You are on page 1of 48

Line differential protection IED Buyer's Guide

RED 670 Pre-configured


1MRK 505 164-BEN
Revision: G
Issued: February 2007
Data subject to change without notice

Page 1

Features Four configuration alternatives for single- or - For automatic or manual synchrocheck and
multi-breaker arrangements available ready to with different settings
connect
Auto-reclosing function for single- two-, and/or
For overhead lines and cables three-phase reclosing:
For transformer feeders - Two functions with priority circuits for
multi-breaker arrangements
For single and/or three phase tripping
- Co-operation with synchrocheck function
High impedance differential protection for
tee-feeders - Can be switched On-Off from remote through
communication or with local switches through
Phase-segregated line differential protection binary inputs
with up to six stabilized inputs for up to five line
Selectable additional software functions such as
terminals with:
distance protection, control and monitoring
- Charging current compensation
Built-in data communication modules for station
- Separate inputs for each CT in double bus IEC 61850-8-1
breaker, ring and one and a half breaker
installations for improved through fault stabil- Data communication modules for station bus
ity IEC 60870-5-103, LON and SPA

- Suitable for multiplexed, route switched, as Integrated disturbance and event recorder for up
well as dedicated fibre, communication net- to 40 analog and 96 binary signals
works using C37.94 protocol Time synchronization over IEC 61850-8-1, LON,
- Power transformers can be included in the SPA, binary input or with optional GPS module
protected zone
Analog measurements accuracy up to below
- Transfer of up to eight binary signals 0.5% for power and 0.25% for current and volt-
- Time synchronization with the echo-method age and with site calibration to optimize total
or built-in GPS accuracy

Full scheme phase-to-phase and phase-to-earth Versatile local human-machine interface


distance protection with up to three zones: Extensive self-supervision with internal event
- All types of scheme communication recorder

- Load encroachment feature Six independent groups of complete setting


parameters with password protection
Synchrocheck and dead-line check function for
single- or multi-breaker arrangements: Powerful software PC tool for setting, distur-
bance evaluation and configuration
- Selectable energizing direction
Remote end data communication modules for
- Two functions with built-in voltage selection C37.94 and G.703

Application The RED 670 IED is used for the protection, con- tection of heavily loaded lines and multi-terminal
trol and monitoring of overhead lines and cables in lines where the requirement for tripping is one-,
all types of networks. The IED can be used up to two-, and/or three pole. The IED is also suitable
the highest voltage levels. It is suitable for the pro-
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 2

for protection of cable feeders to generator block graphical configuration tool ensures simple and
transformers. fast testing and commissioning.

The phase segregated current differential protec- Serial data communication is via optical connec-
tion provides an excellent sensitivity for high tions to ensure immunity against disturbances.
resistive faults and gives a secure phase selection.
The availability of six stabilized current inputs The wide application flexibility makes this product
allows use on multi-breaker arrangements in three an excellent choice for both new installations and
terminal applications or up to five terminal appli- the refurbishment of existing installations.
cations with single breaker arrangements. Remote
communication based on the IEEE C37.94 stan- Four packages has been defined for following
dard can be redundant when required for important applications:
installations. Charging current compensation Single-breaker (double or single bus) with
allows high sensitivity also on long overhead lines
three phase tripping (A31)
and cables. A full scheme distance protection is
included as independent protection or as back-up Single-breaker (double or single bus) with sin-
at remote end communication failures. Eight chan- gle phase tripping (A32)
nels for intertrip and binary signals are available in Multi-breaker (one-and a half or ring) with
the communication between the IEDs.
three phase tripping (B31)
The auto-reclose for single-, two- and/or three Multi-breaker (one-and a half or ring) with sin-
phase reclosing includes priority circuits for gle phase tripping (B32)
multi-breaker arrangements. It co-operates with
the synchrocheck function with high-speed or The packages are configured and set with basic
delayed reclosing. functions active to allow direct use. Optional func-
High set instantaneous phase and earth overcur- tions are not configured but a maximum configura-
rent, four step directional or un-directional delayed tion with all optional functions are available as
phase and earth overcurrent, thermal overload and template in the graphical configuration tool. Inter-
two step under and overvoltage functions are face to analogue and binary IO are configurable
examples of the available functions allowing the from the Signal matrix tool without need of con-
user to fulfill any application requirement. figuration changes. Analogue and tripping IO has
been pre-defined for basic use on the, as standard
The IED can also be provided with a full control supplied one binary input module and one binary
and interlocking functionality including co-opera- output module. Add IO as required for your appli-
tion with the synchrocheck function to allow inte- cation at ordering. Other signals need to be applied
gration of the main or back-up control. as required for each application.

The advanced logic capability, where the user For details on included basic functions refer to sec-
logic is prepared with a graphical tool, allows spe- tion "Available functions".
cial applications such as automatic opening of dis-
connectors in multi-breaker arrangements, closing The applications are shown in figures 1 and 2 for
of breaker rings, load transfer logics etc. The single resp. multi-breaker arrangement.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 3

BUS B

BUS A

TRIP BUSBAR A or/and B

79 25
CLOSE
O->I SC/VC

94/86
TRIP
I->O

50BF
3I>

87L

3Id/I>

50/51
3I>

59
3U>

27
3U<

TO REMOTE END: en05000302.vsd


FIBRE OPTIC OR TO MUX
Figure 1: The single breaker packages for single- and three phase tripping typical arrangement for one
protection sub-system is shown here. The differential function is more sensitive than any earth
fault or directional earth fault function and these functions are thus an option.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 4

BUS A

TRIP BUSBAR
&CB2

79 25
CLOSE
O->I SC/VC

94/86 CB1
TRIP
I->O
79 25

O->I SC/VC

50BF
50/51
3I>
3I> TRIP
50BF
CB1/3
3I>
94/86
87L
I->O

CLOSE
59
3Id/I>

TRIP
3U>

27
3U< CB2

en05000303.vsd
TO REMOTE END:
FIBRE OPTIC OR TO MUX
Figure 2: The multi breaker packages for single- and three phase tripping typical arrangement for one pro-
tection sub-system is shown here. The differential function is more sensitive than any earth fault
or directional earth fault function and these functions are thus an option. Auto-reclose, Synchro-
check and Breaker failure functions are included for each of the two breakers.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 5

Available
functions
ANSI Function description Single breaker, Multi breaker, Singel breaker, Multi breaker,
3-phase tripping 3-phase tripping 1-phase tripping 1-phase tripping
(A31) (B31) (A32) (B32)
Basic Option Basic Option Basic Option Basic Option
(Qty/ (Qty/ (Qty/ (Qty/
option option option option
design) design) design) design)
Differential protection
(Only one alternative can be selected)
87 High impedance differential protection (PDIF) - 3/A02 - 3/A02 - 3/A02 - 3/A02
87L Line differential protection, 3 CT sets, 2-3 line ends (PDIF) 1 - - - 1 - - -
87L Line differential protection, 6 CT sets, 3-5 line ends (PDIF) - 1/A04 1 - - 1/A04 1 -
87LT Line differential protection 3 CT sets, with in-zone transformers, - 1/A05 - - - 1/A05 - -
2-3 line ends (PDIF)
87LT Line differential protection 6 CT sets, with in-zone transformers, - 1/A06 - 1/A06 - 1/A06 - 1/A06
3-5 line ends (PDIF)

Distance protection
21 Distance protection zones (PDIS) - 3/B01 - 3/B01 - 3/B01 - 3/B01
21 Phase selection with load enchroachment (PDIS) - 1/B01 - 1/B01 - 1/B01 - 1/B01
Directional impedance (RDIR) 1/B01 1/B01 1/B01 1/B01
78 Power swing detection (RPSB) - 1/B01 - 1/B01 - 1/B01 - 1/B01
Automatic switch onto fault logic (PSOF) - 1/B01 - 1/B01 - 1/B01 - 1/B01

Current protection
50 Instantaneous phase overcurrent protection (PIOC) 1 - 1 - 1 - 1 -
51/67 Four step phase overcurrent protection (POCM) 1 - 1 - 1 - 1 -
50N Instantaneous residual overcurrent protection (PIOC) - 1/C04 - 1/C04 - 1/C04 - 1/C04
51N/67N Four step residual overcurrent protection (PEFM) - 1/C04 - 1/C04 - 1/C04 - 1/C04
26 Thermal overload protection, one time constant (PTTR) 1 - 1 - 1 - 1 -
50BF Breaker failure protection (RBRF) 1 - 2 - 1 - 2 -
50STB Stub protection (PTOC) - - 1 - - - 1 -
52PD Pole discordance protection (RPLD) - - - - 1 - 2 -

Voltage protection
27 Two step undervoltage protection (PUVM) 1 - 1 - 1 - 1 -
59 Two step overvoltage protection (POVM) 1 - 1 - 1 - 1 -
59N Two step residual overvoltage protection (POVM) 1 - 1 - 1 - 1 -

Frequency protection
81 Underfrequency protection (PTUF) - 2/E02 - 2/E02 - 2/E02 - 2/E02
81 Overfrequency protection (PTOF) - 2/E02 - 2/E02 - 2/E02 - 2/E02
81 Rate-of-change frequency protection (PFRC) - 2/E02 - 2/E02 - 2/E02 - 2/E02

Multipurpose protection
General current and voltage protection (GAPC) - 4/F01 - 4/F01 - 4/F01 - 4/F01

Secondary system supervision


Current circuit supervision (RDIF) 1 - 2 - 1 - 2 -
Fuse failure supervision (RFUF) 3 - 3 - 3 - 3 -

Control
25 Synchrocheck and energizing check (RSYN) 1 - 2 - 1 - 2 -
79 Autorecloser (RREC) 1 - 2 - 1 - 2 -
Apparatus control for single bay, - 1/H07 - - - 1/H07 - -
max 8 apparatuses (1CB) incl. interlocking (APC8)
Apparatus control for single bay, - - - 1/H08 - - - 1/H08
max 15 apparatuses (2CBs) incl. interlocking (APC15)

Scheme communication
85 Scheme communication logic for distance protection (PSCH) - 1/B01 - 1/B01 - 1/B01 - 1/B01
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 6

ANSI Function description Single breaker, Multi breaker, Singel breaker, Multi breaker,
3-phase tripping 3-phase tripping 1-phase tripping 1-phase tripping
(A31) (B31) (A32) (B32)
Basic Option Basic Option Basic Option Basic Option
(Qty/ (Qty/ (Qty/ (Qty/
option option option option
design) design) design) design)
85 Current reversal and weak-end infeed logic for - 1/B01 - 1/B01 - 1/B01 - 1/B01
distance protection (PSCH)
Local acceleration logic (PLAL) - 1/B01 - 1/B01 - 1/B01 - 1/B01
85 Scheme communication logic for - 1/C04 - 1/C04 - 1/C04 - 1/C04
residual overcurrent protection (PSCH)
85 Current reversal and weak-end infeed logic for - 1/C04 - 1/C04 - 1/C04 - 1/C04
residual overcurrent protection (PSCH)

Logic
94 Tripping logic (PTRC) 1 - 2 - 1 - 2 -
Trip matrix logic (GGIO) 12 - 12 - 12 - 12 -

Monitoring
Measurements (MMXU) 3/10/3 - 3/10/3 - 3/10/3 - 3/10/3 -
Event counter (GGIO) 5 - 5 - 5 - 5 -
Disturbance report (RDRE) 1 - 1 - 1 - 1 -
Fault locator (RFLO) 1 - 1 - 1 - 1 -

Metering
Pulse counter logic (GGIO) 16 - 16 - 16 - 16 -

Station communication
IEC61850-8-1 Communication 1 - 1 - 1 - 1 -
LON communication protocol 1 - 1 - 1 - 1 -
SPA communication protocol 1 - 1 - 1 - 1 -
IEC60870-5-103 communication protocol 1 - 1 - 1 - 1 -
Single command, 16 signals 3 - 3 - 3 - 3 -
Multiple command and transmit 60/10 - 60/10 - 60/10 - 60/10 -

Remote communication
Binary signal transfer 4 - 4 - 4 - 4 -

Functionality Differential protection Line differential protection, 3 or 6


CT sets (PDIF, 87L)
High impedance differential protection The line differential function compares the cur-
(PDIF, 87) rents entering and leaving the protected overhead
The high impedance differential protection can be line or cable. It offers phase-segregated true cur-
used when the involved CT cores have same turn rent differential protection with high sensitivity
ratio and similar magnetizing characteristic. It uti- and provides phase selection information for sin-
lizes an external summation of the phases and neu- gle-pole tripping.
tral current and a series resistor and a voltage
dependent resistor externally to the relay. The three terminal version is used for conventional
two-terminal lines with or without 1 1/2 circuit
breaker arrangement in one end, as well as three
terminal lines with single breaker arrangements at
all terminals.

Protected zone

RED Comm. Channel RED


670 670

en05000039.vsd

Figure 3: Example of application on a conventional two-terminal line


Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 7

The six terminal version is used for conventional arrangements in both ends, as well as multi termi-
two-terminal lines with 1 1/2 circuit breaker nal lines with up to five terminals.

