You are on page 1of 37

Table Of Contents

VIEW OF BARE CONDUCTOR 2

AAC ALL ALUMINUM CONDUCTOR 3

AAAC ALL ALUMINUM ALLOY CONDUCTOR 6

T - AAAC THERMAL RESISTANCE ALL ALUMINUM ALLOY CONDUCTOR 8

ACSR ALUMINUM CONDUCTOR STEEL REINFORCED 9

T - ACSR THERMAL RESISTANCE ALUMINUM CONDUCTOR 15


STEEL REINFORCED

ACSR / AS ALUMINUM CONDUCTOR - ALUMINUM CLAD STEEL 16


REINFORCED

T - ACSR / AS THERMAL RESISTANCE ALUMINUM CONDUCTOR - 22


ALUMINUM CLAD STEEL REINFORCED

23
STACIR SUPER THERMAL RESISTANCE - INVAR REINFORCED

STACIR / AW SUPER THERMAL RESISTANCE - ALUMINUM CLAD 24


INVAR REINFORCED

25
ACCR ALUMINUM CONDUCTOR COMPOSITE REINFORCED

ACCC / TW ALUMINUM CONDUCTOR COMPOSITE CORE 26


TRAPEZOIDAL CONCENTRIC-LAY-STRANDED

AAAC - S ALL ALUMINUM ALLOY CONDUCTOR, XLPE INSULATED 27

CONVERSION TABLE 28

NF/NFA2X COPPER/ALUMINUM CONDUCTOR, XLPE INSULATED 29

NFA2X - T ALUMINUM CONDUCTOR, XLPE INSULATED + NEUTRAL 30


NEUTRAL MESSENGER

DUPLEX ALUMINUM CONDUCTOR, XLPE INSULATED + NEUTRAL 34


NEUTRAL MESSENGER

TRIPLEX ALUMINUM CONDUCTOR, XLPE INSULATED + NEUTRAL


NEUTRAL MESSENGER 35

QUADRUPLEX ALUMINUM CONDUCTOR, XLPE INSULATED + NEUTRAL 36


NEUTRAL MESSENGER
View Of Bare Conductor

AAC All Aluminum Conductor


AAAC All Aluminum Alloy Conductor
T-AAAC Thermal Resistance All Aluminum
Alloy Conductor

ACSR 1. All Aluminum Conductor

1 2. Galvanized Steel Wire

T-ACSR 1. Thermal Resistance Aluminum


Alloy Conductor

2. Galvanized Steel Wire

STACIR 1. Super Thermal Resistance Aluminum


Alloy Conductor

2. Galvanized Invar
2
ACCR 1. Aluminum-Zirconium

2. Galvanized Steel Wire

ACSR / AS 1. All Aluminum Conductor


1
2. Aluminum - Clad Steel Wire

T-ACSR / AS 1. Thermal Resistance Aluminum


Alloy Conductor

2. Aluminum - Clad Steel Wire

STACIR / AW 1. Super Thermal Resistance Aluminum


Alloy Conductor

2 2. Aluminum - Clad Invar

ACCC / TW 1. Aluminum Conductor

2. High Strength Carbon Fiber

2
AAC All Aluminum Conduc
Conductor
tor
Application : Used for overhead power transmission purpose, medium tension. Overhead system and distribution
network.

Construction
Conductor : Circular stranded All Aluminum Conductor [AAC]

Packing : Drum

Specification : SPLN 41-6

Cross Section DC Rated


Overall Weight
Area No. of Diameter of Current Standard
Diameter Resistance Ultimated
Wires Wires Approx Rating
At 20C Strength Length
Nominal Actual Approx
mm mm pcs mm mm kg/km /km A kg m
16 16.84 7 1.75 5.25 46 1.7000 150 310 10,000
25 27.83 7 2.25 6.75 76 1.0290 145 490 10,000
35 34.36 7 2.50 7.50 94 0.8332 165 590 10,000
50 49.48 7 3.00 9.00 135 0.5786 205 810 10,000
50 45.70 19 1.75 8.75 126 0.6295 195 835 10,000
55 58.07 7 3.25 9.75 159 0.4930 230 935 10,000
70 75.55 19 2.25 11.25 208 0.3808 270 1,040 5,000
95 93.27 19 2.50 12.50 257 0.3084 305 1,560 5,000
100 99.30 7 4.25 12.75 272 0.2883 320 1,540 5,000
120 112.85 19 2.75 13.75 310 0.2549 345 1,890 5,000
150 157.62 19 3.25 16.25 434 0.1825 430 2,530 5,000
150 147.11 37 2.25 15.75 406 0.1960 410 2,575 5,000
185 181.62 37 2.50 17.50 501 0.1587 470 3,110 5,000
200 209.85 19 3.75 18.75 577 0.1371 510 3,290 3,000
24 238.76 19 4.00 20.00 657 0.1205 555 3,700 3,000
240 242.54 61 2.25 20.25 670 0.1191 560 4,020 3,000
300 299.43 61 2.50 22.50 827 0.0965 640 4,850 3,000
400 431.18 61 3.00 27.00 1,191 0.0670 805 6,675 2,000
500 506.04 61 3.25 29.25 1,398 0.0571 890 7,700 2,000
630 643.24 91 3.00 33.00 1,782 0.0450 1,030 9,960 1,500
800 754.91 91 3.25 35.75 2,091 0.0384 1,135 11,480 1,000
1.000 1,005.06 91 3.75 41.25 2,784 0.0288 1,345 14,925 1,000

03
AAC All Aluminum Conduc
Conductor
tor
Application : Used for overhead power transmission purpose, medium tension. Overhead system and distribution
network.

Construction
Conductor : Circular stranded All Aluminum Conductor [AAC]

Packing : Drum

Specification : ASTM B231

Overall
Cross Section
Area Diameter Weight DC Rated
Code No. of Diameter Approx. Approx. Resistance Current Ultimated Standard
Name AWG or Wires of Wires At 20C Rating Strength Length
MCM mm2 pcs mm mm kg/km /km A kg m
Peachbell 6 13.29 7 1.55 4.70 37 2.1710 90 254 10,000
Rose 4 21.16 7 1.96 5.90 58 1.3638 120 404 10,000
Iris 2 33.61 7 2.47 7.40 93 0.8568 160 610 10,000
Pansy 1 42.38 7 2.78 8.30 117 0.6804 185 726 10,000
Poppy 1/0 53.48 7 3.12 9.40 147 0.5391 215 890 10,000
Aster 2/0 67.41 7 3.50 10.40 186 0.4281 250 1,121 5,000
Phlox 3/0 85.03 7 3.93 11.80 234 0.3392 290 1,373 5,000
Oxlip 4/0 107.22 7 4.42 13.30 259 0.2688 335 1,732 5,000
Valerian 250.000 126.70 19 2.91 14.60 349 0.2277 370 2,101 5,000
Sneezewort 250.000 126.72 7 4.80 14.60 349 0.2275 370 2,047 5,000
Daisy 266.800 135.16 7 4.96 14.90 373 0.2131 385 2,185 5,000
Laurel 266.800 135.16 19 3.01 15.10 373 0.2132 390 2,180 5,000
Peony 300.000 152.00 19 3.19 16.00 419 0.1895 420 2,452 5,000
Tulip 336.400 170.45 19 3.38 16.90 470 0.1690 450 2,750 5,000
Daffodil 350.000 177.35 19 3.45 17.20 489 0.1626 460 2,858 5,000
Canna 397.500 201.41 19 3.68 18.40 556 0.1431 500 3,249 3,000
Goldentuft 450.000 228.00 19 3.91 19.60 628 0.1264 540 3,567 3,000
Syringa 477.000 241.54 37 2.88 20.18 667 0.1194 560 3,922 3,000
Cosmos 477.000 241.67 19 4.02 20.10 666 0.1194 560 3,778 3,000
Hyacinth 500.000 253.06 37 2.95 20.66 699 0.1139 575 4,109 3,000
Zinnia 500.000 253.35 19 4.12 20.60 698 0.1138 575 3,963 3,000
Dahlia 556.500 282.00 19 4.35 21.70 777 0.1023 615 4,409 3,000
Mistletoe 556.500 282.00 37 3.11 21.80 777 0.1023 615 4,444 3,000
Meadowsweet 600.000 304.00 37 3.23 22.60 838 0.0949 645 4,790 3,000
Orchid 636.000 322.25 37 3.33 23.30 888 0.0895 670 5,082 2,000
Heuchera 650.000 329.35 37 3.37 23.60 908 0.0875 680 5,199 2,000
Flag 700.000 354.71 61 2.72 24.50 978 0.0813 715 5,854 2,000
Verbena 700.000 354.71 37 3.49 24.50 978 0.0813 710 5,592 2,000

04
AAC All Aluminum Conduc
Conductor
tor
Application : Used for overhead power transmission purpose, medium tension. Overhead system and distribution
network.

Construction
Conductor : Circular stranded All Aluminum Conductor [AAC]

Packing : Drum

Specification : ASTM B 231

Cross Section Rated


Overall DC
Area No. of Diameter Weight Current Standard
Diameter Resistance Ultimated
Code Wires of Wires Approx. Rating Length
Approx. At 20C Strength
Name AWG or
MCM mm2 pcs mm mm kg/km /km A kg m
Nasturtium 715.500 362.58 61 2.75 24.80 1,000 0.0795 725 5,822 2,000
Violet 715.500 362.58 37 3.53 24.70 1,000 0.0795 725 5,721 2,000
Cattail 750.000 380.00 61 2.82 25.30 1,048 0.0758 745 6,104 2,000
Petunia 750.000 380.00 37 3.62 25.30 1,048 0.0758 745 5,996 2,000
Lilac 795.000 402.84 61 2.90 26.10 1,111 0.0715 770 6,474 2,000
Arbutus 795.000 402.84 37 3.72 26.10 1,111 0.0715 770 6,356 2,000
Snapdragon 900.000 456.06 61 3.09 27.80 1,257 0.0632 835 7,117 2,000
Cockscomb 900.000 456.06 37 3.96 27.70 1,257 0.0632 835 6,982 2,000
Goldenrod 954.000 483.42 61 3.18 28.60 1,333 0.0596 865 7,547 2,000
Magnolia 954.000 483.42 37 4.08 28.60 1,333 0.0596 865 7,401 2,000
Camelia 1,000.000 506.71 61 3.25 29.30 1,397 0.0569 890 7,898 2,000
Hawkweed 1,000.000 506.71 37 4.18 29.20 1,397 0.0569 890 7,757 2,000
Larkspur 1,033.500 523.68 61 3.31 29.80 1,444 0.0550 910 8,172 2,000
Bluebell 1,033.500 523.68 37 4.24 29.70 1,444 0.0551 910 8,012 2,000
Marigold 1,113.000 563.93 61 3.43 30.90 1,555 0.0511 950 8,802 1,000
Hawthorn 1,192.500 604.26 61 3.55 32.00 1,665 0.0477 990 9,423 1,000
Narcissus 1,272.000 644.51 61 3.67 33.00 1,777 0.0447 1,030 10,054 1,000
Columbine 1,351.500 684.84 61 3.78 34.00 1,888 0.0421 1,070 10,363 1,000
Carnation 1,431.000 725.10 61 3.89 35.00 1,999 0.0397 1,110 10,980 1,000
Gladiolus 1,510.500 765.35 61 4.00 36.00 2,110 0.0376 1,145 11,593 1,000
Coreopsis 1,590.000 805.68 61 4.10 37.00 2,222 0.0358 1,180 12,192 1,000
Jessamine 1,750.000 886.71 61 4.30 38.70 2,445 0.0325 1,250 13,429 1,000
Cowslip 2,000.000 1,013.00 91 3.76 41.40 2,793 0.0288 1,345 15,329 1,000
Sagebrush 2,250.000 1,140.00 91 3.99 43.90 3,174 0.0255 1,440 17,250 500
Lupine 2,500.000 1,267.00 91 4.21 46.30 3,527 0.0230 1,530 19,167 500
Bitterroot 2,750.000 1,393.00 91 4.42 48.60 3,880 0.0209 1,610 21,089 500
Trillium 3,000.000 1,520.00 127 3.90 50.70 4,232 0.0192 1,690 22,758 500
Bluebonnet 3,500.000 1,773.00 127 4.22 54.80 4,985 0.0164 1,830 26,540 500

05
AAAC All Aluminum Alloy Conduc
Conductor
tor
Application : Used for overhead power transmission purpose, medium tension. Overhead system and distribution
network.

