ETAP

Project: Tugas KSTL 7 Page: 21


12.6.0H
Location: Date: 12-30-2016
Classt:
Contract: C SN:
Engineer: Muhammad Syahendra Anindyantoro Revision: Base
Study Case: LF
Filename: D400140010
77 Config.: Normal

Bus Voltage Generation LOAD FLOW


Load REPORT Load Flow XFMR
ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

Bus18 0.000 0.000 0.0 0.0


Bus Voltage Generation Load Load Flow XFMR
Bus19 0.000 0.000 0.0 0.0
ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap
Bus20 0.000 0.000 0.0 0.0
BDSLN1 150.000 97.636 -3.0 0 0 588.201 224.704 KMJNG -74.089 -15.540 298.4 97.9
NTMSY1 150.000 98.697 -1.7 0 0 52.117 20.450 TSMYA1 55.050 25.985 237.4 90.4
WYWND1 -27.124 -2.098 107.2 99.7
Bus22 -107.167 -46.435 455.5 91.8
Bus23 -243.494 -103.533 1043.1 92.0
TSMYA1 150.000 98.443 -1.9 0 0 51.849 20.345 GARUT1 3.162 5.355 24.3 50.8
Bus23 -243.494 -103.533 1043.1 92.0
NTMSY1 -55.011 -25.700 237.4 90.6
* Bus7 150.000 100.000 0.0 577.655 111.483 403.386 56.301 KMJNG 84.173 26.653 339.8 95.3
WYWND1 150.000 98.119 -2.0 0 0 9.627 9.627 BDSLN1 27.219 2.566 107.2 99.6
KMJNG 90.096 28.529 363.8 95.3
KMJNG -36.846 -12.193 152.2 94.9
Bus9 150.000 99.286 -0.9 0 0 0 0 Bus 19 0.000 0.000 0.0 0.0
Bus24 0.000 0.000 0.0 0.0
* Indicates a voltage regulated bus (voltage controlled or swing type machine connected to it) Bus10 0.000 0.000 0.0 0.0
#Bus10
Indicates a bus with a load mismatch
70.000of more than 0.1 MVA
99.286 -0.9 0 0 0 0 Bus9 0.000 0.000 0.0 0.0
Bus11 150.000 99.286 -0.9 0 0 0 0 DRJAT 0.000 0.000 0.0 0.0
Bus12 0.000 0.000 0.0 0.0
Bus12 70.000 99.286 -0.9 0 0 0 0 Bus11 0.000 0.000 0.0 0.0
Bus13 70.000 99.286 -0.9 0 0 0 0 DRJAT 0.000 0.000 0.0 0.0
Bus18 70.000 99.286 -0.9 0 0 0 0 KMJNG 0.000 0.000 0.0 0.0
Bus19 70.000 99.286 -0.9 0 0 0 0 KMJNG 0.000 0.000 0.0 0.0
Bus 19 150.000 99.286 -0.9 0 0 0 0 GARUT1 52.257 16.014 211.9 95.6
Bus9 0.000 0.000 0.0 0.0
DRJAT -52.257 -16.014 211.9 95.6
Bus20 70.000 99.286 -0.9 0 0 0 0 KMJNG 0.000 0.000 0.0 0.0
* Bus22 500.000 100.000 0.0 107.167 50.188 0 0 NTMSY1 107.167 50.188 136.6 90.6
* Bus23 500.000 100.000 0.0 486.989 237.911 0 0 BDSLN1 243.494 118.955 312.9 89.9
BDSLN1 243.494 118.955 312.9 89.9
Bus24 70.000 98.119 -2.0 0 0 0 0 WYWND1 0.000 0.000 0.0 0.0
DRJAT 150.000 99.286 -0.9 0 0 0 0 KMJNG -52.241 -16.009 211.8 95.6
Bus11 0.000 0.000 0.0 0.0
KMJNG -0.016 -0.005 0.1 95.6
Bus13 0.000 0.000 0.0 0.0
Bus 19 52.257 16.014 211.9 95.6
GARUT1 150.000 97.982 -2.0 0 0 55.009 20.166 Bus 19 -51.857 -14.839 211.9 96.1
TSMYA1 -3.152 -5.327 24.3 50.9
KMJNG 150.000 99.286 -0.9 0 0 9.858 4.437 Bus7 -83.969 -25.174 339.8 95.8
Bus7 -89.878 -26.946 363.8 95.8
DRJAT 52.242 16.010 211.8 95.6
BDSLN1 74.705 18.579 298.4 97.0
WYWND1 37.027 13.089 152.2 94.3
DRJAT 0.016 0.005 0.1 95.6
Rangkaian

Load=10+10i=14,142<45

PLTP

BDLN
WYWND
Semua Power grid dimatikan dan catu daya hanya dari
PLTP lokal
GARUT TSMYA
Jika semua powergrid diaktifkan maka sistem normal namun
jika semua power grid di matikan dan catu daya hanya dari
PLTP lokal maka yang terjadi adalah kelebihan beban dan
kekurangan daya sumber. Error yang terjadi jumlah bus
energi kurang dari 2, Jaringan ini tidak memiliki swing jaringan
listrik atau generator,sistem ini tidak memiliki cabang energi
seperti kabel, garis, dan transformer dll. Maka sistem perlu
penambahan.