Protected zone

RED RED
670 Comm. Channel 670

Comm. Channel Comm. Channel


RED
670

en05000040.vsd

Figure 4: Example of application on a three-terminal line with 1 1/2 breaker arrangements

The current differential algorithm in RED 670 pro- considered to be negligible, and special measures
vides high sensitivity for internal faults, at the need only to be taken in the event of a short circuit
same time as it has excellent stability for external on the LV side of the transformer. In this applica-
faults. Current samples from all CTs are tion, the tripping of the differential protection can
exchanged between the IEDs in the line ends (mas- be time delayed for low differential currents in
ter-master mode) or sent to one IED (master-slave order to achieve coordination with down stream
mode) for evaluation. over current relays.

A restrained dual biased slope evaluation is made A line charging current compensation provides
where the bias current is the highest phase current increased sensitivity of the differential function.
in any line end giving a secure through fault stabil-
ity even with heavily saturated CTs. In addition to Line differential protection 3 or 6 CT sets,
the restrained evaluation, an unrestrained high dif- with in-zone transformers (PDIF, 87LT)
ferential current setting can be used for fast trip- One or two power transformers can be included in
ping of internal faults with very high currents. the line differential protection zone. Both two- and
three-winding transformers are correctly repre-
A special feature with RED 670 is that applica- sented with vector group compensations made in
tions with small power transformers (rated current the algorithm. The function includes 2nd and 5th
less than 50% of differential current setting) con- harmonic restraint and zero sequence current elim-
nected as line taps without measurement in the tap ination.
can be handled. The normal load current is here

Protected zone

RED Comm. Channel RED


670 670

Comm. Channel Comm. Channel


RED
670
en05000042.vsd

Figure 5: Example of application on a three-terminal line with a power transformer in the protection zone

Analog signal transfer for and an evaluation is made in each terminal. This
line differential protection (MDIF) means that a 64 kbit/s communication channel is
The line differential communication can be needed between every IED included in the same
arranged as a master-master system or a mas- line differential protection zone. In the latter, cur-
ter-slave system alternatively. In the former, cur- rent samples are sent from all slave IEDs to one
rent samples are exchanged between all terminals, master IED where the evaluation is made, and trip
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 8

signals are sent to the remote ends when needed. In only needed between the master, and each one of
this system, a 64 kbit/s communication channel is the slave terminals.

Protected zone

RED RED
670 670
Comm.
Channels

RED RED RED


670 670 670

en05000043.vsd

Figure 6: Five terminal line with master-master system

Protected zone

RED RED
670 670

Comm.
Channels

RED RED RED


670 670 670

en05000044.vsd

Figure 7: Five terminal line with master-slave system

Current samples from IEDs located geographically resistive faults on heavily loaded lines (see
apart from each other, must be time coordinated so figure 8).
that the current differential algorithm can be exe-
cuted correctly. In RED 670 it is possible to make
this coordination in two different ways. The echo X
method of time synchronizing is normally used
whereas for applications where transmit and
receive times can differ, the optional built in GPS Forward
receivers shall be used. operation

The communication link is continuously moni-


tored, and an automatic switchover to a standby
link is possible after a preset time.
R
Distance protection
Reverse
Distance protection zones (PDIS, 21) operation
The line distance protection is a three zone full
scheme protection with three fault loops for phase
to phase faults and three fault loops for phase to
earth fault for each of the independent zones. Indi- en05000034.vsd
vidual settings for each zone resistive and reactive
Figure 8: Typical distance protection zone with
reach gives flexibility for use on overhead lines load encroachment function activated
and cables of different types and lengths.

The function has a functionality for load encroach- The independent measurement of impedance for
ment which increases the possibility to detect high each fault loop together with a sensitive and reli-
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 9

able built in phase selection makes the function eighty percent of the power line at minimum
suitable in applications with single phase source impedance. The function can be configured
auto-reclosing. to measure the residual current from the three
phase current inputs or the current from a separate
Built-in adaptive load compensation algorithm current input.
prevents overreaching of zone1 at load exporting
end at phase-to-earth faults on heavily loaded Four step residual overcurrent
power lines. protection (PEFM, 51N/67N)
The four step single input overcurrent function has
The distance protection zones can operate, inde-
an inverse or definite time delay independent for
pendent of each other, in directional (forward or
each step separately.
reverse) or non-directional mode. This makes them
suitable, together with different communication All IEC and ANSI time delayed characteristics are
schemes, for the protection of power lines and available together with an optional user defined
cables in complex network configurations, such as characteristic.
parallel lines, multi-terminal lines etc.
The function can be set to be directional, forward,
Power swing detection (RPSB, 78) reverse or non-directional independently for each
Power swings may occur after disconnection of of the steps.
heavy loads or trip of big generation plants.
A second harmonic blocking can be set individu-
Power swing detection function is used to detect ally for each step.
power swings and initiate block of selected dis-
tance protection zones. Occurrence of earth fault The function can be used as main protection for
currents during a power swing can block the power phase to earth faults.
swing detection function to allow fault clearance.
The function can be used to provide a system
back-up e.g. in the case of the primary protection
Automatic switch onto fault logic (PSOF)
being out of service due to communication or volt-
Automatic switch onto fault logic is a function that
age transformer circuit failure.
gives an instantaneous trip at closing of breaker
onto a fault. A dead line detection check is pro- Directional operation can be combined together
vided to activate the function when the line is with corresponding communication blocks into
dead. permissive or blocking teleprotection scheme.
Current reversal and weak-end infeed functionality
Current protection are available as well.

The function can be configured to measure the


Instantaneous phase overcurrent residual current from the three phase current inputs
protection (PIOC, 50) or the current from a separate current input.
The instantaneous three phase overcurrent function
has a low transient overreach and short tripping Thermal overload protection, one time
time to allow use as a high set short-circuit protec- constant (PTTR, 26)
tion function, with the reach limited to less than The increasing utilizing of the power system closer
typical eighty percent of the power line at mini- to the thermal limits have generated a need of a
mum source impedance. thermal overload function also for power lines.
Four step phase overcurrent A thermal overload will often not be detected by
protection (POCM, 51_67) other protection functions and the introduction of
The four step phase overcurrent function has an the thermal overload function can allow the pro-
inverse or definite time delay independent for each tected circuit to operate closer to the thermal lim-
step separately. its.

All IEC and ANSI time delayed characteristics are The three phase current measuring function has an
available together with an optional user defined I2t characteristic with settable time constant and a
time characteristic. thermal memory.
The function can be set to be directional or An alarm level gives early warning to allow opera-
non-directional independently for each of the tors to take action well before the line will be
steps. tripped.

Instantaneous residual overcurrent Breaker failure protection (RBRF, 50BF)


protection (PIOC, 50N) The circuit breaker failure function ensures fast
The single input overcurrent function has a low back-up tripping of surrounding breakers. The
transient overreach and short tripping times to breaker failure protection operation can be current
allow use as a high set short circuit protection based, contact based or adaptive combination
function, with the reach limited to less than typical between these two principles.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 10

A current check with extremely short reset time is Two step overvoltage
used as a check criteria to achieve a high security protection (POVM, 59)
against unnecessary operation. Overvoltages will occur in the power system dur-
ing abnormal conditions such as sudden power
The breaker failure protection can be single- or loss, tap changer regulating failures, open line
three-phase started to allow use with single phase ends on long lines.
tripping applications. For the three-phase version
of the breaker failure protection the current criteria The function can be used as open line end detector,
can be set to operate only if two out of four e.g. normally then combined with directional reactive
two phases or one phase plus the residual current over-power function or as system voltage supervi-
starts. This gives a higher security to the back-up sion, normally then giving alarm only or switching
trip command. in reactors or switch out capacitor banks to control
the voltage.
The function can be programmed to give a single-
or three phase re-trip of the own breaker to avoid The function has two voltage steps, each of them
unnecessary tripping of surrounding breakers at an with inverse or definite time delayed.
incorrect starting due to mistakes during testing.
The overvoltage function has an extremely high
Stub protection (PTOC, 50STB) reset ratio to allow setting close to system service
When a power line is taken out of service for voltage.
maintenance and the line disconnector is opened in
multi-breaker arrangements the voltage transform- Two step residual overvoltage
ers will mostly be outside on the disconnected part. protection (POVM, 59N)
The primary line distance protection will thus not Residual voltages will occur in the power system
be able to operate and must be blocked. during earth faults.

The stub protection covers the zone between the The function can be configured to calculate the
current transformers and the open disconnector. residual voltage from the three phase voltage input
The three phase instantaneous overcurrent function transformers or from a single phase voltage input
is released from a NO (b) auxiliary contact on the transformer fed from an open delta or neutral point
line disconnector. voltage transformer.

The function has two voltage steps, each with


Pole discordance protection (RPLD, 52PD)
inverse or definite time delayed.
Single pole operated circuit breakers can due to
electrical or mechanical failures end up with the
different poles in different positions (close-open). Frequency protection
This can cause negative and zero sequence cur-
rents which gives thermal stress on rotating Underfrequency protection (PTUF, 81)
machines and can cause unwanted operation of Underfrequency occurs as a result of lack of gener-
zero sequence current functions. ation in the network.
Normally the own breaker is tripped to correct the The function can be used for load shedding sys-
positions. If the situation consists the remote end tems, remedial action schemes, gas turbine start-up
can be intertripped to clear the unsymmetrical load etc.
situation.
The function is provided with an undervoltage
The pole discordance function operates based on blocking. The operation may be based on single
information from auxiliary contacts of the circuit phase, phase-to-phase or positive sequence voltage
breaker for the three phases with additional criteria measurement.
from unsymmetrical phase current when required.
Up to two independent under frequency function
instances are available.
Voltage protection
Overfrequency protection (PTOF, 81)
Two step undervoltage Overfrequency will occur at sudden load drops or
protection (PUVM, 27) shunt faults in the power network. In some cases
Undervoltages can occur in the power system dur- close to generating part governor problems can
ing faults or abnormal conditions. The function also cause overfrequency.
can be used to open circuit breakers to prepare for
system restoration at power outages or as The function can be used for generation shedding,
long-time delayed back-up to primary protection. remedial action schemes etc. It can also be used as
a sub-nominal frequency stage initiating load
The function has two voltage steps, each with restoring.
inverse or definite time delay.
The function is provided with an undervoltage
blocking. The operation may be based on single
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 11

phase, phase-to-phase or positive sequence voltage A detection of a difference indicates a fault in the
measurement. circuit and is used as alarm or to block protection
functions expected to give unwanted tripping.
Up to two independent over frequency function
instances are available. Fuse failure supervision (RFUF)
Failures in the secondary circuits of the voltage
Rate-of-change frequency transformer can cause unwanted operation of dis-
protection (PFRC, 81) tance protection, undervoltage protection, neutral
Rate of change of frequency function gives an point voltage protection, energizing function (syn-
early indication of a main disturbance in the sys- chrocheck) etc. The fuse failure supervision func-
tem. tion prevents such unwanted operations.
The function can be used for generation shedding, There are three methods to detect fuse failures.
load shedding, remedial action schemes etc.
The method based on detection of zero sequence
The function is provided with an undervoltage voltage without any zero sequence current. This is
blocking. The operation may be based on single a useful principle in a directly earthed system and
phase, phase-to-phase or positive sequence voltage can detect one or two phase fuse failures.
measurement.
The method based on detection of negative
Each step can discriminate between positive or sequence voltage without any negative sequence
negative change of frequency. current. This is a useful principle in a non-directly
earthed system and can detect one or two phase
Up to two independent rate-of-change frequency fuse failures.
function instances are available.
The method based on detection of du/dt-di/dt
where a change of the voltage is compared to a
Multipurpose protection change in the current. Only voltage changes means
a voltage transformer fault. This principle can
General current and voltage detect one, two or three phase fuse failures.
protection (GAPC)
The function can be utilized as a negative
sequence current protection detecting unsymmetri- Control
cal conditions such as open phase or unsymmetri-
cal faults. Synchrocheck and energizing check
(RSYN, 25)
The function can also be used to improve phase The synchrocheck function checks that the volt-
selection for high resistive earth faults, outside the ages on both sides of the circuit breaker are in syn-
distance protection reach, for the transmission line. chronism, or with at least one side dead to ensure
Three functions are used which measures the neu- that closing can be done safely.
tral current and each of the three phase voltages.
This will give an independence from load currents The function includes a built-in voltage selection
and this phase selection will be used in conjunc- scheme for double bus and one- and a half or ring
tion with the detection of the earth fault from the busbar arrangements.
directional earth fault protection function.
Manual closing as well as automatic reclosing can
be checked by the function and can have different
Secondary system supervision settings, e.g. the allowed frequency difference can
be set to allow wider limits for the auto-reclose
Current circuit supervision (RDIF) attempt than for the manual closing.
Open or short circuited current transformer cores
can cause unwanted operation of many protection Autorecloser (RREC, 79)
functions such as differential, earth fault current The autoreclosing function provides high-speed
and negative sequence current functions. and/or delayed auto-reclosing for single or
multi-breaker applications.
It must be remembered that a blocking of protec-
tion functions at an occurring open CT circuit will Up to five reclosing attempts can be programmed.
mean that the situation will remain and extremely The first attempt can be single-, two and/or three
high voltages will stress the secondary circuit. phase for single phase or multi-phase faults
respectively.
The current circuit supervision function compares
the residual current from a three phase set of cur- Multiple autoreclosing functions are provided for
rent transformer cores with the neutral point cur- multi-breaker arrangements. A priority circuit
rent on a separate input taken from another set of allows one circuit breaker to close first and the
cores on the current transformer. second will only close if the fault proved to be
transient.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 12

