LIT-059
Edition 01/2013
Automatic
Series Control Valves
300 Valves General Information
Overview
BEECOS ACV, the latest line of state-of-the-art globe type automatic control valves, is designed to withstand even the
most demanding requirements of water system control.
This Engineering Data guide will asist the reader in the selection of the optimal BEECO ACV valve.
Features
Air release nut
Position indicator (optional)
Diaphragm discs
Double Chamber disc (optional)
Fully guided stem
Rubber seal
Seal discs
Seat
Stainless Steel internal parts
Centering guide
2 MIFAB, Inc., 1321 West 119th Street, Chicago, Illinois 60643-5109, USA Toll Free: 1-800-465-2736, Fax: 1-773-341-3049
All sales subject to MIFABs Terms and Warranties. Please refer to inside front cover. sales@mifab.com Canada Toll Free: 1-800-387-3880
Edition 01/2013
Engineering Data Automatic
Series 300Control
Valves Valves
Technical Specifications
Parameter Standard Optional
Connections
Flanged ANSI B16 Flanges ISO, AS10, JIS B22, and others
Threaded NPT
0 min. press. with N.O spring assisted opening.
Model ACV-HF: 7 250 psi 3 psi min. pressure without a spring
Pressure range Models ACV &: 7 360 psi
ACV-HF-HP Note: both options require usage of external higher
closing pressure
Materials
Part Standard Optional
Main Valve Internals SST, Bronze and Coated Steel SST 316, HASTELLOY, SMO, DUPLEX
EPDM
Seals NBR (Buna-N)
Viton
SST 304
Control Trim: Fittings and control devices Brass
SST 316
Copper
Control Trim: Tubes Reinforced, heavy-duty Nylon, Polypropylene
SST 316
Note: The Beeco ACV valves in all sizes, meet the USA amendment for reducing lead in drinking water marked as
S.3874 dated 01.05.2010.
3
MIFAB, Inc., 1321 West 119th Street, Chicago, Illinois 60643-5109, USA Toll Free: 1-800-465-2736, Fax: 1-773-341-3049
All sales subject to MIFABs Terms and Warranties. Please refer to inside front cover. sales@mifab.com Canada Toll Free: 1-800-387-3880
Edition 01/2013
Automatic
Series Control Valves
300 Valves Engineering Data
Closed Mode
Opened Mode
Opened Mode
4 MIFAB, Inc., 1321 West 119th Street, Chicago, Illinois 60643-5109, USA Toll Free: 1-800-465-2736, Fax: 1-773-341-3049
All sales subject to MIFABs Terms and Warranties. Please refer to inside front cover. sales@mifab.com Canada Toll Free: 1-800-387-3880
Edition 01/2013
Engineering Data Automatic
Series 300Control
Valves Valves
Closed
Closed
Closed Valve
FullyOpen
Fully Open
Cavitation energy
dissipation area
Fully-opened
Regulating
Regulating Valve
5
MIFAB, Inc., 1321 West 119th Street, Chicago, Illinois 60643-5109, USA Toll Free: 1-800-465-2736, Fax: 1-773-341-3049
All sales subject to MIFABs Terms and Warranties. Please refer to inside front cover. sales@mifab.com Canada Toll Free: 1-800-387-3880
Edition 01/2013
Series 300
Automatic Valves
Control Valves Engineering Data
Pressures logged
Pressures loggedatat1 1
Saughton Hall under 10 0mm DOROT 300 S eries CX Pilot Control Minute Intervals
Minute Intervals
100mm Beeco CX Pilot Control Flow
Flowlogged
loggedatat1515Minute
Minute
intervals
intervals
80 9
70 8
7
60
6
Metres
50
Flow Litre/sec
Pressure Metres
Flow Litre/sec
5
40
Pressure
30
3
20
2
10 1
0 0
9.2.2001 10.2.2001 11.2.2001 12.2.2001 13.2.2001 14.2.2001 15.2.2001 16.2.2001
Inlet
Inlet Pressure
Pressure Outlet
Outlet Pressure
Pressure Flow
Flow
Comparison of different
SERIES 300 seal structures
CHARACTERISTIC CURVE
% COMPARISON WITH COMPETITIVE DESIGNS
100
90
80
70
60
Valve opening
50
40
30
20
10
Unstable
Unstable regulation zone
regulation zone
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.6 0.7 0.8 1.0
Kn
Kv
** Independent
Independentlaboratory report
laboratory data
report source
data source
106
MIFAB, Inc., 1321 West 119th Street, Chicago, Illinois 60643-5109, USA Toll Free: 1-800-465-2736, Fax: 1-773-341-3049
All sales subject to MIFABs Terms and Warranties. Please refer to inside front cover. sales@mifab.com Canada Toll Free: 1-800-387-3880
Edition 01/2013
Engineering Data Series 300Control
Automatic Valves Valves
Cavitation Data
Inlet
Inlet pressure
pressure
psi mwc
360 250
240
340
230
320 220
210
300
200 Noisy
Noisy
280 190 Destructive
Destructive Operating
Operating
Cavitation
Cavitation
260 180
170
240
160
Case II
Case- 2
220 150
140
200 Case-1I
Case
130
180
120
160 110
CaseIII
Case- 3
100
140
90
120 80
100
70 Safe
Safe
60 Operating
Operating
80
50
Conditions
conditions
60 40
30
40
20
20 10 Outlet
Outlet
0 pressure
pressure
10 20 30 40 50 60 70 80 mwc
10 20 30 40 50 60 70 80 90 100 110 psi
Cavitation Chart
Limits of operating conditions
The chart above sets the safe limits for valves that are supposed to operate at a considerable pressure differential.
