You are on page 1of 5

IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 18, NO.

4, DECEMBER 2003 525

Power Generation Efficiency Improvement Through


Auxiliary System Modifications
Zhengyu Huang and Robert M. Edwards, Member, IEEE

AbstractThermal performance analyses have been performed (CW) flow to auxiliary condensers (i.e., thus to increase CW
for some proposed modifications in the Three Mile Island Nuclear flow to the main condenser to improve its vacuum), so that the
Power Plant auxiliary systems, including: 1) auxiliary-condenser main turbine electricity output could be increased.
circulating-water (ACCW) flow reduction; 2) ACCW discharge
diversion to the main condenser; and 3) feedwater heater drain Analysis shows that by auxiliary-condenser circulating-water
recycling. Analysis shows that the secondary-system thermal (ACCW) reduction, the plant electricity output can be increased
efficiency can be improved by reducing circulating-water (CW) by up to 839 kW at the CW temperature of 30 C (86 F). How-
flow to the auxiliary condensers at high CW temperatures. This ever, this improvement is not consistent. It decreases with CW
improvement decreases as CW temperature decreases. No benefit inlet temperature. There is no benefit obtained from auxiliary
can be obtained from ACCW flow reduction at low CW temper-
atures. It is also shown that electricity output can be increased CW reduction when the CW water is sufficiently cold. Opti-
by diverting ACCW discharge to the main condenser instead of mization results show that the optimal ACCW flow increases
directly to cooling towers as in the current practice. This increase, with the CW inlet temperature decrease.
though also varying with CW temperature, is consistently positive An alternative to ACCW reduction is to redirect the ACCW
within the considered CW temperature range. For feedwater discharge to the main condenser instead of to the cooling tower.
heater drain recycling, thermal efficiency improvement is signifi-
cant for the two lowest-pressure stages. This alternative takes advantage of the design feature that CW
has a much lower temperature rise in auxiliary condensers
Index TermsNuclear power generation, power generation,
power generation auxiliary systems, power generation economics. (1.67.8 C, or 2.814 F) than in the main condenser (15.6 C
or 28 F) [2]. Redirection of the circulating water leaving
auxiliary condensers to the middle of the main condenser is
I. INTRODUCTION predicted to result in an electricity increase of up to 1138 kW,
and more attractively, this increase is consistent for all circu-
I T HAS BEEN a persistent practice to achieve higher thermal
efficiency in both nuclear power plants and fossil-fired
power plants. The methods considered range from modifica-
lating-water temperatures considered.
The use of drain pumps with feedwater heaters to inject heater
tions in systems and components to performance monitoring, drain into feedwater system or condensate system was the third
etc. method analyzed to be able to improve thermal efficiency for
In this paper, some modifications that can possibly improve fossil-fired power plants [3], in which main steam is signifi-
power plant efficiency have been proposed on two auxiliary cantly superheated. This technique is considered as a candidate
systemsauxiliary condenser system and feedwater heater method to improve TMI-NPP thermal efficiency, though steam
drain system in the Three Mile Island Nuclear Power Plant in TMI-NPP is just slightly superheated. The analysis shows that
(TMI-NPP).1 The analyses were performed using an integrated drain pumps at the low-pressure stages will result in significant
optimization procedure (IOP) [1], which is composed of a thermal efficiency improvement. The combination of all pos-
MATLAB Optimization Toolbox, PEPSE code, and a Visual sible drain pumps applied to the four considered stages is pre-
Basic Application code specially designed to provide a user dicted to result in a net power increase of 1238 kW. The use of
interface to PEPSE and a communication bridge between drain pump only to the lowest pressure stage is also predicted to
PEPSE and MATLAB. result in a power increase of 926 kW.
In TMI-NPP, it was observed that the auxiliary condensers
have an excessively high vacuum compared to the main con- II. BRIEF DESCRIPTION OF TMI-NPP AND ITS CONDENSER
denser. It was, therefore, suggested to reduce circulating-water AND FEEDWATER HEATER SYSTEMS