Construction
Conductor : Circular stranded All Aluminum Alloy Conductor [AAAC]

Packing : Drum

Specification : SPLN 41-8

Cross Section Area Overall DC Rated


Weight Current Standard
No. of Diameter Diameter Resistance Ultimated
Approx. Rating Length
Wires of Wires Approx. At 20C Strength
Nominal Actual
mm2 mm2 pcs mm mm kg/km /km A kg m
16 16.84 7 1.75 5.25 46 1,955 100 480 10,000
25 27.83 7 2.25 6.75 76 1,183 135 790 10,000
35 34.36 7 2.50 7.50 94 0,958 155 980 10,000
50 49.48 7 3.00 9.00 135 0,665 195 1,410 10,000
50 45.70 19 1.75 8.75 126 0,724 185 1,300 10,000
55 58.07 7 3.25 9.75 160 0,567 215 1,655 10,000
70 75.55 19 2.25 11.25 208 0,438 255 2,150 5,000
95 93.27 19 2.50 12.50 256 0,355 290 2,660 5,000
100 99.30 7 4.25 12.75 272 0,332 300 2,830 5,000
120 112.85 19 2.75 13.75 310 0,293 325 3,220 5,000
150 157.62 19 3.25 16.25 434 0,210 405 4,490 5,000
150 147.11 37 2.25 15.75 406 0,225 385 4,190 5,000
185 181.62 37 2.50 17.50 501 0,183 440 5,175 5,000
240 238.76 19 4.00 20.00 670 0,137 525 6,805 3,000
240 242.54 61 2.25 20.25 657 0,139 525 6,910 3,000
300 299.43 61 2.50 22.50 827 0,111 605 8,530 3,000
400 431.18 61 3.00 27.00 1,191 0,077 760 12,290 2,000
500 506.04 61 3.25 29.25 1,398 0,066 835 14,420 2,000
630 643.24 91 3.00 33.00 1,782 0,052 965 18,330 1,500
800 754.91 91 3.25 35.75 2,091 0,044 1,075 21,515 1,000
1.000 1,005.06 91 3.75 41.25 2,784 0,033 1,265 28,640 1,000

06
AAAC All Aluminum Aloy Conduc
Conductor
tor
Application : Used for overhead power transmission purpose, medium tension. Overhead system and distribution
network.

Construction
Conductor : Circular stranded All Aluminum Aloy Conductor [AAAC]

Packing : Drum

Specification : ASTM B 399

Cross Section Rated


Overall DC
Area No. of Diameter Weight Current Standard
Diameter Resistance Ultimated
Wires of Wires Approx. Rating Length
Approx. At 20C Strength
AWG or
MCM mm2 pcs mm mm kg/km /km A kg m
6 13.28 7 1.55 4.66 37, 2.52240 85 429 10,000
4 21.14 7 1.96 5.88 59 1.58460 115 683 10,000
2 33.65 7 2.47 7.42 93 0.99550 150 1,087 10,000
1/0 53.48 7 3.12 9.36 147 0.62640 200 1,728 10,000
2/0 67.35 7 3.50 10.50 185 0.49740 235 2,077 5,000
3/0 85.00 7 3.93 11.80 235 0.39410 270 2,621 5,000
4/0 107.26 7 4.42 13.25 296 0.31230 315 3,307 5,000
250.000 126.63 19 2.91 14.57 348 0.26450 350 3,962 5,000
300.000 152.14 19 3.19 15.97 419 0.22020 390 4,760 5,000
350.000 177.28 19 3.45 17.25 490 0.18900 430 5,295 5,000
400.000 202.70 19 3.69 18.43 560 0.16530 470 6,054 3,000
450.000 228.03 19 3.91 19.55 629 0.14690 505 6,810 3,000
500.000 253.30 19 4.12 20.60 699 0.13230 540 7,564 3,000
550.000 278.59 37 3.10 21.67 769 0.12020 575 8,529 3,000
600.000 303.74 37 3.23 22.63 839 0.11030 605 9,299 3,000
650.000 329.64 37 3.37 23.58 909 0.10160 640 9,633 2,000
700.000 354.56 37 3.49 24.45 979 0.09448 670 10,361 2,000
750.000 380.18 37 3.62 25.32 1,049 0.08811 700 11,109 2,000
800.000 405.13 37 3.73 26.14 1,119 0.08268 725 11,839 2,000
900.000 456.26 37 3.96 27.73 1,258 0.07342 785 13,333 2,000
1,000.000 506.77 37 4.18 29.23 1,399 0.06610 835 14,808 2,000
1,250.000 633.04 61 3.64 32.72 1,737 0.05292 960 18,295 1,500
1,500.000 760.05 61 3.98 35.85 2,086 0.04407 1,075 21,965 1,000
1,750.000 887.08 61 4.30 38.73 2,434 0.03776 1,180 25.636 1,000

07
AAAC All Aluminum Alloy Conduc
Conductor
tor
Application : Used for overhead power transmission purpose, medium tension. Overhead system and distribution
network.

Construction
Conductor : Circular stranded thermal resistance All Aluminum Alloy Conductor (T-AAAC)

Packing : Drum

Specification : JEC 197

Cross Section Area Overall DC Rated


Weight Current Standard
No. of Diameter Diameter Resistance Ultimated
Approx. Rating Length
Wires of Wires Approx. At 20C Strength
Nominal Actual
mm2 mm2 pcs mm mm kg/km /km A kg m
150 152.81 19 3.20 16.00 419 0.1910 650 2,270 5,000
200 204.29 19 3.70 18.50 560 0.1430 790 3,030 5,000
240 238.76 19 4.00 20.00 655 0.1220 897 3,490 3,000
300 297.57 37 3.20 22.40 820 0.0985 1,030 4,430 3,000
400 397.83 37 3.70 25.90 1,097 0.0737 1,258 5,890 2,000
510 512.61 37 4.20 29.40 1,413 0.0571 1,491 7,460 2,000
660 655.88 61 3.70 33.30 1,812 0.0448 1,753 9,720 1,500
850 845.12 61 4.20 37.80 2,334 0.0347 2,073 12,300 1,000
980 978.44 91 3.70 40.70 2,716 0.0302 2,272 14,500 1,000
1,030 1,032.04 91 3.80 41.80 2,864 0.0286 2,353 15,320 1,000
1,260 1,260.75 91 4.20 46.20 3,449 0.0234 2,672 18,350 500
1,600 1,595.93 127 4.00 52.00 4,439 0.0186 3,225 23,320 500
2,020 2,019.85 127 4.50 58.50 5,618 0.0147 3,705 29,490 500
2,500 2,493.64 127 5.00 65.00 6,936 0.0118 4,180 36,350 300

08
ACSR Aluminum Conductor Steel Reinforced

Application : Used for overhead transmission lines.

Construction
Conductor : The center wire or wires of galvanized steel and the outer layer or layers of aluminum.

Packing : Drum

Specification : SPLN 41-7

Cross Section Area No. / Diameter of Wires Overall DC Rated


Weight Current Standard
Actual Diameter Approx Resistance Ultimated
Nominal Rating Length
Aluminum Steel At 20C Strength
Al / St Aluminum Steel Approx
mm mm mm pcs / mm pcs / mm mm kg/km /km A kg m
16 / 2.5 15.27 2.54 6 / 1.80 1 / 1.80 5.40 62 1.87900 100 606 10,000
25 / 4 23.86 3.98 6 / 2.25 1 / 2.25 6.80 97 1.20300 135 938 10,000
35 / 6 34.35 5.73 6 / 2.70 1 / 2.70 8.10 140 0.83530 165 1.290 10,000
44 / 32 43.98 31.67 14 / 2.00 7 / 2.40 11.20 372 0.65730 205 4.348 5,000
50 / 8 48.25 8.04 6 / 3.20 1 / 3.20 9.60 196 0.59460 205 1.743 10,000
50 / 30 51.17 29.85 12 / 2.33 7 / 2.33 11.70 378 0.56440 225 4.466 5,000
70 / 12 69.89 11.40 26 / 1.85 7 / 1.44 11.70 284 0.41300 260 2.732 5,000
95 / 15 94.39 15.33 26 / 2.15 7 / 1.67 13.60 383 0.30580 315 3.566 5,000
95 / 55 96.51 56.30 12 / 3.20 7 / 3.20 16.00 712 0.29920 335 8.091 3,000
105 / 75 105.67 75.55 14 / 3.10 19 / 2.25 17.50 908 0.27360 355 11.058 3,000
120 / 20 121.57 19.85 26 / 2.44 7 / 1.90 15.50 494 0.23740 370 4.655 3,000
120 / 70 122.15 71.25 12 / 3.60 7 / 3.60 18.00 915 0.23640 385 10.197 3,000
125 / 30 127.92 29.85 30 / 2.33 7 / 2.33 16.30 593 0.22590 385 5.873 3,000
150 / 25 148.86 24.25 26 / 2.70 7 / 2.10 17.10 604 0.19390 420 5.633 3,000
170 / 40 171.77 40.08 30 / 2.70 7 / 2.70 18.90 796 0.16820 465 7.826 3,000
185 / 30 183.78 29.85 26 / 3.00 7 / 2.33 19.00 745 0.15710 480 6.750 3,000
210 / 35 209.10 34.09 26 / 3.20 7 / 2.49 20.30 848 0.13800 520 7.637 3,000
210 / 50 212.06 49.48 30 / 3.00 7 / 3.00 21.00 982 0.13630 530 9.575 3,000
230 / 30 230.91 29.85 24 / 3.50 7 / 2.33 21.00 873 0.12490 555 7.454 3,000

09
ACSR Aluminum Conductor Steel Reinforced

Application : Used for overhead transmission lines.

Construction
Conductor : The center wire or wires of galvanized steel and the outer layer or layers of aluminum.

Packing : Drum

Specification : SPLN 41-7

Cross Section Area No. / Diameter of Wires Overall DC Rated


Weight Current Standard
Actual Diameter Resistance Ultimated
Nominal Approx Rating Length
Aluminum Steel Approx At 20C Strength
Al / St Aluminum Steel
mm mm mm pcs / mm pcs / mm mm kg/km /km A kg m
240 / 40 243.05 39.49 26 / 3.45 7 / 2.68 21.90 985 0.11830 575 8,640 2,000
265 / 35 263.66 34.09 24 / 3.74 7 / 2.49 22.40 998 0.10940 600 8,468 2,000
300 / 50 304.26 49.48 26 / 3.86 7 / 3.00 24.50 1,233 0.09497 755 10,910 2,000
305 / 40 304.62 39.49 54 / 2.68 7 / 2.68 24.10 1,155 0.09490 750 10,135 2,000
340 / 30 339.29 29.85 48 / 3.00 7 / 2.33 25.00 1,174 0.08525 800 9,473 2,000
380 / 50 381.70 49.48 54 / 3.00 7 / 3.00 27.00 1,448 0.07573 865 12,552 2,000
385 / 35 386.04 34.09 48 / 3.20 7 / 2.49 26.70 1,344 0.07493 870 10,686 2,000
435 / 55 434.29 56.30 54 / 3.20 7 / 3.20 28.80 1,647 0.06656 940 13,914 1,500
450 / 40 448.71 39.49 48 / 3.45 7 / 2.68 28.70 1,553 0.06446 955 12,313 1,500
490 / 65 490.28 63.55 54 / 3.40 7 / 3.40 30.60 1,856 0.05896 1,015 15,611 1,500
495 / 35 494.36 34.09 45 / 3.74 7 / 2.49 29.90 1,636 0.05846 1,015 12,420 1,500
510 / 45 510.54 45.28 48 / 3.68 7 / 2.87 30.70 1,761 0.05655 1,035 13,682 1,500
550 / 70 549.65 71.25 54 / 3.60 7 / 3.60 32.40 2,085 0.05259 1,090 17,396 1,000
560 / 50 561.70 49.48 48 / 3.86 7 / 3.00 32.20 1,943 0.05149 1,100 15,188 1,500
570 / 40 571.16 39.49 45 / 4.02 7 / 2.68 32.20 1,888 0.05060 1,110 13,897 1,500
650 / 45 653.49 45.28 45 / 4.30 7 / 2.87 34.40 2,163 0.04426 1,205 15,856 1,000
680 / 85 678.58 85.95 54 / 4.00 19 / 2.40 36.00 2,566 0.04260 1,245 21,044 1,000
1,045/ 45 1,045.58 45.38 72 / 4.30 7 / 2.87 43.00 3,220 0.02770 1,600 22,201 500

10
ACSR Aluminum Conductor Steel Reinforced

Application : Used for overhead transmission lines.

Construction
Conductor : The center wire or wires of galvanized steel and the outer layer or layers of aluminum.

