Professional Documents
Culture Documents
Bare&Twisted PDF
Bare&Twisted PDF
23
STACIR SUPER THERMAL RESISTANCE - INVAR REINFORCED
25
ACCR ALUMINUM CONDUCTOR COMPOSITE REINFORCED
CONVERSION TABLE 28
2. Galvanized Invar
2
ACCR 1. Aluminum-Zirconium
2
AAC All Aluminum Conduc
Conductor
tor
Application : Used for overhead power transmission purpose, medium tension. Overhead system and distribution
network.
Construction
Conductor : Circular stranded All Aluminum Conductor [AAC]
Packing : Drum
03
AAC All Aluminum Conduc
Conductor
tor
Application : Used for overhead power transmission purpose, medium tension. Overhead system and distribution
network.
Construction
Conductor : Circular stranded All Aluminum Conductor [AAC]
Packing : Drum
Overall
Cross Section
Area Diameter Weight DC Rated
Code No. of Diameter Approx. Approx. Resistance Current Ultimated Standard
Name AWG or Wires of Wires At 20C Rating Strength Length
MCM mm2 pcs mm mm kg/km /km A kg m
Peachbell 6 13.29 7 1.55 4.70 37 2.1710 90 254 10,000
Rose 4 21.16 7 1.96 5.90 58 1.3638 120 404 10,000
Iris 2 33.61 7 2.47 7.40 93 0.8568 160 610 10,000
Pansy 1 42.38 7 2.78 8.30 117 0.6804 185 726 10,000
Poppy 1/0 53.48 7 3.12 9.40 147 0.5391 215 890 10,000
Aster 2/0 67.41 7 3.50 10.40 186 0.4281 250 1,121 5,000
Phlox 3/0 85.03 7 3.93 11.80 234 0.3392 290 1,373 5,000
Oxlip 4/0 107.22 7 4.42 13.30 259 0.2688 335 1,732 5,000
Valerian 250.000 126.70 19 2.91 14.60 349 0.2277 370 2,101 5,000
Sneezewort 250.000 126.72 7 4.80 14.60 349 0.2275 370 2,047 5,000
Daisy 266.800 135.16 7 4.96 14.90 373 0.2131 385 2,185 5,000
Laurel 266.800 135.16 19 3.01 15.10 373 0.2132 390 2,180 5,000
Peony 300.000 152.00 19 3.19 16.00 419 0.1895 420 2,452 5,000
Tulip 336.400 170.45 19 3.38 16.90 470 0.1690 450 2,750 5,000
Daffodil 350.000 177.35 19 3.45 17.20 489 0.1626 460 2,858 5,000
Canna 397.500 201.41 19 3.68 18.40 556 0.1431 500 3,249 3,000
Goldentuft 450.000 228.00 19 3.91 19.60 628 0.1264 540 3,567 3,000
Syringa 477.000 241.54 37 2.88 20.18 667 0.1194 560 3,922 3,000
Cosmos 477.000 241.67 19 4.02 20.10 666 0.1194 560 3,778 3,000
Hyacinth 500.000 253.06 37 2.95 20.66 699 0.1139 575 4,109 3,000
Zinnia 500.000 253.35 19 4.12 20.60 698 0.1138 575 3,963 3,000
Dahlia 556.500 282.00 19 4.35 21.70 777 0.1023 615 4,409 3,000
Mistletoe 556.500 282.00 37 3.11 21.80 777 0.1023 615 4,444 3,000
Meadowsweet 600.000 304.00 37 3.23 22.60 838 0.0949 645 4,790 3,000
Orchid 636.000 322.25 37 3.33 23.30 888 0.0895 670 5,082 2,000
Heuchera 650.000 329.35 37 3.37 23.60 908 0.0875 680 5,199 2,000
Flag 700.000 354.71 61 2.72 24.50 978 0.0813 715 5,854 2,000
Verbena 700.000 354.71 37 3.49 24.50 978 0.0813 710 5,592 2,000
04
AAC All Aluminum Conduc
Conductor
tor
Application : Used for overhead power transmission purpose, medium tension. Overhead system and distribution
network.
