no 2 A=19.61, B=0.491, P=2.0,
tr=21.6
ANSI Normal Inverse no 3 A=0.0086, B=0.0185, P=0.02,
tr=0.46
ANSI Moderately Inverse no 4 A=0.0515, B=0.1140, P=0.02,
tr=4.85
ANSI Long Time Extremely Inverse no 6 A=64.07, B=0.250, P=2.0, tr=30
ANSI Long Time Very Inverse no 7 A=28.55, B=0.712, P=2.0,
tr=13.46
ANSI Long Time Inverse no 8 k=(0.01-1.20) in steps of 0.01
A=0.086, B=0.185, P=0.02,
tr=4.6
A
t = P k
( I 1)
I = Imeasured/Iset
Time delay to reset, IEC inverse time (0.000-60.000) s 0.5% of set time 10 ms
IEC Normal Inverse no 9 A=0.14, P=0.02 IEC 60255-3, class 5 + 40 ms
IEC Very inverse no 10 A=13.5, P=1.0
IEC Inverse no 11 A=0.14, P=0.02
IEC Extremely inverse no 12 A=80.0, P=2.0
IEC Short-time inverse no 13 A=0.05, P=0.04
IEC Long-time inverse no 14 A=120, P=1.0
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 39
I = Imeasured/Iset
RI inverse characteristic no 18 k=(0.05-999) in steps of 0.01 IEC 60255-3, class 5 + 40 ms
1
t = k
0.236
0.339
I
I = Imeasured/Iset
Logarithmic inverse characteristic no 19 k=(0.05-1.10) in steps of 0.01 IEC 60255-3, class 5 + 40 ms
t = 5.8 1.35 In
I
k
I = Imeasured/Iset
Table 73: Inverse time characteristics for Two step undervoltage protection (PUVM, 27)
Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in steps of 0.01 Class 5 +40 ms
k
t =
U < U
U<
U< = Uset
U = Umeasured
Type B curve: k = (0.05-1.10) in steps of 0.01
k 480
t = + 0.055
32 U < U 0.5
2.0
U <
U< = Uset
U = Umeasured
Programmable curve: k = (0.05-1.10) in steps of 0.01
A = (0.005-200.000) in steps of
0.001
B = (0.50-100.00) in steps of
kA
0.01
t = +D C = (0.0-1.0) in steps of 0.1
U < U
P
B C D = (0.000-60.000) in steps of
U < 0.001
U< = Uset P = (0.000-3.000) in steps of
U = Umeasured 0.001
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 40
Table 74: Inverse time characteristics for Two step overvoltage protection (POVM, 59)
Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in steps of 0.01 Class 5 +40 ms
k
t =
U U >
U>
U> = Uset
U = Umeasured
Type B curve: k = (0.05-1.10) in steps of 0.01
k 480
t =
32 U U > 0.5
2.0
0.035
U >
Type C curve: k = (0.05-1.10) in steps of 0.01
k 480
t =
32 U U > 0.5
3.0
0.035
U >
Programmable curve: k = (0.05-1.10) in steps of 0.01
A = (0.005-200.000) in steps of
0.001
kA
t = +D B = (0.50-100.00) in steps of
B U U >
P 0.01
C C = (0.0-1.0) in steps of 0.1
U >
D = (0.000-60.000) in steps of
0.001
P = (0.000-3.000) in steps of
0.001
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 41
Table 75: Inverse time characteristics for Two step residual overvoltage protection (POVM, 59N)
Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in steps of 0.01 Class 5 +40 ms
k
t =
U U >
U>
U> = Uset
U = Umeasured
Type B curve: k = (0.05-1.10) in steps of 0.01
k 480
t =
32 U U > 0.5
2.0
0.035
U >
Type C curve: k = (0.05-1.10) in steps of 0.01
k 480
t =
32 U U > 0.5
3.0
0.035
U >
Programmable curve: k = (0.05-1.10) in steps of 0.01
A = (0.005-200.000) in steps of
0.001
kA
t = +D B = (0.50-100.00) in steps of
B U U >
P 0.01
C C = (0.0-1.0) in steps of 0.1
U >
D = (0.000-60.000) in steps of
0.001
P = (0.000-3.000) in steps of
0.001
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 42
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management. Please refer to the function matrix for included software functions given in
each software option package. Please observe that the character length of the software option section varies depending on the included options.
Enter option codes in the shaded spaces to complete the ordering number. To obtain the complete ordering code, please combined code from sheet 1 and sheet
2, as given in the example below. 1 BIM and 1 BOM is basic. Order futher I/O as required.