Packing : Drum

Specification : ASTM B232-69

Aluminum Cross No. / Diameter Overall DC Rated


Weight Current Standard
Section Area of Wires Diameter Resistance Ultimated
Code Approx. Rating Length
Aluminum Steel Approx. At 20C Strength
Name AWG or
MCM mm2 pcs/mm pcs/mm mm kg/km /km A kg m
Grouse 80.000 40.54 8 / 2.54 1 / 4.24 9.32 222 0.71120 185 2,333 5,000
Petrel 101.800 51.56 12/ 2.34 7 / 2.34 11.70 378 0.56190 225 4,702 5,000
Minorca 110.800 56.16 12/ 2.44 7 / 2.44 12.21 412 0.51590 235 5,121 5,000
Leghorn 134.600 68.20 12/ 2.69 7 / 2.69 13.45 500 0.42480 265 6,185 5,000
Guinea 159.000 80.58 12/ 2.92 7 / 2.92 14.62 591 0.35950 295 7,268 5,000
Dotterel 176.900 89.64 12/ 3.08 7 / 3.08 15.42 657 0.32320 315 7,837 3,000
Dorking 190.800 96.69 12/ 3.20 7 / 3.20 16.02 709 0.29960 335 8,453 3,000
Brahma 203.200 103.00 16/ 2.86 19 / 2.48 18.14 1,006 0.28130 355 12,920 2,000
Cochin 211.300 107.10 12/ 3.37 7 / 3.37 16.86 785 0.27050 355 9,363 3,000
Turkey 6 13.28 6 / 1.68 1 / 1.68 5.04 54 2.16030 90 537 10,000
Swan 4 21.14 6 / 2.12 1 / 2.12 6.36 85 1.35710 125 845 10,000
Swanate 4 21.14 7 / 1.96 1 / 2.61 6.53 100 1.35710 125 1,077 10,000
Sparrow 2 33.64 6 / 2.67 1 / 2.67 8.01 137 0.85280 165 1,296 10,000
Sparate 2 33.65 7 / 2.47 1 / 3.30 8.24 159 0.85260 165 1,647 10,000
Robin 1 42.40 6 / 3.00 1 / 3.00 9.00 172 0.67650 190 1,612 10,000
Raven 1/0 53.55 6 / 3.37 1 / 3.37 10.11 217 0.53570 220 1,974 5,000
Quail 2/0 67.40 6 / 3.78 1 / 3.78 11.34 273 0.42570 255 2,375 5,000
Pigeon 3/0 85.00 6 / 4.25 1 / 4.25 12.75 344 0.33750 295 2,995 5,000
Penguin 4/0 107.20 6 / 4.77 1 / 4.77 14.31 434 0.26760 340 3,778 5,000
Waxwing 266.800 135.10 18/ 3.09 1 / 3.09 15.45 432 0.21340 390 3,088 5,000
Partridge 266.800 135.20 26/ 2.57 7 / 2.00 16.28 548 0.21430 395 5,133 5,000
Ostrich 300.000 152.00 26/ 2.73 7 / 2.12 17.28 615 0.19060 425 5,765 3,000
Merlin 336.400 170.40 18/ 3.47 1 / 3.47 17.35 544 0.16920 450 3,896 5,000
Linnet 336.400 170.30 26/ 2.89 7 / 2.25 18.31 689 0.16920 455 6,378 3,000
Oriole 336.400 170.50 30/ 2.69 7 / 2.69 18.83 785 0.17010 460 7,893 3,000

11
ACSR Aluminum Conductor Steel Reinforced

Application : Used for overhead transmission lines.

Construction
Conductor : The center wire or wires of galvanized steel and the outer layer or layers of aluminum.

Packing : Drum

Specification : ASTM B232-69

Aluminum Cross No. / Diameter Overall DC Rated


Weight Current Standard
Section Area of Wires Diameter Resistance Ultimated
Code Approx. Rating Length
Aluminum Steel Approx. At 20C Strength
Name AWG or
MCM mm2 pcs/mm pcs/mm mm kg/km /km A kg m
Chikadee 397.500 201.40 18/ 3.77 1 / 3.77 18.87 643 0.14310 500 4,432 5,000
Brant 397.500 201.40 24/ 3.27 7 / 2.18 19.61 763 0.14390 505 6,592 3,000
Ibis 397.500 201.20 26/ 3.14 7 / 2.44 19.88 814 0.14400 510 7,347 3,000
Lark 397.500 201.40 30/ 2.92 7 / 2.92 20.47 927 0.14420 510 9,229 3,000
Pelican 477.000 241.70 18/ 4.14 1 / 4.14 20.68 772 0.11930 565 5,319 3,000
Flicker 477.000 241.70 24/ 3.58 7 / 2.39 21.50 916 0.11990 570 7,823 3,000
Hawk 477.000 241.50 26/ 3.44 7 / 2.68 21.78 977 0.12000 570 8,820 2,000
Hen 477.000 241.70 30/ 3.20 7 / 3.20 22.42 1,113 0.12010 575 10,740 2,000
Osprey 556.500 281.80 18/ 4.47 1 / 4.47 22.33 900 0.10230 620 6,202 3,000
Parakeet 556.500 282.00 24/ 3.87 7 / 2.58 23.21 1,068 0.10270 625 8,989 2,000
Dove 556.500 282.00 26/ 3.72 7 / 2.89 23.54 1,141 0.10270 630 10,301 2,000
Eagle 556.500 281.90 30 / 3.46 7 / 3.46 24.21 1,298 0.10300 630 12,526 2,000
Peacock 605.000 306.70 24/ 4.03 7 / 2.69 24.21 1,162 0.09446 660 9,781 2,000
Squab 605.000 306.50 26 / 3.87 7 / 3.01 24.54 1,240 0.09452 660 11,043 2,000
Wood Duck 605.000 306.60 30/ 3.61 7 / 3.61 25.25 1,411 0.09472 665 13,132 2,000
Teal 605.000 306.60 30/ 3.61 19 / 2.16 25.25 1,400 0.09472 665 13,620 2,000
Kingbird 636.000 322.30 18/ 4.78 1 / 4.78 23.88 1,029 0.08945 675 7,093 2,000
Rook 636.000 322.30 24/ 4.14 7 / 2.76 24.82 1,220 0.08989 680 10,273 2,000
Grosbeak 636.000 322.30 26/ 3.97 7 / 3.09 25.15 1,304 0.08989 685 11,408 2,000
Scoter 636.000 322.20 30/ 3.70 7 / 3.70 25.90 1,483 0.09014 690 13,801 2,000

12
ACSR Aluminum Conductor Steel Reinforced

Application : Used for overhead transmission lines.

Construction
Conductor : The center wire or wires of galvanized steel and the outer layer or layers of aluminum.

Packing : Drum

Specification : ASTM B232-69

Aluminum No./Diameter of Overall DC


Weight Rated
Cross Section Area Wires Current Standard
Diameter Resistance Ultimated
Code Approx. Rating Length
Aluminum Steel Approx. At 20C Strength
Name AWG or
MCM mm2 pcs/mm pcs/mm mm kg/km /km A kg m
Egret 636.000 322.20 30 / 3.70 19 / 2.22 25.90 1,472 0.09014 690 14,326 2,000
Swift 636.000 322.30 36 / 3.38 1 / 3.38 23.63 959 0.08945 675 6,169 2,000
Flamingo 666.600 337.90 24 / 4.23 7 / 2.82 25.40 1,279 0.08574 700 10,770 2,000
Gannet 666.600 337.80 26 / 4.07 7 / 3.16 25.76 1,366 0.08577 705 11,955 2,000
Stilt 715.500 362.80 24 / 4.39 7 / 2.92 26.32 1,374 0.07986 735 11,563 2,000
Starling 715.500 362.60 26 / 4.21 7 / 3.28 26.70 1,467 0.07990 735 12,837 2,000
Redwing 715.500 362.40 30 / 3.92 19 / 2.35 27.45 1,654 0.08014 740 15,686 1,500
Tern 795.000 402.80 45 / 3.38 7 / 2.25 27.01 1,335 0.07193 775 9,920 2,000
Coot 795.000 402.70 36 / 3.77 1 / 3.77 26.42 1,199 0.07159 775 7,445 2,000
Condor 795.000 402.60 54 / 3.08 7 / 3.08 27.73 1,524 0.07196 780 12,682 1,500
Cuckoo 795.000 402.90 24 / 4.62 7 / 3.08 27.74 1,525 0.07191 785 12,636 1,500
Drake 795.000 402.90 26 / 4.44 7 / 3.45 28.13 1,630 0.07191 785 14,262 1,500
Mallard 795.000 402.90 30 / 4.14 19 / 2.48 28.95 1,840 0.07208 790 17,458 1,500
Ruddy 900.000 456.00 45 / 3.59 7 / 2.40 28.74 1,511 0.06353 840 11,142 1,500
Canary 900.000 456.00 54 / 3.28 7 / 3.28 29.52 1,727 0.06353 845 14,364 1,500
Catbird 954.000 483.40 36 / 4.14 1 / 4.14 28.95 1,439 0.05964 865 8,937 2,000
Rail 954.000 483.30 45 / 3.70 7 / 2.47 29.60 1,602 0.05995 870 11,809 1,500
Cardinal 954.000 483.40 54 / 3.38 7 / 3.38 30.38 1,830 0.05993 875 15,227 1,500
Tanager 1,033.50 523.50 36 / 4.30 1 / 4.30 30.12 1,558 0.05507 910 9,678 1,500
Ortolan 1,033.50 523.30 45 / 3.85 7 / 2.57 30.78 1,734 0.05536 915 12,541 1,500

13
ACSR Aluminum Conductor Steel Reinforced

Application : Used for overhead transmission lines.

Construction
Conductor : The center wire or wires of galvanized steel and the outer layer or layers of aluminum.

Packing : Drum

Specification : ASTM B232-69

Aluminum No./Diameter of Overall DC Rated


Cross Section Area Wires Weight Current Standard
Diameter Resistance Ultimated
Code Approx. Rating Length
Aluminum Steel Approx. At 20C Strength
Name AWG or
MCM mm2 pcs/mm pcs/mm mm kg/km /km A kg m
Curlew 1,033.500 523.40 54/ 3.51 7 / 3.51 31.62 1,982 0.05535 920 16,488 1,500
Bluejay 1,33.000 564.10 45/ 4.00 7 / 2.66 31.96 1,869 0.05136 960 13,522 1,500
Finch 1,133.000 564.10 54/ 3.65 19 / 2.19 32.83 2,132 0.05161 960 17,776 1,500
Bunting 1,92.500 604.30 45/ 4.14 7 / 2.76 33.08 2,005 0.04793 1,000 14,175 1,000
Grackle 1,192.500 604.10 54/ 3.77 19 / 2.27 34.97 2,282 0.04800 1,005 18,000 1,000
Skylark 1,272.000 644.70 36/ 4.78 1 / 4.78 33.43 1,920 0.04472 1,035 11,621 1,500
Bittern 1,272.000 644.10 45/ 4.27 7 / 2.85 34.17 2,140 0.04500 1,040 15,118 1,000
Pheasant 1,272.000 644.40 54/ 3.90 19 / 2.34 35.08 2,433 0.04500 1,045 19,198 1,000
Dipper 1,351.500 684.50 45/ 4.40 7 / 2.93 35.21 2,275 0.04230 1,080 16,059 1,000
Martin 1,351.500 684.70 54/ 4.02 19 / 2.41 36.17 2,585 0.04230 1,085 20,389 1,000
Bobolink 1,431.000 724.60 45/ 4.53 7 / 3.02 36.25 2,410 0.04000 1,115 17,009 1,000
Plover 1,431.000 725.20 54/ 4.14 19 / 2.48 37.22 2,738 0.03990 1,125 21,602 1,000
Nuthatch 1,510.500 765.20 45/ 4.65 7 / 3.10 37.22 2,540 0.03790 1,155 17,952 1,000
Parrot 1,510.500 764.60 54/ 4.25 19 / 2.55 38.21 2,890 0.03790 1,160 22,772 1,000
Lapwing 1,590.000 805.80 45/ 4.78 7 / 3.18 38.20 2,678 0.03600 1,190 18,904 1,000
Falcon 1,590.000 805.50 54/ 4.36 19 / 2.62 39.23 3,042 0.03600 1,200 24,005 500
Chukar 1,780.000 902.20 84/ 3.70 19 / 2.22 40.68 3,095 003230 1,270 22,473 500
Bluebird 2,156.000 1,092.30 84/ 4.07 19 / 2.44 44.75 3,747 0.02670 1,420 26,692 500
Kiwi 2,167.000 1,097.80 72 / 4.41 7 / 2.94 44.06 3,419 0.02640 1,420 22,220 500
Thrasher 2,312.000 1,170.90 76/ 4.43 19 / 2.07 45.77 3,767 0.02490 1,475 25,015 500

14
T-ACSR Thermal Resistance-Aluminum Conduc
Conductor
Steel Reinforced
Application : Used for overhead transmission lines.

Construction
Conductor : The center wire or wires of galvanized steel and the outer layer or layers of thermal resistance alloy
aluminum.