TMI-NPP is a pressurized water reactor unit. The rated


Manuscript received September 18, 2000; revised November 28, 2001. net electricity output is about 819 MW. The main turbine
Z. Huang is with Thermoflow, Inc., Sudbury, MA 01776 USA (e-mail: is composed of one high-pressure turbine section and three
hzy001@yahoo.com).
R. M. Edwards is with the Department of Mechanical and Nuclear Engi- low-pressure sections. Two feedwater pumps are each driven
neering, the Pennsylvania State University, University Park, PA 16802 USA by a steam turbine. The condenser system is composed of one
(e-mail: e48@psu.edu). main condenser, which is composed of three compartments, and
Digital Object Identifier 10.1109/TEC.2003.816607
two auxiliary condensers connected to the two feedwater-pump
1The theoretical results presented in this paper are based on analysis using turbines.
the original plant thermal kit and do not necessarily reflect current plant con- The main condenser is a Tandem Twin Shell, three pressure
figuration and capacities. The purpose of this work has been to develop and
demonstrate the possible plant thermal performance improvement through the level, single pass, and vertically divided surface condenser. See
considered system modification. Fig. 1 for details. CW goes from the inlet water box (unseen in
0885-8969/03$17.00 2003 IEEE

Authorized licensed use limited to: TOKYO INSTITUTE OF TECHNOLOGY. Downloaded on February 7, 2010 at 04:30 from IEEE Xplore. Restrictions apply.
526 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 18, NO. 4, DECEMBER 2003

Fig. 2. Feedwater heater drain configuration.

Fig. 1. Main condenser side view cutaway. drain into the next lower-pressure stage (for stage #12, to the
main condenser). The schematic configuration of feedwater
heater system is shown in Fig. 2 (only one string is shown).
TABLE I
MAIN DESIGN DATA OF CONDENSERS
III. TOOLS USED FOR ANALYSIS
To perform thermal-performance analysis, a procedure called
IOP is used. The detailed description of IOP is presented in
[1]. In brief, the IOP consists of three main parts: MATLAB
Optimization Toolbox [4], PEPSE [5] code, and a Visual Basic
[6] Application (VBA) interface. MATLAB Optimization
Toolbox is used to perform parameter optimization; PEPSE
code is used to build plant secondary thermodynamics model
and perform plant secondary-system heat-balance calculation;
while the VBA interface is used to communicate between
PEPSE and MATLAB.
In order for the analysis to be more reliable, the PEPSE model
was adjusted so that the results from PEPSE model calcula-
tion match well with the vendor thermal-kit heat-balance cal-
the figure) to the center water box through two banks of tube culation. Values of electricity output, heat rate, steam-extraction
bundles and mixes in the center water box. Then it continues to pressures, and feedwater-heater performance indexes (DCA and
go to the outlet water box (unseen in the figure) through another TTD) from PEPSE calculation are very close to those in the
two banks of tube bundles. thermal kit. Relative differences in extracted steam flow-rates
On the shell side, the main condenser is divided into three are within 1%.
separate compartments (pressure zones) by two internal support
plates. Steam exhausted from three low-pressure turbine sec-
IV. PROPOSED MODIFICATIONS
tions is directed down to their corresponding condenser com-
partments, which have different vacuums. A. Scheme I: Auxiliary Condenser Circulating Water (ACCW)
The two auxiliary condensers receive exhaust steam from two Flow Reduction
feedwater-pump turbines, respectively. Circulating water from Since the auxiliary condensers experience excessively high
the natural-draft cooling towers is pumped and goes in parallel vacuum compared to the main condenser, it is intuitive to
to the main condenser and the two auxiliary condensers. The consider reducing CW flow to auxiliary condensers so that
main design data of condensers are listed in Table I. more CW is forced into the main condenser to produce higher
CW to condensers is provided by the circulating water system vacuum, improving thermal efficiency of the main turbine. The
(CWS). The CWS is a closed cycled cooling system utilizing schematic diagram of the proposed modification is shown in
two natural-draft cooling towers. CW pumps take suction from Fig. 3.
the main circulating flume. The pumps discharge to two parallel In this scheme, total CW flow is assumed to be constant, so
strings to the main condenser and auxiliary condensers and the decreasing CW flow to auxiliary condenser will increase flow
CWS terminates in two natural-draft cooling towers. to the main condenser.
Feedwater system and condensate systems have two strings
of feedwater heaters,2 each including six stages (#2, #4, #6, B. Scheme II: ACCW Discharge Diversion
#8, #10, and #12). Except for stage #6, whose drain is pumped
forward to the main feedwater stream, all stages cascade their It has been noticed that the CW temperature increase in
auxiliary condensers is no more than 50% of that in the main
2Here feedwater heaters refers to heaters in both feedwater system and con- condenser under all conditionsthe design values are 15.6 C
densate system. Consequently, feedwater heater system includes all of these (28 F) and 1.67.8 C F) for the main condenser and
heaters.