Each autoreclosing function can be configured to using permissive overreach protection schemes in
co-operate with a synchrocheck function. application with parallel lines when the overreach
from the two ends overlaps on the parallel line.
Apparatus control (APC)
The apparatus control is a function for control and The weak-end infeed logic is used in cases where
supervision of circuit breakers, disconnectors and the apparent power behind the protection can be
earthing switches within a bay. Permission to oper- too low to activate the distance protection func-
ate is given after evaluation of conditions from tion. When activated, received carrier signal
other functions such as interlocking, synchro- together with local under voltage criteria and no
check, operator place selection and external or reverse zone operation gives an instantaneous trip.
internal blockings. The received signal is also echoed back to acceler-
ate the sending end.
Interlocking
The interlocking function blocks the possibility to Local acceleration logic (PLAL)
operate primary switching devices, for instance To achieve fast clearing of faults on the whole line,
when a disconnector is under load, in order to pre- when no communication channel is available, local
vent material damage and/or accidental human acceleration logic (ZCLC) can be used. This logic
injury. enables fast fault clearing during certain condi-
tions, but naturally, it can not fully replace a com-
Each apparatus control function has interlocking munication channel.
modules included for different switchyard arrange-
ments, where each function handles interlocking of The logic can be controlled either by the auto
one bay. The interlocking function is distributed to re-closer (zone extension) or by the loss of load
each IED and is not dependent on any central func- current (loss-of-load acceleration).
tion. For the station-wide interlocking, the IEDs
communicate via the system-wide interbay bus Logic
(IEC 61850-8-1) or by using hard wired binary
inputs/outputs. The interlocking conditions depend
on the circuit configuration and apparatus position Tripping logic (PTRC, 94)
status at any given time. A function block for protection tripping is pro-
vided for each circuit breaker involved in the trip-
For easy and safe implementation of the interlock- ping of the fault. It provides the pulse prolongation
ing function, the IED is delivered with standard- to ensure a trip pulse of sufficient length, as well as
ized and tested software interlocking modules all functionality necessary for correct co-operation
containing logic for the interlocking conditions. with autoreclosing functions.
The interlocking conditions can be altered, to meet
the customers specific requirements, by adding The trip function block includes functionality for
configurable logic by means of the graphical con- evolving faults and breaker lock-out.
figuration tool.
Trip matrix logic (GGIO, 94X)
Twelve trip matrix logic blocks are included in the
Scheme communication IED. The function blocks are used in the configu-
ration of the IED to route trip signals and/or other
Scheme communication logic for logical output signals to the different output relays.
distance protection and directional
residual overcurrent protection (PSCH, 85) The matrix and the physical outputs will be seen in
To achieve instantaneous fault clearance for all the PCM 600 engineering tool and this allows the
line faults, a scheme communication logic is pro- user to adapt the signals to the physical tripping
vided. All types of communication schemes e.g. outputs according to the specific application needs.
permissive underreach, permissive overreach,
blocking, intertrip etc. are available. The built-in Configurable logic blocks
communication module (LDCM) can be used for A high number of logic blocks and timers are
scheme communication signalling when included. available for user to adapt the configuration to the
specific application needs.
Logic for loss of load and/or local acceleration in
co-operation with autoreclose function is also pro- Fixed signal function block
vided for application where no communication The fixed signals function block generates a num-
channel is available. ber of pre-set (fixed) signals that can be used in the
configuration of an IED, either for forcing the
Current reversal and weak-end infeed logic unused inputs in the other function blocks to a cer-
for distance protection and directional tain level/value, or for creating a certain logic.
residual overcurrent protection (PSCH, 85)
The current reversal function is used to prevent
unwanted operations due to current reversal when
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 13

Monitoring Event List (EL)


Indications (IND)
Measurements (MMXU) Event recorder (ER)
The service value function is used to get on-line
information from the IED. These service values Trip Value recorder (TVR)
makes it possible to display on-line information on Disturbance recorder (DR)
the local HMI and on the Substation automation
system about: Fault Locator (FL)

measured voltages, currents, frequency, active, The function is characterized by great flexibility
reactive and apparent power and power factor, regarding configuration, starting conditions,
recording times and large storage capacity.
the primary and secondary phasors,
differential currents, bias currents, A disturbance is defined as an activation of an
input in the DRAx or DRBy function blocks which
positive, negative and zero sequence currents
is set to trigger the disturbance recorder. All sig-
and voltages, nals from start of pre-fault time to the end of
mA, post-fault time, will be included in the recording.
pulse counters, Every disturbance report recording is saved in the
measured values and other information of the IED in the standard Comtrade format. The same
different parameters for included functions, applies to all events, which are continuously saved
in a ring-buffer. The Local Human Machine Inter-
logical values of all binary in- and outputs and
face (LHMI) is used to get information about the
general IED information. recordings, but the disturbance report files may be
uploaded to the PCM 600 (Protection and Control
Supervision of mA input signals (MVGGIO) IED Manager) and further analysis using the dis-
The main purpose of the function is to measure turbance handling tool.
and process signals from different measuring
transducers. Many devices used in process control Event list (RDRE)
represent various parameters such as frequency, Continuous event-logging is useful for monitoring
temperature and DC battery voltage as low current of the system from an overview perspective and is
values, usually in the range 4-20 mA or 0-20 mA. a complement to specific disturbance recorder
functions.
Alarm limits can be set and used as triggers, e.g. to
generate trip or alarm signals. The event list logs all binary input signals con-
nected to the Disturbance report function. The list
The function requires that the IED is equipped may contain of up to 1000 time-tagged events
with the mA input module. stored in a ring-buffer.

Event counter (GGIO) Indications (RDRE)


The function consists of six counters which are To get fast, condensed and reliable information
used for storing the number of times each counter about disturbances in the primary and/or in the
has been activated. It is also provided with a com- secondary system it is important to know e.g.
mon blocking function for all six counters, to be binary signals that have changed status during a
used for example at testing. Every counter can sep- disturbance. This information is used in the short
arately be set on or off by a parameter setting. perspective to get information via the LHMI in a
straightforward way.
Disturbance report (RDRE)
Complete and reliable information about distur- There are three LEDs on the LHMI (green, yellow
bances in the primary and/or in the secondary sys- and red), which will display status information
tem together with continuous event-logging is about the IED and the Disturbance Report function
accomplished by the disturbance report functional- (trigged).
ity.
The Indication list function shows all selected
The disturbance report, always included in the binary input signals connected to the Disturbance
IED, acquires sampled data of all selected ana- Report function that have changed status during a
logue input and binary signals connected to the disturbance.
function block i.e. maximum 40 analogue and 96
binary signals. Event recorder (RDRE)
Quick, complete and reliable information about
The disturbance report functionality is a common disturbances in the primary and/or in the second-
name for several functions: ary system is vital e.g. time tagged events logged
during disturbances. This information is used for
different purposes in the short term (e.g. corrective
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 14

actions) and in the long term (e.g. Functional Event function block. The event function block is
Analysis). used for LON and SPA communication.

The event recorder logs all selected binary input Analog and double indication values are also
signals connected to the Disturbance Report func- transferred through the event block.
tion. Each recording can contain up to 150
time-tagged events. Fault locator (RFLO)
The accurate fault locator is an essential compo-
The event recorder information is available for the nent to minimize the outages after a persistent fault
disturbances locally in the IED. and/or to pin-point a weak spot on the line.
The event recording information is an integrated The built-in fault locator is an impedance measur-
part of the disturbance record (Comtrade file). ing function giving the distance to the fault in per-
cent, km or miles. The main advantage is the high
Trip value recorder (RDRE) accuracy achieved by compensating for load cur-
Information about the pre-fault and fault values for rent and for the mutual zero sequence effect on
currents and voltages are vital for the disturbance double circuit lines.
evaluation.
The compensation includes setting of the remote
The Trip value recorder calculates the values of all and local sources and calculation of the distribu-
selected analogue input signals connected to the tion of fault currents from each side. This distribu-
Disturbance report function. The result is magni- tion of fault current, together with recorded load
tude and phase angle before and during the fault (pre-fault) currents, is used to exactly calculate the
for each analogue input signal. fault position. The fault can be recalculated with
new source data at the actual fault to further
The trip value recorder information is available for increase the accuracy.
the disturbances locally in the IED.
Specially on heavily loaded long lines (where the
The trip value recorder information is an inte- fault locator is most important) where the source
grated part of the disturbance record (Comtrade voltage angles can be up to 35-40 degrees apart the
file). accuracy can be still maintained with the advanced
compensation included in fault locator.
Disturbance recorder (RDRE)
The Disturbance Recorder function supplies fast,
complete and reliable information about distur- Metering
bances in the power system. It facilitates under-
standing system behavior and related primary and Pulse counter logic (GGIO)
secondary equipment during and after a distur- The pulse counter logic function counts externally
bance. Recorded information is used for different generated binary pulses, for instance pulses com-
purposes in the short perspective (e.g. corrective ing from an external energy meter, for calculation
actions) and long perspective (e.g. Functional of energy consumption values. The pulses are cap-
Analysis). tured by the binary input module and then read by
the pulse counter function. A scaled service value
The Disturbance Recorder acquires sampled data is available over the station bus. The special
from all selected analogue input and binary signals Binary input module with enhanced pulse counting
connected to the Disturbance Report function capabilities must be ordered to achieve this func-
(maximum 40 analog and 96 binary signals). The tionality.
binary signals are the same signals as available
under the event recorder function.
Basic IED functions
The function is characterized by great flexibility
and is not dependent on the operation of protection
Time synchronization
functions. It can record disturbances not detected
Use the time synchronization source selector to
by protection functions.
select a common source of absolute time for the
The disturbance recorder information for the last IED when it is a part of a protection system. This
100 disturbances are saved in the IED and the makes comparison of events and disturbance data
Local Human Machine Interface (LHMI) is used between all IEDs in a SA system possible.
to view the list of recordings.
Human machine interface
Event function (EV) The local human machine interface is available in
When using a Substation Automation system with a small, and a medium sized model. The principle
LON or SPA communication, time-tagged events difference between the two is the size of the LCD.
can be sent at change or cyclically from the IED to The small size LCD can display seven line of text
the station level. These events are created from any and the medium size LCD can display the single
available signal in the IED that is connected to the line diagram with up to 15 objects on each page.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 15

Six SLD pages can be defined.

The local human machine interface is equipped


with an LCD that can display the single line dia-
gram with up to 15 objects.

The local human-machine interface is simple and


easy to understand the whole front plate is
divided into zones, each of them with a
well-defined functionality:

Status indication LEDs


Alarm indication LEDs which consists of 15
LEDs (6 red and 9 yellow) with user printable
label. All LEDs are configurable from the
PCM 600 tool
Liquid crystal display (LCD)
Keypad with push buttons for control and nav-
igation purposes, switch for selection between
local and remote control and reset
An isolated RJ45 communication port

Figure 10: Medium graphic HMI, 15 controllable


objects

Station communication
Overview
Each IED is provided with a communication inter-
face, enabling it to connect to one or many substa-
tion level systems or equipment, either on the
Substation Automation (SA) bus or Substation
Monitoring (SM) bus.

Following communication protocols are available:

IEC 61850-8-1 communication protocol


LON communication protocol
SPA or IEC 60870-5-103 communication pro-
tocol

Theoretically, several protocols can be combined


in the same IED.
Figure 9: Small graphic HMI
IEC 61850-8-1 communication protocol
Single or double optical Ethernet ports for the new
substation communication standard IEC61850-8-1
for the station bus are provided. IEC61850-8-1
allows intelligent devices (IEDs) from different
vendors to exchange information and simplifies
SA engineering. Peer- to peer communication
according to GOOSE is part of the standard. Dis-
turbance files uploading is provided.

Serial communication, LON


Existing stations with ABB station bus LON can
be extended with use of the optical LON interface.
This allows full SA functionality including
peer-to-peer messaging and cooperation between
existing ABB IED's and the new IED 670.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 16

SPA communication protocol Remote communication


A single glass or plastic port is provided for the
ABB SPA protocol. This allows extensions of sim- Binary signal transfer to remote end,
ple substation automation systems but the main 8 signals
use is for Substation Monitoring Systems SMS. The binary signal transfer function can be used for
sending and receiving of eight communication
IEC 60870-5-103 communication protocol scheme related signals, transfer trip and/or other
A single glass or plastic port is provided for the binary signals between line differential IEDs. The
IEC60870-5-103 standard. This allows design of number of function blocks depends on the number
simple substation automation systems including of remote terminals. An IED can communicate
equipment from different vendors. Disturbance with up to 4 remote IEDs. Each function block cor-
files uploading is provided. responds to one communication channel.

Single command, 16 signals Line data communication module, short,


The IEDs can receive commands either from a medium and long range (LDCM)
substation automation system or from the local The line data communication module (LDCM) is
human-machine interface, LHMI. The command used for communication between the IEDs situated
function block has outputs that can be used, for at distances <150 km or from the IED to optical to
example, to control high voltage apparatuses or for electrical converter with G.703 or G.703E1 inter-
other user defined functionality. face located on a distances <3 km away. The
LDCM module sends and receives data, to and
Multiple command and transmit from another LDCM module. The IEEE/ANSI
When 670 IED's are used in Substation Automa- C37.94 standard format is used.
tion systems with LON, SPA or IEC60870-5-103
communication protocols the Event and Multiple The line data communication module is used for
Command function blocks are used as the commu- binary signal transfer. The module has one optical
nication interface for vertical communication to port with ST connectors.
station HMI and gateway and as interface for hori-
zontal peer-to-peer communication (over LON Galvanic interface G.703
only). The external galvanic data communication con-
verter G.703 makes an optical-to-galvanic conver-
sion for connection to a multiplexer. These units
are designed for 64 kbit/s operation. The converter
is delivered with 19 rack mounting accessories.

