3KVA DC Ripple Current Analysis

The report analyzes the ripple current in a 3KVA DC system under various load conditions from no load to full load and overload, finding that the ripple current increases from 0.8A at no load to 102.6A at full load and 76A at a 2800W overload, with measurements taken using a clamp meter. Testing was done with four 680uF 100V capacitors in the DC link, and results show the ripple current is low enough to avoid heating issues at full load.

Uploaded by

shalu29
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
94 views6 pages

3KVA DC Ripple Current Analysis

The report analyzes the ripple current in a 3KVA DC system under various load conditions from no load to full load and overload, finding that the ripple current increases from 0.8A at no load to 102.6A at full load and 76A at a 2800W overload, with measurements taken using a clamp meter. Testing was done with four 680uF 100V capacitors in the DC link, and results show the ripple current is low enough to avoid heating issues at full load.

Uploaded by

shalu29
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd

3KVA DC Ripple Current Analysis Report

DC Current
(Battery Current)
Load Rating (Bulb Load Clamp Meter
Sr. No. Wattage) (A)
1 No Load Current 0.8
2 100 3
3 200 5.2
4 300 7.4
5 500 12
6 700 16.8
7 1100 23.6
8 1200 28.8
9 1400 34.3
10 1600 39.9

11 2800 76

12 3600 102.6
13 During Charging 14
Note: DC Link Capacitors are in 4 Nos. of 680uf 100V WV RD Samwha Make.

As per readings it is concluded that the rms of value of current which can cause th
low as compared to the DC Current flowing through the system at full load & hence
Result:
problem with the screws. Thus there is no need of extra Jumper wire to be used for
current.
3KVA DC Ripple Current Analysis Report

High Frequency Ripple at


1100W Bulb Load
(Volt values equal to
Ampere Values)

Created By:
3KVA DC Ripple Current Analysis Report

High Frequency High Frequency


Ripple Current Ripple Current Ripple Current Measured at
Pk-Pk rms Clamp Meter
(A) (A) (A)
- - -
12 3.1 0.2
17.4 4.49 0.3
22.8 5.83 0.5
34 8.29 1
43.2 10.8 1.4
60 15.4 2.1
72 18.4 2.4
82 20 2.8
90 21.2 3.1

150 29.7 5.5

188 32.3 7
68.8 15.7 3.2
00V WV RD Samwha Make.

of value of current which can cause the heating effect is


through the system at full load & hence it cannot create
eed of extra Jumper wire to be used for carrying the
3KVA DC Ripple Current Analysis Report

Low Frequency Ripple at


1100W Bulb Load
(Volt values equal to Ampere
Values)
3KVA DC Ripple Current Analysis Report

Remarks

Full Load Value


of the 3KVA
system

Overload Value
at 90E Burden
Resistance
3KVA DC Ripple Current Analysis Report