You are on page 1of 1

Project:

ETAP

Location:

12.6.0H

Contract:

Date:

28-03-2016

SN:

Engineer:
Filename:

Page:

Revision: Base

Study Case: LF

Config.:

Kandibata 1

PLTM + GI

LOAD FLOW REPORT


Bus
ID
BUS PLTM

* Bus1

Voltage
kV

Generation

% Mag.

Ang.

20.000 105.928

2.9

150.000 100.000

0.0

MW

Load

Mvar
0

5.865

MW
0

4.862

Load Flow

Mvar
0

ID
0 Bus3

MW

XFMR
Mvar

Amp

%PF

9.954

5.593

311.1

87.2

Bus_1

-4.977

-2.796

155.6

87.2

Bus_2

-4.977

-2.796

155.6

87.2

0 Bus_TD1

-2.014

-0.201

7.8

99.5

Bus_TD2

7.879

5.063

36.1

84.1

Bus_1

6.300 109.151

5.4

5.000

3.099

0 BUS PLTM

5.000

3.099

493.9

85.0

Bus2

20.000 100.136

0.5

0 Bus_TD1

9.625

4.936

311.8

89.0

Bus3

-4.813

-2.468

155.9

89.0

Bus3

-4.813

-2.468

155.9

89.0

Bus_2

6.300 109.151

5.4

5.000

3.099

0 BUS PLTM

5.000

3.099

493.9

85.0

Bus3

20.000 105.898

2.9

0 BUS PLTM

-9.951

-5.590

311.1

87.2

Bus2

4.976

2.795

155.6

87.2

Bus2

4.976

2.795

155.6

87.2

-9.623

-4.933

311.8

89.0

Bus_TD1

20.000 100.106

Bus_TD2

20.000

98.922

0.5

7.608

4.715 Bus2
Bus1

2.015

0.218

58.4

99.4

-0.9

7.875

4.881 Bus1

-7.875

-4.881

270.4

85.0

* Indicates a voltage regulated bus (voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA