MV Air Insulated

Metal Enclosed
Switchgears

Rated Voltage : 12 kV - 38.5 kV


Rated Current : 400 A - 1250 A
Short Circuit Current : 16 kA - 25 kA

Standard IEC 62271-200

Nature is
Our Most
Valuable Partner
MV Air Insulated Metal Enclosed Switchgears
Brief History Of Company; Elimsan

for manufacturing electrical switchgears and switching


devices.

ELIMSAN is a specialist company in the electrical


switchgears production for the range 7,2 kV 525 kV.
We have a very big capacity for the production of SF6
Gas and Vacuum Circuit Breakers (10000 pcs./year),
Metal Enclosed Switchgears (3000 panels/year), Metal
Clad Switchgears (1500 panels / year), High Voltage-
Disconnectors (3000 units / year).

Some of other main products are; MV-HV CTs, VTs, Fuses, and Lighting Fixtures. All of
ourproducts have type test reports from CESI (Italy), KEMA (Holland), IPH (Germany) and ICMET (Romania).

By developing its own technology considering quality importance, Elimsan became one of

transmission and distribution systems. Since last 29 years, more than 100.000 units of these equipments had been
manufactured and distributed over all Turkey and world.They are all under operation satisfactorily since their assembly

Elimsan has a very large land more than 550.000 sqm and 50.000 sqm closed facilities. All of our
equipments are manufactured with CNC controlled workbenches under the ISO 9001 Quality Management
System and ISO 14001 Environmental Management System. Our products are tested in our accredited High Voltage
Laboratories according to ISO 17025 standards.

Since the establishment date, Elimsan always produces advanced technology along the Turkeysdevelopment
process; represents our country successfully, challenges in competitive international market conditions. Its
products are preferred on wide geographical areas from Australia to Estonia, from Far East to South America.

In the year of 2008 Elimsan has signed a partnership agreement with Saudi Cable which is on of the

Elimsan is a creative, innovated and dynamic company. We respect and pay much attention to
communicate and interact with our clients; and meeting each customers needs is our number one priority.

3
MV Air Insulated Metal Enclosed Switchgears

Elimsan TG21-XX designation covers medium voltage cubicles or prefabricated systems with SF6 or vacuum

switchgears TG21-XX type suitable for:

Small substations for private users


MV- LV public distribution substations
Medium voltage metering substations
Network substations and industrial applications
Motor control centers with vacuum contactors

These switchgears permit carry out all the functions that could be presented, so much in the networks of
electrical energy distribution and transformer centers.

Operations of development, such as to break in no-load of the ring networks or radial networks.
Disconnecting with earthing of the active parts, to effect periodic maintenance.
Protection of power transformers for overloads and short circuits.
Troubleshooting in cables and monitoring the phases conformity before making of cloosed- loops.

STANDARTS

The switchgears have been developed and tested according to the following procedures:

IEC 62271-200. A.C. Metal-Enclosed Switchgear and Controlgear


IEC 62271-100. High-voltage circuit breakers
IEC 60265-1. High-voltage switches
IEC 60420. High-voltage alternating current switch-fuse combinations.
IEC 62271-102. High-voltage disconnector and earthing switchs.

PROTECTION DEGREE
Load Break Switch : IP68
Busbar Compartment : IP3X
Between Compartment : IP3X
Mechanisms : IP3X
Cable Compartment : IP3X

Switchgear in service:

Being in service with the switch closed, to access to the interior of the switchgear, its necessary to accomplish
the following operations:
Open the switch.
Verify the absence of tension in the cables by means of the neon lamps of voltage indicators.
Close the earthing-switch.
Open the door.

Switchgear out of service:

To open the door previously earthing switch must be closed. In this position:
The switch can not be closed.
The earthing switch can not be opened.

4
MV Air Insulated Metal Enclosed Switchgears
EXAMPLE 1

Distribution feeder with measuring and protection

Exist a double interlock:

Among the Load Break Switch and the earthing switch


Among the Load Break Switch, the earthing switch and the door.

To accomplish the measure in cables will can be get, by a wiling action, realising the interlocks using an

This equipment prevents closing of the door and, before closing it have to be removed, remaining the
interlocks in its initial position.

To prevent that someone could operate the switchgear, while are effected the measurements in the cables,
exits a safety device that prevents the introduction of the operating lever.

Limited overall dimensions:


The switchboards can be installed in small rooms and be leaned against the wall. All the operations are carried
out at the front of the switchboard.