Packing : Drum

Specification : JEC 197

Cross Section Area No. / Diameter of Wires Overall DC Rated


Weight Current Standard
Diameter Resistance Ultimated
Nominal Actual Approx
TAL Steel Approx Rating Length
At 20C Strength
TAL TAL Steel
mm mm mm pcs / mm pcs / mm mm kg/km /km A kg m
58 57.73 9.62 6 / 3.50 1 / 3.50 10.50 234 0.5050 375 1,980 5,000
80 83.13 13.85 6 / 4.20 1 / 4.20 12.60 336 0.3500 480 2,770 5,000
80 79.64 21.24 15/ 2.60 4 / 2.60 13.00 386 0.3680 470 3,810 5,000
95 95.43 15.90 6 / 4.50 1 / 4.50 13.50 386 0.3050 525 3,180 5,000
100 99.08 26.42 15/ 2.90 4 / 2.90 14.50 480 0.2960 545 4,740 5,000
120 120.64 32.17 15/ 3.20 4 / 3.20 16.00 585 0.2430 620 5,550 5,000
120 124.64 29.08 30 / 2.30 7 / 2.30 16.10 574 0.2370 630 5,460 5,000
160 159.28 37.17 30 / 2.60 7 / 2.60 18.20 734 0.1850 745 6,980 3,000
200 198.16 46.24 30 / 2.90 7 / 2.90 20.30 912 0.1490 860 8,680 3,000
240 241.27 56.30 30 / 3.20 7 / 3.20 22.40 1,111 0.1220 980 10,170 2,000
330 326.73 52.83 26 / 4.00 7 / 3.10 25.30 1,320 0.0901 1,190 10,940 2,000
410 413.51 67.35 26 / 4.50 7 / 3.50 28.50 1,674 0.0712 1,390 13,900 1,500
520 519.54 67.35 54 / 3.50 7 / 3.50 31.50 1,969 0.0567 1,610 15,590 1,500
610 612.42 79.39 54 / 3.80 7 / 3.80 34.20 2,321 0.0481 1,795 18,380 1,000
680 678.58 87.96 54 / 4.00 7 / 4.00 36.00 2,572 0.0434 1,920 19,790 1,000
680 684.24 46.24 45 / 4.40 7 / 2.90 35.10 2,260 0.0431 1,910 15,590 1,000
810 814.30 56.30 45 / 4.80 7 / 3.20 38.40 2,700 0.0362 2,145 18,460 1,000
1.160 1,163.77 96.98 84 / 4.20 7 / 4.20 46.20 3,997 0.0254 2,700 27,870 500
1.520 1,520.03 126.67 84 / 4.80 7 / 4.80 52.80 5,221 0.0195 3,185 36,410 500

15
ACSR /AS Aluminum Conductor - Aluminum
Clad Steel Reinforced
Application : Used for overhead transmission lines.

Construction
Conductor : The center wire or wires of aluminum clad steel and the outer layer or layers of aluminum.

Packing : Drum

Specification : DIN 48204

Cross Section Area No. / Diameter of Wires Overall DC Rated


Weight Current Standard
Diameter Resistance Ultimated
Nominal Actual Approx Rating
Aluminum Steel Strength Length
Approx At 20C
Al / St Aluminum Steel
mm mm mm pcs / mm pcs / mm mm kg/km /km A kg m
16 / 2.5 15.27 2.54 6 / 1.80 1 / 1.80 5.40 59 1.7790 105 607 10,000
25 / 4 23.86 3.98 6 / 2.25 1 / 2.25 6.75 93 1.1390 135 938 10,000
35 / 6 34.35 5.73 6 / 2.70 1 / 2.70 8.10 133 0.7906 170 1,321 10,000
44 / 32 43.98 31.67 14 / 2.00 7 / 2.40 11.20 333 0.5282 230 4,797 5,000
50 / 8 48.25 8.04 6 / 3.20 1 / 3.20 9.60 187 0.5629 210 1,825 10,000
50 / 30 51.17 29.85 12 / 2.33 7 / 2.33 11.65 341 0.4712 245 4,664 5,000
70 / 12 69.89 11.40 26 / 1.85 7 / 1.44 11.72 270 0.3915 270 2,743 5,000
95 / 15 103.38 15.33 26 / 2.25 7 / 1.67 14.01 362 0.2899 325 3,660 5,000
95 / 55 96.51 56.30 12 / 3.20 7 / 3.20 16.00 640 0.2498 365 8,686 3,000
105 / 75 105.67 75.55 14 / 3.10 19 / 2.25 17.75 797 0.2203 400 11,254 3,000
120 / 20 121.57 19.85 26 / 2.44 7 / 1.90 15.46 470 0.2250 380 4,674 5,000
120 / 70 122.15 71.25 12 / 3.60 7 / 3.60 18.00 810 0.1974 425 10,148 3,000
125 / 30 127.92 29.85 30 / 2.33 7 / 2.33 16.31 554 0.2093 400 6,045 5,000
150 / 25 148.86 24.25 26 / 2.70 7 / 2.10 17.10 575 0.1838 430 5,658 5,000
170 / 40 171.77 40.08 30 / 2.70 7 / 2.70 18.90 744 0.1559 480 8,048 3,000
185 / 30 183.78 29.85 26 / 3.00 7 / 2.33 18.99 709 0.1489 495 6,902 3,000
210 / 35 209.10 34.09 26 / 3.20 7 / 2.49 20.27 805 0.1308 535 7,804 3,000
210 / 50 212.06 49.48 30 / 3.00 7 / 3.00 21.00 918 0.1263 550 9,853 3,000
230 / 30 230.91 29.85 24 / 3.50 7 / 2.33 20.99 835 0.1197 565 7,600 3,000

16
ACSR /AS Aluminum Conductor - Aluminum
Clad Steel Reinforced
Application : Used for overhead transmission lines.

Construction
Conductor : The center wire or wires of aluminum clad steel and the outer layer or layers of aluminum.
Packing : Drum

Specification : DIN 48204

No./ Diameter
Cross Section Area of Wires Overall DC Rated
Weight
Diameter Resistance Current Ultimated Standard
Nominal Actual Approx.
Aluminum Steel Approx. At 20C Rating Strength Length
A1/St Aluminum Steel
mm2 mm2 mm2 pcs/mm pcs/mm mm kg/km /km A kg m
240 / 40 243,05 39,49 26 / 3,45 7 / 2,68 21,84 938 0,1126 590 9.012 3.000
265 / 35 263,66 34,09 24 / 3,74 7 / 2,49 22,43 958 0,1048 615 8.624 3.000
300 / 50 304,26 49,48 26 / 3,86 7 / 3,00 24,40 1.170 0,0899 680 11.163 2.000
305 / 40 304,62 39,49 54 / 2,68 7 / 2,68 24,12 1.108 0,0909 670 10.311 2.000
340 / 30 339,29 29,85 48 / 3,00 7 / 2,33 24,99 1.140 0,0827 710 9.577 2.000
380 / 50 381,70 49,48 54 / 3,00 7 / 3,00 27,00 1.388 0,0725 725 12.768 2.000
385 / 35 386,04 34,09 48 / 3,20 7 / 2,49 26,67 1.298 0,0727 770 10.796 2.000
435 / 55 434,29 56,30 54 / 3,20 7 / 3,20 28,80 1.578 0,0638 840 14.394 1.500
450 / 40 448,71 39,49 48 / 3,45 7 / 2,68 28,74 1.508 0,0625 845 12.442 1.500
490 / 65 490,28 63,55 54 / 3,40 7 / 3,40 30,60 1.780 0,0565 905 15.704 1.500
495 / 35 494,36 34,09 45 / 3,74 7 / 2,49 29,91 1.598 0,0571 898 12.427 1.500
510 / 45 510,54 45,28 48 / 3,68 7 / 2,87 30,69 1.710 0,0549 915 14.098 1.500
550 / 70 549,65 71,25 54 / 3,60 7 / 3,60 32,40 1.995 0,0504 970 17.202 1.500
560 / 50 561,70 49,48 48 / 3,86 7 / 3,00 32,16 1.880 0,0500 970 15.352 1.500
570 / 40 571,16 39,49 45 / 4,02 7 / 2,68 32,16 1.823 0,0494 975 14.256 1.500
650 / 45 653,49 45,28 45 / 4,30 7 / 2,87 34,41 2.110 0,0432 1.060 16.265 1.000
680 / 85 678,58 85,95 54 / 4,00 19 / 2,40 36,00 2.454 0,0409 1.100 21.830 1.000
1.045 / 45 1.045,58 45,28 72 / 4,30 7 / 2,87 43,01 3.207 0,0274 1.390 22.615 500

17
ACSR /AS Aluminum Conductor - Aluminum
Clad Steel Reinforced
Application : Used for overhead transmission lines.

Construction
Conductor : The center wire or wires of aluminum clad steel and the outer layer or layers of aluminum.
Packing : Drum

Specification : ASTM B 549

Aluminum No./Diameter of Overall DC Rated


Cross Section Area Wires Weight Current Standard
Diameter Resistance Ultimated
Code Approx. Rating Length
AWG or Aluminum Approx. At 20C Strength
Name Steel
MCM mm2 pcs/mm pcs/mm mm kg/km /km A kg m
Grouse 80,000 40,54 8 / 2,54 1 / 4,24 9,32 205 0,63580 200 2.191 5.000
Petrel 101,800 51,60 12/ 2,34 7 / 2,34 11,70 343 0,46850 245 4.456 5.000
Minorca 110,800 56,20 12/ 2,44 7 / 2,44 12,21 373 0,43010 260 4.852 5.000
Leghorn 134,600 68,20 12/ 2,69 7 / 2,69 13,45 453 0,35440 290 5.859 5.000
Guinea 159,000 80,60 12/ 2,92 7 / 2,92 14,62 535 0,29990 325 6.885 5.000
Dotterel 176,900 89,60 12/ 3,08 7 / 3,08 15,42 595 0,26980 345 7.616 5.000
Dorking 190,800 96,70 12/ 3,20 7 / 3,20 16,02 642 0,25000 365 8.215 3.000
Brahma 203,200 103,00 16/ 2,86 19 / 2,48 18,14 896 0,21590 405 12.275 3.000
Cochin 211,300 107,10 12/ 3,37 7 / 3,37 16,86 711 0,22570 390 8.891 3.000
Turkey 6 13,29 6 / 1,68 1 / 1,68 5,04 52 2,04280 95 515 10.000
Swan 4 21,10 6 / 2,12 1 / 2,12 6,35 82 1,28740 125 808 10.000
Swanate 4 21,10 7 / 1,96 1 / 2,61 6,54 94 1,25130 130 1.037 10.000
Sparrow 2 33,61 6 / 2,67 1 / 2,67 8,02 130 0,80830 170 1.255 10.000
Sparate 2 33,70 7 / 2,47 1 / 3,30 8,25 149 0,78440 175 1.591 10.000
Robbin 1 42,39 6 / 3,00 1 / 3,00 9,00 164 0,64030 195 1.561 10.000
Raven 1/0 53,50 6 / 3,37 1 / 3,37 10,11 206 0,50770 225 1.914 10.000
Quail 2/0 67,40 6 / 3,78 1 / 3,78 11,35 260 0,40300 260 2.301 10.000
Pigeon 3/0 85,00 6 / 4,25 1 / 4,25 12,74 327 0,31950 305 2.854 5.000
Penguin 4/0 107,20 6 / 4,77 1 / 4,77 14,31 413 0,25330 350 3.480 5.000
Waxwing 266,800 135,10 18/ 3,09 1 / 3,09 15,45 423 0,20940 395 3.063 5.000
Partridge 266,800 135,20 26/ 2,57 7 / 2,00 16,30 521 0,20300 405 4.909 5.000
Ostrich 300,000 152,00 26/ 2,73 7 / 2,12 17,28 614 0,18060 435 5.513 5.000
Merlin 336,400 170,40 18/ 3,47 1 / 3,47 17,35 533 0,16600 455 3.833 5.000
Linnet 336,400 170,30 26/ 2,89 7 / 2,25 18,29 689 0,16120 470 6.096 3.000
Oriole 336,400 170,50 30/ 2,69 7 / 2,69 18,83 738 0,15780 480 7.605 3.000

18
ACSR /AS Aluminum Conductor - Aluminum
Clad Steel Reinforced
Application : Used for overhead transmission lines.

Construction
Conductor : The center wire or wires of aluminum clad steel and the outer layer or layers of aluminum.
Packing : Drum