Construction
Conductor : Circular stranded All Aluminum Conductor [AAC]
Packing : Drum
05
AAAC All Aluminum Alloy Conduc
Conductor
tor
Application : Used for overhead power transmission purpose, medium tension. Overhead system and distribution
network.
Construction
Conductor : Circular stranded All Aluminum Alloy Conductor [AAAC]
Packing : Drum
06
AAAC All Aluminum Aloy Conduc
Conductor
tor
Application : Used for overhead power transmission purpose, medium tension. Overhead system and distribution
network.
Construction
Conductor : Circular stranded All Aluminum Aloy Conductor [AAAC]
Packing : Drum
07
AAAC All Aluminum Alloy Conduc
Conductor
tor
Application : Used for overhead power transmission purpose, medium tension. Overhead system and distribution
network.
Construction
Conductor : Circular stranded thermal resistance All Aluminum Alloy Conductor (T-AAAC)
Packing : Drum
08
ACSR Aluminum Conductor Steel Reinforced
Construction
Conductor : The center wire or wires of galvanized steel and the outer layer or layers of aluminum.
Packing : Drum
09
ACSR Aluminum Conductor Steel Reinforced
Construction
Conductor : The center wire or wires of galvanized steel and the outer layer or layers of aluminum.
Packing : Drum
10
ACSR Aluminum Conductor Steel Reinforced
Construction
Conductor : The center wire or wires of galvanized steel and the outer layer or layers of aluminum.
Packing : Drum
11
ACSR Aluminum Conductor Steel Reinforced
Construction
Conductor : The center wire or wires of galvanized steel and the outer layer or layers of aluminum.
Packing : Drum
12
ACSR Aluminum Conductor Steel Reinforced
Construction
Conductor : The center wire or wires of galvanized steel and the outer layer or layers of aluminum.
Packing : Drum
13
ACSR Aluminum Conductor Steel Reinforced
Construction
Conductor : The center wire or wires of galvanized steel and the outer layer or layers of aluminum.
Packing : Drum
14
T-ACSR Thermal Resistance-Aluminum Conduc
Conductor
Steel Reinforced
Application : Used for overhead transmission lines.
Construction
Conductor : The center wire or wires of galvanized steel and the outer layer or layers of thermal resistance alloy
aluminum.
Packing : Drum
15
ACSR /AS Aluminum Conductor - Aluminum
Clad Steel Reinforced
Application : Used for overhead transmission lines.
Construction
Conductor : The center wire or wires of aluminum clad steel and the outer layer or layers of aluminum.
Packing : Drum
16
ACSR /AS Aluminum Conductor - Aluminum
Clad Steel Reinforced
Application : Used for overhead transmission lines.
Construction
Conductor : The center wire or wires of aluminum clad steel and the outer layer or layers of aluminum.
Packing : Drum
No./ Diameter
Cross Section Area of Wires Overall DC Rated
Weight
Diameter Resistance Current Ultimated Standard
Nominal Actual Approx.