Service continuity:
The segregations of the various compartments allow to operate when switchboard alive to re-place
components such as fuses, relays, cable terminals, etc.

Safety:
Suitables mechanical and key locks, guarantee the safety of personel, prevent-
ing from any possibility of wrong operations. The metal segregations between the bus-
bar compartment and the instruments compartment, prevents accidental contacts with medium
voltage components. The switchboard is provided with grounding of the whole structure and components.

Inspection and maintenance:


Inspection of the equipment is facilitated by porthole placed on the unit door and the maintenance is simple by
the easy access to equipment with open door.

Construction characteristics and painting:


The structural steelwork is made of bent and bolted sheet plate, painting with electrostatic powder colour
RAL7032.

5
MV Air Insulated Metal Enclosed Switchgears

The busbar insulating supports are integral with the switchgear (switch or disconnector)

The busbars consist of:


Aluminium or copper bar for 400A and 630A

conventional crew/spring washer attachment. The connection screw is covered by a stress cap.

The front access is elosed by a bolted plate with a yellow warning plate.

EXAMPLE 2 EXAMPLE 3
Customer Measurement and Distrubution Center
Transformer Protection System

Load Break Switch cubicles and off-load disconnector cubicles: The lower part of the switch and of the

clips.
Transformer protection cubicles: Connection is made at the fuse lower supports.
Circuit Breaker cubicles: connection is made on a support lug mounted on the capacitor dividers.

The reduced depth of the cubicles results in the last phase being within arm reach, and this greatly facilitates
cable installation.
For easier work, a stud enables the operator to hook up the cable end clip during the connection operation.

EARTHING SWITCHES
In generally Elimsan switchboards have two simultaneously operated earthing switches. The station earth
bar is situated on the cubicle top. The station is connected to earth by means of a contact stud on the
forward part of the side partition.

The lower part of cubicles houses standardized for fuses. During fuses changing the operators safety is
ensured by two earthing switches.

Capacitor bank protection:

6
MV Air Insulated Metal Enclosed Switchgears
Motor protection:
Within the limit of 3 starting per hour, each of a duration
of 10 seconds and with Id/ln < 6 (Id = starting current and
In = motor rated current), use fuses with a rated current
immediately superior to 3 times the motor rated current.

Safety is a constructional feature at the switchboards.


During the internal arc fault the gases are directed into
the rear vent, thus preserving the safety of the
operator standing in front of the cubicle.

Tests have demonstrated the absence of dangerous


distortions or projections of elements in way
of the station front panel.

DISCONNECTOR MONITORING
The disconnector control is shown on the mimic
diagram by the position of a rod directly coupled to the
control shaft carrying the contacts without any intermediate
linkage. This provides a fail safe indication of the position
(open or closed) of the switch.
Circuit Breaker Compartment

VOLTAGE MONITORING
Voltage presence or absence is shown by means of
neon indicator lights connected to the capacitor dividers

possible to check the phase sequence of two adjacent


panels in a fail safe way, as shown on the sketch opposite.

Correct phase sequence:


Presence lights on. Test light off.
Incorrect phase sequence:
Presence lights dimming. Test light on.
No voltage condition without test light.
Light off. Disconnector and Earthing
Switch Control Panel
Checking that cables which are not live is of major
importance prior to closing the earthing switch.
Hence the feature of the neon lamp which is a fail safe
system to indicate live cables.
DATA DEFINING THE
SWITCHBOARD
OPTIONAL ACCESSORIES Single-line diagram
Shunt opening release Layout of the switchboard, relative position
Gearmotor for spring charging of the vairous units
Auxiliary contacts Rated and service voltage
Additional key locks Frequency
Short-circuit current at service voltage
Rated current
Supply voltage for auxiliary services
Digital protective relays Installation ambient
Indicating metering insturments Switchboard accessories
Current transformers
Voltage transformers