Such conditions generate noise and possible cavitation damages to the valve body.
How to use the chart:
i. Determine the maximal dynamic pressure that may be applied in the inlet of the valve.
ii. Draw an horizontal line from the pressure scale at the left side of the chart
iii. Find the requested outlet pressure in the pressure scale at the bottom of the chart.
iv. Draw an upward line at this point.
v. The intersection of the two lines defines the cavitation characteristics of the valve operation.
- In the case that it falls in the RED zone (case I)- the valve may be damaged in a fairly short time.
- In the case that it falls in the YELLOW zone (case II)- the valve may generate a noise that exceeds 80db.
- In the case that the intersection is within the GREEN zone (case III)- the valve will perform safely and quietly
General remark: The cavitation and noise data are based on tests done by the Utah State University, US, and Delft Hydraulic Laboratories, Holland.
7
MIFAB, Inc., 1321 West 119th Street, Chicago, Illinois 60643-5109, USA Toll Free: 1-800-465-2736, Fax: 1-773-341-3049
All sales subject to MIFABs Terms and Warranties. Please refer to inside front cover. sales@mifab.com Canada Toll Free: 1-800-387-3880
Edition 01/2013
Automatic Control
Series Valves
300 Valves Engineering Data
Head Loss Factor K (dimensionless) 1.3 2.8 3.3 4.3 4.3 4.2 3.6 Kv Cv 2g
8 MIFAB, Inc., 1321 West 119th Street, Chicago, Illinois 60643-5109, USA Toll Free: 1-800-465-2736, Fax: 1-773-341-3049
All sales subject to MIFABs Terms and Warranties. Please refer to inside front cover. sales@mifab.com Canada Toll Free: 1-800-387-3880
Edition 01/2013
Engineering Data Automatic
Series 300Control
ValvesValves
Headloss Charts
Models ACV-HF and ACV-HF-HP (Globe Pattern) Pressure Loss Chart
psi mwc
10
8
10
9
6
0mm
m
8
mm
0m
7 5
0mm
, 50
, 80
, 65
m, 5 , 2 "
, 45 ", 20"
300 2", 14"
mm
mm
mm
mm
0mm
0mm
6
m
, 35
, 70 2"
0mm
10"
80m
40m ", 2"
3"
4"
6"
8"
3
8
100
150
200
250
mm
400 16" ,1
1
1
mm
mm
3
24
4
3
2
1
10 100 1,000 10,000 m3/hr
3w 2w
8
10
9
6
8
7 5
0 mm
40m ", 2"
mm
mm
m
6
mm
m
4
m, 5
10"
m
3"
80m
4"
6"
8"
200
250
100
150
1
5
3
4
3
2
1
10 100 1,000 10,000 m3/hr
3w 2w
MIFAB, Inc., 1321 West 119th Street, Chicago, Illinois 60643-5109, USA Toll Free: 1-800-465-2736, Fax: 1-773-341-3049
9
All sales subject to MIFABs Terms and Warranties. Please refer to inside front cover.
sales@mifab.com Canada Toll Free: 1-800-387-3880
Edition 01/2013
Series 300
Automatic Valves
Control Valves Engineering Data
Kv 43 115 165 345 663 1160 1600 1600 3000 3000 3000
Flow rate factor
Cv 50 133 192 400 770 1360 1900 1900 3500 3500 3500
10 MIFAB, Inc., 1321 West 119th Street, Chicago, Illinois 60643-5109, USA Toll Free: 1-800-465-2736, Fax: 1-773-341-3049
All sales subject to MIFABs Terms and Warranties. Please refer to inside front cover. sales@mifab.com Canada Toll Free: 1-800-387-3880
Edition 01/2013
Engineering Data Automatic Control
Series 300 ValvesValves
8
10
0m m
9
6
8
, 60
"
", 24
7 5
0 mm
0 mm
,16"
, 20
6
, 40
, 50
4
14"
18"
mm
mm
5
m
m
m
mm
m
10"
350
450
m
m
m
12"
4"
80m
8"
3"
6"
3
100
150
200
250
300
4
3
2
1
10 100 1,000 10,000 m3/hr
3w 2w
11
MIFAB, Inc., 1321 West 119th Street, Chicago, Illinois 60643-5109, USA Toll Free: 1-800-465-2736, Fax: 1-773-341-3049
All sales subject to MIFABs Terms and Warranties. Please refer to inside front cover. sales@mifab.com Canada Toll Free: 1-800-387-3880
Edition 01/2013
Series 300
Automatic Valves
Control Valves Engineering Data
Components
Bonnet Assembly
Spring
Double-Chamber Diaphragm
Conversion Kit Assembly
Body Assembly
F Version
Conversion Kit
12 MIFAB, Inc., 1321 West 119th Street, Chicago, Illinois 60643-5109, USA Toll Free: 1-800-465-2736, Fax: 1-773-341-3049
All sales subject to MIFABs Terms and Warranties. Please refer to inside front cover. sales@mifab.com Canada Toll Free: 1-800-387-3880
Edition 01/2013
Waterworks Control Application Series 300
Automatic Valves
Control Valves
EL
of the main valve. The electric control can be added to most other control
applications.