Specification : ASTM B549

Aluminum Cross No. / Diameter Overall DC Rated


Weight Current Standard
Section Area of Wires Diameter Resistance Ultimated
Code Approx. Rating Length
AWG or Aluminum Steel Approx. At 20C Strength
Name
MCM mm2 pcs/mm pcs/mm mm kg/km /km A kg m
Chikadee 397,500 201,40 18/ 3,77 1 / 3,77 18,87 630 0,14050 505 4.359 3.000
Brant 397,500 201,40 24/ 3,27 7 / 2,18 19,61 732 0,13780 515 6.327 3.000
Ibis 397,500 201,20 26/ 3,14 7 / 2,44 19,88 775 0,13640 520 7.109 3.000
Lark 397,500 201,40 30/ 2,92 7 / 2,92 20,47 871 0,13360 530 8.889 3.000
Pelican 477,000 241,70 18/ 4,14 1 / 4,14 20,70 756 0,11710 570 5.185 3.000
Flicker 477,000 241,70 24/ 3,58 7 / 2,39 21,49 878 0,11480 580 7.596 3.000
Hawk 477,000 241,50 26/ 3,44 7 / 2,68 21,78 930 0,11370 585 8.535 3.000
Hen 477,000 241,70 30/ 3,20 7 / 3,20 22,42 1.045 0,11130 595 10.552 2.000
Osprey 556,500 281,80 18/ 4,47 1 / 4,47 22,33 881 0,10040 625 5.993 3.000
Parakeet 556,500 282,00 24/ 3,87 7 / 2,58 23,21 1.024 0,09840 640 8.724 2.000
Dove 556,500 282,00 26/ 3,72 7 / 2,89 23,54 1.086 0,09730 645 9.968 2.000
Eagle 556,500 281,90 30/ 3,46 7 / 3,46 24,21 1.219 0,09540 655 12.088 2.000
Peacock 605,000 306,70 24/ 4,03 7 / 2,69 24,21 1.114 0,09050 675 9.493 2.000
Squab 605,000 306,30 26/ 3,87 7 / 3,01 24,53 1.180 0,08960 680 10.678 2.000
Wood Duck 605,000 306,60 30/ 3,61 7 / 3,61 25,25 1.326 0,08770 690 12.901 2.000
Teal 605,000 306,60 30/ 3,61 19 / 2,16 25,25 1.316 0,08790 690 12.931 2.000
Kingbird 636,000 322,30 18/ 4,78 1 / 4,78 23,88 1.008 0,08780 680 6.795 2.000
Rook 636,000 322,30 24/ 4,14 7 / 2,76 24,81 1.170 0,08610 695 9.970 2.000
Grosbeak 636,000 322,30 26/ 3,97 7 / 3,09 25,16 1.241 0,08520 700 11.233 2.000
Scoter 636,000 322,20 30/ 3,70 7 / 3,70 25,89 1.393 0,08350 715 13.308 2.000

19
ACSR /AS Aluminum Conductor - Aluminum
Clad Steel Reinforced
Application : Used for overhead transmission lines.
Construction
Conductor : The center wire or wires of aluminum clad steel and the outer layer or layers of aluminum

Packing : Drum

Specification : ASTM B549

Aluminum Cross No. / Diameter Overall DC Rated


Weight Current Standard
Section Area of Wires Diameter Resistance Ultimated
Code Approx. Rating Length
AWG or Aluminum Steel Approx. At 20C Strength
Name
MCM mm2 pcs/mm pcs/mm mm kg/km /km A kg m
Egret 636,000 322,20 30/ 3,70 19 / 2,22 25,89 1.384 0,08360 715 13.601 2.000
Swift 636,000 322,30 36/ 3,38 1 / 3,38 23,63 949 0,08860 675 6.221 3.000
Flamingo 666,600 337,90 24/ 4,23 7 / 2,82 25,40 1.227 0,08210 715 10.453 2.000
Gannet 666,600 337,80 26/ 4,07 7 / 3,16 25,75 1.301 0,08130 725 11.772 2.000
Stilt 715,500 362,80 24/ 4,39 7 / 2,92 26,32 1.317 0,07650 750 11.222 2.000
Starling 715,500 362,60 26/ 4,21 7 / 3,28 26,69 1.396 0,07570 755 12.444 2.000
Redwing 715,500 362,40 30/ 3,92 19 / 2,35 27,45 1.555 0,07437 770 15.107 1.500
Cuckoo 795,000 402,90 24/ 4,62 7 / 3,08 27,74 1.463 0,06887 800 12.462 2.000
Drake 795,000 402,90 26/ 4,44 7 / 3,45 28,13 1.552 0,06813 805 13.825 1.500
Coot 795,000 402,70 36/ 3,77 1 / 3,77 26,42 1.185 0,07092 780 7.372 2.000
Tern 795,000 402,80 45/ 3,38 7 / 2,25 27,01 1.301 0,07027 785 9.637 2.000
Condor 795,000 402,60 54/ 3,08 7 / 3,08 27,73 1.462 0,06892 800 12.509 2.000
Mallard 795,000 402,90 30/ 4,14 19 / 2,48 28,95 1.730 0,06689 820 16.813 1.500
Ruddy 900,000 456,00 45/ 3,59 7 / 2,40 28,74 1.473 0,06207 850 10.914 1.500
Canary 900,000 456,00 54/ 3,28 7 / 3,28 29,51 1.656 0,06085 865 13.971 1.500
Catbird 954,000 483,40 36/ 4,14 1 / 4,14 28,95 1.423 0,05908 870 8.803 2.000
Rail 954,000 483,30 45/ 3,70 7 / 2,47 29,59 1.562 0,05857 880 11.567 1.500
Cardinal 954,000 483,40 54/ 3,38 7 / 3,38 30,38 1.755 0,05740 895 14.810 1.500
Tanager 1.033,500 523,50 36/ 4,30 1 / 4,30 30,12 1.541 0,05456 915 9.533 1.500
Ortolan 1.033,500 523,30 45/ 3,85 7 / 2,57 30,78 1.691 0,05409 925 12.279 1.500

20
ACSR /AS Aluminum Conductor - Aluminum
Clad Steel Reinforced
Application : Used for overhead transmission lines.

Construction
Conductor : The center wire or wires of aluminum clad steel and the outer layer or layers of aluminum.

Packing : Drum

Specification : ASTM B 549

Aluminum Cross No. / Diameter Overall DC Rated


Weight Current Standard
Section Area of Wires Diameter Resistance Ultimated
Code Approx. Rating Length
AWG or Aluminum Steel Approx. At 20C Strength
Name
MCM mm2 pcs/mm pcs/mm mm kg/km /km A kg m
Curlew 1,033.500 523.40 54/ 3.51 7 / 3.51 31.62 1,901 0.05301 940 15,804 1,500
Bluejay 1,113.000 564.10 45/ 4.00 7 / 2.66 31.96 1,823 0.05018 970 13,240 1,500
Finch 1,113.000 564.10 54/ 3.65 19 / 2.19 32.83 2,046 0.04947 980 17,071 1,000
Bunting 1,192.500 604.30 45/ 4.14 7 / 2.76 33.08 1,952 0.04684 1,010 14,175 1,000
Grackle 1,192.500 604.10 54/ 3.77 19 / 2.27 33.97 2,183 0.04598 1,025 18,000 1,000
Skylark 1,272.000 644.70 36/ 4.78 1 / 4.78 33.43 1,897 0.04430 1,040 11,621 1,500
Bittern 1,272.000 644.10 45/ 4.27 7 / 2.85 34.16 2,081 0.04395 1,050 15,118 1,000
Pheasant 1,272.000 644.40 54/ 3.90 19 / 2.34 35.08 2,328 0.04310 1,070 19,198 1,000
Dipper 1,351.500 684.50 45/ 4.40 7 / 2.93 35.21 2,211 0.04135 1,090 16,059 1,000
Martin 1,351.500 684.70 54/ 4.02 19 / 2.41 36.16 2,473 0.04057 1,110 20,389 1,000
Bobolink 1,431.000 724.60 45/ 4.53 7 / 3.02 36.23 2,341 0.03906 1,130 17,009 1,000
Plover 1,431.000 725.20 54/ 4.14 19 / 2.48 37.22 2,620 0.03830 1,145 21,602 1,000
Nuthatch 1,510.500 765.20 45/ 4.65 7 / 3.10 37.22 2,472 0.03699 1,165 17,952 1,000
Parrot 1,510.500 764.60 54/ 4.25 19 / 2.55 38.21 2,762 0.03633 1,185 22,772 1,000
Lapwing 1,590.000 805.80 45/ 4.78 7 / 3.18 38.20 2,603 0.03513 1,205 18,904 1,000
Falcon 1,590.000 805.50 54/ 4.36 19 / 2.62 39.23 2,911 0.03448 1,220 24,005 500
Chuckar 1,780.000 902.20 84/ 3.70 19 / 2.22 40.68 3,001 0.03140 1,290 22,473 500
Bluebird 2,156.000 1,092.30 84/ 4.07 19 / 2.44 44.75 3,633 0.02593 1,440 26,692 500
Kiwi 2,167.000 1,097.80 72/ 4.41 7 / 2.94 44.06 3,358 0.02601 1,430 22,220 500
Thrasher 2,312.000 1,170.90 76/ 4.43 19 / 2.07 45.77 3,686 0.02441 1,485 25,015 500

21
T-ACSR/AS Thermal Resistance - Aluminum
Conductor Clad Steel Reinforced
Application : Used for overhead transmission lines.

Construction
Conductor : The center wire or wires of aluminum clad steel and the outer layer or layers of thermal resistance
aluminum alloy..

Packing : Drum

Specification : JEC 197

Cross Section Area No./ Diameter DC


of Wires Overall Rated
Weight Current Standard
Actual Diameter Resistance Ultimated
Nominal Approx. Rating Length
TAL Steel Approx. At 20C Strength
TAL TAL Steel
mm2 mm2 mm2 pcs/mm pcs/mm mm kg/km /km A kg m
58 57.73 9.62 6 / 3.50 1 / 3.50 10.50 219 0.4736 390 1,980 5,000
80 83.13 13.85 6 / 4.20 1 / 4.20 12.60 315 0.3289 495 2,830 5,000
80 79.64 21.24 15/ 2.60 4 / 2.60 13.00 359 0.3380 495 3,810 5,000
95 95.43 15.90 6 / 4.50 1 / 4.50 13.50 362 0.2870 540 3,180 5,000
100 99.08 26.42 15/ 2.90 4 / 2.90 14.50 447 0.2717 570 1,740 5,000
120 120.64 32.17 15/ 3.20 4 / 3.20 16.00 535 0.2196 655 5,550 5,000
120 124.64 29.08 30 / 2.30 7 / 2.30 16.10 537 0.2190 655 5,460 5,000
160 159.28 37.17 30 / 2.60 7 / 2.60 18.20 686 0.1718 770 6,980 3,000
200 198.16 46.24 30 / 2.90 7 / 2.90 20.30 853 0.1381 890 8,680 3,000
240 241.27 56.30 30 / 3.20 7 / 3.20 22.40 1,024 0.1118 1,025 10,170 2,000
330 326.73 52.83 26 / 4.00 7 / 3.10 25.30 1,239 0.0847 1,225 10,940 2,000
410 413.51 67.35 26 / 4.50 7 / 3.50 28.50 1,570 0.0669 1,435 13,900 1,500
520 519.54 67.35 54/ 3.50 7 / 3.50 31.50 1,866 0.0535 1,655 15,590 1,500
610 612.42 79.39 54/ 3.80 7 / 3.80 34.20 2,199 0.0458 1,840 18,380 1,000
680 678.58 87.96 54/ 4.00 7 / 4.00 36.00 2,436 0.0415 1,960 20,180 1,000
680 684.24 46.24 45/ 4.40 7 / 2.90 35.10 2,201 0.0421 1,930 15,590 1,000
810 814.30 56.30 45/ 4.80 7 / 3.20 38.40 2,613 0.0352 2,170 18,460 1,000
1,160 1,163.77 96.98 84/ 4.20 7 / 4.20 46.20 3,848 0.0246 2,740 28,310 500
1,520 1,520.03 126.67 84/ 4.80 7 / 4.80 52.80 5,026 0.0188 3,230 36,410 500

22
STACIR Super Thermal Resistance - Invar Reinforced

Application : Used for overhead transmission lines.

Construction
Conductor : The center wires of galvanized invar and the outer layers of super thermal resistance
aluminum alloy.