Hardware Hardware modules Binary input/output module (IOM)


The binary input/output module is used when only
description a few input and output channels are needed. The
Power supply module (PSM)
The power supply module is used to provide the ten standard output channels are used for trip out-
correct internal voltages and full isolation between put or any signalling purpose. The two high speed
the terminal and the battery system. An internal signal output channels are used for applications
fail alarm output is available. where short operating time is essential. Eight opti-
cally isolated binary inputs cater for required
Binary input module (BIM) binary input information.
The binary input module has 16 optically isolated
inputs and is available in two versions, one stan- mA input module (MIM)
dard and one with enhanced pulse counting capa- The milli-ampere input module is used to interface
bilities on the inputs to be used with the pulse transducer signals in the 20 to +20 mA range
counter function. The binary inputs are freely pro- from for example OLTC position, temperature or
grammable and can be used for the input of logical pressure transducers.The module has six indepen-
signals to any of the functions. They can also be dent, galvanically separated channels.
included in the disturbance recording and
event-recording functions. This enables extensive Optical ethernet module (OEM)
monitoring and evaluation of operation of the IED The optical fast-ethernet module is used to connect
and for all associated electrical circuits. an IED to the communication buses (like the sta-
tion bus) that use the IEC 61850-8-1 protocol. The
Binary output modules (BOM) module has one or two optical ports with ST con-
The binary output module has 24 independent out- nectors.
put relays and is used for trip output or any signal-
ling purpose. Serial SPA/IEC 60870-5-103 and LON
communication module (SLM)
The optical serial channel and LON channel mod-
ule is used to connect an IED to the communica-
tion that use SPA, LON, or IEC608705103. The
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 17

module has two optical ports for plastic/plastic, Transformer input module (TRM)
plastic/glass, or glass/glass. The transformer input module is used to galvani-
cally separate and transform the secondary cur-
Line data communication module (LDCM) rents and voltages generated by the measuring
The line data communication module is used for transformers. The module has twelve inputs in dif-
binary signal transfer. Each module has one optical ferent combinations.
port, one for each remote end to which the IED
communicates. High impedance resistor unit
The high impedance resistor unit, with resistors for
Alternative cards for Short range (900 nm multi pick-up value setting and a voltage dependent
mode) are available. resistor, is available in a single phase unit and a
three phase unit. Both are mounted on a 1/1 19
GPS time synchronization module (GSM) inch apparatus plate with compression type term-
This module includes the GPS receiver used for nals.
time synchronization. The GPS has one SMA con-
tact for connection to an antenna.

Layout and dimensions


Dimensions

B C
D

xx05000003.vsd
xx05000004.vsd

Figure 11: 1/2 x 19 case with rear cover Figure 12: Side-by-side mounting

Case size A B C D E F
6U, 1/2 x 19 265.9 223.7 201.1 242.1 252.9 205.7
6U, 3/4 x 19 265.9 336.0 201.1 242.1 252.9 318.0
6U, 1/1 x 19 265.9 448.1 201.1 242.1 252.9 430.3
(mm)

Mounting alternatives Wall mounting kit


Following mounting alternatives (IP40 protection
from the front) are available: See ordering for details about available mounting
alternatives.
19 rack mounting kit
Flush mounting kit with cut-out dimensions:
- 1/2 case size (h) 254.3 mm (w) 210.1 mm
- 3/4 case size (h) 254.3 mm (w) 322.4mm
- 1/1 case size (h) 254.3 mm (w) 434.7mm
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 18

Connection Table 1: Designations for 1/2 x 19 casing with 1 TRM slot


diagrams
Module Rear Positions
PSM X11
BIM, BOM or IOM X31 and X32 etc. to X51 and X52
GSM X51
SLM X301:A, B, C, D
OEM X311:A, B, C, D
LDCM X312:A, B
LDCM X313:A, B
TRM X401

Table 2: Designations for 3/4 x 19 casing with 2TRM slot

Module Rear Positions


PSM X11
BIM, BOM, IOM or MIM X31 and X32 etc. to X71 and X72
GSM X71
SLM X301:A, B, C, D
LDCM X302:A, B
LDCM X303:A, B
OEM X311:A, B, C, D
LDCM X312:A, B
LDCM X313:A, B
TRM X401, 411

Table 3: Designations for 1/1 x 19 casing with 2 TRM slots

Module Rear Positions


PSM X11
BIM, BOM or IOM X31 and X32 etc. to X131 and X132
MIM X31, X41, etc. or X131
GSM X131
SLM X301:A, B, C, D
OEM X311:A, B, C, D
LDCM X312:A, B
LDCM X313:A, B
TRM 1 X401
TRM 2 X411
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 19

CT/VT-input designation according to figure 13


Current/voltage AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 AI09 AI10 AI11 AI12
configuration
(50/60 Hz)
9I and 3U, 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 0-220V 0-220V 0-220V
9I and 3U, 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 0-220V 0-220V 0-220V
5I, 1A and 4I, 5A 1A 1A 1A 1A 1A 5A 5A 5A 5A 0-220V 0-220V 0-220V
and 3U
6I and 6U, 1A 1A 1A 1A 1A 1A 1A 0-220V 0-220V 0-220V 0-220V 0-220V 0-220V
6I and 6U, 5A 5A 5A 5A 5A 5A 5A 0-220V 0-220V 0-220V 0-220V 0-220V 0-220V

Figure 13: Transformer input


module (TRM)

Figure 14: Binary input module (BIM). Input contacts named XA Figure 15: mA input module (MIM)
corresponds to rear position X31, X41, etc. and input
contacts named XB to rear position X32, X42, etc.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 20

Figure 17: Communication interfaces (OEM,


LDCM, SLM and HMI)
Note to figure 17
1) Rear communication port IEC 61850, ST-connector
Figure 16: Binary in/out module (IOM). Input contacts named XA corresponds to rear 2) Rear communication port C37.94, ST-connector
position X31, X41, etc. and output contacts named XB to rear position X32, 3) Rear communication port SPA/ IEC 60870-5-103,
X42, etc. ST connector for glass alt. HFBR Snap-in connector
for plastic as ordered
4) Rear communication port LON, ST connector for
glass alt. HFBR Snap-in connector for plastic as
ordered
5) Front communication port, Ethernet, RJ45 connector

Figure 19: GPS time synchronization module


(GSM)

Figure 18: Power supply module (PSM)


Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 21

Figure 20: Binary output module (BOM). Output contacts named XA corresponds to rear position X31,
X41, etc. and output contacts named XB to rear position X32, X42, etc.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 22

BUS A
BBP-TRIP BUS B
QB1-OPEN
ST BFP L1 *) QB1-CL
ST BFP L2 *) QB2-OPEN
ST BFP L3 *) QB2-CL -QB1
ST BFP 3PH -QB2

START AR
INHIBIT AR
TRM1:10
3PH TRIP *) MCB-OK

IN TEST
TRM1:11
MAN CLOSE MCB-OK

-QA1
CLOSE QA1 C
C
CLOSE Reinf
*) TRIP QA1 L1,L2,L3 REL/RED 3 Phase T
C
*) TRIP Reinf MAIN 2 TRIP T
QA1-OPEN C

QA1-CL
SIGNALLING

QA1-PD
FAULT

QA1-SPR UNCH

-BI1 P1
TRM1:1-3

Reserved for parallal line


TRM1:5
IN at mutual comp of FL

TO MAIN 2 RELAY

BUSBAR TRIP
PERMIT 1PH *) TO BUS PROT
TRIP MAIN 2
1PH AR IN PROG *)

CR Z<
CS Z<
TO/FROM PLC/MUX

QB9-OPEN
QB9-CL
CR DEF
CS DEF
-QB9

CR DIT
MCB OR
FUSE -BU1
CS DIT
TRM1:7-9
MCB-OK

X11 O NOTE! CB CLosed is


3 IRF X11 2 CB Closed L1&L2&L3
5 4
- + REMOTE END CB Open is CB Open
COMMUNICATION L1 OR L2 OR L3
*) is only valid for single phase tripping arrangements en05000261.vsd

Figure 21: Typical connection diagram for a single breaker arrangement with control integrated.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 23

BUS A
BBP-TRIP
QB1-OPEN
ST BFP L1 *) QB1-CL -BU1
ST BFP L2 *) QB6-OPEN
-QB1
ST BFP L3 *) QB6-CL
ST BFP 3PH

START AR MCB OR
FUSE
INHIBIT AR
TRM1:11
3PH TRIP *) MCB-OK
=1-QA1
MAN CLOSE =1 CLOSE QA1 C
C
CLOSE Reinf
TRIP QA1 L1,L2,L3 REL/RED 3 Phase
*) T
C
*) TRIP Reinf MAIN 2 TRIP
T
QA1-OPEN
SIGNALLING

C
QA1-CL
FAULT

QA1-PD
QA1-SPR UNCH

-BI1 P1
TRM1:1-3
ST BFP L1 TO MAIN 2 RELAY
ST BFP L2
=2-QB9-OPEN
ST BFP L3 TO BUS PROT
=2-QB9-CL
ST BFP 3PH For Voltage
=2-QA1-OPEN
selection
START AR =2-QA1-CL
MCB OR -BU1 -QB6
INHIBIT AR FUSE
TRM1:7-9
3PH TRIP -QB9
MCB-OK

IN TEST QB9-OPEN
QB9-CL
-QB61
MAN CLOSE =3
TO MAIN 2 RELAY -BI1
BUSBAR TRIP
TRM2:1-3
TRIP =2-QA1 Reserved for parallal line IN P1
PERMIT 1PH TRIP TRM1:5 at mutual comp of FL =3-QA1
MAIN 2, =1 *) CLOSE QA1 C
C
PERMIT 1PH TRIP CLOSE Reinf
MAIN 2, =3 *) TRIP QA1 L1,L2,L3 T
C
1PH AR IN PROG *) TRIP Reinf MAIN 2 TRIP T
QA1-OPEN C
CR Z< QA1-CL
CS Z< QA1-PD
TO/FROM PLC/MUX

QA1-SPR
CR DEF UNCH
-QB62 -QB9
CS DEF MCB-OK
-BU1 -QB6
CR DIT TRM2:11
MCB OR
CS DIT
TRM1:12 FUSE
DIT2 Line 2 MCB OR =2-QA1 NOTE! CB CLosed is
MCB-OK FUSE
CB Closed L1&L2&L3
CB Open is CB Open
X11 O -BU1 L1 OR L2 OR L3
3 IRFX11 2
5 4
- + REMOTE END -QB2 BUS B
COMMUNICATION
*) is only valid for single phase tripping arrangements en05000267.vsd

Figure 22: Typical connection diagram for a multi breaker arrangement (1 1/2 CB) with control integrated.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 24

Technical data General


Definitions

Reference value:
The specified value of an influencing factor to which are referred the characteristics of the equipment.
Nominal range:
The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the
specified requirements.
Operative range:
The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform
its intended functions according to the specified requirements.

Energizing quantities, rated values and limits


Analog inputs
Table 4: TRM - Energizing quantities, rated values and limits
Quantity Rated value Nominal range
Current Ir = 1 or 5 A (0.2-40) Ir
Operative range (0.02-100) x Ir
Permissive overload 4 Ir cont.
100 Ir for 1 s *)
Burden < 0.25 VA at Ir = 1 or 5 A
Ac voltage Ur = 110 V 0.5288 V
Operative range (0340) V
Permissive overload 420 V cont.
450 V 10 s
Burden < 0.2 VA at 220 V
< 0.1 VA at 110 V
Frequency fr = 50/60 Hz 5%
*)
max. 350 A for 1 s when COMBITEST test switch is included.

