NSGAFOEU CPR

1,8/3 kV

Application
- For fixed installation and occasionally moving indoors and outdoors;
- In conduits for electrical wiring at, in and under plaster as well as in closed installation conduits;
- In switchgear and distribution boards up to 1000 V, also for unfused connections (DIN VDE 0100-520 and DIN VDE 0660-500);
Because of their increased mechanical strength due to the greater insulation thickness as compared with LV single-core cables, they are classified
as shortcircuit-proof and earth-fault-proof. The short-circuit withstand capability, on the other hand, must be assured by specifying a conductor
cross-section suitable for the short-circuit currents concerned. Please see table below for the permissible short-circuit currents.
The cables have a covering over the insulation to serve as mechanical protection during the cable installation, but are without protection against
accidental contact. Therefore it has to be secured that the unscreened cables with voltages over 1000 V shall not be touched during operation.
In other respects the specifications of DIN VDE 0298-3 apply.

Global data
Type designation NSGAFOEU
Standard DIN VDE 0250-602
Construction product regulation (CPR) CPR acc. to DIN EN 50575, class and DoP-Code: see data table below
DoP: see www.prysmiangroup.com/cpr

Design features
Conductor Material Copper tinned
Conductor shape Round (R)
Conductor class Class 5, multistranded (F)
Conductor Tinned copper, round (R), fine stranded (F), class 5 acc. to DIN EN 60228
Insulation Vulcanized rubber compound, basis Ethylen-Propylen-Rubber (EPR), compound 3GI3 acc. to DIN
EN 50363-1
Outer sheath Vulcanized rubber compound, basis CPE, compound 5GM3 acc. to DIN EN 50363-2-1
Outer sheath colour Black

Electrical parameters
Rated voltage 1.8/3 kV
Max. permissible operating voltage AC 2.1/3.6 kV
Max. permissible operating voltage DC 2,7/5,4
AC test voltage 6 kV

Chemical parameters
Flame propagation DIN EN 60332-1-2
Resistance to oil DIN EN 60811-404

Thermal parameters
Max. operating temperature of the conductor 90 °C
Max. short circuit temperature of the conductor 250 °C
Ambient temperature for fix installation min. -40 °C
Ambient temp. in fully flex. operation min. -25 °C

NSGAFOEU CPR Prysmian Kabel und Systeme GmbH Technical data, dimensions and weights are
1,8/3 kV Alt Moabit 91D, 10559 Berlin subject to change.
Revision: 11. Jun 2019 phone: +49 30 3675 40 © Prysmian Group, Germany 2018
email: kontakt@prysmiangroup.com www.prysmiangroup.com
Number of cores x Part Conduc- Insula- Outer Outer Bending Bending Weight Permis- Con- Current Short CPR fire CPR DoP-
cross section number tor tion diameter diameter radius radius (approx.) sible ductor carrying Circuit class Code
diameter thick- min. max. fixed free tensile resis- capacity Current
max. ness min. moving kg/km force tance (1) (conduc-
nom. mm mm min. max. at 20°C tor)
mm mm max. A
mm mm N kA
Ω/km
1 x 1.5 20261538 1.8 1.3 5.4 7 42 70 50 22.5 13.7 30 0.21 Eca 1007107
1 x 2.5 20261539 2.4 1.3 5.9 7.5 45 75 65 37.5 8.21 41 0.36 Eca 1007107
1x4 20261540 3 1.3 6.5 9 54 90 85 60 5.09 55 0.57 Eca 1007107
1x6 20261541 3.9 1.3 7.1 9.5 57 95 105 90 3.39 70 0.86 Eca 1007107
1 x 10 20261542 5.1 1.5 8.5 11 66 110 160 150 1.95 98 1.43 Eca 1007107
1 x 16 20261543 6.3 1.5 9.9 13 78 130 235 240 1.24 132 2.29 Eca 1007107
1 x 25 20261544 7.8 1.8 12 15 90 150 360 375 0.795 176 3.58 Eca 1007107
1 x 35 20261545 9.2 1.8 13.2 16.5 99 165 460 525 0.565 218 5.01 Eca 1007107
1 x 50 20261546 11 1.8 14.6 18 108 180 620 750 0.393 276 7.15 Eca 1007107
1 x 70 20261547 13.1 1.8 16.2 20.5 123 205 820 1050 0.277 347 10.01 Eca 1007107
1 x 95 20261548 15.1 2.2 19 24 144 240 1070 1425 0.21 416 13.59 Eca 1007107
1 x 120 20261549 17 2.2 20.6 26 156 260 1320 1800 0.164 488 17.16 Eca 1007107
1 x 150 20261550 19 2.2 22.7 28 168 280 1620 2250 0.132 566 21.45 Eca 1007107
1 x 185 20261551 21 2.4 24.5 31 186 310 1950 2775 0.108 644 26.46 Eca 1007107
1 x 240 20261552 24 2.6 28 34.5 207 345 2540 3600 0.0817 775 34.32 Eca 1007107
1 x 300 20261553 27 2.8 30.5 38 228 380 3088 4500 0.0654 898 42.9 Eca 1007107

(1) The values are valid for a cable in permanent operation with DC or AC with 50 up to 60 Hz at 30 °C ambient temperature, free in air. acc. to
VDE 0298-4

NSGAFOEU CPR Prysmian Kabel und Systeme GmbH Technical data, dimensions and weights are
1,8/3 kV Alt Moabit 91D, 10559 Berlin subject to change.
Revision: 11. Jun 2019 phone: +49 30 3675 40 © Prysmian Group, Germany 2018
email: kontakt@prysmiangroup.com www.prysmiangroup.com