Packing : Drum

Specification : KEPCO

Cross Section Area No./ Diameter


of Wires Overall DC Rated
Weight Current Standard
Diameter Resistance Ultimated
Actual Approx. Rating Length
Nominal ST - AI Invar Approx. At 20C Strength
ST-AI Invar
mm2 mm2 mm2 pcs/mm pcs/mm mm kg/km /km A kg m
120 124.64 29.08 30/ 2.30 7/ 2.30 16.10 580 0.23700 746 4,890 5,000
160 159.28 37.17 30/ 2.60 7/ 2.60 18.20 740 0.18500 883 6,140 3,000
240 241.27 56.30 30/ 3.20 7/ 3.20 22.40 1,122 0.12200 1,172 9,170 3,000
330 326.73 52.83 26/ 4.00 7/ 3.10 25.30 1,330 0.09040 1,424 10,000 2,000
410 413.51 67.35 26/ 4.50 7/ 3.50 28.50 1,687 0.07140 1,674 12,720 2,000
480 483.84 33.54 45/ 3.70 7 /2.47 29.61 1,611 0.06070 1,800 10,500 1,500
610 612.42 79.39 54/ 3.80 7/ 3.80 34.20 2,336 0.04810 2,137 16,960 1,500
810 814.30 56.30 45/ 4.80 7/ 3.20 38.40 2,712 0.36300 2,559 17,440 1,500

23
STACIR/AW Super Thermal Resistance - Aluminum
Clad Invar Reinforced
Application : Used for overhead transmission lines.

Construction
Conductor : The center wires of aluminum clad invar and the outer layers of super thermal resistance
aluminum alloy.

Packing : Drum

Specification : KEPCO

Cross Section Area No./ Diameter


of Wires Overall DC Rated
Weight Current
Actual Diameter Resistance Ultimated Standard
AI - Vlad Approx. Rating
Nominal AI - Clad Aluminum Invar Approx. At 20C Strength Length
ST - AI Invar
mm2 mm2 mm2 pcs/mm pcs/mm mm kg/km /km A kg m
160 159.28 37.17 30 / 2.60 7 / 2.60 18.20 707 0.1745 909 6,140 3,000
240 241.27 56.30 30 / 3.20 7 / 3.20 22.40 1,070 0.1159 1,203 9,170 3,000
280 281.07 40.08 26 / 3.71 7 / 2.70 21.60 1,064 0.1015 1,280 8,980 2,000
330 326.73 52.83 26 / 4.00 7 / 3.10 25.30 1,285 0.0869 1,452 10,000 2,000
410 413.51 67.35 26 / 4.50 7 / 3.50 28.50 1,625 0.0686 1,708 12,720 2,000
480 (Rail) 483.84 33.54 45 / 3.70 7 / 2.47 29.61 1,580 0.0600 1,812 10,500 1,500
480 (Cardinal) 484.53 62.81 54 / 3.38 7 / 3.38 30.40 1,796 0.0591 1,846 13,280 1,500

24
ACCR Aluminum Conductor Composite Reinforced

Application : Used for overhead transmission lines.

Construction
Conductor : The center wires of galvanized steel and the outer layers of aluminum-zirconium.

Packing : Drum

Specification : ASTM B779

Cross Section No. / Diameter DC Current Rating


Rated
Code Overall Weight at Standard
Area of Wires Resistance Ultimated
Name Diameter Approx. 210C 240C Length
Aluminum Total Aluminum Steel At 20C Strength
*
mm2 mm2 pcs/mm pcs/mm mm kg/km /km A A kgf m
Linnet 336 172 200 26/2.90 7 /2.30 18.4 573 0.1596 942 1,010 6,305 5,000
Ibis 397 205 239 26/3.20 7 /2.50 20.1 684 0.1338 1,058 1,135 7,484 3,000
Hawk 477 238 277 26/3.40 7 /2.70 21.6 793 0.1153 1,167 1,253 8,709 3,000
Dove 557 291 338 26/3.80 7 /2.90 23.9 967 0.0945 1,331 1,430 10,478 3,000
Grosbeak 636 323 375 26/4.00 7 /3.10 25.2 1,073 0.0851 1,426 1,533 11,612 2,000
Drake 795 418 484 26/4.50 19/2.10 28.6 1,384 0.0658 1,691 1,820 14,606 2,000
Cardinal 954 490 552 54/3.40 19/2.00 30.6 1,576 0.0572 1,855 1,997 15,059 2,000
Curlew 1033 525 591 54/3.50 19/2.10 31.7 1,687 0.0534 1,941 2,090 16,148 2,000
Finch 1113 566 638 54/3.70 19/2.20 32.9 1,820 0.0495 2,042 2,199 17,418 2,000
Pheasant 1272 642 723 54/3.90 19/2.30 35.0 2,063 0.0437 2,219 2,392 19,505 1,500
Martin 1351 676 761 54/4.00 19/2.40 35.9 2,172 0.0415 2,298 2,477 20,548 1,500
Falcon 1590 808 910 54/4.40 19/2.60 39.3 2,596 0.0347 2,588 2,792 24,313 1,500

25
ACCC / TW Aluminum Conductor Composite Core
Trapezoidal Concentric-Lay-Stranded
Application : Used for overhead power distribution and transmission lines.

Construction
Conductor : The central is a proprietary high strength carbon fiber composite core and around which are
aluminum wires.

Packing : Drum

Specification : ASTM B 857 ASTM B 609, Manufacturer Specification

Current
Cross Section No. of DC Rated
Code Diameter Weight Carrying Standard
Area Aluminum Wires Ultimated
Name of Approx. Resistance Capacity Length
Nominal At 20C Strength
Conductor (A)
mm2 pcs mm kg/km /km A kg m
Helsinki 160 16 15.65 480 0.1861 775 64.0 2.000
Copenhagen 220 16 18.29 670 0.1279 986 65.6 2.000
Lisbon 310 16 21.78 957 0.0896 1,250 93.2 2.000
Amsterdam 360 20 23.55 1,113 0.0769 1,386 110.6 2.000
Brussels 415 20 25.14 1,275 0.0673 1,515 122.1 2.000
Stockholm 460 20 26.40 1,406 0.0612 1,616 141.1 2.000
Warsaw 510 22 27.72 1,539 0.0556 1,723 142.3 2.000
Dublin 520 22 28.15 1,559 0.0541 1,756 166.4 2.000
Hamburg 550 22 28.62 1,646 0.0517 1,806 143.2 2.000

* Condition of Current Carrying Capacity Calculation


- Conductivity of Aluminium : 63%
- Ambient Temperature : 35C
- Wind Velocity : 0.6 m/s
- Solar Radiation : 0.1 W/cm2
- Radiation Factor : 0.9
- Continous Operating Temperature : @ 175C

26
AAAC - S All Aluminum Alloy Conductor, XLPE Insulated
Application : Used for overhead transmission and distribution.

Construction
Conductor : All Aluminum Alloy Conductor (AAAC), circular stranded according to SPLN 41-8
Insulation : Cross-linked Polyethylene (XLPE), complied with SPLN 41-9.
Packing : Drum
Note : (rm) Circular stranded

Specification : SPLN 41-10

CONSTRUCTION
Cross - Section of Conductor mm2 35 rm 50 rm 70 rm 95 rm 120 rm 150 rm 185 rm 240 rm
Number of cores pcs 7 19 19 19 19 37 37 61
Diameter of Conductor (approx.) mm 7,5 8,8 11,3 12,5 13,8 15,8 17,5 20.3
Thickness of Insulation (nom.) mm 3,0 3,0 3,0 3,0 3,0 3,0 3,0 3.0
Overall Cable Diameter (approx.) mm 13,5 14,8 17,3 18,5 19,8 21,8 26,3 26.3

DELIVERY
Standard Delivery Length m 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000
Drum Type (D) 09C 09C 11A 11A 15A 15A 15A 14B
Cable Weight (approx.) kg/km 195 268 345 407 475 593 700 893

MECHANICAL
Minimum Bending Radius mm 243 266 311 333 356 392 423 473
Breaking Strength kgf 980 1,300 2,150 2,660 3,220 4,190 5,175 6,910

ELECTRICAL
AC Voltage Test kV/min 3,5/5 3,5/5 3,5/5 3,5/5 3,5/5 3,5/5 3,5/5 3,5/5
Max. Conductor DC Resistance at 200C /km 0,868 0,641 0,443 0,320 0,253 0,206 0,164 0,125
Min. Insulation Resistance at 200C M/km 1.000 900 900 800 800 800 800 700

CURRENT RATINGS
at 300C A 167 200 275 315 356 423 484 586
In Air
at 40 C
0 A 150 180 246 282 319 378 432 523

SHORT CIRCUIT CURRENT


Max. Permissible 0.1 Second kA 10,63 15,18 21,25 28,84 36,43 45,54 56,16 72,86
Short Circuit 0.5 Second kA 4,75 6,79 9,50 12,90 16,29 20,36 25,12 32,58
Current For 1.0 Second kA 3,36 4,80 6,72 9,12 11,52 14,40 17,76 23,04

27
CONVERSION TABLE

IEC JIS AMERICAN STANDARD

s q.mm s q.mm AWG or MCM s q.mm


0,5 0,50 AWG
20 [0.517]

19 [0.653]
0,75 0,75
18 [0.823]

17 [1.04]

16 [1.31]
1,25
15 [1.65]
1,5
2,0
14 [2.08]
2,5
13 [2.62]

12 [3.31]
3,5
11 [4.17]
4
10 [5.26]

5,5
9 [6.63]
6
8,0
8 [8.37]
10
7 [10.55]

6 [13.30]
14
5 [16.77]
25
4 [21.15]
22
3 [26.67]
35
2 [33.63]
50 38
1 [42.41]

1/0 [53.48]
60
2/0 [67.43]
70
3/0 [85.03]
95
4/0 [107.20]
100
120 MCM
250 [126.64]
150 150
300 [152.00]
185
200
240
400 [202.71]
250
500 [353.35]
300
600 [304.00]
350
700 [354.71]
400 400
800 [405.35]
500 500
1000 [506.71]
600
630

28
NF/NFA 2X Copper or Aluminum Conductor, XLPE
0.6 / 1 kV Insulated
Application : Used for secondary distribution and street lighting overhead low voltage power cable.

Construction
Conductor : annealed copper conductor, circular stranded according to SPLN 41-1
or aluminum conductor, circular stranded according to SPLN 41-1
Insulation : Cross-linked Polyethylene (XLPE), complied with SPLN 41-9.
Identification of core : rip core
Packing : Drum
Note : (rm) Circular stranded

Specification : SPLN 42-10

CONSTRUCTION
No. of Core 2 4
Cross-Section of Conductor mm2 2 x 6 rm 2 x 10 rm 2 x 16 rm 4 x 6 rm 4 x 10 rm 4 x 16 rm 4 x 25 rm 4 x 35 rm
Diameter of Conductor (approx.) mm 3.2 4.1 5.1 3.2 4.1 5.1 6.4 7.6
Thickness of Insulation (nom.) mm 1.2 1.2 1.2 1.2 1.2 1.2 1.4 1.6
Overall Cable Diameter (approx.) mm 11.1 12.9 15.1 13.4 15.5 18.2 22.2 25.9

DELIVERY
Standard Delivery Length m 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000
Drum Type (D) 09C 09C 09C 09C 09C 11A 15A 14B
Cable Weight Copper (approx.) kg/km 144 224 345 288 448 690 1,063 1,481
Aluminum (approx.) kg/km 67 97 141 135 195 283 429 594

MECHANICAL
Copper kgf 394 656 1051 788 1312 2102 3284 -
Breaking Strength
Aluminum kgf - 322 515 - 644 1030 1610 2250
Minimum Bending Radius mm 200 232 272 241 279 328 400 466

ELECTRICAL
AC Voltage Test kV/min 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5
Max. Conductor Copper /km3.08 1.83 1.15 3.08 1.83 1.15 1.727 0.524
DC Resistance at 200C Aluminum /km 4.61 3.08 1.91 4.61 3,08 1,91 1,20 0,868
Min.Insulation Resistance Copper M.km 1,500 1,200 1,100 1,500 1,200 1,100 1,100 1,000
Aluminum M.km 1,500 1,200 1,100 1,500 1,200 1,100 1,100 1,000

CURRENT RATINGS
Copper A 54 73 97 54 73 97 133 -
In Air at 350C
Aluminum A - 54 72 - 54 72 102 125

SHORT CIRCUIT CURRENT


Copper kA 2.69 4.49 7.18 2.69 4.49 7.18 11.23 15.72
Max. Permissible 0.1 Second
Aluminum kA 1.82 3.04 4.86 1.82 3.04 4.86 7.59 10.63
Copper kA 1.20 2.01 3.21 1.20 2.01 3.21 5.02 7.03
Short Circuit 0.5 Second
Aluminum kA 0.81 1.36 2.17 0.81 1.36 2.17 3.39 4.75
Current For 1.0 Second Copper kA 0.85 1.42 2.27 0.85 1.42 2.27 3.55 4.97
Aluminum kA 0.58 0.96 1.54 0.58 0.96 1.54 2.40 3.36

29
NFA2X-T Aluminum Conductor, XLPE Insulated +
0.6 / 1 kV Neutral Messenger
Application : Used for secondary distribution and street lighting overhead low voltage power cable.