Aluminum Steel Approx. At 20C Rating Strength Length
A1/St Aluminum Steel
mm2 mm2 mm2 pcs/mm pcs/mm mm kg/km /km A kg m
240 / 40 243,05 39,49 26 / 3,45 7 / 2,68 21,84 938 0,1126 590 9.012 3.000
265 / 35 263,66 34,09 24 / 3,74 7 / 2,49 22,43 958 0,1048 615 8.624 3.000
300 / 50 304,26 49,48 26 / 3,86 7 / 3,00 24,40 1.170 0,0899 680 11.163 2.000
305 / 40 304,62 39,49 54 / 2,68 7 / 2,68 24,12 1.108 0,0909 670 10.311 2.000
340 / 30 339,29 29,85 48 / 3,00 7 / 2,33 24,99 1.140 0,0827 710 9.577 2.000
380 / 50 381,70 49,48 54 / 3,00 7 / 3,00 27,00 1.388 0,0725 725 12.768 2.000
385 / 35 386,04 34,09 48 / 3,20 7 / 2,49 26,67 1.298 0,0727 770 10.796 2.000
435 / 55 434,29 56,30 54 / 3,20 7 / 3,20 28,80 1.578 0,0638 840 14.394 1.500
450 / 40 448,71 39,49 48 / 3,45 7 / 2,68 28,74 1.508 0,0625 845 12.442 1.500
490 / 65 490,28 63,55 54 / 3,40 7 / 3,40 30,60 1.780 0,0565 905 15.704 1.500
495 / 35 494,36 34,09 45 / 3,74 7 / 2,49 29,91 1.598 0,0571 898 12.427 1.500
510 / 45 510,54 45,28 48 / 3,68 7 / 2,87 30,69 1.710 0,0549 915 14.098 1.500
550 / 70 549,65 71,25 54 / 3,60 7 / 3,60 32,40 1.995 0,0504 970 17.202 1.500
560 / 50 561,70 49,48 48 / 3,86 7 / 3,00 32,16 1.880 0,0500 970 15.352 1.500
570 / 40 571,16 39,49 45 / 4,02 7 / 2,68 32,16 1.823 0,0494 975 14.256 1.500
650 / 45 653,49 45,28 45 / 4,30 7 / 2,87 34,41 2.110 0,0432 1.060 16.265 1.000
680 / 85 678,58 85,95 54 / 4,00 19 / 2,40 36,00 2.454 0,0409 1.100 21.830 1.000
1.045 / 45 1.045,58 45,28 72 / 4,30 7 / 2,87 43,01 3.207 0,0274 1.390 22.615 500
17
ACSR /AS Aluminum Conductor - Aluminum
Clad Steel Reinforced
Application : Used for overhead transmission lines.
Construction
Conductor : The center wire or wires of aluminum clad steel and the outer layer or layers of aluminum.
Packing : Drum
18
ACSR /AS Aluminum Conductor - Aluminum
Clad Steel Reinforced
Application : Used for overhead transmission lines.
Construction
Conductor : The center wire or wires of aluminum clad steel and the outer layer or layers of aluminum.
Packing : Drum
19
ACSR /AS Aluminum Conductor - Aluminum
Clad Steel Reinforced
Application : Used for overhead transmission lines.
Construction
Conductor : The center wire or wires of aluminum clad steel and the outer layer or layers of aluminum
Packing : Drum
20
ACSR /AS Aluminum Conductor - Aluminum
Clad Steel Reinforced
Application : Used for overhead transmission lines.
Construction
Conductor : The center wire or wires of aluminum clad steel and the outer layer or layers of aluminum.
Packing : Drum
21
T-ACSR/AS Thermal Resistance - Aluminum
Conductor Clad Steel Reinforced
Application : Used for overhead transmission lines.
Construction
Conductor : The center wire or wires of aluminum clad steel and the outer layer or layers of thermal resistance
aluminum alloy..
Packing : Drum
22
STACIR Super Thermal Resistance - Invar Reinforced
Construction
Conductor : The center wires of galvanized invar and the outer layers of super thermal resistance
aluminum alloy.
Packing : Drum
Specification : KEPCO
23
STACIR/AW Super Thermal Resistance - Aluminum
Clad Invar Reinforced
Application : Used for overhead transmission lines.
Construction
Conductor : The center wires of aluminum clad invar and the outer layers of super thermal resistance
aluminum alloy.
Packing : Drum
Specification : KEPCO
24
ACCR Aluminum Conductor Composite Reinforced
Construction
Conductor : The center wires of galvanized steel and the outer layers of aluminum-zirconium.
Packing : Drum
25
ACCC / TW Aluminum Conductor Composite Core
Trapezoidal Concentric-Lay-Stranded
Application : Used for overhead power distribution and transmission lines.
Construction
Conductor : The central is a proprietary high strength carbon fiber composite core and around which are
aluminum wires.