7
MV Air Insulated Metal Enclosed Switchgears

TYPES DESCRIPTION 1 2 3 4 5 6 7 8 9 10 11 12

TG21-01 X X

TG21-02 X X X X X X

TG21-02V X X X X X X

TG21-03 X X X X

TG21-04 X X X X

-
TG21-04V X X X X
NECTOR

TG21-05 X X X X X

TG21-05V X X X X X

TG21-07 X X X X X

TG21-11 X X X X

TG21-13 X X X X X

TG21-14 X X X X

TG21-15 X X X

TG21-16 X X X X X

TG21-17 X X

TG21-18 X

TG21-19 X X

TG21-22 X X

TG21-27 X X X X X X X

TG21-27V X X X X X X X

1 Disconnector Switch 5 Current Transformer 9 Fuses with 3P Tripping

2 Load Break Switch 6 Voltage Transformer 10 Fuses without 3P Tripping

3 SF6 Circuit Breaker 7 Protection relay 11 Earthing Switch

4 Vacuum Circuit Breaker 8 Capacitive Voltage Divider 12 Bushing Insulator

8
MV Air Insulated Metal Enclosed Switchgears
General 12 kV 17.5 kV 24 kV 36 kV 38,5 kV

Rated voltage 12 kV 17.5 kV 24 kV 36 kV 38,5 kV

Rated withstand voltage 50-60 Hz. 1min. 28 kV 38 kV 50 kV 70 kV 80 kV

Rated withstand voltage across isolating distance 50-60


32 kV 45 kV 60 kV 80 kV 95 kV
Hz 1min

Rated impulse withstand voltage 1.2 / 50s 75 kV 95 kV 125 kV 170 kV 180 kV

Rated impulse withstand voltage across isolating


85 kV 110 kV 145 kV 195 kV 195 kV
distance 1,2 / 50s

Rated current of transformer feeder 400/630/1250A 400/630/1250A 400/630/1250A 400/630/1250A 400/630/1250A

Atmosphere conditions -5/+50 C -5/+50 C -5/+50 C -5/+50 C -5/+50 C

Load Break Switch 12 kV 17.5 kV 24 kV 36 kV 38,5 kV

Rated mainly active load breaking current 400 A 400/630 A 400/630 A 400/630 A 400/630 A

Rated closed-loop breaking current 400 A 400/630 A 400/630 A 400/630 A 400/630 A

Rated cable-charging breaking current 25 A 25 A 25 A 25 A 25 A

Rated no-load transformer breaking current 10(16) A 10(16) A 10(16) A 10(16) A 10(16) A

Rated short-circuit making current (peak) 40 kA 40/50 kA 40/50/63 kA 40/50/63 kA 40/50/63 kA

Rated short-time current 1s (rms) 16 kA 16/20 kA 16/20/25 kA 16/20/25 kA 16/20/25 kA

0.5 Bar 0.5 Bar 0.5 Bar 0.5 Bar 0.5 Bar
switch 20 C

Earthing Switch 12 kV 17.5 kV 24 kV 36 kV 38,5 kV

Rated short-time current, 1s (rms) 16 kA 16/20 kA 16/20/25 kA 16/20/25 kA 16/20/25 kA

Rated short-circuit making current (peak) 40/50 kA 40/50/63 kA 40/50/63 kA 40/50/63 kA 40/50/63 kA

Fuses (Striker fuse units according IEC 60282) 12 kV 17.5 kV 24 kV 36 kV 38,5 kV

Dimensions (Medium Type) 292 mm 442 mm 442 mm 537 mm 537 mm

Maximum power dissipate value 75 W 75 W 75 W 75 W 75 W

Main Dimensions 12 kV 17.5 kV 24 kV 36 kV 38,5 kV

Height (mm) 1950 1950 1950 2250 2250

Wide (mm) 750/500/375 750/500/376 900/500 1150/1000/750 1150/1000/750

Depth (mm) 1000 1000 1000 1400 1400

9
MV Air Insulated Metal Enclosed Switchgears

10
11
MV Air Insulated Metal Enclosed Switchgears
MV Air Insulated Metal Enclosed Switchgears

Elimsan Medium Voltage Elimsan Voltage Elimsan Medium


Circuit Breaker Detector Systems Voltage Fuses

Elimsan Medium Voltage Elimsan Medium Voltage Elimsan Medium Voltage


Voltage Transformers Current Transformers Earthing Switches

12
LEGEND

13
MV Air Insulated Metal Enclosed Switchgears
MV Air Insulated Metal Enclosed Switchgears

TG21-13-36 Metering With TG21-01-36 Incoming and Outgoing TG21-02-36 Transformer


Load Break Switch With Load Break Switch Protection With CB and CT

TG21-14-24 Transformer TG21-01-24 Incoming and Outgoing TG21-02-24 Transformer


Protection with LBS With Load Break Switch Protection With CB and CT

CONTACT
EQUIPMENT VOLTAGE POWER
QUANTITY

Motor 24,48,110,VDC 340 W

Tripping Coil 24,48,110,VDC 80 VA


4NO + 4NC,6NO + 6NC
8NO + 8NC
Closing Coil 24,48,110,VDC 80 VA

Auxiliary Switch 10 A -220VAC