Construction
Conductor - Phasa : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
- Messanger : All Aluminum Alloy Conductor (AAAC), circular stranded according to SPLN 41-8
Insulation : Cross-linked Polyethylene (XLPE), complied with SPLN 41-9.
Identification of core : rip core
Packing : Drum
Note : (rm) Circular stranded

Specification : SPLN 42-10

CONSTRUCTION

Cable Size mm2 2 x 25 + 25 rm 2 x 35 + 25 rm 2 x 50 + 35 rm 2 x 70 + 50 rm 2 x 95 + 70 rm


Phasa mm2 25 rm 35 rm 50 rm 70 rm 95 rm
Cross-Section of Conductor Neutral mm2 25 rm 25 rm 35 rm 50 rm 70 rm
Phasa (approx.) mm 6.4 7.6 9.1 10.9 12.6
Diameter of Conductor Neutral (approx.) mm 6.4 6.4 7.6 9.1 10.9
Phasa (nom.) mm 1.4 1.6 1.6 1.8 2.0
Thickness of Insulation Neutral (nom.) mm 1.4 1.4 1.6 1.6 1.8
Overall Cable Diameter (approx.) mm 19.9 22.1 25.4 29.6 34.3

DELIVERY
Standard Delivery Length m 500 500 500 500 500
Drum Type (D) 11A 11A 15A 15A 15A
Cable Weight (approx.) kg/km 325 408 556 756 1,012

MECHANICAL

Breaking Strength kgf 712 712 997 1,395 1,932


Minimum Bending Radius mm 358 398 457 533 617

ELECTRICAL
AC Voltage Test kV/min 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5
Max. Conductor Phasa /km 1.20 0.868 0.641 0.443 0.320
DC Resistance at 200C Neutral /km 1.38 1.38 0.986 0.690 0.450
Min.Insulation Resistance Phasa M.km 1,100 1,000 900 900 800
Neutral M.km 1,100 1,100 1,000 900 900

CURRENT RATINGS

In Air at 350C A 103 125 154 196 242

SHORT CIRCUIT CURRENT


Phasa kA 7.59 10.63 15.18 21.25 28.84
0.1 Second
Max. Permissible Neutral kA 7.59 7.59 10.63 15.18 21.25
Short Circuit 0.5 Second Phasa kA 3.39 4.75 6.79 9.50 12.90
Neutral kA 3.39 3.39 4.75 6.79 9.50
Current For
1.0 Second Phasa kA 2.40 3.36 4.80 6.72 9.12
Neutral kA 2.40 2.40 3.36 4.80 6.72

30
NFA 2X-T Aluminum Conductor, XLPE Insulated +
0.6 / 1 kV Neutral Messenger
Application : Used for secondary distribution and street lighting overhead low voltage power cable.

Construction
Conductor - Phasa : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1.
- Messenger : All Aluminum Alloy Conductor (AAAC), circular stranded according to SPLN 41-8
Insulation : Cross-linked Polyethylene (XLPE), complied with SPLN 41-9.
Identification of core : rip core
Packing : Drum
Note : (rm) Circular stranded

Specification : SPLN 42-10

CONSTRUCTION

Cable Size mm2 3 x 25 + 25 rm 3 x 35 + 25 rm 3 x 50 + 35 rm 3 x 70 + 50 rm 3 x 95 + 70 rm


Cross-Section of Conductor Phasa mm2 25 rm 35 rm 50 rm 70 rm 95 rm
Neutral mm2 25 rm 25rm 35 rm 50 rm 70 rm
Diameter of Conductor Phasa [approx.] mm 6.4 7.6 9.1 10.9 12.6
Neutral [approx.] mm 6.4 6.4 7.6 9.1 10.9
Thickness of Insulation Phasa [nom.] mm 1.4 1.6 1.6 1.8 2.0
Neutral [nom.] mm 1.4 1.4 1.6 1.6 1.8
Overall Cable Diameter [approx.] mm 22.2 25.1 28.6 33.6 38.9

DELIVERY
Standard Delivery Length m 500 500 500 500 500
Drum Type [D] 11A 11A 15A 15A 18A
Cable Weight [approx.] kg/km 434 558 759 1,032 1,380

MECHANICAL
Breaking Strength kgf 712 712 997 1,395 1,932
Minimum Bending mm 400 452 515 605 700

ELECTRICAL
AC Voltage Test kV/min 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5
Max Conductor Phasa /km 1.20 0.868 0.641 0.443 0.320
DC Resistance at 20 0C Neutral /km 1.38 1.38 0.986 0.690 0.450
Phasa M.km 1,100 1,000 900 900 800
Min. Insulation Resistance Neutral M.km 1,100 1,100 1,000 900 900

CURRENT RATINGS
In Air at 350C A 103 125 154 196 242

SHORT CIRCUIT CURRENT


Max Permissible 0.1 Second Phasa kA 7.59 10.63 15.18 21.25 28.84
Neutral kA 7.59 7.59 10.63 15.18 21.25
Short Circuit 0.5 Second Phasa kA 3.39 4.75 6.79 9.50 12.90
Neutral kA 3.39 3.39 4.75 6.79 9.50
Current for 1.0 Second Phasa kA 2.40 3.36 4.80 6.72 9.12
Neutral kA 2.40 2.40 3.36 4.80 6.72

31
NFA2X-T Aluminum Conductor, XLPE Insulated +
0.6 / 1 kV Neutral Messenger + Public Lighting
Application : Used for secondary distribution and street lighting overhead low voltage power cable.

Construction
Conductor - Phasa : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
- Messanger : All Aluminum Alloy Conductor (AAAC), circular stranded according to SPLN 41-8
- Public Lighting : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
Insulation : Cross-linked Polyethylene (XLPE), complied with SPLN 41-9.
Identification of core : rip core
Packing : Drum
Note : (rm) Circular stranded

Specification : SPLN 42-10


CONSTRUCTION DATA
Cable Size mm2 3 x 25 + 25 rm 2 x 35 + 25 rm 3 x 50 + 35 rm 3 x 70 + 50 rm 3 x 95 + 70 rm
+ 1 X 16 rm + 1 X 16 rm + 1 X 16 rm + 1 X 16 rm +1 X 16 rm
Phasa mm2 25 rm 35 rm 50 rm 70 rm 95 rm
Cross-Section of Conductor Neutral mm2 25 rm 25rm 35 rm 50 rm 70 rm
Public Lighting mm2 16 rm 16 rm 16 rm 16 rm 16 rm
Phasa [approx.] mm 6.4 7.6 9.1 10.9 12.6
Diameter of Conductor Neutral [approx.] mm 6.4 6.4 7.6 9.1 10.9
Public Lighting [approx.] mm 5.1 5.1 5.1 5.1 5.1
Phasa [nom.] mm 1.4 1.6 1.6 1.8 2.0
Thickness of Insulation Neutral [nom.] mm 1.4 1.4 1.6 1.6 1.8
Public Lighting [nom.] mm 1.2 1.2 1.2 1.2 1.2
Overall Cable Diameter [approx.] mm 23.9 26.5 29.7 34.1 38.8

DELIVERY DATA
Standard Delivery Length m 500 500 500 500 500
Drum Type [D] 11A 11A 15A 15A 18A
Cable Weight [approx.] kg/km 505 630 831 1,104 1,451

MECHANICAL DATA
Breaking Strength kgf 712 712 997 1,395 1,932
Minimum Bending mm 430 477 535 614 698

ELECTRICAL DATA
AC Voltage Test kV/min 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5
Phasa /km 1.20 0.868 0.641 0.443 0.320
Max Conductor
Neutral /km 1.38 1.38 0.986 0.690 0.450
DC Resistance at 20 0C
Public Lighting .km 1.91 1.91 1.91 1.91 1.91
Phasa M.km 1,100 1,000 900 900 800
Min. Insulation Resistance Neutral M.km 1,100 1,100 1,000 900 900
Public Lighting M.km 1,100 1,100 1,100 1,100 1,100

CURRENT RATINGS
In Air at 350C Phasa A 103 125 154 196 242
Public Lighting A 72 72 72 72 72

SHORT CIRCUIT CURRENT


Phasa kA 7.59 10.63 15.18 21.25 28.84
Max Permissible Neutral kA 7.59 7.59 10.63 15.18 21.25
0.1 Second
Public Lighting kA 4.86 4.86 4.86 4.86 4.86
Phasa kA 3.39 4.75 6.79 9.50 12.90
Short Circuit 0.5 Second Neutral kA 3.39 3.39 4.75 6.79 9.50
Public Lighting kA 2.17 2.17 2.17 2.17 2.17
Phasa kA 2.40 3.36 4.80 6.72 9.12
Current for 1.0 Second Neutral kA 2.40 2.40 3.36 4.80 6.72
Public Lighting kA 1.54 1.54 1.54 1.54 1.54

32
NFA2X-T Aluminum Conductor, XLPE Insulated +
0.6 / 1 kV Neutral Messenger + Public Lighting
Application : Used for secondary distribution and street lighting overhead low voltage power cable.

Construction
Conductor - Phasa : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
- Messanger : All Aluminum Alloy Conductor (AAAC), circular stranded according to SPLN 41-8
- Public Lighting : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
Insulation : Cross-linked Polyethylene (XLPE), complied with SPLN 41-9.
Identification of core : rip core
Packing : Drum
Note : (rm) Circular stranded

Specification : SPLN 42-10


CONSTRUCTION DATA
mm2 3 x 25 + 25 rm 2 x 35 + 25 rm 3 x 50 + 35 rm 3 x 70 + 50 rm 3 x 95 + 70 rm
Cable Size
+ 2 X 16 rm + 2 X 16 rm + 2 X 16 rm + 2 X 16 rm +2 X 16 rm
Phasa mm2 25 rm 35 rm 50 rm 70 rm 95 rm
Cross-Section of Conductor Neutral mm2 25 rm 25rm 35 rm 50 rm 70 rm
Public Lighting mm2 16 rm 16 rm 16 rm 16 rm 16 rm
Phasa [approx.] mm 6.4 7.6 9.1 10.9 12.6
Diameter of Conductor Neutral [approx.] mm 6.4 6.4 7.6 9.1 10.9
Public Lighting [approx.] mm 5.1 5.1 5.1 5.1 5.1
Phasa [nom.] mm 1.4 1.6 1.6 1.8 2.0
Thickness of Insulation Neutral [nom.] mm 1.4 1.4 1.6 1.6 1.8
Public Lighting [nom.] mm 1.2 1.2 1.2 1.2 1.2
Overall Cable Diameter [approx.] mm 25.5 27.8 30.8 34.6 39.0

DELIVERY DATA
Standard Delivery Length m 500 500 500 500 500
Drum Type [D] 11A 11A 15A 15A 18A
Cable Weight [approx.] kg/km 576 701 903 1,175 1,522

MECHANICAL DATA
Breaking Strength kgf 712 712 997 1,395 1,932
Minimum Bending mm 459 500 554 623 702

ELECTRICAL DATA
AC Voltage Test kV/min 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5
Phasa /km 1.20 0.868 0.641 0.443 0.320
Max Conductor Neutral /km 1.38 1.38 0.986 0.690 0.450
DC Resistance at 20 0C Public Lighting .km 1.91 1.91 1.91 1.91 1.91
Phasa M.km 1,100 1,000 900 900 800
Min. Insulation Resistance Neutral M.km 1,100 1,100 1,000 900 900
Public Lighting M.km 1,100 1,100 1,100 1,100 1,100

CURRENT RATINGS
In Air at 350C Phasa A 103 125 154 196 242
Public Lighting A 72 72 72 72 72

SHORT CIRCUIT CURRENT


Phasa kA 7.59 10.63 15.18 21.25 28.84
Max Permissible Neutral kA 7.59 7.59 10.63 15.18 21.25
0.1 Second
Public Lighting kA 4.86 4.86 4.86 4.86 4.86
Phasa kA 3.39 4.75 6.79 9.50 12.90
Short Circuit
0.5 Second Neutral kA 3.39 3.39 4.75 6.79 9.50
Public Lighting kA 2.17 2.17 2.17 2.17 2.17
Phasa kA 2.40 3.36 4.80 6.72 9.12
Current for
1.0 Second Neutral kA 2.40 2.40 3.36 4.80 6.72
Public Lighting kA 1.54 1.54 1.54 1.54 1.54

33
DUPLEX Aluminum Conductor, XLPE Insulated +
0.6 / 1 kV Neutral Messenger
Application : Used for secondary distribution and street lighting overhead low voltage power cable.