Table 5: MIM - mA input module


Quantity: Rated value: Nominal range:
Input range 5, 10, 20mA -
0-5, 0-10, 0-20, 4-20mA
Input resistance Rin = 194 Ohm -
Power consumption -
each mA-board 4W
each mA input 0.1 W

Auxiliary DC voltage
Table 6: PSM - Power supply module
Quantity Rated value Nominal range
Auxiliary dc voltage, EL (input) EL = (24 - 60) V EL 20%
EL = (90 - 250) V EL 20%
Power consumption 50 W typically -
Auxiliary DC power in-rush < 5 A during 0.1 s -

Binary inputs and outputs


Table 7: BIM - Binary input module
Quantity Rated value Nominal range
Binary inputs 16 -
DC voltage, RL RL24 (24/40) V RL 20%
RL48 (48/60) V RL 20%
RL110 (110/125) V RL 20%
RL220 (220/250) V RL 20%
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 25

Quantity Rated value Nominal range


Power consumption
RL24 = (24/40) V max. 0.05 W/input -
RL48 = (48/60) V max. 0.1 W/input
RL110 = (110/125) V max. 0.2 W/input
RL220 = (220/250) V max. 0.4 W/input
Counter input frequency 10 pulses/s max -
Oscillating signal discriminator Blocking settable 140 Hz
Release settable 130 Hz

Table 8: BIM - Binary input module with enhanced pulse counting capabilities
Quantity Rated value Nominal range
Binary inputs 16 -
DC voltage, RL RL24 (24/40) V RL 20%
RL48 (48/60) V RL 20%
RL110 (110/125) V RL 20%
RL220 (220/250) V RL 20%
Power consumption
RL24 = (24/40) V max. 0.05 W/input -
RL48 = (48/60) V max. 0.1 W/input
RL110 = (110/125) V max. 0.2 W/input
RL220 = (220/250) V max. 0.4 W/input
Counter input frequency 10 pulses/s max -
Balanced counter input frequency 40 pulses/s max -
Oscillating signal discriminator Blocking settable 140 Hz
Release settable 130 Hz

Table 9: IOM - Binary input/output module


Quantity Rated value Nominal range
Binary inputs 8 -
DC voltage, RL RL24 = (24/40) V RL 20%
RL48 = (48/60) V RL 20%
RL110 = (110/125) V RL 20%
RL220 = (220/250) V RL 20%
Power consumption -
RL24 = (24/40) V max. 0.05 W/input
RL48 = (48/60) V max. 0.1 W/input
RL110 = (110/125) V max. 0.2 W/input
RL220 = (220/250) V max. 0.4 W/input

Table 10: IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel reed relay)
Binary outputs 10 2
Max system voltage 250 V AC, DC 250 V AC, DC
Test voltage across open contact, 1 min 1000 V rms 800 V DC
Current carrying capacity
Continuous 8A 8A
1s 10 A 10 A
Making capacity at inductive load with
L/R>10 ms
0.2 s 30 A 0.4 A
1.0 s 10 A 0.4 A
Breaking capacity for AC, cos > 0.4 250 V/8.0 A 250 V/8.0 A
Breaking capacity for DC with L/R < 40 48 V/1 A 48 V/1 A
ms 110 V/0.4 A 110 V/0.4 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A
Maximum capacitive load - 10 nF
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 26

Table 11: BOM - Binary output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and Signal relays
Binary outputs 24
Max system voltage 250 V AC, DC
Test voltage across open contact, 1 min 1000 V rms
Current carrying capacity
Continuous 8A
1s 10 A
Making capacity at inductive load with L/R>10 ms
0.2 s 30 A
1.0 s 10 A
Breaking capacity for AC, cos >0.4 250 V/8.0 A
Breaking capacity for DC with L/R < 40 ms 48 V/1 A
110 V/0.4 A
220 V/0.2 A
250 V/0.15 A

Influencing factors
Table 12: Temperature and humidity influence
Parameter Reference value Nominal range Influence
Ambient temperature, oper- +20 C -10 C to +55 C 0.02% /C
ate value
Relative humidity 10%-90% 10%-90% -
Operative range 0%-95%
Storage temperature -40 C to +70 C - -

Table 13: Auxiliary DC supply voltage influence on functionality during operation


Dependence on Reference value Within nominal range Influence
Ripple, in DC auxiliary voltage max. 2% 12% of EL 0.01% /%
Operative range Full wave rectified
Auxiliary voltage dependence, operate value 20% of EL 0.01% /%
Interrupted auxiliary DC voltage 24-60 V DC 20%
90-250 V DC 20%
Interruption interval
050 ms No restart
0 s Correct behaviour at
power down
Restart time <140 s

Table 14: Frequency influence (reference standard: IEC 602556)


Dependence on Within nominal range Influence
Frequency dependence, operate value fr 2.5 Hz for 50 Hz 1.0% / Hz
fr 3.0 Hz for 60 Hz
Harmonic frequency dependence (20% 2nd, 3rd and 5th harmonic of fr 1.0%
content)
Harmonic frequency dependence for 2nd, 3rd and 5th harmonic of fr 6.0%
distance protection (10% content)

Type tests according to standards


Table 15: Electromagnetic compatibility
Test Type test values Reference standards
1 MHz burst disturbance 2.5 kV IEC 60255-22-1, Class III
100 kHz disturbance 2.5 kV IEC 61000-4-12, Class III
Electrostatic discharge 15 kV air discharge IEC 60255-22-2, Class IV
Direct applicaton 8 kV contact discharge
Indirect application 8 kV contact discharge IEC 61000-4-2, Class IV
Fast transient disturbance 4 kV IEC 60255-22-4, Class A
Surge immunity test 1-2 kV, 1.2/50 s IEC 60255-22-5
high energy
Power frequency immunity test 150-300 V, IEC 60255-22-7, Class A
50 Hz
Power frequency magnetic field test 1000 A/m, 3 s IEC 61000-4-8, Class V
Radiated electromagnetic field disturbance 20 V/m, 80-1000 MHz IEC 60255-22-3
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 27

Test Type test values Reference standards


Radiated electromagnetic field disturbance 20 V/m, 80-2500 MHz EN 61000-4-3
Radiated electromagnetic field disturbance 35 V/m IEEE/ANSI C37.90.2
26-1000 MHz
Conducted electromagnetic field distur- 10 V, 0.15-80 MHz IEC 60255-22-6
bance
Radiated emission 30-1000 MHz IEC 60255-25
Conducted emission 0.15-30 MHz IEC 60255-25

Table 16: Insulation


Test Type test values Reference standard
Dielectric test 2.0 kV AC, 1 min. IEC 60255-5
Impulse voltage test 5 kV, 1.2/50 s, 0.5 J
Insulation resistance >100 M at 500 VDC

Table 17: Environmental tests


Test Type test value Reference standard
Cold test Test Ad for 16 h at -25C IEC 60068-2-1
Storage test Test Ad for 16 h at -40C IEC 60068-2-1
Dry heat test Test Bd for 16 h at +70C IEC 60068-2-2
Damp heat test, steady state Test Ca for 4 days at +40 C and humidity IEC 60068-2-3
93%
Damp heat test, cyclic Test Db for 6 cycles at +25 to +55 C and IEC 60068-2-30
humidity 93 to 95% (1 cycle = 24 hours)

Table 18: CE compliance


Test According to
Immunity EN 61000-6-2
Emissivity EN 61000-6-4
Low voltage directive EN 50178

Table 19: Mechanical tests


Test Type test values Reference standards
Vibration Class I IEC 60255-21-1
Shock and bump Class I IEC 60255-21-2
Seismic Class I IEC 60255-21-3

Differential protection
Table 20: High impedance differential protection (PDIF, 87)
Function Range or value Accuracy
Operate voltage (20-400) V 1.0% of Ur for U < Ur
1.0% of U for U > Ur
Reset ratio >95% -
Maximum continuous voltage U>Trip2/series resistor 200 W -
Operate time 10 ms typically at 0 to 10 x Ud -
Reset time 90 ms typically at 10 to 0 x Ud -
Critical impulse time 2 ms typically at 0 to 10 x Ud -

Table 21: Line differential protection (PDIF, 87L, 87LT)


Function Range or value Accuracy
Minimum operate current (20-200)% of Ibase 2.0% of Ir at I Ir
2.0% of I at I >Ir
SlopeSection2 (10.0-50.0)% -
SlopeSection3 (30.0-100.0)% -
EndSection 1 (20150)% of Ibase -
EndSection 2 (1001000)% of Ibase -
Unrestrained limit function (1005000)% of Ibase 2.0% of Ir at I Ir
2.0% of I at I > Ir
Second harmonic blocking (5.0100.0)% of fundamental 2.0% of Ir
Fifth harmonic blocking (5.0100.0)% of fundamental 5.0% of Ir
Inverse characteristics, see table 71 and 19 curve types See table 71 and table 72
table 72
Operate time 25 ms typically at 0 to 10 x Id -
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 28

Function Range or value Accuracy


Reset time 15 ms typically at 10 to 0 x Id -
Critical impulse time 2 ms typically at 0 to 10 x Id -
Charging current compensation On/Off -

Distance protection
Table 22: Distance protection zones (PDIS, 21)
Function Range or value Accuracy
Number of zones 3 with selectable direction -
Minimum operate current (10-30)% of Ibase -
Positive sequence reactance (0.50-3000.00) /phase 2.0% static accuracy
Positive sequence resistance (0.10-1000.00) /phase 2.0 degrees static angular accuracy
Zero sequence reactance (0.50-9000.00) /phase Conditions:
Zero sequence resistance (0.50-3000.00) /phase Voltage range: (0.1-1.1) x Ur
Fault resistance, Ph-E (1.00-9000.00) /loop Current range: (0.5-30) x Ir
Fault resistance, Ph-Ph (1.00-3000.00) /loop Angle: at 0 degrees and 85 degrees
Dynamic overreach <5% at 85 degrees measured with -
CVTs and 0.5<SIR<30
Impedance zone timers (0.000-60.000) s 0.5% 10 ms
Operate time 24 ms typically -
Reset ratio 105% typically -
Reset time 30 ms typically -

Table 23: Phase selection with load encroachment (PDIS, 21)


Function Range or value Accuracy
Minimum operate current (5-30)% of Ibase 1.0% of Ir
Reactive reach, positive sequence, for- (0.503000.00) /phase 2.0% static accuracy
ward and reverse 2.0 degrees static angular accuracy
Resistive reach, positive sequence (0.101000.00) /phase Conditions:
Reactive reach, zero sequence, forward (0.509000.00) /phase
Voltage range: (0.1-1.1) x Ur
and reverse
Resistive reach, zero sequence (0.503000.00) /phase Current range: (0.5-30) x Ir

Fault resistance, phase-earth faults, for- (1.009000.00) /loop Angle: at 0 degrees and 85 degrees
ward and reverse
Fault resistance, phase-phase faults, (0.503000.00) /loop
forward and reverse
Load encroachment criteria:
Load resistance, forward and reverse (1.003000.00) /phase
Safety load impedance angle
(5-70) degrees
Reset ratio 105% typically -

Table 24: Power swing detection (RPSB, 78)


Function Range or value Accuracy
Reactive reach (0.10-3000.00) /phase 2.0% static accuracy
2.0 degrees static angular accuracy
Conditions:
Voltage range: (0.1-1.1) x Ur
Resistive reach (0.101000.00) /loop Current range: (0.5-30) x Ir
Angle: at 0 degrees and 85 degrees
Timers (0.000-60.000) s 0.5% 10 ms

Table 25: Automatic switch onto fault logic (PSOF)


Parameter Range or value Accuracy
Operate voltage, detection of dead line (1100)% of Ubase 1.0% of Ur
Operate current, detection of dead line (1100)% of Ibase 1.0% of Ir
Delay following dead line detection input before SOTF function 200 ms 0.5% 10 ms
is automatically enabled
Time period after circuit breaker closure in which SOTF func- 1000 ms 0.5% 10 ms
tion is active
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 29

Current protection
Table 26: Instantaneous phase overcurrent protection (PIOC, 50)
Function Range or value Accuracy
Operate current (1-2500)% of lbase 1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio > 95% -
Operate time 25 ms typically at 0 to 2 x Iset -
Reset time 25 ms typically at 2 to 0 x Iset -
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Operate time 10 ms typically at 0 to 10 x Iset -
Reset time 35 ms typically at 10 to 0 x Iset -
Critical impulse time 2 ms typically at 0 to 10 x Iset -
Dynamic overreach < 5% at = 100 ms -

Table 27: Four step phase overcurrent protection (POCM, 51/67)


Function Setting range Accuracy
Operate current (1-2500)% of lbase 1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio > 95% -
Min. operating current (1-100)% of lbase 1.0% of Ir
Relay characteristic angle (RCA) (-70.0 -50.0) degrees 2.0 degrees
Maximum forward angle (40.070.0) degrees 2.0 degrees
Minimum forward angle (75.090.0) degrees 2.0 degrees
Second harmonic blocking (5100)% of fundamental 2.0% of Ir
Independent time delay (0.000-60.000) s 0.5% 10 ms
Minimum operate time (0.000-60.000) s 0.5% 10 ms
Inverse characteristics, see table 71 19 curve types See table 71 and table 72
and table 72
Operate time, start function 25 ms typically at 0 to 2 x Iset -
Reset time, start function 25 ms typically at 2 to 0 x Iset -
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Impulse margin time 15 ms typically -

Table 28: Instantaneous residual overcurrent protection (PIOC, 50N)


Function Range or value Accuracy
Operate current (1-2500)% of lbase 1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio > 95% -
Operate time 25 ms typically at 0 to 2 x Iset -
Reset time 25 ms typically at 2 to 0 x Iset -
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Operate time 10 ms typically at 0 to 10 x Iset -
Reset time 35 ms typically at 10 to 0 x Iset -
Critical impulse time 2 ms typically at 0 to 10 x Iset -
Dynamic overreach < 5% at = 100 ms -

Table 29: Four step residual overcurrent protection (PEFM, 51N/67N)


Function Range or value Accuracy
Operate current (1-2500)% of lbase 1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio > 95% -
Operate current for directional compari- (1100)% of lbase 1.0% of Ir
son
Timers (0.000-60.000) s 0.5% 10 ms
Inverse characteristics, see table 71 19 curve types See table 71 and table 72
and table 72
Second harmonic restrain operation (5100)% of fundamental 2.0% of Ir
Relay characteristic angle (-180 to 180) degrees 2.0 degrees
Minimum polarizing voltage (1100)% of Ubase 1.0% of Ur
Operate time, start function 25 ms typically at 0 to 2 x Iset -
Reset time, start function 25 ms typically at 2 to 0 x Iset -
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Impulse margin time 15 ms typically -
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 30