Authorized licensed use limited to: TOKYO INSTITUTE OF TECHNOLOGY. Downloaded on February 7, 2010 at 04:30 from IEEE Xplore. Restrictions apply.
HUANG AND EDWARDS: POWER GENERATION EFFICIENCY IMPROVEMENT THROUGH AUXILIARY SYSTEM MODIFICATIONS 527

Fig. 5. Scheme III: Feedwater heater drain recycling.

Fig. 3. Scheme I: ACCW flow reduction.

Fig. 4. Scheme II: ACCW discharge diversion (refer to Fig. 1 for the Fig. 6. Effects on power generation of Auxiliary condenser CW flow change.
inboard-water-box location in the main condenser). T : CW inlet temperature; P : System net power generation at design value
2
of auxiliary condenser CW flow of 12:8 10 lb=h (1613 kg/s).

auxiliary condensers, respectively. This means that the circu-


stream of that FW heater (feedwater inlet). Since the drain from
lating water discharged from auxiliary condensers can still be
FWH #6 is pumped forward to the main FW line, there is no
used in the main condenser provided that piping configuration
need to change the drain flow for stage #6. Since the pressure at
and hydraulic (pressure loss) analysis allows.
the FWH stage #6 drain pump inlet is lower than the drain pres-
For this analysis, a splitter is assumed on the auxiliary-con-
sure of FWH stage #4, the drain from stage #4 can be directly
denser CW discharge pipe, from which a part of or all auxil-
drained to the inlet of FWH stage #6 drain pump. Schematic di-
iary CW flow can be diverted to the main condenser through its
agram of this scheme is shown in Fig. 5.
center water box. A schematic diagram of this scheme is shown
in Fig. 4.
V. RESULTS
C. Scheme III: Feedwater Heater Drain Recycling A. Scheme I: AC CW Flow Reduction
For system simplicity, drain of feedwater heaters in most Main results corresponding to three CW temperatures, 30 C
power plants is cascaded to the next lower pressure stage. In (86 F), 22.4 C, (72.3 F), and 15.6 C (60 F) are shown in
this configuration, the drain from the higher-pressure stage Fig. 6. Results show that at high CW temperature, decreasing
expels steam extraction to lower-pressure stages thus resulting CW flow to the auxiliary condenser results in an increase of net
in irreversible losses. When the drain flows into the main power generation. With further decrease of CW flow, however,
condenser, a part of cooling capability of circulating water is net power generation will drop down. There exists an optimal
lost. Both cases result in loss of power generation. To avoid CW flow at which the power generation reaches the maximum
this kind of loss, feedwater heater drain can be pumped directly at that temperature. As CW temperature decreases, this optimal
to the main feedwater stream. In practice, pumps may not be CW flow increases. At about 13 C (55 ), the optimal CW
appropriate for all stages. But for analysis purposes, all stages flow reaches the design value. This trend is clearly shown in
except stages #6, where drain pumps already exist and, #12, Fig. 7 (a constraint for the optimization is set that the maximum
are considered to have one drain pump for each string that can CW flow to the auxiliary condenser is the design value.
pump partial or full flow of the drain to the main feedwater line. Net electricity increase by operating the system at optimal
The principle to add drain pumps to the system is that the CW flow to auxiliary condensers is 838, 227, and 0 kW at CW
drain temperature should be no less than the main condensate temperature of 30 C, 22.4 C, and 15.6 C, respectively.
or feedwater temperature where the drain is pumped. With this The reason for the electricity power increase at high CW inlet
constraint, the drain from each stage is pumped to the point up- temperature is that the operation of auxiliary condensers does

Authorized licensed use limited to: TOKYO INSTITUTE OF TECHNOLOGY. Downloaded on February 7, 2010 at 04:30 from IEEE Xplore. Restrictions apply.
528 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 18, NO. 4, DECEMBER 2003