Packing : Drum
Current
Cross Section No. of DC Rated
Code Diameter Weight Carrying Standard
Area Aluminum Wires Ultimated
Name of Approx. Resistance Capacity Length
Nominal At 20C Strength
Conductor (A)
mm2 pcs mm kg/km /km A kg m
Helsinki 160 16 15.65 480 0.1861 775 64.0 2.000
Copenhagen 220 16 18.29 670 0.1279 986 65.6 2.000
Lisbon 310 16 21.78 957 0.0896 1,250 93.2 2.000
Amsterdam 360 20 23.55 1,113 0.0769 1,386 110.6 2.000
Brussels 415 20 25.14 1,275 0.0673 1,515 122.1 2.000
Stockholm 460 20 26.40 1,406 0.0612 1,616 141.1 2.000
Warsaw 510 22 27.72 1,539 0.0556 1,723 142.3 2.000
Dublin 520 22 28.15 1,559 0.0541 1,756 166.4 2.000
Hamburg 550 22 28.62 1,646 0.0517 1,806 143.2 2.000
26
AAAC - S All Aluminum Alloy Conductor, XLPE Insulated
Application : Used for overhead transmission and distribution.
Construction
Conductor : All Aluminum Alloy Conductor (AAAC), circular stranded according to SPLN 41-8
Insulation : Cross-linked Polyethylene (XLPE), complied with SPLN 41-9.
Packing : Drum
Note : (rm) Circular stranded
CONSTRUCTION
Cross - Section of Conductor mm2 35 rm 50 rm 70 rm 95 rm 120 rm 150 rm 185 rm 240 rm
Number of cores pcs 7 19 19 19 19 37 37 61
Diameter of Conductor (approx.) mm 7,5 8,8 11,3 12,5 13,8 15,8 17,5 20.3
Thickness of Insulation (nom.) mm 3,0 3,0 3,0 3,0 3,0 3,0 3,0 3.0
Overall Cable Diameter (approx.) mm 13,5 14,8 17,3 18,5 19,8 21,8 26,3 26.3
DELIVERY
Standard Delivery Length m 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000
Drum Type (D) 09C 09C 11A 11A 15A 15A 15A 14B
Cable Weight (approx.) kg/km 195 268 345 407 475 593 700 893
MECHANICAL
Minimum Bending Radius mm 243 266 311 333 356 392 423 473
Breaking Strength kgf 980 1,300 2,150 2,660 3,220 4,190 5,175 6,910
ELECTRICAL
AC Voltage Test kV/min 3,5/5 3,5/5 3,5/5 3,5/5 3,5/5 3,5/5 3,5/5 3,5/5
Max. Conductor DC Resistance at 200C /km 0,868 0,641 0,443 0,320 0,253 0,206 0,164 0,125
Min. Insulation Resistance at 200C M/km 1.000 900 900 800 800 800 800 700
CURRENT RATINGS
at 300C A 167 200 275 315 356 423 484 586
In Air
at 40 C
0 A 150 180 246 282 319 378 432 523
27
CONVERSION TABLE
19 [0.653]
0,75 0,75
18 [0.823]
17 [1.04]
16 [1.31]
1,25
15 [1.65]
1,5
2,0
14 [2.08]
2,5
13 [2.62]
12 [3.31]
3,5
11 [4.17]
4
10 [5.26]
5,5
9 [6.63]
6
8,0
8 [8.37]
10
7 [10.55]
6 [13.30]
14
5 [16.77]
25
4 [21.15]
22
3 [26.67]
35
2 [33.63]
50 38
1 [42.41]
1/0 [53.48]
60
2/0 [67.43]
70
3/0 [85.03]
95
4/0 [107.20]
100
120 MCM
250 [126.64]
150 150
300 [152.00]
185
200
240
400 [202.71]
250
500 [353.35]
300
600 [304.00]
350
700 [354.71]
400 400
800 [405.35]
500 500
1000 [506.71]
600
630
28
NF/NFA 2X Copper or Aluminum Conductor, XLPE
0.6 / 1 kV Insulated
Application : Used for secondary distribution and street lighting overhead low voltage power cable.
Construction
Conductor : annealed copper conductor, circular stranded according to SPLN 41-1
or aluminum conductor, circular stranded according to SPLN 41-1
Insulation : Cross-linked Polyethylene (XLPE), complied with SPLN 41-9.
