Professional Documents
Culture Documents
Project: Page: 1
6.0.0
Location: Date: 05-15-2017
Study Case: LF
Filename: TAWILl BEBAN 56% Config.: Normal
Transformer
CKT / Branch Cable & Reactor
Ampacity Loading Capability Loading (input) Loading (output)
Study Case: LF
Filename: TAWILl BEBAN 56% Config.: Normal
Vd
CKT / Branch From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
% Drop
Line1 843.449 450.477 -842.433 -440.758 1015.9 9719.5 100.0 99.4 0.57
Line2 690.982 357.445 -689.758 -347.135 1223.9 10309.4 100.0 99.3 0.75
Line3 73.526 39.608 -73.372 -38.749 154.4 859.4 99.4 98.8 0.65
Line4 591.765 279.538 -589.984 -271.823 1781.2 7715.7 99.4 98.7 0.74
Line5 60.907 30.221 -60.736 -29.179 171.2 1042.4 99.4 98.5 0.89
Line6 -39.139 -37.358 39.140 37.390 1.1 32.1 98.6 98.7 0.04
Line7 -63.647 -38.187 63.707 38.375 60.8 188.5 98.6 98.8 0.25
Line8 15.337 18.492 -15.335 -18.479 2.4 13.3 98.8 98.8 0.05
Line9 77.686 32.323 -77.586 -31.736 100.0 587.6 98.8 98.5 0.37
Line10 -334.838 -182.786 335.279 185.432 441.1 2645.9 98.8 99.3 0.43
Line11 60.690 35.038 -60.615 -33.723 74.9 1315.0 98.8 97.8 1.03
Line12 71.625 37.728 -71.605 -37.612 20.1 115.2 98.8 98.7 0.09
Line40 622.324 282.165 -621.685 -276.418 639.2 5746.3 98.7 98.3 0.42
Line13 -94.415 -43.793 94.422 44.140 7.0 347.2 97.8 97.9 0.14
Line14 -463.530 -208.180 464.076 211.177 545.6 2996.9 97.9 98.3 0.33
Line15 42.812 10.750 -42.748 -10.473 64.2 277.0 97.9 97.6 0.29
Line16 159.771 62.820 -159.636 -62.492 135.2 327.5 97.9 97.8 0.14
ETAP
Project: Page: 3
6.0.0
Location: Date: 05-15-2017
Line17 96.835 49.006 -96.768 -48.715 67.8 290.9 97.9 97.8 0.17
Line39 69.689 41.464 -69.569 -41.063 120.7 400.9 97.9 97.6 0.37
Line18 55.700 16.413 -55.478 -15.790 222.6 622.9 98.5 97.8 0.66
Line19 -9.859 -3.724 9.862 3.738 2.9 14.2 98.5 98.5 0.08
Line20 52.411 18.673 -52.184 -18.118 226.4 555.4 98.3 97.6 0.70
Line21 -12.433 -3.837 12.435 3.845 1.5 7.7 97.5 97.6 0.03
Line22 -5.520 -3.839 5.521 3.841 0.5 2.4 97.5 97.6 0.03
Line23 -9.753 -4.618 9.755 4.628 2.0 9.7 97.5 97.6 0.06
Line24 9.825 -0.692 -9.825 0.695 0.6 3.3 97.6 97.6 0.00
Line25 -13.396 -2.133 13.399 2.141 3.1 7.5 97.6 97.6 0.03
Line26 -48.389 -13.604 48.658 13.767 268.5 162.7 97.6 98.2 0.59
Study Case: LF
Filename: TAWILl BEBAN 56% Config.: Normal
Vd
CKT / Branch From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
% Drop
Line27 -43.382 -26.843 43.432 26.964 49.3 120.8 97.6 97.8 0.20
Line28 -156.815 -71.247 157.030 75.227 214.5 3980.8 98.2 99.3 1.08
Line29 9.674 9.503 -9.648 -9.454 25.2 49.1 98.2 97.8 0.38
Line30 -16.656 4.535 16.663 -4.501 7.9 34.6 97.6 97.6 0.01
Line31 -14.112 7.826 14.117 -7.805 5.1 20.6 97.6 97.6 0.04
Line33 7.094 -3.455 -7.090 3.463 3.4 8.2 97.8 97.8 0.01
Line34 48.978 5.163 -48.965 -5.130 13.5 33.0 97.8 97.8 0.03
Line35 19.723 10.894 -19.705 -10.837 18.0 57.0 97.8 97.6 0.19
Line36 27.535 11.081 -27.518 -11.024 16.6 56.8 97.8 97.6 0.12
Line37 61.864 15.226 -61.805 -15.060 58.5 166.1 97.8 97.6 0.15
Line38 -20.363 0.539 20.397 -0.498 34.4 40.7 97.6 97.8 0.16
9924.5 59903.3
ETAP
Project: Page: 4
6.0.0
Location: Date: 05-15-2017
Study Case: LF
Filename: TAWILl BEBAN 56% Config.: Normal
% Alert Settings
Critical Marginal
Loading
Bus 100.0 95.0
Bus Voltage
OverVoltage 110.0 105.0
Generator Excitation
OverExcited (Q Max.) 100.0 95.0
Critical Report
Marginal Report
MW Mvar MVA % PF
Number of Iterations: 2