Fig. 8. Effects on power generation of auxiliary condenser CW discharge


Fig. 7. Relationship between the optimal CW flow and the CW temperature. diversion to main condenser. T
2
The upper bound of the CW flow is chosen as the design value (12:8 10 lb=h
: CW inlet temperature; P : Gross power
generation without auxiliary condenser CW discharge diversion.
or 1613 kg/h).

not match that of the main condenser at the design CW flow (i.e.,
auxiliary condensers consume excessive CW to produce a low
pressure). Reduction of the CW flow to auxiliary condensers can
increase CW flow to the main condenser, lowering the main con-
denser pressure and, hence, increasing the work done by steam
in the low-pressure turbine sections. Although this change does
reduce the efficiency of the auxiliary condensers by increasing
steam flow to drive feedwater pumps, this reduction is offset by
the main condenser vacuum improvement if the flow change is
within a proper range.
At low CW temperature, however, the pressures at main con-
denser compartments are already very low, a small amount of
CW flow increase does not significantly improve vacuum in the
main condenser. However, the decrease in auxiliary-condenser
CW flow makes auxiliary condensers less efficient and this ef-
fect is not offset by the vacuum improvement in the main con-
denser. This can be seen in Fig. 6 for the case that CW inlet
temperature is 15.6 C (60 F), which shows that the optimal
auxiliary CW flow rate is close to the design point.
Fig. 9. Effects of feedwater drain diversion.

B. Scheme II: Diversion of Auxiliary-Condenser CW The electricity output increase also varies with the CW inlet
Discharge temperature. This trend is explicitly depicted in Fig. 8. Unlike
Main results corresponding to three CW temperatures, 30 C ACCW flow optimization, however, the electricity output in-
(86 F), 22.4 C (72.3 F), and 15.6 C (60 F) are shown in crease from auxiliary-condenser CW discharge diversion is al-
Fig. 8. ways the greatest at full diversion for all CW temperatures.
At a given CW inlet temperature, electricity output increases
due to auxiliary-condenser CW (ACCW) discharge diversion is C. Scheme III: Feedwater Heater Drain Recycling
almost proportional to the diverting fraction. Increase of net power generation from the system is plotted
The maximum electricity output increases are expected to be versus the drain diversion fraction for all four individual con-
1138, 770, and 263 kW obtained at CW inlet temperature of 30 sidered FWH stages and for some stage combinations at an air
C (86 F), 22.4 C, (72.3 F), and 15.6 C (60 F), respec- temperature of 21 (70 ), shown in Fig. 9.
tively, with full ACCW discharge diversion. (In this sense, the It is clear from Fig. 9 that for all individual FWH stages and
expression ACCW redirection can be used.) all combinations, the net increase of power generation (power
The main contribution of electricity output due to ACCW dis- consumption of drain pumps has been deducted) is an increasing
charge diversion is mainly from the main condenser hot com- function of diversion fractions. At full flow diversions, power
partment vacuum improvement. There is no vacuum change in generation is maximized. Table II gives power generation net
the cold compartment and little vacuum change in the warm increase at full flow diversion for several feedwater heater stage
compartment. combinations.

Authorized licensed use limited to: TOKYO INSTITUTE OF TECHNOLOGY. Downloaded on February 7, 2010 at 04:30 from IEEE Xplore. Restrictions apply.
HUANG AND EDWARDS: POWER GENERATION EFFICIENCY IMPROVEMENT THROUGH AUXILIARY SYSTEM MODIFICATIONS 529

TABLE II ficiency of the heater drain pumps. To benefit from Scheme III,
NET POWER GENERATION INCREASE AT FULL DIVERSION OF DIFFERENT FWH there is a certain limit for pump efficiency since the power con-
STAGE COMBINATIONS
sumption of these pumps takes a significant part of the addi-
tional power generation due to this modification. Too low pump
efficiency may cause the reversed effectnet power output in-
crease may be negative. Close monitoring of the system oper-
ation and careful maintenance of the system are essential for
better system performance.