Table 30: Thermal overload protection, one time constant (PTTR, 26)
Function Range or value Accuracy
Reference current (0-400)% of Ibase 1.0% of Ir
Start temperature reference (0-400)C 1.0C
Operate time: Ip = load current before overload occurs IEC 60255-8, class 5 + 200 ms
Time constant = (01000) minutes

I 2 I p2
t = ln 2
I Ib 2

I = Imeasured
Alarm temperature (0-200)C 2.0% of heat content trip
Trip temperature (0-400)C 2.0% of heat content trip
Reset level temperature (0-400)C 2.0% of heat content trip

Table 31: Breaker failure protection (RBRF, 50BF)


Function Range or value Accuracy
Operate phase current (5-200)% of lbase 1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio, phase current > 95% -
Operate residual current (2-200)% of lbase 1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio, residual current > 95% -
Phase current level for blocking of con- (5-200)% of lbase 1.0% of Ir at I Ir
tact function 1.0% of I at I > Ir
Reset ratio > 95% -
Timers (0.000-60.000) s 0.5% 10 ms
Operate time for current detection 10 ms typically -
Reset time for current detection 15 ms maximum -

Table 32: Stub protection (PTOC, 50STB)


Function Range or value Accuracy
Operate current (1-2500)% of Ibase 1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio > 95% -
Definite time (0.000-60.000) s 0.5% 10 ms
Operate time, start function 25 ms typically at 0 to 2 x Iset -
Reset time, start function 25 ms typically at 2 to 0 x Iset -
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Impulse margin time 15 ms typically -

Table 33: Pole discordance protection (RPLD, 52PD)


Function Range or value Accuracy
Operate current (0100% of Ibase 1.0% of Ir
Time delay (0.000-60.000) s 0.5% 10 ms

Voltage protection
Table 34: Two step undervoltage protection (PUVM, 27)
Function Range or value Accuracy
Operate voltage, low and high step (1100)% of Ubase 1.0% of Ur
Absolute hysteresis (0100)% of Ubase 1.0% of Ur
Internal blocking level, low and high (1100)% of Ubase 1.0% of Ur
step
Inverse time characteristics for low - See table 73
and high step, see table 73
Definite time delays (0.000-60.000) s 0.5% 10 ms
Minimum operate time, inverse char- (0.00060.000) s 0.5% 10 ms
acteristics
Operate time, start function 25 ms typically at 2 to 0 x Uset -
Reset time, start function 25 ms typically at 0 to 2 x Uset -
Critical impulse time 10 ms typically at 2 to 0 x Uset -
Impulse margin time 15 ms typically -
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 31

Table 35: Two step overvoltage protection (POVM, 59)


Function Range or value Accuracy
Operate voltage, low and high step (1-200)% of Ubase 1.0% of Ur at U < Ur
1.0% of U at U > Ur
Absolute hysteresis (0100)% of Ubase 1.0% of Ur at U < Ur
1.0% of U at U > Ur
Inverse time characteristics for low - See table 74
and high step, see table 74
Definite time delays (0.000-60.000) s 0.5% 10 ms
Minimum operate time, Inverse char- (0.000-60.000) s 0.5% 10 ms
acteristics
Operate time, start function 25 ms typically at 0 to 2 x Uset -
Reset time, start function 25 ms typically at 2 to 0 x Uset -
Critical impulse time 10 ms typically at 0 to 2 x Uset -
Impulse margin time 15 ms typically -

Table 36: Two step residual overvoltage protection (POVM, 59N)


Function Range or value Accuracy
Operate voltage, low and high step (1-200)% of Ubase 1.0% of Ur at U < Ur 1.0% of U at U
> Ur
Absolute hysteresis (0100)% of Ubase 1.0% of Ur at U < Ur
1.0% of U at U > Ur
Inverse time characteristics for low - See table 75
and high step, see table 75
Definite time setting (0.00060.000) s 0.5% 10 ms
Minimum operate time (0.000-60.000) s 0.5% 10 ms
Operate time, start function 25 ms typically at 0 to 2 x Uset -
Reset time, start function 25 ms typically at 2 to 0 x Uset -
Critical impulse time 10 ms typically at 0 to 2 x Uset -
Impulse margin time 15 ms typically -

Frequency protection
Table 37: Underfrequency protection (PTUF, 81)
Function Range or value Accuracy
Operate value, start function (35.00-75.00) Hz 2.0 mHz
Operate time, start function 100 ms typically -
Reset time, start function 100 ms typically -
Operate time, definite time function (0.000-60.000)s 0.5% + 10 ms
Reset time, definite time function (0.000-60.000)s 0.5% + 10 ms
Voltage dependent time delay Settings: Class 5 + 200 ms
UNom=(50-150)% of Ubase
UMin=(50-150)% of Ubase
Exponent
U UMin
t= ( tMax tMin ) + tMin Exponent=0.0-5.0
UNom UMin tMax=(0.001-60.000)s
tMin=(0.000-60.000)s
U=Umeasured

Table 38: Overfrequency protection (PTOF, 81)


Function Range or value Accuracy
Operate value, start function (35.00-75.00) Hz 2.0 mHz
Operate time, start function 100 ms typically -
Reset time, start function 100 ms typically -
Operate time, definite time function (0.000-60.000)s 0.5% + 10 ms
Reset time, definite time function (0.000-60.000)s 0.5% + 10 ms

Table 39: Rate-of-change frequency protection (PFRC, 81)


Function Range or value Accuracy
Operate value, start function (-10.00-10.00) Hz/s 10.0 mHz/s
Operate value, internal blocking level (0-100)% of Ubase 1.0% of Ur
Operate time, start function 100 ms typically -
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 32

Multipurpose protection
Table 40: General current and voltage protection (GAPC)
Function Range or value Accuracy
Measuring current input phase1, phase2, phase3, PosSeq, -
NegSeq, 3*ZeroSeq, MaxPh, MinPh,
UnbalancePh, phase1-phase2,
phase2-phase3, phase3-phase1,
MaxPh-Ph, MinPh-Ph, Unbalan-
cePh-Ph
Base current (1 - 99999) A -
Measuring voltage input phase1, phase2, phase3, PosSeq, -
-NegSeq, -3*ZeroSeq, MaxPh, MinPh,
UnbalancePh, phase1-phase2,
phase2-phase3, phase3-phase1,
MaxPh-Ph, MinPh-Ph, Unbalan-
cePh-Ph
Base voltage (0.05 - 2000.00) kV -
Start overcurrent, step 1 and 2 (2 - 5000)% of Ibase 1.0% of Ir for I<Ir
1.0% of I for I>Ir
Start undercurrent, step 1 and 2 (2 - 150)% of Ibase 1.0% of Ir for I<Ir
1.0% of I for I>Ir
Definite time delay (0.00 - 6000.00) s 0.5% 10 ms
Operate time start overcurrent 25 ms typically at 0 to 2 x Iset -
Reset time start overcurrent 25 ms typically at 2 to 0 x Iset -
Operate time start undercurrent 25 ms typically at 2 to 0 x Iset -
Reset time start undercurrent 25 ms typically at 0 to 2 x Iset -
See table 71 and table 72 Parameter ranges for customer See table 71 and table 72
defined characteristic no 17:
k: 0.05 - 999.00
A: 0.0000 - 999.0000
B: 0.0000 - 99.0000
C: 0.0000 - 1.0000
P: 0.0001 - 10.0000
PR: 0.005 - 3.000
TR: 0.005 - 600.000
CR: 0.1 - 10.0
Voltage level where voltage memory (0.0 - 5.0)% of Ubase 1.0% of Ur
takes over
Start overvoltage, step 1 and 2 (2.0 - 200.0)% of Ubase 1.0% of Ur for U<Ur
1.0% of U for U>Ur
Start undervoltage, step 1 and 2 (2.0 - 150.0)% of Ubase 1.0% of Ur for U<Ur
1.0% of U for U>Ur
Operate time, start overvoltage 25 ms typically at 0 to 2 x Uset -
Reset time, start overvoltage 25 ms typically at 2 to 0 x Uset -
Operate time start undervoltage 25 ms typically 2 to 0 x Uset -
Reset time start undervoltage 25 ms typically at 0 to 2 x Uset -
High and low voltage limit, voltage (1.0 - 200.0)% of Ubase 1.0% of Ur for U<Ur
dependent operation 1.0% of U for U>Ur
Directional function Settable: NonDir, forward and reverse -
Relay characteristic angle (-180 to +180) degrees 2.0 degrees
Relay operate angle (1 to 90) degrees 2.0 degrees
Reset ratio, overcurrent > 95% -
Reset ratio, undercurrent < 105% -
Reset ratio, overvoltage > 95% -
Reset ratio, undervoltage < 105% -
Overcurrent:
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Impulse margin time 15 ms typically -
Undercurrent:
Critical impulse time 10 ms typically at 2 to 0 x Iset -
Impulse margin time 15 ms typically -
Overvoltage:
Critical impulse time 10 ms typically at 0 to 2 x Uset -
Impulse margin time 15 ms typically -
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 33

Function Range or value Accuracy


Undervoltage:
Critical impulse time 10 ms typically at 2 to 0 x Uset -
Impulse margin time 15 ms typically -

Secondary system supervision


Table 41: Current circuit supervision (RDIF)
Function Range or value Accuracy
Operate current (5-200)% of Ir 10.0% of Ir at I Ir
10.0% of I at I > Ir
Block current (5-500)% of Ir 5.0% of Ir at I Ir
5.0% of I at I > Ir

Table 42: Fuse failure supervision (RFUF)


Function Range or value Accuracy
Operate voltage, zero sequence (1-100)% of Ubase 1.0% of Ur
Operate current, zero sequence (1100)% of Ibase 1.0% of Ir
Operate voltage, negative sequence (1100)% of Ubase 1.0% of Ur
Operate current, negative sequence (1100)% of Ibase 1.0% of Ir
Operate voltage change level (1100)% of Ubase 5.0% of Ur
Operate current change level (1100)% of Ibase 5.0% of Ir

Control
Table 43: Synchrocheck and energizing check (RSYN, 25)
Function Range or value Accuracy
Phase shift, line - bus (-180 to 180) degrees -
Voltage ratio, Ubus/Uline (0.20-5.00)% of Ubase -
Voltage high limit for synchrocheck (50.0-120.0)% of Ubase 1.0% of Ur at U Ur
1.0% of U at U > Ur
Reset ratio, synchrocheck > 95% -
Frequency difference limit between bus (0.003-1.000) Hz 2.0 mHz
and line
Phase angle difference limit between (5.0-90.0) degrees 2.0 degrees
bus and line
Voltage difference limit between bus (2.0-50.0)% of Ubase 1.0% of Ur
and line
Time delay output for synchrocheck (0.000-60.000) s 0.5% 10 ms
Voltage high limit for energizing check (50.0-120.0)% of Ubase 1.0% of Ur at U Ur
1.0% of U at U > Ur
Reset ratio, voltage high limit > 95% -
Voltage low limit for energizing check (10.0-80.0)% of Ubase 1.0% of Ur
Reset ratio, voltage low limit < 105% -
Maximum voltage for energizing (80.0-140.0)% of Ubase 1.0% of Ur at U Ur
1.0% of U at U > Ur
Time delay for energizing check (0.000-60.000) s 0.5% 10 ms
Operate time for synchrocheck function 160 ms typically -
Operate time for energizing function 80 ms typically -

Table 44: Autorecloser (RREC, 79)


Function Range or value Accuracy
Number of autoreclosing shots 1-5 -
Number of autoreclosing programs 8 -
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 34

Function Range or value Accuracy


Autoreclosing open time:
shot 1 - t1 1Ph (0.000-60.000) s 0.5% 10 ms
shot 1 - t1 2Ph
shot 1 - t1 3PhHS
shot 1 - t1 3PhDld
shot 2 - t2 (0.00-6000.00) s
shot 3 - t3
shot 4 - t4
shot 5 - t5
Extended autorecloser open time (0.000-60.000) s
Autorecloser maximum wait time for sync (0.00-6000.00) s
Maximum trip pulse duration (0.000-60.000) s
Inhibit reset time (0.000-60.000) s
Reclaim time (0.00-6000.00) s
Minimum time CB must be closed before AR (0.00-6000.00) s
becomes ready for autoreclosing cycle
Circuit breaker closing pulse length (0.000-60.000) s
CB check time before unsuccessful (0.00-6000.00) s
Wait for master release (0.00-6000.00) s
Wait time after close command before pro- (0.000-60.000) s
ceeding to next shot

Scheme communication
Table 45: Scheme communication logic for distance protection (PSCH, 85)
Function Range or value Accuracy
Scheme type Intertrip -
Permissive UR
Permissive OR
Blocking
Co-ordination time for blocking communica- (0.000-60.000) s 0.5% 10 ms
tion scheme
Minimum duration of a carrier send signal (0.000-60.000) s 0.5% 10 ms
Security timer for loss of carrier guard (0.000-60.000) s 0.5% 10 ms
detection
Operation mode of unblocking logic Off -
NoRestart
Restart

