Control Cables

PVC Insulated, PVC Sheathed


Multicore Cables for Fixed
Wiring, 0.6/1 kV

APPLICATION:
For fixed installation in open air in tray, trough
and conduit or for direct burial in free draining
soil or inside duct. General purpose control
cable for control circuits in industrial plants,
power stations and substations. Suitable for
the operation and interconnection of
protective break devices with heavy magnetic
trip where inductively induced over voltages
may occur. For systems operating at not
more than 0.6 kV between a conductor to
earth or 1 kV between conductors at
maximum conductor temperatures of 70 °C
for continuous normal operation and insulated and PVC sheathed cables is METALLIC ARMOUR:
160 °C for short circuit. available upon request. Double tape, wire or flat wire galvanized
steel armour conforming Israel Standard
STANDARDS: CONSTRUCTION:
1516 - available upon request.
1. Conforms to Israeli Standard IS 1516: A copper single wire circular conductor has
“Extruded solid dielectric insulated power an extruded PVC insulation applied around PACKAGING:
cables for rated voltages from 1 kV to the conductor. The cores are twisted and 500 m or 1000 m bobbins. Other bobbin
30 kV” for the type NYY FR1. wrapped together with a non-hygroscopic lengths or cut to length - available upon
2. The cable construction wholly meeting tape. An extruded black PVC sheath with request.
the IEC 60502-1 standard for PVC printed marking covers the core assembly.

Max. Short Current Voltage


Nominal Approximate Approximate Minimum conductor circuit rating (2) drop (3)
Catalog Nominal cross insulation outer cable bending resistance rating (1 sec) In Air Buried Single Three
Number sectional area thickness diameter weight radius at 20 oC (1) (3) (4) Phase Phase
AC AC
mm2 mm mm kg/km mm Ω/km kA A A mV/A/m mV/A/m
142025 6 x 1.5 0.6 12.5 255 150 12.1 0.17 13 17 29 25
14202696 7 x 1.5 0.6 12.5 275 150 12.1 0.17 12 16 29 25
142028 8 x 1.5 0.6 14 310 168 12.1 0.17 11.3 15 29 25
142030 10 x 1.5 0.6 15 365 180 12.1 0.17 10.2 13 29 25
14212396 12 x 1.5 0.6 17 450 204 12.1 0.17 9.6 12 29 25
142174 14 x 1.5 0.6 17.5 500 210 12.1 0.17 9.3 12 29 25
142204 16 x 1.5 0.6 18 550 216 12.1 0.17 8.9 11.2 29 25
142209 19 x 1.5 0.6 19 600 228 12.1 0.17 8.3 10.4 29 25
142336 24 x 1.5 0.6 21.5 800 258 12.1 0.17 7.4 9.1 29 25
142379 30 x 1.5 0.6 22.2 830 266 12.1 0.17 7.0 8.6 29 25
142387 37 x 1.5 0.6 22.5 880 270 12.1 0.17 6.7 8.1 29 25
142019 6 x 2.5 0.7 13.5 400 162 7.41 0.29 17 22 18 15
142034 7 x 2.5 0.7 13.5 420 162 7.41 0.29 16 20 18 15
142035 8 x 2.5 0.7 16.5 435 198 7.41 0.29 15 19 18 15
142037 10 x 2.5 0.7 18 515 216 7.41 0.29 14 17 18 15
142039 12 x 2.5 0.7 18 535 216 7.41 0.29 13 16 18 15
142132 14 x 2.5 0.7 18.5 575 222 7.41 0.29 13 15 18 15
142134 16 x 2.5 0.7 19.5 635 234 7.41 0.29 12 15 18 15
142137 19 x 2.5 0.7 20 735 240 7.41 0.29 11.3 14 18 15
142470 24 x 2.5 0.7 23.5 920 282 7.41 0.29 10.0 12 18 15
142480 30 x 2.5 0.7 25.5 1135 306 7.41 0.29 9.5 11.2 18 15
142469 37 x 2.5 0.7 28.5 1600 342 7.41 0.29 9.0 10.5 18 15
(1) Short circuit rating is based on an initial conductor temperature of 70 °C and a final temperature of 160 °C.
(2) Current rating based upon operation at 70 °C conductor, all the cores loaded. According to VDE 0298.
PCD 45-11, October 2007

(3) Cable laid in freely circulating air at 30 °C, protected against direct thermal radiation due to sun, etc.
(4) Cable directly buried at 0.7 m deep in soil at 20 °C, with 1 K . m/W thermal resistivity. Load factor 0.7.
(5) Voltage drop according to BS 7671:1992.3 assuming that the conductor temperature is 70 °C and the phase angle of the cable equals that of the load.
TEMPERATURE RATING FACTORS (Protection against short-circuit only). According to BS 7671:1992.3
Ambient Temperature °C 20 25 30 35 40 45 50 55 60 65
Correction factor air 1.08 1.06 1.00 0.94 0.87 0.79 0.71 0.61 0.50 0.35
Correction factor ground 1.00 0.95 0.89 0.84 0.77 0.71 0.63 - - -

The information given in this page is subject to change without notice.


Control Cables
PVC Insulated, PVC Sheathed
Multicore Cables for Fixed
Wiring, 0.6/1 kV
Specification

SCOPE OVERSHEATH
This specification describes PVC insulated - An extruded black PVC sheath shall be
PVC sheathed multicore cables for fixed applied on the tape wrapped cores
wiring in industrial and utilities plants. assembly.
They are intended for use on single phase - Properties of the sheath shall be in
and three phase installations not accordance with Israeli Standard 1516.
exceeding 1000 Volt phase to phase at
maximum conductor temperatures of TESTS
70°C for continuous normal operation The cable shall be tested in accordance
and 160 °C for short circuit maximum with Israeli Standard 1516.

STANDARDS CHARACTERISTICS
The following standard shall form a part Mechanical resistance
of this specification to the extent - to impacts: Low
specified herein: - Flexibility: Semi-flexible
- Israeli Standard IS 1516: “Cables, cords - Temperature range: -15 to +70 °C
and insulated conductors for nominal - Flame retardant: IEC 60332-1*
voltage up to 1000 Volt: PVC insulated - Weather resistance: Good
round cables” for the type NYY FR1. - Chemical resistance: Accidental

CONDUCTORS * Enhanced fire retardant behavior as


- Annealed, high conductivity copper per IS 1516 type NYY FR3 (IEEE 383),
single wire circular conductor according available upon request.
to IEC 60228 class 1.
- Seven wire stranded conductor,
according to IEC 60228 class 2, may
be supplied upon request.

INSULATION
- Directly over the conductor shall be
applied a homogeneous wall of
polyvinyl chloride (PVC) insulation.
- Properties of the insulation shall be in
accordance with Israeli Standard 1516.
- Core identification:
White insulation with printed numbers.
- Other insulation colours may be
supplied upon request.

CABLING
The cores, each with its corresponding
PCD 33-24/3.02 March 6, 2002

identification number, shall be twisted


together.

CORE ASSEMBLY WRAPPING


PCD 45-11, October 2007

A non-hygroscopic non-metallic tape shall Tel: (972) 4-8466222


be applied on the cabled cores assembly. Fax: (972) 4-8466286
e-mail: export@synergy-cables.com
http://www.synergy-cables.com