You are on page 1of 1

***************

PowerWorldSimulator7.0
ContingencyAnalysis

NameofBaseCase:H:\Mary\ExampleScripts\B7OPF.pwb
Reportprintedat:7/11/0211:27:24AM

***************
BASECASE
BRANCHMVAVIOLATIONS:
Bus1TOBus3CKT1MVA:65.0LIM:65.0%:100.0
BRANCHAMPVIOLATIONS:
None.
BUSLOWVOLTAGEVIOLATIONS:
None.
BUSHIGHVOLTAGEVIOLATIONS:
None.
INTERFACEVIOLATIONS:
None.
***************
CONTINGENCYContingencies
ELEMENTS:
OPENGenBus1#1
OPENBranchBus1TOBus3CKT1
OPENBranchBus2TOBus5CKT1
OPENBranchBus6TOBus7CKT1
OPENGenBus4#1
OPENGenBus2#1
NUMBEROFVIOLATIONS:
BRANCH:2
BUSVOLTAGE:2
INTERFACE:0
ISOLATEDBUSES:0
BRANCHMVAVIOLATIONS:
Bus4TOBus5CKT1MVA:113.6LIM:60.0%:189.4
Bus7TOBus5CKT1MVA:267.8LIM:200.0%:133.9
BRANCHAMPVIOLATIONS:
None.
BUSLOWVOLTAGEVIOLATIONS:
Bus3LOWVVOLT:0.8781LIMIT:0.9000
Bus4LOWVVOLT:0.8831LIMIT:0.9000
BUSHIGHVOLTAGEVIOLATIONS:
None.
INTERFACEVIOLATIONS:
None.