Identification of core : rip core
Packing : Drum
Note : (rm) Circular stranded
CONSTRUCTION
No. of Core 2 4
Cross-Section of Conductor mm2 2 x 6 rm 2 x 10 rm 2 x 16 rm 4 x 6 rm 4 x 10 rm 4 x 16 rm 4 x 25 rm 4 x 35 rm
Diameter of Conductor (approx.) mm 3.2 4.1 5.1 3.2 4.1 5.1 6.4 7.6
Thickness of Insulation (nom.) mm 1.2 1.2 1.2 1.2 1.2 1.2 1.4 1.6
Overall Cable Diameter (approx.) mm 11.1 12.9 15.1 13.4 15.5 18.2 22.2 25.9
DELIVERY
Standard Delivery Length m 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000
Drum Type (D) 09C 09C 09C 09C 09C 11A 15A 14B
Cable Weight Copper (approx.) kg/km 144 224 345 288 448 690 1,063 1,481
Aluminum (approx.) kg/km 67 97 141 135 195 283 429 594
MECHANICAL
Copper kgf 394 656 1051 788 1312 2102 3284 -
Breaking Strength
Aluminum kgf - 322 515 - 644 1030 1610 2250
Minimum Bending Radius mm 200 232 272 241 279 328 400 466
ELECTRICAL
AC Voltage Test kV/min 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5
Max. Conductor Copper /km3.08 1.83 1.15 3.08 1.83 1.15 1.727 0.524
DC Resistance at 200C Aluminum /km 4.61 3.08 1.91 4.61 3,08 1,91 1,20 0,868
Min.Insulation Resistance Copper M.km 1,500 1,200 1,100 1,500 1,200 1,100 1,100 1,000
Aluminum M.km 1,500 1,200 1,100 1,500 1,200 1,100 1,100 1,000
CURRENT RATINGS
Copper A 54 73 97 54 73 97 133 -
In Air at 350C
Aluminum A - 54 72 - 54 72 102 125
29
NFA2X-T Aluminum Conductor, XLPE Insulated +
0.6 / 1 kV Neutral Messenger
Application : Used for secondary distribution and street lighting overhead low voltage power cable.
Construction
Conductor - Phasa : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
- Messanger : All Aluminum Alloy Conductor (AAAC), circular stranded according to SPLN 41-8
Insulation : Cross-linked Polyethylene (XLPE), complied with SPLN 41-9.
Identification of core : rip core
Packing : Drum
Note : (rm) Circular stranded
CONSTRUCTION
DELIVERY
Standard Delivery Length m 500 500 500 500 500
Drum Type (D) 11A 11A 15A 15A 15A
Cable Weight (approx.) kg/km 325 408 556 756 1,012
MECHANICAL
ELECTRICAL
AC Voltage Test kV/min 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5
Max. Conductor Phasa /km 1.20 0.868 0.641 0.443 0.320
DC Resistance at 200C Neutral /km 1.38 1.38 0.986 0.690 0.450
Min.Insulation Resistance Phasa M.km 1,100 1,000 900 900 800
Neutral M.km 1,100 1,100 1,000 900 900
CURRENT RATINGS
30
NFA 2X-T Aluminum Conductor, XLPE Insulated +
0.6 / 1 kV Neutral Messenger
Application : Used for secondary distribution and street lighting overhead low voltage power cable.
Construction
Conductor - Phasa : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1.
- Messenger : All Aluminum Alloy Conductor (AAAC), circular stranded according to SPLN 41-8
Insulation : Cross-linked Polyethylene (XLPE), complied with SPLN 41-9.