Construction
Conductor - Phasa : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
- Messenger : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
All Aluminum Alloy Conductor (AAAC), circular stranded according to SPLN 41-8
Aluminum Conductor Steel Reinforced (ACSR), circular stranded according to SPLN 41-7
Insulation : Cross-linked Polyethylene (XLPE), complied with SPLN 41-9.
Packing : Drum
Note : (rm) Circular stranded

DUPLEX CABLE WITH AAC NEUTRAL MESSENGER


CONSTRUCTION DATA
Cross-Section of Cable mm2 16 rm 25 rm 35 rm 50 rm
Phasa AAC pcs/mm 7 / 1.75 7 / 2.25 7 / 2.50 19 / 1.75
No./Diameter of Wire Neutral AAC pcs/mm 7 / 1.75 7 / 2.25 7 / 2.50 19 / 1.75
Breaking Strength Neutral AAC kgf 310 490 590 835
Thickness of Insulation Phasa [nom.] mm 1.20 1.40 1.60 1.60
Overall Cable Diameter [approx.] mm 12.90 16.30 18.20 20.70
Cable Weight [approx.] kg/km 120 194 241 314
Minimum Bending Radius mm 232 293 328 373

DUPLEX CABLE WITH ACSR NEUTRAL MESSENGER


CONSTRUCTION DATA
Cross-Section of Cable mm2 16 rm 25 rm 35 rm 50 rm
Phasa AAC pcs/mm 7 / 1.75 7 / 2.25 7 / 2.50 19 / 1.75
No./Diameter of Wire Neutral AAC pcs/mm 6 / 1.80 6 / 2.25 6 / 2.70 12 / 2.33
ACSR Steel pcs/mm 1 / 1.80 1 / 2.25 1 / 2.70 7 / 2.33
Breaking Strength Neutral ACSR kgf 5,950 9,200 12,650 23,800
Thickness of Insulation Phasa [nom.] mm 1.20 1.40 1.60 1.60
Overall Cable Diameter [approx.] mm 13.10 16.30 18.80 23.60
Cable Weight [approx.] kg/km 136 215 287 566
Minimum Bending Radius mm 236 293 338 425

DUPLEX CABLE WITH AAAC NEUTRAL MESSENGER


CONSTRUCTION DATA
Cross-Section of Cable mm2 - 25 rm 35 rm 50 rm
Phasa AAC pcs/mm - 7 / 2.25 7 / 2.50 19 / 1.75
No./Diameter of Wire Neutral AAAC pcs/mm - 7 / 2.25 7 / 2.50 19 / 1.75
Breaking Strength Neutral AAAC kgf - 790 980 1,410
Thickness of Insulation Phasa [nom.] mm - 1,40 1.60 1.60
Overall Cable Diameter [approx.] mm - 16.30 18.20 20.70
Cable Weight [approx.] kg/km - 194 241 314
Minimum Bending Radius mm - 293 328 373

DELIVERY DATA
Standard Delivery Length m 1,000 1,000 1,000 1,000

ELECTRICAL DATA
AC Voltage Test kV/min 3.5/5 3.5/5 3.5/5 3.5/5
Max Conductor DC Resistance at 20 0C /km 1.91 1.20 0.868 0.641
Min. Insulation Resistance at 20 0C Phasa M.km 1,100 1,100 1,000 900
Current Rating in Air at 30 0C A 100 132 166 210
Max. Permissible 0,1 Second Phasa kA 4.86 7.59 10.63 15.18
Short Circuit 0,5 Second Phasa kA 2.17 3.39 4.75 6.79
Current for 1,0 Second Phasa kA 1.54 2.40 3.36 4.80

34
TRIPLEX Aluminum Conductor, XLPE Insulated +
0.6 / 1 kV Neutral Messenger
Application : Used for secondary distribution and street lighting overhead low voltage power cable.

Construction
Conductor - Phasa : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
- Messenger : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
All Aluminum Alloy Conductor (AAAC), circular stranded according to SPLN 41-8
Alluminum Conductor Steel Reinforced (ACSR), circular stranded according to SPLN 41-7
Insulation : Cross-linked Polyethylene (XLPE), complied with SPLN 41-9.
Identification of core : rip core
Packing : Drum
Note : (rm) Circular stranded

TRIPLEX CABLE WITH AAC NEUTRAL MESSENGER


CONSTRUCTION DATA
Cross-Section of Cable mm2 16 rm 25 rm 35 rm 50 rm 70 rm 95 rm 120 rm
Phasa AAC pcs/mm 7 / 1.75 7 / 2.25 7 / 2.50 19 / 1.75 19 / 2.25 19 / 2.50 19 / 2.75
No./Diameter of Wire Neutral AAC pcs/mm 7 / 1.75 7 / 2.25 7 / 2.50 19 / 1.75 19 / 2.25 19 / 2.50 19 / 2.75
Breaking Strength Neutral AAC kgf 310 490 590 835 1,040 1,560 1,890
Thickness of Insulation Phasa [nom.] mm 1.20 1.40 1.60 1.60 1.80 1.80 1.80
Overall Cable Diameter [approx.] mm 14.80 18.60 20.80 23.50 29.50 32.20 34.90
Cable Weight [approx.] kg/km 194 312 388 499 808 977 1,164
Minimum Bending Radius mm 266 335 374 423 531 580 628

TRIPLEX CABLE WITH ACSR NEUTRAL MESSENGER


CONSTRUCTION DATA
Cross-Section of Cable mm2 16 rm 25 rm 35 rm 50 rm 70 rm 95 rm 120 rm
Phasa AAC pcs/mm 7 / 1.75 7 / 2.25 7 / 2.50 19 / 1.75 19 / 2.25 19 / 2.50 19 / 2.75
No./Diameter of Wire Neutral AAC pcs/mm 6 / 1.80 6 / 2.25 6 / 2.70 12 / 2.33 26 / 1.85 26 / 2.25 26 / 2.44
ACSR Steel pcs/mm 1 / 1.80 1 / 2.25 1 / 2.70 7 / 2.33 7 / 1.44 7 / 1.67 7 / 1.90
Breaking Strength Neutral ACSR kgf 5,950 9,200 12.650 23,800 26,800 35,750 45,650
Thickness of Insulation Phasa [nom.] mm 1.20 1.40 1.60 1.60 1.80 1.80 1.80
Overall Cable Diameter [approx.] mm 14.90 18.60 21.30 25.60 29.80 33.30 36.10
Cable Weight [approx.] kg/km 209 332 433 752 877 1,120 1,337
Minimum Bending Radius mm 268 335 483 461 536 599 650

TRIPLEX CABLE WITH AAAC NEUTRAL MESSENGER


CONSTRUCTION DATA
Cross-Section of Cable mm2 - 25 rm 35 rm 50 rm 70 rm 95 rm 120 rm
Phasa AAC pcs/mm - 7 / 2.25 7 / 2.50 19 / 1.75 19 / 2.25 19 / 2.50 19 / 2.75
No./Diameter of Wire Neutral AAAC pcs/mm - 7 / 2.25 7 / 2.50 19 / 1.75 19 / 2.25 19 / 2.50 19 / 2.75
Breaking Strength Neutral AAAC kgf - 790 980 1,300 2,150 2,660 3,220
Thickness of Insulation Phasa [nom.] mm - 1.40 1.60 1.60 1.80 1.80 1.80
Overall Cable Diameter [approx.] mm - 18.60 20.80 23.50 29.50 32.20 34.90
Cable Weight [approx.] kg/km - 312 388 499 808 977 1,164
Minimum Bending Radius mm - 335 374 423 531 580 628

DELIVERY DATA
Standard Delivery Length m 1,000 1,000 1,000 1,000 1,000 1,000 1,000

ELECTRICAL DATA
AC Voltage Test kV/min 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5
Max Conductor DC Resistance at 20 0C /km 1.91 1.20 0.868 0.641 0.443 0.32 0.253
Min. Insulation Resistance at 20 0C Phasa M.km 1,100 1,100 1,000 900 900 800 800
Current Rating in Air at 30 0C A 83 109 135 171 211 258 296
Max. Permissible 0,1 Second Phasa kA 4.86 7.59 10.63 15.18 21.25 28.84 36.43
Short Circuit 0,5 Second Phasa kA 2.17 3.39 4.75 6.79 9.50 12.90 16.29
Current for 1,0 Second Phasa kA 1.54 2.40 3.36 4.80 6.72 9.12 11.52

35
QUADRUPLEX Aluminum Conductor, XLPE Insulated +
0.6 / 1 kV Neutral Messenger
Application : Used for secondary distribution and street lighting overhead low voltage power cable.

Construction
Conductor - Phasa : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
- Messanger : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
All Aluminum Alloy Conductor (AAAC), circular stranded according to SPLN 41-8
Alluminum Conductor Steel Reinforced (ACSR), circular stranded according to SPLN 41-7
Insulation : Cross-linked Polyethylene (XLPE), complied with SPLN 41-9.
Identification of core : rip core
Packing : Drum
Note : (rm) Circular stranded

QUADRUPLEX CABLE WITH AAC NEUTRAL MESSENGER


CONSTRUCTION DATA
Cross-Section of Cable mm2 - 25 rm 35 rm 50 rm 70 rm 95 rm 120 rm
Phasa AAC pcs/mm - 7 / 2.25 7 / 2.50 19 / 1.75 19 / 2.25 19 / 2.50 19 / 2.75
No./Diameter of Wire Neutral AAC pcs/mm - 7 / 2.25 7 / 2.50 19 / 1.75 19 / 2.25 19 / 2.50 19 / 2.75
Breaking Strength Neutral AAC kgf - 490 590 835 1,040 1,560 1,890
Thickness of Insulation Phasa [nom.] mm - 1.40 1.60 1.60 1.80 1.80 1.80
Overall Cable Diameter [approx.] mm - 20.80 23.20 26.20 32.90 35.90 38.90
Cable Weight [approx.] kg/km - 429 534 685 1,106 1,336 1,558
Minimum Bending Radius mm - 374 418 472 592 646 700

QUADRUPLEX CABLE WITH ACSR NEUTRAL MESSENGER


CONSTRUCTION DATA
Cross-Section of Cable mm2 16 rm 25 rm 35 rm 50 rm 70 rm 95 rm 120 rm
Phasa AAC pcs/mm 7 / 1.75 7 / 2.25 7 / 2.50 19 / 1.75 19 / 2.25 19 / 2.50 19 / 2.75
No./Diameter of Wire Neutral AAC pcs/mm 6 / 1.80 6 / 2.25 6 / 2.70 12 / 2.33 26 / 1.85 26 / 2.25 26 / 2.44
ACSR Steel pcs/mm 1 / 1.80 1 / 2.25 1 / 2.70 7 / 2.33 7 / 1.44 7 / 1.67 7 / 1.90
Breaking Strength Neutral ACSR kgf 5,950 9,200 12,650 23,800 26,800 35,750 45,650
Thickness of Insulation Phasa [nom.] mm 1.20 1.40 1.60 1.60 1.80 1.80 1.80
Overall Cable Diameter [approx.] mm 16.60 20.80 23.70 28.60 33.30 37.10 40.30
Cable Weight [approx.] kg/km 283 449 579 938 1,173 1,476 1,758
Minimum Bending Radius mm 299 374 427 515 599 668 725

QUADRUPLEX CABLE WITH AAAC NEUTRAL MESSENGER


CONSTRUCTION DATA
Cross-Section of Cable mm2 - 25 rm 35 rm 50 rm 70 rm 95 rm 120 rm
Phasa AAC pcs/mm - 7 / 2.25 7 / 2.50 19 / 1.75 19 / 2.25 19 / 2.50 19 / 2.75
No./Diameter of Wire Neutral AAAC pcs/mm - 7 / 2.25 7 / 2.50 19 / 1.75 19 / 2.25 19 / 2.50 19 / 2.75
Breaking Strength Neutral AAAC kgf - 790 980 1,300 2,150 2,660 3,220
Thickness of Insulation Phasa [nom.] mm - 1.40 1.60 1.60 1.80 1.80 1.80
Overall Cable Diameter [approx.] mm - 20.80 23.20 26.20 32.90 35.90 38.90
Cable Weight [approx.] kg/km - 429 534 685 1,106 1,336 1,558
Minimum Bending Radius mm - 374 418 472 592 646 700

DELIVERY DATA
Standard Delivery Length m 1,000 1,000 1,000 1,000 1,000 1,000 1,000

ELECTRICAL DATA
AC Voltage Test kV/min 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5
Max Conductor DC Resistance at 20 0C /km 1.91 1.20 0.868 0.641 0.443 0.32 0.253
Min. Insulation Resistance at 20 0C Phasa M.km 1,100 1,100 1,000 900 900 800 800
Current Rating in Air at 30 0C A 83 109 135 171 211 258 296
Max. Permissible 0,1 Second Phasa kA 4.86 7.59 10.63 15.18 21.25 28.84 36.43
Short Circuit 0,5 Second Phasa kA 2.17 3.39 4.75 6.79 9.50 12.90 16.29
Current for 1,0 Second Phasa kA 1.54 2.40 3.36 4.80 6.72 9.12 11.52

36