EC
Pressure Regulating functions
PR Pressure Reducing valve
PR
Reduces high upstream pressure to a steady, lower downstream pressure,
regardless of fluctuations in the values of upstream-pressure or rate of flow.
Should downstream pressure exceed the required set point (due to
stoppage of the flow in the pipeline), the valve closes drip tight.
Beeco PR valve is also UL listed, for use in fire fighting systems.
Optional Pressure Reducing applications:
PRM(T2) Dual Set-Point, Timer-modulated pressure reducing valve
PRM
PRM(FM) Electronically-Controlled, Flow-Modulated PRV
PRM(HyMod) Hydraulically-Controlled, Flow-Modulated PRV
PR(D) Differential Pressure Reducing valve
PR(D)
the network upstream of its location.
Beeco PS valve is UL listed for use in fire-fighting systems.
Optional Pressure Sustaining applications:
PS(R) Pressure Sustaining\Relief valve
DI Differential- sustaining valve
PS
13
MIFAB, Inc., 1321 West 119th Street, Chicago, Illinois 60643-5109, USA Toll Free: 1-800-465-2736, Fax: 1-773-341-3049
All sales subject to MIFABs Terms and Warranties. Please refer to inside front cover. sales@mifab.com Canada Toll Free: 1-800-387-3880
Edition 01/2013
Series 300
Automatic Valves
Control Valves Waterworks Control Application
FL
and opens when the water level drops.
FLDI
The valve is activated by the hydrostatic pressure of the water level. It
closes when the water rise to the requested maximal level, and opens fully
when the water level drops to the preset minimal point. The differential
between the water levels is adjustable.
FLEL
the water levels is adjustable.
14 MIFAB, Inc., 1321 West 119th Street, Chicago, Illinois 60643-5109, USA Toll Free: 1-800-465-2736, Fax: 1-773-341-3049
All sales subject to MIFABs Terms and Warranties. Please refer to inside front cover. sales@mifab.com Canada Toll Free: 1-800-387-3880
Edition 01/2013
Waterworks Control Application Series 300
Automatic Valves
Control Valves
NS
The valve is in open position when inlet pressure is higher than outlet
pressure.
The valve closes, preventing returning flow, on inverted flow direction.
BC
by rapid change of the pipe velocity. Opens slowly on the pump startup,
and closes at adjustable pace before shut-off. The pump motor is then
switched-off by an electric interlink with the valve.
Optional Pump Control valve applications:
BC/PS Pump control and Back-pressure sustaining valve
BC/CD Pump control valve with extended closure, for long pipelines
BC/DI Booster pump control, maintains constant flow at varying suction
conditions
DW
the Check valve. Eliminating pressure surges caused by sudden change of
the pipe velocity through start-up and shut-off.
SP Surge-preventing closure
A unique BEECO control module, that can be added to any automatic valve.
It prevents water hammer, that is generated by the valve closure, when it is
located at the end of a long pipeline.
15
MIFAB, Inc., 1321 West 119th Street, Chicago, Illinois 60643-5109, USA Toll Free: 1-800-465-2736, Fax: 1-773-341-3049
All sales subject to MIFABs Terms and Warranties. Please refer to inside front cover. sales@mifab.com Canada Toll Free: 1-800-387-3880
Edition 01/2013
Automatic Control
Series 300 Valves
Valves Fire Fighting Applications
Deluge Valves
The Beeco UL Deluge Valves are suitable for systems that include Electric,
Hydraulic or Pneumatic detections. The Beeco ACV Deluge Valves are
DE/EL
activated by each signal or by combinations thereof. All applications are
equipped with a manual emergency actuation valve and approved for use in
Fire Protection Systems as Automatic Reset or Manual Reset Valves.
Monitor Valves
The Beeco ACV Monitor Valves are designed to open immediately as a
response to Electric, Hydraulic, Pneumatic or manual activation. The valves
use the line pressure to develop maximum power and do not need any
U-DE/EL
external source of power.
The Beeco ACV Monitor Valves are designed to be activated locally or
remotely.
PR/UL
The Beeco ACV UL Pressure Reducing Valves are designed to maintain
constant downstream pressure at all flow conditions.
16 MIFAB, Inc., 1321 West 119th Street, Chicago, Illinois 60643-5109, USA Toll Free: 1-800-465-2736, Fax: 1-773-341-3049
All sales subject to MIFABs Terms and Warranties. Please refer to inside front cover. sales@mifab.com Canada Toll Free: 1-800-387-3880