Identification of core : rip core
Packing : Drum
Note : (rm) Circular stranded
CONSTRUCTION
DELIVERY
Standard Delivery Length m 500 500 500 500 500
Drum Type [D] 11A 11A 15A 15A 18A
Cable Weight [approx.] kg/km 434 558 759 1,032 1,380
MECHANICAL
Breaking Strength kgf 712 712 997 1,395 1,932
Minimum Bending mm 400 452 515 605 700
ELECTRICAL
AC Voltage Test kV/min 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5
Max Conductor Phasa /km 1.20 0.868 0.641 0.443 0.320
DC Resistance at 20 0C Neutral /km 1.38 1.38 0.986 0.690 0.450
Phasa M.km 1,100 1,000 900 900 800
Min. Insulation Resistance Neutral M.km 1,100 1,100 1,000 900 900
CURRENT RATINGS
In Air at 350C A 103 125 154 196 242
31
NFA2X-T Aluminum Conductor, XLPE Insulated +
0.6 / 1 kV Neutral Messenger + Public Lighting
Application : Used for secondary distribution and street lighting overhead low voltage power cable.
Construction
Conductor - Phasa : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
- Messanger : All Aluminum Alloy Conductor (AAAC), circular stranded according to SPLN 41-8
- Public Lighting : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
Insulation : Cross-linked Polyethylene (XLPE), complied with SPLN 41-9.
Identification of core : rip core
Packing : Drum
Note : (rm) Circular stranded
DELIVERY DATA
Standard Delivery Length m 500 500 500 500 500
Drum Type [D] 11A 11A 15A 15A 18A
Cable Weight [approx.] kg/km 505 630 831 1,104 1,451
MECHANICAL DATA
Breaking Strength kgf 712 712 997 1,395 1,932
Minimum Bending mm 430 477 535 614 698
ELECTRICAL DATA
AC Voltage Test kV/min 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5
Phasa /km 1.20 0.868 0.641 0.443 0.320
Max Conductor
Neutral /km 1.38 1.38 0.986 0.690 0.450
DC Resistance at 20 0C
Public Lighting .km 1.91 1.91 1.91 1.91 1.91
Phasa M.km 1,100 1,000 900 900 800
Min. Insulation Resistance Neutral M.km 1,100 1,100 1,000 900 900
Public Lighting M.km 1,100 1,100 1,100 1,100 1,100
CURRENT RATINGS
In Air at 350C Phasa A 103 125 154 196 242
Public Lighting A 72 72 72 72 72
32
NFA2X-T Aluminum Conductor, XLPE Insulated +
0.6 / 1 kV Neutral Messenger + Public Lighting
Application : Used for secondary distribution and street lighting overhead low voltage power cable.
Construction
Conductor - Phasa : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
- Messanger : All Aluminum Alloy Conductor (AAAC), circular stranded according to SPLN 41-8
- Public Lighting : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
Insulation : Cross-linked Polyethylene (XLPE), complied with SPLN 41-9.
Identification of core : rip core
Packing : Drum
Note : (rm) Circular stranded
DELIVERY DATA
Standard Delivery Length m 500 500 500 500 500
Drum Type [D] 11A 11A 15A 15A 18A
Cable Weight [approx.] kg/km 576 701 903 1,175 1,522
MECHANICAL DATA
Breaking Strength kgf 712 712 997 1,395 1,932
Minimum Bending mm 459 500 554 623 702
ELECTRICAL DATA
AC Voltage Test kV/min 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5
Phasa /km 1.20 0.868 0.641 0.443 0.320
Max Conductor Neutral /km 1.38 1.38 0.986 0.690 0.450
DC Resistance at 20 0C Public Lighting .km 1.91 1.91 1.91 1.91 1.91
Phasa M.km 1,100 1,000 900 900 800
Min. Insulation Resistance Neutral M.km 1,100 1,100 1,000 900 900
Public Lighting M.km 1,100 1,100 1,100 1,100 1,100
CURRENT RATINGS
In Air at 350C Phasa A 103 125 154 196 242
Public Lighting A 72 72 72 72 72
33
DUPLEX Aluminum Conductor, XLPE Insulated +
0.6 / 1 kV Neutral Messenger
Application : Used for secondary distribution and street lighting overhead low voltage power cable.
