FPA-5000 Level 1 + 2
User Interface
Course instructor
Josef Angstenberger
1 Table of Contents
2 Legend
9 Goal: Here you can see what the main goals in the follow-
ing chapter are. What you should remember, know
at the end of the chapter
Caution: Here the main malfunction sources listed, that
can cause serious damage to the hardware or
influence the functionality of the panel negatively.
Hint: Here are some useful facts you will not read in the
documentation but may be very helpful for you and
your customers
Practical Hint: Here you get some practical information
Field Explanation
1 Function keys These keys are fix, they cannot be changed. They are language
independent.
The LEDs and their meaning is well explained in the manual of the MPC XX00 B.
Please refer on that on page 21, paragraph 4.2
User is logged in
The networked panel is operated from another panel / keypad and is blocked for
operation
Remote connection exists between two panels and the panel is operated by an-
other panel (3rd panel)
Only on remote keypad shown if connection has not yet been established
Similar to mobile phones all possible numbers and letters are shown when press-
ing an alpha numeric key
) For more info see pages 22 and 33 to 37 of the manual of the MPC XX00 B
n o p q r s
q Shows all faults/troubles. Here: 1 fault. To see all faults, press the key.
Shows all elements that are in bypass or isolate status. Here: 1 element is in
bypass or isolate status. To see all elements, press the key.
r
& Save time: The quick way to unbypass elements: Press this key,
select element(s) from the list and unbypass
Press this key and you receive a complete overview of the entire system. A
s list with all message types, e.g. On, Fault, Bypassed etc. is shown in a con-
centrated form.
Save time: Pressing these keys are the fasted way to get to the elements not
& in normal stat
The function specific Status Bars are linked to certain processes and functions. They
are displayed automatically when the specific function (e.g. History File) is started. They
disappear automatically when this function is exited. Exception is the Scroll line, this
does not appear automatically.
History log
Walktest
Diagnostics
Scroll Bar
Number Description
To select the field, touch it. In general more than one field can be selected. It is also
2 possible to scroll up or down and select additional fields
In this field you can go directly to the desired field. Depending on what had been se-
3 lected earlier, you can enter the address or description of the device.
With these arrows you can scroll up or down the list. They are only shown when fur-
4 ther fields exist above or below. For fast scrolling use the scroll bar.
By pressing one of these function keys, this function will be assigned to the selected
fields.
5
Principle: this function will be assigned to all selected field regardless of the function
they do have at present.
) For more info see paragraphs 5.6 and 5.8 of the manual of the MPC XX00 B
Step Description
1 In home screen select the function you want to assign the elements to
Select the element type the function shall be assigned to by clicking on them. The
2 color of the field or the frame will change.
3 Press the function key. Now this function will be assigned to all the elements
Standard Markings
Display a bypass group that consists of several elements. In order to display a list of
all elements of the bypass group, press the right-hand field.
Exercise
2. Unbypass 2 of the bypassed detectors and leave the others in bypass state
4 Alarm mode
Switch from day to night mode vice versa. Change the time
Bypass and Block (make bypass groups) unbypass - warning
History log
Diagnostic information
Panel passport (make sure end customer knows it)
Change device on MPC RS 232
Detector sensitivity
The manual of the MPC XX00 B gives you a throrough and detailled description of the
main applications of the user interface.
This document shall not replace the manual. It contains only those features that you
really should know. Partly detailled descriptions will be given, partly it will be referred
to the manual. In addition this document will direct your attention on features that are
very helpful for you, that could save you time or be of benefit for your customer. Some
of them are listed in the manual, some are not. To make sure you at least heard of
them we will list them in this chapter. If a detailled description is offered in the manual
an indication will be given.
Need to Good to End
Feature Category Installer
know know user
Change language x Ease of use x x
Search function / element x Ease of use
Quick unbypass x Ease of use x
Diagnostics: shows tte addresses uses x Maintenance x
Log in user 9 What happens. x Maintenance x
Know panel passport --> diagnostics / Panel x Maintenance x
Walktest: explain compelte structur and benefit.
Explain also what sequential ind simultaneous x Maintenance x
Unbypass internal buzzer x Maintenance x
Quick overview of the panel status (status bar and
status key) x Panel status x
Bypass Alarm Indication x Security x x
Change Detector sensitivity x Standard x
Switch day to night mode vice versa. Change Standard
switch back time x application x
Log in codes for end user and installer x Standard x x
Bypass Groups x Standard x x
Panel overview x Support situation x
Diagnostics: Element details x Support situation x
Diagnostics: Module details x Support situation x
Know installer contact screen x Support situation x
Change device at V.24 interface x x
& The secure way your customer knows who to contact in case of problems
This feature belongs to diagnostics. Calling up this screen you receive information
about the firmware version, the CAN ID number, PCBA material number etc. You
might need it only rarely, but it is good to now it exists
4 Change from day to night mode and night to day mode
Things you should now about this features:
- Changing to day / night mode is done in only 1 second by pressing only two
keys
- Switching the panel to day mode must be done manually, switching to night
mode can be done automatically and programmed in the panel.
- The automatic switch back time to night mode can be changed on the panel.
After HW-reboot of the panel the original switch back time is assigned again,
prior manual got lost
- Only those elements can be switched to day mode, if the day mode feature
has been assigned to their element group in FSP-5000 RPS.
- Indication of the mode is shown in the home status bar:
- Moon = night mode
- Sun = day mode
You can switch the panel to day mode, the status bar will show the sun. BUT all
the elements are still in night mode, because the day mode feature had not been
assigned to it in FSP-5000-RPS
Make sure to always programm the day mode feature in FSP-5000-RPS
) See chapter XXX in this document and chapter 17 of the manual of the MPC XX00 B
During maintenance and test work on the panel the internal buzzer can be annoying.
You can bypass the internal buzzer very easily
How to do it:
In the home screen select Maintenance then press key Bypass buzzer. If the
buzzer is already bypassed, the field would show Unbypass buzzer
& - Security: Security that all outputs are blocked No unwanted activation of out-
puts during maintenance work on the panel.
- Time: By only one click all outputs are bypassed.
3. Overview of Panel status at one glance home status bar / status key
The LED indication offers a first overview of panel status. More detailled information
is available by the Home Status Bar. If information about additional states is nee-
ded, press the key Status on the Home Status Bar. In categories all states not in
normal mode are listed. For more info on concerned elements, press the specific
state field.
& Ease of use, quick and thorough status information in a few seconds!
& Time and Money: Change of setting without changing and downloading the configu-
ration.
) For more info see paragraph 5.7 of the manual of the MPC XX00 B
With this function the user can go directly to the desired function without
going through the complete menu structure. When pressing the back key,
the user will return directly to the home screen.
) For more info see paragraph5.7 of the manual of the MPC XX00 B
2. Quick unbypass
The panel offers a way to unbypass elements in only a few seconds, by ta-
king advantage of the home status bar. Use the home status bar also to ar-
rive quickly at all elements in trouble or all controls activated
How to do it:
Press the key Bypass in the homes status line select Bypassed Se-
lect the list field you require, e.g. detectors Select all the elements you
want to unbypass press function key unbypass
) For more info see paragraph 11 and 11.42 of the manual of the MPC XX00