You are on page 1of 2

ETAP

Project:

12.6.0H

Location:
Contract:

Date:

28-04-2015

SN:

Engineer:
Filename:

Page:

Study Case: LF
Project OJT Section 1

Revision:

Base

Config.:

Normal

Branch Losses Summary Report

CKT / Branch
ID

From-To Bus Flow

To-From Bus Flow

MW

MW

Mvar

Mvar

Losses
kW

% Bus Voltage
kvar

From

To

Vd
% Drop
in Vmag

TD 1

0.778

0.486

-0.778

-0.483

0.1

2.8

100.0

99.8

0.17

Line2

0.778

0.483

-0.774

-0.491

3.5

-7.8

99.8

99.1

0.75

Line4

0.696

0.441

-0.696

-0.441

0.1

-0.5

99.1

99.0

0.03

PS

0.078

0.050

-0.078

-0.048

0.7

2.1

99.1

97.3

1.80

-0.078

-0.048

0.078

0.050

0.7

2.1

97.2

99.0

1.80

0.617

0.391

-0.617

-0.392

0.1

-0.6

99.0

99.0

0.03

-0.078

-0.048

0.078

0.050

0.7

2.1

97.2

99.0

1.80

0.539

0.341

-0.539

-0.342

0.1

-0.3

99.0

99.0

0.02

-0.078

-0.048

0.078

0.050

0.7

2.1

97.2

99.0

1.80

0.461

0.292

-0.461

-0.292

0.0

-0.4

99.0

99.0

0.01

-0.078

-0.048

0.078

0.050

0.7

2.1

97.2

99.0

1.80

MN 0001
Line6
MN 0024Line8
MN 0048
Line10
MN 0047
Line12

0.079

0.050

-0.079

-0.050

0.0

-0.1

99.0

99.0

0.00

Line16

0.304

0.192

-0.304

-0.192

0.0

-0.1

99.0

99.0

0.00

-0.078

-0.048

0.079

0.050

0.5

1.7

97.5

99.0

1.44

MN 0007
Line14

0.000

0.000

0.000

0.000

0.0

-0.1

99.0

99.0

0.00

Line18

0.226

0.142

-0.226

-0.143

0.0

-0.6

99.0

99.0

0.01

MN 0050

0.078

0.050

-0.078

-0.048

0.7

2.1

99.0

97.2

1.80

MN 0002

-0.078

-0.048

0.078

0.050

0.7

2.1

97.2

99.0

1.80

0.147

0.093

-0.147

-0.093

0.0

-0.3

99.0

99.0

0.00

Line20
Line22

0.099

0.062

-0.099

-0.062

0.0

-0.5

99.0

99.0

0.00

MN 0045

0.049

0.031

-0.048

-0.030

0.4

1.3

99.0

97.2

1.80

Line24

0.049

0.031

-0.049

-0.031

0.0

-0.5

99.0

99.0

0.00

MN 0013

0.049

0.031

-0.049

-0.030

0.3

0.8

99.0

97.8

1.13

MN 00051

-0.049

-0.030

0.049

0.031

0.3

0.8

97.8

99.0

1.13

10.2

10.4