Construction
Conductor - Phasa : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
- Messenger : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
All Aluminum Alloy Conductor (AAAC), circular stranded according to SPLN 41-8
Aluminum Conductor Steel Reinforced (ACSR), circular stranded according to SPLN 41-7
Insulation : Cross-linked Polyethylene (XLPE), complied with SPLN 41-9.
Packing : Drum
Note : (rm) Circular stranded
DELIVERY DATA
Standard Delivery Length m 1,000 1,000 1,000 1,000
ELECTRICAL DATA
AC Voltage Test kV/min 3.5/5 3.5/5 3.5/5 3.5/5
Max Conductor DC Resistance at 20 0C /km 1.91 1.20 0.868 0.641
Min. Insulation Resistance at 20 0C Phasa M.km 1,100 1,100 1,000 900
Current Rating in Air at 30 0C A 100 132 166 210
Max. Permissible 0,1 Second Phasa kA 4.86 7.59 10.63 15.18
Short Circuit 0,5 Second Phasa kA 2.17 3.39 4.75 6.79
Current for 1,0 Second Phasa kA 1.54 2.40 3.36 4.80
34
TRIPLEX Aluminum Conductor, XLPE Insulated +
0.6 / 1 kV Neutral Messenger
Application : Used for secondary distribution and street lighting overhead low voltage power cable.
Construction
Conductor - Phasa : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
- Messenger : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
All Aluminum Alloy Conductor (AAAC), circular stranded according to SPLN 41-8
Alluminum Conductor Steel Reinforced (ACSR), circular stranded according to SPLN 41-7
Insulation : Cross-linked Polyethylene (XLPE), complied with SPLN 41-9.
Identification of core : rip core
Packing : Drum
Note : (rm) Circular stranded
DELIVERY DATA
Standard Delivery Length m 1,000 1,000 1,000 1,000 1,000 1,000 1,000
ELECTRICAL DATA
AC Voltage Test kV/min 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5
Max Conductor DC Resistance at 20 0C /km 1.91 1.20 0.868 0.641 0.443 0.32 0.253
Min. Insulation Resistance at 20 0C Phasa M.km 1,100 1,100 1,000 900 900 800 800
Current Rating in Air at 30 0C A 83 109 135 171 211 258 296
Max. Permissible 0,1 Second Phasa kA 4.86 7.59 10.63 15.18 21.25 28.84 36.43
Short Circuit 0,5 Second Phasa kA 2.17 3.39 4.75 6.79 9.50 12.90 16.29
Current for 1,0 Second Phasa kA 1.54 2.40 3.36 4.80 6.72 9.12 11.52
35
QUADRUPLEX Aluminum Conductor, XLPE Insulated +
0.6 / 1 kV Neutral Messenger
Application : Used for secondary distribution and street lighting overhead low voltage power cable.
Construction
Conductor - Phasa : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
- Messanger : All Aluminum Conductor (AAC), circular stranded according to SPLN 41-1
All Aluminum Alloy Conductor (AAAC), circular stranded according to SPLN 41-8
Alluminum Conductor Steel Reinforced (ACSR), circular stranded according to SPLN 41-7
Insulation : Cross-linked Polyethylene (XLPE), complied with SPLN 41-9.
Identification of core : rip core
Packing : Drum
Note : (rm) Circular stranded
DELIVERY DATA
Standard Delivery Length m 1,000 1,000 1,000 1,000 1,000 1,000 1,000
ELECTRICAL DATA
AC Voltage Test kV/min 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5 3.5/5
Max Conductor DC Resistance at 20 0C /km 1.91 1.20 0.868 0.641 0.443 0.32 0.253
Min. Insulation Resistance at 20 0C Phasa M.km 1,100 1,100 1,000 900 900 800 800
Current Rating in Air at 30 0C A 83 109 135 171 211 258 296
Max. Permissible 0,1 Second Phasa kA 4.86 7.59 10.63 15.18 21.25 28.84 36.43
Short Circuit 0,5 Second Phasa kA 2.17 3.39 4.75 6.79 9.50 12.90 16.29
Current for 1,0 Second Phasa kA 1.54 2.40 3.36 4.80 6.72 9.12 11.52
36