VI. CONCLUSIONS
Thermal efficiency improvement by some proposed auxil-
iary system modifications has been investigated for TMI nuclear
power plant. Electricity output can be increased by up to 839
kW and 1138 kW with auxiliary-condenser circulating-water
flow reduction and CW discharge diversion, respectively. Redi-
rection of ACCW to the main condenser is shown to be easy
From the point of cost-benefit consideration, modification to implement and has a persistent effect on thermal efficiency
made only to stage #10 might be of interest to be implemented. improvement.
Though complicated by the requirement of drain pumps,
feedwater heater drain recycling is also able to significantly
D. Comparison of the Three Schemes
increase electricity output, given that the pump efficiency is
Scheme I (auxiliary-condenser CW flow reduction) may be not too low. Drain recycling at stage #10 is shown to be the
the easiest one to implement with respect to mechanical system most promising, which is predicted to increase power output
change. Only a control valve is needed to install on the CW of 926 kW.
supply branch line to the auxiliary condensers and no piping
reconfiguration is required. However, for optimal operation, the REFERENCES
auxiliary CW flow should be automatically adjusted in accor-
[1] Z. Huang, R. M. Edwards, and M. Fauber, Thermal performance anal-
dance with CW inlet temperature. To this end, a reliable con- ysis of TMI NPP auxiliary condenser CW reduction and diversion using
trol system needs to be developed and maintained, which causes integrated optimization procedure, in Proc. 8th Int. Conf. Nucl. Eng.,
an additional cost for the reconstruction and operation/mainte- Apr. 2000, ICONE-8731.
[2] TMI Operations Plant Manual, 3rd ed., 1994.
nance of the system. [3] W. Lin, Quantitative Analysis of Thermal Systems in Fossil Fired Power
Scheme II (diversion of auxiliary-condenser CW discharge Plants (in Chinese). Xian, China: Xian Jiao Tong Univ. Press, 1985.
to the main condenser) leads to a consistent electricity output [4] Optimization Toolbox for Use with MATLAB, Users Guide, The Math-
works, Inc., 1999.
increase and this increase is greater than that from Scheme I [5] G. L. Minner et al., PEPSE: Applications Manual: SCIENTECH, Inc.,
(ACCW flow reduction). This means that there is no parameter 1998.
to adjust for optimal operation. However, this change requires [6] G. Connell, Visual Basic 5: From the Ground Up. New York: McGraw-
Hill, 1997.
retrofit of the plant piping system, specifically, lines from the
auxiliary condensers to the center water box of the main con-
denser need to be added. For proper operation, the pressure at
the center box must be lower than that at the auxiliary condenser
CW outlet with a certain amount of margin. Detailed system hy- Zhengyu Huang received the B.S. and M.S degrees in nuclear engineering and
draulic analyzes are needed, especially on the impacts of this nuclear engineering and nuclear safety from Harbin Shipbuilding Engineering
Institute, Harbin, China, in 1988 and 1991, respectively, and the Ph.D. degree in
change on the CW flow to auxiliary condensers and the main nuclear engineering from The Pennsylvania State University, University Park.
condenser. Moreover, it needs the analysis of possible impacts Currently, he is a Software Engineer with Thermoflow, Inc., Sudbury, MA. He
on the mechanical structure of the main condenser. The advan- was an Engineer with Beijing Institute of Nuclear Engineering, Beijing, China,
from 1991 to 1997. His research interests include power plant system heat bal-
tage of Scheme II over Scheme I is that once the system config- ance calculation and system optimization, reactor control, and simulation.
uration has been modified, there is no additional cost for system
operation and maintenance.
Scheme III (feedwater heater drain recycling) has the similar
effect on net power generation increase as Scheme II (ACCW
flow redirection). However, unlike Scheme II, which only needs Robert M. Edwards (M89) received the B.S. degree in nuclear engineering
from The Pennsylvania State University (PSU), University Park, in 1971, the
piping reconfiguration, Scheme III needs additional active me- M.S. degree in nuclear engineering from the University of Wisconsin-Madison
chanical componentsheater drain pumpsto overcome the in 1972, and the Ph.D. degree in nuclear engineering from PSU in 1991.
backpressure on the main feedwater line. The main concern is Currently, he is a Professor in nuclear engineering at Pennsylvania State Uni-
versity. Prior to returning to PSU, he was the Director of software development
the significantly increased cost for system retrofit and opera- at LeMont Scientific, State College, PA. In the early 1970s, he was with General
tion/maintenance. Another concern is about the mechanical ef- Atomic, San Diego, CA. His research interests are in control and simulation.

Authorized licensed use limited to: TOKYO INSTITUTE OF TECHNOLOGY. Downloaded on February 7, 2010 at 04:30 from IEEE Xplore. Restrictions apply.

You might also like