Table 46: Current reversal and weak-end infeed logic for distance protection (PSCH, 85)
Function Range or value Accuracy
Detection level phase to neutral voltage (10-90)% of Ubase 1.0% of Ur
Detection level phase to phase voltage (10-90)% of Ubase 1.0% of Ur
Reset ratio <105% -
Operate time for current reversal (0.000-60.000) s 0.5% 10 ms
Delay time for current reversal (0.000-60.000) s 0.5% 10 ms
Coordination time for weak-end infeed (0.000-60.000) s 0.5% 10 ms
logic

Table 47: Scheme communication logic for residual overcurrent protection (PSCH, 85)
Function Range or value Accuracy
Communication scheme coordination (0.000-60.000) s 0.5% 10 ms
time
Scheme type Permissive UR -
Permissive OR
Blocking

Table 48: Current reversal and weak-end infeed logic for residual overcurrent protection (PSCH, 85)
Function Range or value Accuracy
Operate voltage 3Uo for WEI trip (5-70)% of Ubase 1.0% of Ur
Reset ratio >95% -
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 35

Function Range or value Accuracy


Operate time for current reversal (0.000-60.000) s 0.5% 10 ms
Delay time for current reversal (0.000-60.000) s 0.5% 10 ms
Coordination time for weak-end infeed (0.00060.000) s 0.5% 10 ms
logic

Logic
Table 49: Tripping logic (PTRC, 94)
Function Range or value Accuracy
Trip action 3-ph, 1/3-ph, 1/2/3-ph -
Minimum trip pulse length (0.000-60.000) s 0.5% 10 ms
Timers (0.000-60.000) s 0.5% 10 ms

Table 50: Configurable logic blocks


Logic block Quantity with update rate Range or value Accuracy
fast medium normal
LogicAND 60 60 160 - -
LogicOR 60 60 160 - -
LogicXOR 10 10 20 - -
LogicInverter 30 30 80 - -
LogicSRMemory 10 10 20 - -
LogicGate 10 10 20 - -
LogicTimer 10 10 20 (0.00090000.000) s 0.5% 10 ms
LogicPulseTimer 10 10 20 (0.00090000.000) s 0.5% 10 ms
LogicTimerSet 10 10 20 (0.00090000.000) s 0.5% 10 ms
LogicLoopDelay 10 10 20 (0.00090000.000) s 0.5% 10 ms

Monitoring
Table 51: Measurements (MMXU)
Function Range or value Accuracy
Frequency (0.95-1.05) fr 2.0 mHz
Voltage (0.1-1.5) Ur 0.5% of Ur at U Ur
0.5% of U at U > Ur
Connected current (0.2-4.0) Ir 0.5% of Ir at I Ir
0.5% of I at I > Ir
Active power, P 0.1 x Ur < U < 1.5 x Ur 1.0% of Sr at S Sr
0.2 x Ir < I < 4.0 x Ir 1.0% of S at S > Sr
Reactive power, Q 0.1 x Ur < U < 1.5 x Ur 1.0% of Sr at S Sr
0.2 x Ir < I < 4.0 x Ir 1.0% of S at S > Sr
Apparent power, S 0.1 x Ur < U < 1.5 x Ur 1.0% of Sr at S Sr
0.2 x Ir < I < 4.0 x Ir 1.0% of S at S > Sr
Power factor, cos () 0.1 x Ur < U < 1.5 x Ur 0.02
0.2 x Ir < I < 4.0 x Ir

Table 52: Supervision of mA input signals (MVGGIO)


Function Range or value Accuracy
mA measuring function 5, 10, 20 mA 0.1 % of set value 0.005 mA
0-5, 0-10, 0-20, 4-20 mA
Max current of transducer to input (-20.00 to +20.00) mA
Min current of transducer to input (-20.00 to +20.00) mA
Alarm level for input (-20.00 to +20.00) mA
Warning level for input (-20.00 to +20.00) mA
Alarm hysteresis for input (0.0-20.0) mA

Table 53: Event counter (GGIO)


Function Range or value Accuracy
Counter value 0-10000 -
Max. count up speed 10 pulses/s -
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 36

Table 54: Disturbance report (RDRE)


Function Range or value Accuracy
Pre-fault time (0.050.30) s -
Post-fault time (0.15.0) s -
Limit time (0.56.0) s -
Maximum number of recordings 100 -
Time tagging resolution 1 ms See Table 70: "Time synchronization,
time tagging".
Maximum number of analog inputs 30 + 10 (external + internally derived) -
Maximum number of binary inputs 96 -
Maximum number of phasors in the Trip 30 -
Value recorder per recording
Maximum number of indications in a 96 -
disturbance report
Maximum number of events in the 150 -
Event recording per recording
Maximum number of events in the 1000, first in - first out -
Event list
Maximum total recording time (3.4 s 340 seconds (100 recordings) at 50 Hz, -
recording time and maximum number of 280 seconds (80 recordings) at 60 Hz
channels, typical value)
Sampling rate 1 kHz at 50 Hz -
1.2 kHz at 60 Hz
Recording bandwidth (5-300) Hz -

Table 55: Fault locator (RFLO)


Function Value or range Accuracy
Reactive and resistive reach (0.001-1500.000) /phase 2.0% static accuracy
2.0% degrees static angular accuracy
Conditions:
Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir
Phase selection According to input signals -
Maximum number of fault locations 100 -

Metering
Table 56: Pulse counter logic (GGIO)
Function Setting range Accuracy
Input frequency See Binary Input Module (BIM) -
Cycle time for report of counter value (03600) s -

Station communication
Table 57: IEC 61850-8-1 communication protocol
Function Value
Protocol IEC 61850-8-1
Communication speed for the IEDs 100BASE-FX

Table 58: LON communication protocol


Function Value
Protocol LON
Communication speed 1.25 Mbit/s

Table 59: SPA communication protocol


Function Value
Protocol SPA
Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd
Slave number 1 to 899

Table 60: IEC 60870-5-103 communication protocol


Function Value
Protocol IEC 60870-5-103
Communication speed 9600, 19200 Bd
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 37

Table 61: SLM LON port


Quantity Range or value
Optical connector Glass fibre: type ST
Plastic fibre: type HFBR snap-in
Fibre, optical budget Glass fibre: 11 dB (1000 m typically *)
Plastic fibre: 7 dB (10 m typically *)
Fibre diameter Glass fibre: 62.5/125 m
Plastic fibre: 1 mm
*) depending on optical budget calculation

Table 62: SLM SPA/IEC 60870-5-103 port


Quantity Range or value
Optical connector Glass fibre: type ST
Plastic fibre: type HFBR snap-in
Fibre, optical budget Glass fibre: 11 dB (1000 m typically *)
Plastic fibre: 7 dB (25 m typically *)
Fibre diameter Glass fibre: 62.5/125 m
Plastic fibre: 1 mm
*) depending on optical budget calculation

Remote communication
Table 63: Line data communication module (LDCM)
Quantity Range or value
Type of fibre Graded-index multimode 62.5/125 m or 50/125 m
Wave length 820 nm
Optical budget
Graded-index multimode 62.5/125 m 13 dB (typical distance 3 km *)
Graded-index multimode 50/125 m 9 dB (typical distance 2 km *)
Optical connector Type ST
Protocol C37.94
Data transmission Synchronous
Transmission rate 64 kbit/s
Clock source Internal or derived from received signal
*) depending on optical budget calculation

Hardware
IED
Table 64: Case
Material Steel sheet
Front plate Steel sheet profile with cut-out for HMI
Surface treatment Aluzink preplated steel
Finish Light grey (RAL 7035)

Table 65: Water and dust protection level according to IEC 60529
Front IP40 (IP54 with sealing strip)
Rear, sides, top and bottom IP20

Table 66: Weight


Case size Weight
6U, 1/2 x 19 10 kg
6U, 3/4 x 19 15 kg
6U, 1/1 x 19 18 kg

Connection system
Table 67: CT and VT circuit connectors
Connector type Rated voltage and current Maximum conductor area
Terminal blocks of feed through type 250 V AC, 20 A 4 mm2

Table 68: Binary I/O connection system


Connector type Rated voltage Maximum conductor area
Screw compression type 250 V AC 2.5 mm2
2 1 mm2
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 38

Basic IED functions


Table 69: Self supervision with internal event list
Data Value
Recording manner Continuous, event controlled
List size 1000 events, first in-first out

Table 70: Time synchronization, time tagging


Function Value
Time tagging resolution, Events and Sampled Measurement 1 ms
Values
Time tagging error with synchronization once/min (minute 1.0 ms typically
pulse synchronization), Events and Sampled Measurement
Values
Time tagging error with SNTP synchronization, Sampled 1.0 ms typically
Measurement Values

Inverse characteristics
Table 71: Inverse time characteristics ANSI
Function Range or value Accuracy
Operate characteristic: k = 0.05-999 in steps of 0.01 -
unless otherwise stated

A
t = P + B k
( I 1)

Reset characteristic:

tr
t = k
(I 2
)
1

I = Imeasured/Iset
ANSI Extremely Inverse no 1 A=28.2, B=0.1217, P=2.0, ANSI/IEEE C37.112, class 5 + 30 ms
tr=29.1
ANSI Very inverse no 2 A=19.61, B=0.491, P=2.0,
tr=21.6
ANSI Normal Inverse no 3 A=0.0086, B=0.0185, P=0.02,
tr=0.46
ANSI Moderately Inverse no 4 A=0.0515, B=0.1140, P=0.02,
tr=4.85
ANSI Long Time Extremely Inverse no 6 A=64.07, B=0.250, P=2.0, tr=30
ANSI Long Time Very Inverse no 7 A=28.55, B=0.712, P=2.0,
tr=13.46
ANSI Long Time Inverse no 8 k=(0.01-1.20) in steps of 0.01
A=0.086, B=0.185, P=0.02,
tr=4.6

Table 72: Inverse time characteristics IEC


Function Range or value Accuracy
Operate characteristic: k = (0.05-1.10) in steps of 0.01 -

A
t = P k
( I 1)

I = Imeasured/Iset
Time delay to reset, IEC inverse time (0.000-60.000) s 0.5% of set time 10 ms
IEC Normal Inverse no 9 A=0.14, P=0.02 IEC 60255-3, class 5 + 40 ms
IEC Very inverse no 10 A=13.5, P=1.0
IEC Inverse no 11 A=0.14, P=0.02
IEC Extremely inverse no 12 A=80.0, P=2.0
IEC Short-time inverse no 13 A=0.05, P=0.04
IEC Long-time inverse no 14 A=120, P=1.0
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 39

Function Range or value Accuracy


Customer defined characteristic no 17 k=0.5-999 in steps of 0.1 IEC 60255, class 5 + 40 ms
Operate characteristic: A=(0.005-200.000) in steps of
0.001
B=(0.00-20.00) in steps of 0.01
A
= + B k
C=(0.1-10.0) in steps of 0.1
(I P C )
t
P=(0.005-3.000) in steps of
0.001
Reset characteristic: TR=(0.005-100.000) in steps of
0.001
CR=(0.1-10.0) in steps of 0.1
TR
t = k
(I )
PR=(0.005-3.000) in steps of
PR
CR 0.001

I = Imeasured/Iset
RI inverse characteristic no 18 k=(0.05-999) in steps of 0.01 IEC 60255-3, class 5 + 40 ms

1
t = k
0.236
0.339
I
I = Imeasured/Iset
Logarithmic inverse characteristic no 19 k=(0.05-1.10) in steps of 0.01 IEC 60255-3, class 5 + 40 ms


t = 5.8 1.35 In
I

k
I = Imeasured/Iset

Table 73: Inverse time characteristics for Two step undervoltage protection (PUVM, 27)
Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in steps of 0.01 Class 5 +40 ms

k
t =
U < U

U<
U< = Uset
U = Umeasured
Type B curve: k = (0.05-1.10) in steps of 0.01

k 480
t = + 0.055
32 U < U 0.5
2.0


U <
U< = Uset
U = Umeasured
Programmable curve: k = (0.05-1.10) in steps of 0.01
A = (0.005-200.000) in steps of
0.001
B = (0.50-100.00) in steps of
kA
0.01
t = +D C = (0.0-1.0) in steps of 0.1
U < U
P

B C D = (0.000-60.000) in steps of
U < 0.001
U< = Uset P = (0.000-3.000) in steps of
U = Umeasured 0.001
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 40

Table 74: Inverse time characteristics for Two step overvoltage protection (POVM, 59)
Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in steps of 0.01 Class 5 +40 ms

k
t =
U U >

U>
U> = Uset
U = Umeasured
Type B curve: k = (0.05-1.10) in steps of 0.01

k 480
t =
32 U U > 0.5
2.0

0.035
U >
Type C curve: k = (0.05-1.10) in steps of 0.01

k 480
t =
32 U U > 0.5
3.0

0.035
U >
Programmable curve: k = (0.05-1.10) in steps of 0.01
A = (0.005-200.000) in steps of
0.001
kA
t = +D B = (0.50-100.00) in steps of
B U U >
P 0.01
C C = (0.0-1.0) in steps of 0.1
U >
D = (0.000-60.000) in steps of
0.001
P = (0.000-3.000) in steps of
0.001
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 41

Table 75: Inverse time characteristics for Two step residual overvoltage protection (POVM, 59N)
Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in steps of 0.01 Class 5 +40 ms

k
t =
U U >

U>
U> = Uset
U = Umeasured
Type B curve: k = (0.05-1.10) in steps of 0.01

k 480
t =
32 U U > 0.5
2.0

0.035
U >
Type C curve: k = (0.05-1.10) in steps of 0.01

k 480
t =
32 U U > 0.5
3.0

0.035
U >
Programmable curve: k = (0.05-1.10) in steps of 0.01
A = (0.005-200.000) in steps of
0.001
kA
t = +D B = (0.50-100.00) in steps of
B U U >
P 0.01
C C = (0.0-1.0) in steps of 0.1
U >
D = (0.000-60.000) in steps of
0.001
P = (0.000-3.000) in steps of
0.001
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 42

Ordering RED 670, Line differential protection IED

Guidelines
Carefully read and follow the set of rules to ensure problem-free order management. Please refer to the function matrix for included software functions given in
each software option package. Please observe that the character length of the software option section varies depending on the included options.
Enter option codes in the shaded spaces to complete the ordering number. To obtain the complete ordering code, please combined code from sheet 1 and sheet
2, as given in the example below. 1 BIM and 1 BOM is basic. Order futher I/O as required.