Sheet 1 Sheet 2
RED 670* - - - - - - -
Binary input and output, mA and time synchronizating boards. Note! Basic 1 BIM and 1 BOM included.
Slot position (rear view) Note! Max 3 positions in 1/2 rack, 5 - - -
X101
X121
X131
X111
X31
X41
X51
X61
X71
X81
X91
in 3/4 rack with 2 TRM and 11 in 1/1
rack with 2 TRM (=grey fields)
Available slots in 1/2 Case with 1 TRM
Available slots in 3/4 Case with 2 TRM
slots
Available slots in 1/1 Case with 2 TRM
No board in this slot X X X X X X X X X
Binary output module 24 output relays Note! Maximum 4 (BOM + MIM) A A A A A A A A A A
(BOM) boards
BIM 16 inputs, 24-30 VDC B B B B B B B B B B
BIM 16 inputs, 48-60 VDC C C C C C C C C C C
BIM 16 inputs, 110-125 VDC D D D D D D D D D D
BIM 16 inputs, 220-250 VDC E E E E E E E E E E
BIMp 16 inputs, 24-30 VDC for pulse F F F F F F F F F
counting
BIMp 16 inputs, 48-60 VDC for pulse G G G G G G G G G
counting
BIMp 16 inputs, 110-125 VDC for pulse H H H H H H H H H
counting
BIMp 16 inputs, 220-250 VDC for pulse K K K K K K K K K
counting
IOM 8 inputs, 10+2 output, 24-30 VDC L L L L L L L L L
IOM 8 inputs, 10+2 output, 48-60 VDC M M M M M M M M M
IOM 8 inputs, 10+2 output, 110-125 VDC N N N N N N N N N
IOM 8 inputs, 10+2 output, 220-250 VDC P P P P P P P P P
mA input module MIM, 6 channels Note! Max 4 (BOM + MIM) board in 1/1 R R R R R R R R R
case. Max 1 MIM + 3 BOM in 3/4 case.
No MIM board in 1/2 case
GPS time synchronization module (GSM) (in last slot) S S S
Serial communication unit for remote end communication
X312
X313
X302
X303
Example:
RED 670*1.0-A31-A03B01C04F01-X0-A-A-B-A-A6X0-DAS-AA-XD
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 44
Accessories
GPS antenna and mounting details
GPS antenna, including mounting kits
Mounting details
19 rack mounting kit for one test switch
Protection cover
Protective cover for rear side of RHGS6, 6U, 1/4 x 19
High impedance resistor unit 1-ph with resistor and voltage dependent
1 2 3
resistor 20-100V
Quantity: RK795101-MA
High impedance resistor unit 3-ph with resistor and voltage dependent
resistor 20-100V Quantity: RK795101-MB
High impedance resistor unit 1-ph with resistor and voltage dependent
1 2 3
resistor 100-400V
Quantity: RK795101-CB
High impedance resistor unit 3-ph with resistor and voltage dependent
resistor 100-400V Quantity: RK795101-DC
Combiflex
Key switch for lock-out of settings via LCD-HMI
Manuals
Note: One (1) IED Connect CD containing user documentation (Operators manual, Technical reference manual, Installa-
tion and commissioning manual, Application manual and Getting started guide), Connectivity packages and LED label tem-
plate is always included for each IED.
Reference information
For our reference and statistics we would be pleased to be provided with the following application data:
Related documents
Documents related to RED 670 Identity number
Operators manual 1MRK 505 133-UEN
Installation and commissioning manual 1MRK 505 134-UEN
Technical reference manual 1MRK 505 132-UEN
Application manual 1MRK 505 135-UEN
Buyers guide 1MRK 505 164-BEN
Connection diagram, Single breaker arr. Three phase tripping arr. 1MRK 002 801-BA
Connection diagram, Single breaker arr. Single phase tripping arr. 1MRK 002 801-CA
Connection diagram, Multi breaker arr. Three phase tripping arr. 1MRK 002 801-DA
Connection diagram, Multi breaker arr. Single phase tripping arr. 1MRK 002 801-EA
Configuration diagram A, Single breaker with single or double busbars 1MRK 004 500-82
Configuration diagram B, Single breakers with single or double busbars 1MRK 004 500-83
Configuration diagram C, Multi breakers such as 1 1/2 or ring busbar arr. 1MRK 004 500-84
Configuration diagram D, Multi breakers such as 1 1/2 or ring busbar arr. 1MRK 004 500-85
Setting example 1, 230 kV Short cable line with 1 1/2 CB arr. 1MRK 505 175-WEN
Manufacturer
ABB Power Technologies AB
Substation Automation Products
SE-721 59 Vsters
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
Internet: www.abb.com/substationautomation
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 48