3KVA DC Ripple Current Analysis Report
DC Current
(Battery Current)
Load Rating (Bulb Load Clamp Meter
Sr. No. Wattage) (A)
1 No Load Current 0.8
2 100 3
3 200 5.2
4 300 7.4
5 500 12
6 700 16.8
7 1100 23.6
8 1200 28.8
9 1400 34.3
10 1600 39.9
11 2800 76
12 3600 102.6
13 During Charging 14
Note: DC Link Capacitors are in 4 Nos. of 680uf 100V WV RD Samwha Make.
As per readings it is concluded that the rms of value of current which can cause th
low as compared to the DC Current flowing through the system at full load & hence
Result:
problem with the screws. Thus there is no need of extra Jumper wire to be used for
current.
3KVA DC Ripple Current Analysis Report
High Frequency Ripple at
1100W Bulb Load
(Volt values equal to
Ampere Values)
Created By:
3KVA DC Ripple Current Analysis Report
High Frequency High Frequency
Ripple Current Ripple Current Ripple Current Measured at
Pk-Pk rms Clamp Meter
(A) (A) (A)
- - -
12 3.1 0.2
17.4 4.49 0.3
22.8 5.83 0.5
34 8.29 1
43.2 10.8 1.4
60 15.4 2.1
72 18.4 2.4
82 20 2.8
90 21.2 3.1
150 29.7 5.5
188 32.3 7
68.8 15.7 3.2
00V WV RD Samwha Make.
of value of current which can cause the heating effect is
through the system at full load & hence it cannot create
eed of extra Jumper wire to be used for carrying the
3KVA DC Ripple Current Analysis Report
Low Frequency Ripple at
1100W Bulb Load
(Volt values equal to Ampere
Values)
3KVA DC Ripple Current Analysis Report
Remarks
Full Load Value
of the 3KVA
system
Overload Value
at 90E Burden
Resistance
3KVA DC Ripple Current Analysis Report