Sheet 1 Sheet 2
RED 670* - - - - - - -

SOFTWARE Notes and Rules


Version number
Latest version XX
Version No 1.0
Configuration alternatives
Single Breaker, 3-Phase Tripping A31
Single Breaker, 1Phase Tripping A32
Multi Breaker, 3-Phase Tripping B31
Multi Breaker, 1Phase Tripping B32
CAP configuration
ABB standard configuration X00
Software options All fields in the ordering form do not need to be filled in
No Option X00
High impedance differential protection A02
Line differential protection 6 CT sets, 3-5 line A04 Note: Only one Line differential protection have to be
ends selected
Line differential protection 3 CT sets, with A05 Note2: A04/A05 only in A31/A32
in-zone transformers, 2-3 line ends
Line differential protection 6 CT sets, with A06
in-zone transformers, 3-5 line ends
Line Distance protection B01
Residual overcurrent protection C04
Frequency protections - line E02
General current and voltage protection F01
Apparatus control 8 objects H07 Note: Only one Apparatus control can be ordered
Apparatus control 15 objects H08 Note: H07 only for A31/A32, H08 only for B31/B32
Additional HMI language
No second HMI language X0 On request
German A1
Russian A2
French A3
Spanish A4
Italian A5
Polish A6
Hungarian A7
Czech A8
Swedish A9
Casing
1/2 x 19 case (1TRM slot) A
3/4 x 19 case (2 TRM slots) C
1/1 x 19 case (2TRM slots) E
Mounting details with IP40 of protection from the front
19 rack mounting kit for 1/2 19 case or 2xRHGS6 or RHGS12 A
19 rack mounting kit for 3/4 19 case or 3xRHGS6 B
19 rack mounting kit for 1/1 19 case C
Wall mounting kit D
Flush mounting kit E
Flush mounting kit + IP54 mounting seal F
Auxiliary power supply
24-60 VDC A
90-250 VDC B
Human machine interface
Small size - text only A
Medium size, 15 controllable objects B
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 43

Sheet 1 (Enter option codes from sheet 1 in spaces below) Sheet 2


RED - - - - - - - - * A - -
670*

Analog system (First module X401, second module X411)


First TRM, 6I+6U, 1A, 100/220V A6
First TRM, 6I+6U, 5A, 100/220V A7
No second TRM included X0
Second TRM, 9I+3U, 1A, 100/220V A3
Second TRM, 9I+3U, 5A, 100/220V A4
Second TRM, 5I, 1A+4I, 5A+3U, 100/220V A5
Second TRM, 6I+6U, 1A, 100/220V A6
Second TRM, 6I+6U, 5A, 100/220V A7

Binary input and output, mA and time synchronizating boards. Note! Basic 1 BIM and 1 BOM included.
Slot position (rear view) Note! Max 3 positions in 1/2 rack, 5 - - -

X101

X121
X131
X111
X31
X41
X51
X61
X71
X81
X91
in 3/4 rack with 2 TRM and 11 in 1/1
rack with 2 TRM (=grey fields)
Available slots in 1/2 Case with 1 TRM
Available slots in 3/4 Case with 2 TRM
slots
Available slots in 1/1 Case with 2 TRM
No board in this slot X X X X X X X X X
Binary output module 24 output relays Note! Maximum 4 (BOM + MIM) A A A A A A A A A A
(BOM) boards
BIM 16 inputs, 24-30 VDC B B B B B B B B B B
BIM 16 inputs, 48-60 VDC C C C C C C C C C C
BIM 16 inputs, 110-125 VDC D D D D D D D D D D
BIM 16 inputs, 220-250 VDC E E E E E E E E E E
BIMp 16 inputs, 24-30 VDC for pulse F F F F F F F F F
counting
BIMp 16 inputs, 48-60 VDC for pulse G G G G G G G G G
counting
BIMp 16 inputs, 110-125 VDC for pulse H H H H H H H H H
counting
BIMp 16 inputs, 220-250 VDC for pulse K K K K K K K K K
counting
IOM 8 inputs, 10+2 output, 24-30 VDC L L L L L L L L L
IOM 8 inputs, 10+2 output, 48-60 VDC M M M M M M M M M
IOM 8 inputs, 10+2 output, 110-125 VDC N N N N N N N N N
IOM 8 inputs, 10+2 output, 220-250 VDC P P P P P P P P P
mA input module MIM, 6 channels Note! Max 4 (BOM + MIM) board in 1/1 R R R R R R R R R
case. Max 1 MIM + 3 BOM in 3/4 case.
No MIM board in 1/2 case
GPS time synchronization module (GSM) (in last slot) S S S
Serial communication unit for remote end communication
X312
X313
X302
X303

Slot position (rear view)

No remote communication board included Note! 1 LDCM in A31 and A32 X X X


C37.94 single channel 3 km Note! 2 LDCM in B31 and B32 A A A A
Serial communication unit for station communication
X301
X311

Slot position (rear view)

No first communication board included X


No second communication board included X
Serial SPA/IEC 60870-5-103 and LON com- A
munication module (plastic)
Serial SPA /IEC 60870-5-103 (plastic) and B
LON (glass) communication module
Serial SPA/IEC 60870-5-103 and LON com- C
munication module (glass)
Optical ethernet module, 1 channel glass D
Optical ethernet module, 2 channel glass E

Example:
RED 670*1.0-A31-A03B01C04F01-X0-A-A-B-A-A6X0-DAS-AA-XD
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 44

Accessories
GPS antenna and mounting details
GPS antenna, including mounting kits

Quantity: 1MRK 001 640-AA


Cable for antenna, 20 m

Quantity: 1MRK 001 665-AA


Cable for antenna, 40 m

Quantity: 1MRK 001 665-BA

Interface converter (for remote end data communication)

External interface converter from C37.94 to G703 including 1U 19 1 2 3 4


rack mounting accessories Quantity: 1MRK 002 245-AA

Test switch Single breaker/Single or Three Phase trip with


The test system COMBITEST intended for use external neutral on current circuits (ordering num-
with the IED670 products is described in 1MRK ber RK926 315-AC).
512 001-BEN and 1MRK 001024-CA. Please refer
to the website www.abb.com/substationautomation Multi-breaker/Single or Three Phase trip with
and ABB Product Guide > High Voltage Products internal neutral on current circuits (ordering num-
> Protection and Control > Modular Relay > Test ber RK926 315-BE).
Equipment for detailed information
Multi-breaker/Single or Three Phase trip with
Due to the high flexibility of our product and the external neutral on current circuit (ordering num-
wide variety of applications possible the test ber RK926 315-BV).
switches needs to be selected for each specific
application. The normally open "In test mode" contact 29-30
on the RTXP test switches should be connected to
Select your suitable test switch base on the avail- the input of the test function block to allow activa-
able contacts arrangements shown in the reference tion of functions individually during testing.
documentation.
Test switches type RTXP 24 are ordered sepa-
However our proposal for suitable variants are; rately. Please refer to Section "Related documents"
for reference to corresponding documents.
Single breaker/Single or Three Phase trip with
internal neutral on current circuits (ordering num- RHGS 6 Case or RHGS 12 Case with mounted
ber RK926 315-AK). RTXP 24 and the on/off switch for dc-supply are
ordered separately. Please refer to Section "Related
documents" for reference to corresponding docu-
ments.

Mounting details
19 rack mounting kit for one test switch

Quantity: 1MRK 002 420-BE


19 rack mounting kit for two test switches

Quantity: 1MRK 002 420-BB


19 rack mounting kit for three test switches

Quantity: 1MRK 002 420-BA


Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 45

Protection cover
Protective cover for rear side of RHGS6, 6U, 1/4 x 19

Quantity: 1MRK 002 420-AE


Protective cover for rear side of IED, 6U, 1/2 x 19

Quantity: 1MRK 002 420-AC


Protective cover for rear side of IED, 6U, 3/4 x 19

Quantity: 1MRK 002 420-AB


Protective cover for rear side of IED, 6U, 1/1 x 19

Quantity: 1MRK 002 420-AA

High impedance resistor unit 1-ph with resistor and voltage dependent
1 2 3
resistor 20-100V
Quantity: RK795101-MA
High impedance resistor unit 3-ph with resistor and voltage dependent
resistor 20-100V Quantity: RK795101-MB
High impedance resistor unit 1-ph with resistor and voltage dependent
1 2 3
resistor 100-400V
Quantity: RK795101-CB
High impedance resistor unit 3-ph with resistor and voltage dependent
resistor 100-400V Quantity: RK795101-DC

Combiflex
Key switch for lock-out of settings via LCD-HMI

Quantity: 1MRK 000 611-A


Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.

Side-by-side mounting kit

Quantity: 1MRK 002 420-Z

Configuration and monitoring tools


Front connection cable between LCD-HMI and PC

Quantity: 1MRK 001 665-CA

LED Label special paper A4, 1 pc

Quantity: 1MRK 002 038-CA


LED Label special paper Letter, 1 pc

Quantity: 1MRK 002 038-DA

Protection and control IED manager PCM 600


PCM 600 ver. 1.1, IED Manager

Quantity: 1MRK 003 395-AA


PCM 600 ver. 1.1, Engineering, IED Manager + CAP 531

Quantity: 1MRK 003 395-BA


PCM 600 ver. 1.1, Engineering Pro, IED Manager + CAP 531 + CCT
for IEC 61850-8-1 configuration of IED
Quantity: 1MRK 003 395-CA
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 46

Manuals
Note: One (1) IED Connect CD containing user documentation (Operators manual, Technical reference manual, Installa-
tion and commissioning manual, Application manual and Getting started guide), Connectivity packages and LED label tem-
plate is always included for each IED.

Rule: Specify additional quantity of IED Connect CD requested

Quantity: 1MRK 002 290-AA

Rule: Specify the number of printed manuals requested


Operators manual

Quantity: 1MRK 505 133-UEN


Technical reference manual

Quantity: 1MRK 505 132-UEN


Installation and commissioning manual

Quantity: 1MRK 505 134-UEN


Application manual

Quantity: 1MRK 505 135-UEN


Engineering guide IED 670 products

Quantity: 1MRK 511 179-UEN

Reference information
For our reference and statistics we would be pleased to be provided with the following application data:

Country: End user:

Station name: Voltage level: kV

Related documents
Documents related to RED 670 Identity number
Operators manual 1MRK 505 133-UEN
Installation and commissioning manual 1MRK 505 134-UEN
Technical reference manual 1MRK 505 132-UEN
Application manual 1MRK 505 135-UEN
Buyers guide 1MRK 505 164-BEN
Connection diagram, Single breaker arr. Three phase tripping arr. 1MRK 002 801-BA
Connection diagram, Single breaker arr. Single phase tripping arr. 1MRK 002 801-CA
Connection diagram, Multi breaker arr. Three phase tripping arr. 1MRK 002 801-DA
Connection diagram, Multi breaker arr. Single phase tripping arr. 1MRK 002 801-EA
Configuration diagram A, Single breaker with single or double busbars 1MRK 004 500-82
Configuration diagram B, Single breakers with single or double busbars 1MRK 004 500-83
Configuration diagram C, Multi breakers such as 1 1/2 or ring busbar arr. 1MRK 004 500-84
Configuration diagram D, Multi breakers such as 1 1/2 or ring busbar arr. 1MRK 004 500-85
Setting example 1, 230 kV Short cable line with 1 1/2 CB arr. 1MRK 505 175-WEN

Connection and Installation components 1MRK 013 003-BEN


Test system, COMBITEST 1MRK 512 001-BEN
Accessories for IED 670 1MRK 514 012-BEN
Getting started guide IED 670 1MRK 500 065-UEN
SPA and LON signal list for IED 670 1MRK 500 075-WEN
IEC 61850 Data objects list for IED 670 1MRK 500 077-WEN
Generic IEC 61850 IED Connectivity package 1KHA001027UEN
Protection and Control IED Manager PCM 600 Installation sheet 1MRS755552
Engineering guide IED 670 products 1MRK 511 179UEN

Latest versions of the described documentation can be found on www.abb.com/substationautomation


Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 47

Manufacturer
ABB Power Technologies AB
Substation Automation Products
SE-721 59 Vsters
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
Internet: www.abb.com/substationautomation
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 164-BEN
Revision: G, Page 48

You might also like